REPLACE POWER GENERATION SYSTEM MARJAN GOSPs BI-10-01247

DATA SCHEDULE FOR POWER TRANSFORMER - R75-XFR(T)-703, R75-XFR(T)-704


ITEM
NO.

DESCRIPTION

SAMSS Attachments & Supplements

Supplemental Pages to Data Schedule 1


Auto/Multi-winding Transformer
Parallel Operation

(Mineral Oil-Immersed)

High Voltage Winding


Continuous OA/FA/FOA Ratings
Voltage Rating
Winding Connection
Neutral Grounding
Winding BIL Level
Neutral BIL Level
Surge Arresters
a) Mounted Complete
b) Provision only forc) Voltage rating
d) Ground Plugs
e) Neutral Terminals

N/A
NO
NO

(Yes/No)
(Yes/No)

Coolant

Loss Evaluation Constants


a) Currency of Evaluation
b) No-load Loss Constant A
c) Load Loss Constant B

BEST

14-SAMSS-531 & 26-SAMSS-059

(One, Three)
(C)
(Hz)
(2/3/4winding, or Auto)

Forced Cooling & Controls


Fan or Pump Motor Voltage & Phases

ABB

BI 10-01247

Number of Phases
Temperature Rise
Frequency
Transformer Type

Operation
Angular Displacement
Impedance (% at C on OA Base of High Voltage Winding)
Other:
Multi Winding Transformers
0
Impedance HV to LVX (% at 85 C on OA Base of X Secondary Winding)
0
Impedance HV to LVX (% at 85 C on OA Base of Y Secondary Winding)
0
Impedance LVX to LVY (% at 85 C on OA Base of X or Y Winding)

SIEMENS

Buyers Purchase Order/Quotation Request


Buyers Budget Item/Job Order Number
Buyers Line Item Number

FEED Stage

(Step-up/Step-down/Intertie)

(ANSI or IEC 60076)


ANSI:

Three
0
65 C
60
Two
Oil- Immersed

Three
65
60
2-winding
Mineral Oil

Step-down
ANSI -Dyn1
11.0%
At ONAN

Step-down
Dyn1
11.0%
At ONAN

Three
60
2 Winding
ONAN/ONAF/OFAF
Step-down
Dyn1
11%
At OA Base

n.a
n.a
n.a
(YES/NO)

YES (ONAN/ONAF/OFAF)
480V/ 3-PH

120V,1-PH or 480V, 3-PH

Symbol

YES * (ONAN/ONAF)
Data not provided

YES (ONAN/ONAF/OFAF)
Data not provided

n.a.
n.a.
n.a.

Cost/kW
Cost/kW

(MVA)
(kV)
(Delta, Wye)
(Solid, Ungrounded)
(kV)
(kV)
(Yes/No)
Manufacturer
(kV)
(Yes/No)
(kV)

130/173/230
0
230
Delta
Ungrounded
900
N/A

120/160
230
Delta
Ungrounded
900

Delta
Ungrounded
Data not provided

Yes
N/A
N/A
Yes
N/A

No

Data not provided

130/173/230

REPLACE POWER GENERATION SYSTEM MARJAN GOSPs BI-10-01247


DATA SCHEDULE FOR POWER TRANSFORMER - R75-XFR(T)-703, R75-XFR(T)-704
ITEM
NO.

DESCRIPTION
Low-Voltage Winding
Continuous OA/FA/FOA Ratings
Voltage Rating
Winding Connection
Neutral Grounding
Winding BIL Level
Neutral BIL Level
Surge Arresters
a) Mounted Complete
b) Provisions only forc) Voltage Rating
d) Grounding Plugs
e) Neutral Terminal
High Voltage Winding Termination
Type: Bushings/Junction Box/Throat
Position
a) Outdoor Bushings
Terminal Type
Take-off Angle
Conductor Size and Type
Conductor Material
b) Junction Box Type
(Cable, Conduit, Separable Connectors)
1. Cable Junction Box
Cable Size
Cable Type
Number of Cables
Number of Potheads
Number of Conductors per Phase
2. Conduit Junction Box
Conduit Size
Number of Hubs
Entry Location
Conductor Size
Conduction Material
c) Throat Connection
(Buyer will supply full details after award of contract)

FEED Stage

SIEMENS
(MVA)
(kV)

(Delta, Wye)
(Solid, Ungrounded)
(kV)
(kV)
(Yes/No)
Manufacturer:
(kV)
(Yes/No)
(kV)

(Top Cover/Tank Side)


Line-end BIL (kV)
Neutral-end BIL (kV)
(Stud/NEMA Pad)
(Vert/Hor/Angle)
2
Stranded mm
Tube IPS-in
(Copper/Aluminum)

(mm )

(inch)
(Top/Bottom)
2

(mm )
(Cu/Al)

130/173/230
115
Wye
Solid
450
450

ABB

BEST

120/160
115
Wye
Data not provided
450
Data not provided

Wye
Data not provided
Data not provided
Data not provided

No
N/A
N/A
N/A
N/A

No

Data not provided

Bushings
Top Cover
1050
N/A
NEMA Pad
Vertical
2-795
N/A
Aluminum
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

Bushings
Top Cover
1300 (ABB Type GOE 1300)
N/A
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided

Data not provided


Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided

N/A

130/173/230

REPLACE POWER GENERATION SYSTEM MARJAN GOSPs BI-10-01247


DATA SCHEDULE FOR POWER TRANSFORMER - R75-XFR(T)-703, R75-XFR(T)-704
ITEM
NO.

