HVAC Basics
CO2—What it is
CO2 is exhaled from us all. Although not normally a health concern, CO2 levels increase as building occupancy levels
increase. Number of occupants, activity level, building tightness, ventilation rate, space volume, plants, and building
construction all affect building CO2 levels. CO2 levels typically correlate with other bio-effluents such as gases, odors,
particulates, bacteria, viruses, and perfumes. Monitoring CO2 levels helps facilitate ventilation decisions that allow
balancing occupant comfort and energy-savings.
CO2 Levels
Rural outdoor CO2 levels are about 350 parts per million (ppm) while urban CO2 levels are considerably higher. OSHA
guidelines allow a CO2 air contaminant limit of 5,000 ppm for more than 8 hoursa. In comparison, submarines can reach
as high as 7,000 ppm (and on rare occasions even reach a level of 30,000 ppm). Offices typically are 800-1200 ppm.
Tightly packed conference rooms with minimal ventilation can be 2,000 ppm. To learn how stuffy the air feels at higher
CO2 levels, carry a portable C7242 and monitor CO2 levels throughout your day. This is an excellent way to sell CO2
sensors.
Claims that 1,000 ppm and greater CO2 levels cause drowsiness, fatigue or headaches are highly subjective and often
unfounded. Elevated CO2 levels do not necessarily cause these symptoms, but can indicate a buildup of other contami-
nants that do cause such symptoms. Managing ventilation using CO2 levels can improve occupant comfort because other
pollutants are also exhausted with the CO2.
IMPORTANT
Do not confuse carbon dioxide (CO2) with carbon monoxide (CO), a highly toxic gas that is also a byproduct of
combustion in furnaces, fireplaces and automobiles. Carbon monoxide (CO) can be harmful, even at very low
levels (25 to 50 ppm).
NOTE: Refer to ASHRAE 62-1989 Standard for details relating CO2 level to ventilation rate.
There are devices marketed as IAQ sensors that output one composite signal. Regardless of what some vendors may say,
there are no reliable HVAC market priced indoor air quality sensors because IAQ is a complex problem that includes
many variables. To further confuse the issue, some substances are deadly when present in low ppm while others are
harmless when present in high thousands of ppm. The list of substances is quite long and not totally defined; see the
OSHA web sitea. Sensors currently sold on the market cannot solve these issues. However, when one becomes available,
Honeywell plans to offer it.
It is anticipated that CO2 sensor use in codes and legislation will improve in the future. The codes will define relation-
ships among ventilation, occupancy and IAQ parameters (including CO2). The new family of C7242 products is designed
to meet all CO2 sensor needs and is also compatible with most controllers. Watch for geographic area code changes that
can affect your CO2 sensor sales.
63-7049 2
CARBON DIOXIDE, DEMAND-CONTROLLED
VENTILATION (DCV) QUESTIONS AND ANSWERS
IMPORTANT
Always refer to state and local codes for details on required and recommended CO2 levels.
There are also differences between CO2 and temperature sensing and control. Temperature is usually quite uniform
throughout a zone whereas CO 2 levels can vary widely. CO2 levels within a conference room can reach 2,500 ppm while
the level on the other side of the door remains at 800 ppm. Therefore, sensor placement strongly affects the result
because the control system attempts to control CO 2 levels at the sensor location.
There are a variety of CO2 control strategies and algorithms used in ventilation control. Proper selection depends on the
complexity of the building and its HVAC system. Three common strategies follow.
On/Off
On/Off control employs an open-closed damper strategy based on CO2 level. This strategy is the most common approach to
CO2 control. A damper opens at a setpoint and closes when levels drop 50 to 100 ppm below setpoint. This strategy works
best in applications with high occupancy densities (20 to 50 people per 1,000 sq ft) and with occupancy varying from zero to
full in a very short time. Theaters, conference rooms and some school classrooms are applications where this strategy is used.
When CO2 levels vary around the setpoint, the dampers drive fully open and fully closed, depending on the reading so
when other control options are not available, use setpoint control.
Proportional
The amount of heating or cooling energy provided to a space is the basis for staging many HVAC systems. Ventilation
systems with proportional control use a CO2 sensor signal proportional to CO2 level. Control begins when indoor levels
exceed outdoor levels by a defined difference (100 ppm). Air delivery to the space increases proportionally to provide
100% ventilation rate. Compared to setpoint control, this approach allows faster system reaction to varying occupancy
levels. It does not always wait for levels to build to the control point. Applications requiring a higher degree of control
use a proportional strategy. Proportional control uses sensor models that allow the installer to scale the output to corre-
spond with the control range desired. For example, a 2 to 10 Vdc signal can be adjusted to match a CO2 level differential
range of 400 to 1,000 ppm. Proportional ventilation control is ideal in spaces with highly variable and unpredictable
occupancies such as bars, restaurants, conference rooms, courtrooms, classrooms, and retail spaces.
Proportional-Integral-Derivative (PID)
Time required to reach equilibrium CO2 levels in low-density applications creates a potential disadvantage for CO2
control. Low densities such as six people per 1,000 sq ft can require hours to reach equilibrium CO2 and staggered or
varying occupancy can aggravate these problems. Temperature control of large complex buildings encounters similar
problems as a result of unpredictable changes in outdoor temperature, solar gain and internal heat generation. Simple
temperature control approaches, such as setpoint or proportional, can be disaster in this type of building.
A solution to these complex control problems is PID control. PID control directs system control sequences to examine
distance from setpoint, time spent at setpoint, and speed of change from setpoint. PID CO2 control views trends and CO2 level
change rates. For example, minutes after people enter a building in the morning, the HVAC system reacts to adjust fresh air
delivery. This adjustment is based on actual occupancy predicted by the CO2 level rate of rise. Much like the proportional
control system, the PID controller operates based on the linear output signal from a CO2 sensor. Most DDC and building
control systems use PID control algorithms. Stand-alone controllers are available that can translate a linear signal from a CO2
sensor into a PID signal. However, only experienced control designers and installers should apply PID control approaches.
When applied properly, PID control provides fast ventilation rate response to changing occupancy conditions. Remember that
PID control integrates best in high-rise, multi-zone buildings with low density, highly variable or unpredictable patterns of
occupancy.
3 63-7049
Why is CO2 Control Important?
Most building codes base new building ventilation recommendations on ASHRAE Standard 62-1989, “Ventilation for
Acceptable Air Quality.” This standard has a wide variety of recommended ventilation rates based on space use. Problems
related to poor IAQ increase when a serious energy crisis creates sufficient energy savings interest to prompt lowering
ventilation standards. A study of 500 IAQ investigations conducted by the National Institute for Occupational Safety and
Health (NIOSH) in the 1970s and 1980s indicated that 50% of problems identified resulted from inadequate ventilation.
Recognize that using cfm per person and cfm per square foot CO2 are attempts to simplify the discussion. Actual measure-
ments more accurately determine CO2 levels. Always refer to local code and requirements for implementation requirements.
NOTE: Use the second approach with extreme variations in outdoor levels (more than 200 to 300 ppm during a
day). Extreme variation occurs with building air intakes near sources of pollution (major highways, loading
docks, etc.)
63-7049 4
When outdoor air CO2 levels exceed 800 ppm, investigate the source of CO2. Levels this high indicate polluted outdoor
air that likely contains high levels of other contaminants. When periodic high levels occur, devise a control strategy to
close air intakes during unacceptable levels (higher than 600 ppm).
IMPORTANT
The key factor in determining ventilation rate is the difference between indoor and outdoor CO2 levels.
The time required to reach equilibrium depends on number of people, activity level, space volume, and ventilation rate.
Poorly-ventilated rooms with low occupant densities can require several hours to reach equilibrium level. Once indoor level
exceeds a certain indoor/outdoor differential, the ventilation rate is below acceptable. If a space has high occupant density
(school classroom, bar or theater), or poor ventilation, the equilibrium level can be reached rapidly, in 20 minutes or less.
The use of spot CO 2 measurements has several drawbacks. A more effective diagnostic measurement approach is
recording space CO2 levels for 24 hours. Use a data logger and a continuous CO2 monitor to record level changes. This
provides information about the HVAC system and fresh outdoor air delivery to building zones (in proportion to occu-
pancy levels). For diagnostic purposes, take CO2 measurements in at least every zone containing a single air handler.
Take measurements during typical occupancy patterns. If the HVAC system uses Variable Air Volume (VAV) systems,
perform measurements in every VAV zone during full occupancy. If diverse occupancies occur throughout the zone, take
separate measurements in each occupied area. It can also be worthwhile to measure CO2 levels in return air ducting. It is
important to take at least one measurement each season.
NOTE: For proportional or rate of rise (PID) strategy, begin control 100 ppm above outdoor conditions.
5 63-7049
Table 1. Recommended Control Strategy Based on Occupancy Density.
Occupancy Density (number of people per 1,000 sq ft) Recommended Control Strategy
Highly variable (unpredictable changes greater than 25% occupancy) PID or Proportional
Low (7 or fewer) PID or Proportional
Medium (7 to 20) Proportional
High (20 to 50) Setpoint or Proportional
When NDIR CO2 sensors were first introduced to HVAC markets, they used an aluminum tube to guide the light.
However, these aluminum tubes corroded due to normal air pollutants. The tube corrosion absorbed energy resulting in
false CO2 indications. The new Honeywell CO2 sensors are gold-plated to resist corrosion. Therefore, calibration lasts far
longer than other CO2 sensors. No other CO 2 sensor on the market offers gold-plating reliability, or the lasting calibration
these sensors offer. Using gold eliminates not only sensor chamber corrosion, but the need for a second sensor to
measure drift, and all the problems associated with a second sensor. (Products that incorporate a reference sensor must
deal with issues of reference sensor drift, correlation between the sensors, added cost and reliability issues.) Honeywell
has been closely tracking CO2 sensor product developments for years and discovered that many units evaluated did not
meet expectations. The new C7242 Sensors use technology unavailable in any other product and they provide the best
performance at the lowest service costs while remaining competitively priced.
Each unit has two analog outputs. Some models use the second output for other purposes such as a relay, heater control,
or low-battery indication. The available analog outputs can use factory defaults for plug and play simplicity, see Table 2.
The installer can reconfigure the devices to meet control requirements using the accessory 32002183-001 PC Configura-
tion Software. The analog outputs typically produce a linear output relative to the sensor reading (0-10 Vdc). By custom-
configuring the sensor, CO2, temperature and contact input can be combined to generate custom output curves. The
number of output options are too numerous to discuss.
63-7049 6
TARGET APPLICATIONS
The primary control strategy using CO2 is outdoor air intake regulation to provide fresh air when required, based on
occupancy. This avoids over-ventilation and associated energy costs. ECONOMIZER™ Logic Module applications, both
standalone and DDC based, represent the largest opportunity for CO2 sensor sales.
Residential Systems
Houses are subject to the same, if not worse, IAQ issues as buildings. Commercial building codes require a minimum
fresh air intake. Houses are now tighter and rarely have to follow codes that require fresh air intake. However, in a tight
house, CO2 levels increase during periods of higher occupancy or during use of unvented gas combustion appliances.
Houses equipped with fresh air ventilation devices, such as the Honeywell HR150 or HR200, can use the C7242 to
control the ventilation rate based on the indoor CO2 level. This can result in increased comfort and energy savings. The
C7242A1030 and 1048 models are compatible with the PC8900 Perfect Climate Comfort Center™, the Honeywell ERV
and HRV devices. CO2 sensor contact closure signals the controller or ventilation device that the CO2 threshold was
reached and the device takes appropriate action. See the device literature for wiring and control options.
NOTE: CO2 levels can differ widely within the ventilation zone, resulting in over- or under-ventilation. Finer
control requires more sensors and greater area-independent ventilation ability.
2. Identify and set the level at which ventilation should increase; for example, an application requires increased
ventilation at 800 ppm. Configure the (effective) sensor zero point at 800 ppm.
3. Identify and set the level at which 100 percent ventilation should occur; for example, 100 percent ventilation is
required at 2,000 ppm. Configure the sensor to 10 Vdc at 2,000 ppm.
NOTE: The CO2 sensor cannot compensate for equipment that cannot handle the ventilation requirements.
7 63-7049
Table 3. C7242 Models and Accessories.
Output
Product Description Display No display (quantity) Comments
Wall Mount with relay C7242A1030 C7242A1048 Analog (1), 7-1/16 in. x 3-15/16 in. x 2-3/16 in.
Relay (1)
Wall Mount C7242A1014 C7242A1022 Analog (2)
Portable C7242C1002 N/A Analog (1) 9 Vdc NiMH and 120 Vac Charger.
Duct Mount C7242B1012 C7242B1020 Analog (2) 9-5/8 in. x 3-11/16 in. x 2-3/16 in. with
1-3/16 in. D x 9-1/16 in. sampling tube.
Outside Air N/A C7242E1007 Analog (1) 9-5/8 in. x 3-11/16 in. x 2-3/16 in.
Zero Calibration Service Kit 32002181-001 N/A 7-1/2 in. x 7-1/2 in. x 4-1/2 in.
Duct Mount Housing only 32002182-001 9-5/8 in. x 3-11/16 in. x 2-3/16 in. with
1-3/16 in. D x 9-1/16 in. sampling tube.
PC Configuration Software 32002183-001 Includes RS232 Cable.
FOOTNOTES
a See http://www.osha-slc.gov/OshStd_data/1910_1000_TABLE_Z-1.html