DESCRIPTION
Low-Voltage Winding Termination
Type:
Position
a) Outdoor Bushings
Terminal Type
Take-off Angle
Conductor Size and Type
Conductor Material
b) Junction Box Type
(Cable, Conduit, Separable Connectors)
1. Cable Junction Box
Cable Size
Cable Type
Number of Cables
Number of Potheads
Number of Conductors per Phase
2. Conduit Junction Box
Conduit Size
Number of Hubs
Entry Location
Conductor Size
Conduction Material
3. Separable Connectors
c) Throat Connection

10

Tap Changer Type


Type:
Tap kVA Ratings
Location
Number of Steps
Step Size
Mechanical key Interlock
Compartment Pressure-Rise Relay
Load Tap Changer Control
Local Control
Remote Control
Manual Control
Supervisory Control
Position Telemetering
Automatic Voltage Control
AC Reference Voltage
Parallel Operation Required
Line Drop Compensator
Motor Supply Voltage, Phase

FEED Stage
Bushings/Junction Box/Throat

(Top Cover/Tank Side)


Line-end BIL (kV)
Neutral-end BIL (kV)
(Stud/NEMA Pad)
(Vert/Hor/Angle)
2
Stranded mm
Tube IPS-in
(Copper/Aluminum)

ABB

Bushing
Top Cover
(See Note-5)
650
650

Bushing
Top Cover

Data not provided


Data not provided

650 (ABB Type GOB


650)
650 (ABB
Type GOB
650)
GIB (oil
toSF6)
Vertical

Data not provided


Data not provided
Data not provided
Data not provided

Data not provided

Data not provided

GIB (oil toSF6)

(mm )

(inch)
(Top/Bottom)
2

(mm )
(Cu/Al)
(Yes/No)

(De-energized/Load)
(Full/Reduced-Capacity)
(High Voltage/Low Voltage)
Above:
Below:
(Percent)
(Yes/No)
(Yes/No)
(If applicable)
(Yes/No)
(Yes/No)
(Yes/No)
(Yes/No)
(Yes/No)
(Yes/No)
(RMS Nominal)
(Yes/No)
(Yes/No)
(AC RMS)

SIEMENS

Vertical
N/A
N/A
Aluminum
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

Load
Full
High Voltage
16
16
0.625
No
Yes
Yes
Yes
Yes*
Yes
Yes
Yes
Yes
120
No
Yes
480V,3

Load
Data not provided
High Voltage
16
16
0.625
Data not provided
Yes
Yes
Data not provided
Yes
Data not provided
provided
Yes
Data not provided
Yes
Data not provided
No
Data not provided
Data not provided

BEST

Data not provided


Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided

REPLACE POWER GENERATION SYSTEM MARJAN GOSPs BI-10-01247


DATA SCHEDULE FOR POWER TRANSFORMER - R75-XFR(T)-703, R75-XFR(T)-704

ITEM
NO.

11

12

13

DESCRIPTION
Current Transformers
a) High-Voltage Windings/Bushings
Number Required per Phase
Accuracy Class (C-50/100/200/400/800 or 0.3/0.6/1.2)
Standard Burden (B-1/2/4/8, or B-0.1/0.2/0.5/0.9/1.8)
Primary Current Rating
Secondary Current Rating
Number of Ratios
Cont. Thermal Current Rating Factor
* to be advised later
b) Low-Voltage Windings/Bushings
Number Required per Phase
Accuracy Class (C-50/100/200/400/800 or 0.3/0.6/1.2
Standard Burden (B-1/2/4/8, or B-0.1/0.2/0.5/0.9/1.8)
Primary Current Rating
Secondary Current Rating
Number of Ratios
Cont. Thermal Current Rating Factor
* to be advised later
c) Winding Neutral End/Bushing
Number Required
Location (Bushing/External)
Accuracy Class (C-50/100/200/400/800)
Standard Burden (B-1/2/4/8)
Primary Current Rating
Secondary Current Rating
Number of Ratios
Cont. Thermal Current Rating Factor
* to be advised later
d) Unloaded tertiary also requires one CT for
ground fault Protection
Number Required
Location (Bushing/External)
Accuracy Class (C-50/100/200/400/800)
Standard Burden (B-1/2/4/8)
Primary Current Rating
Secondary Current Rating
Number of Ratios
Cont. Thermal Current Rating Factor

SIEMENS

FEED Stage

(Amperes)
(Amperes)
(Single/Dual/Multi)

(Amperes)
(Amperes)
(Single/Dual/Multi)

Protection Class

(Amperes)
(Amperes)
(Single/Dual/Multi)

(Amperes)
(Amperes)
(Single/Dual/Multi)

Relaying

Metering

2
2
TPS TPS
*
*
2000 2000
5
1
MULTI
1.33

1
TP
S
0.2
20
00
1
M
UL
1.3
TI
3
Metering

Relaying
2
TPS
*
2000
5
MULTI
1.33
HV
1.33

LV
2
Bushing
TPS
*
2000
5
MULTI
1.33

HV

LV

5
DUAL
1.33

5
DUAL
1.33

Additional ANSI Test Requirements


Zero Sequence Impedance

(Yes/No)

Yes

Miscellaneous & Accessories (Typical)


Combustible Gas Detector (Buchholz relay)
Padlockable Drain Valve

(Yes/No)
(Yes/No)

Yes
Yes

ABB

BEST

Data not provided


Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided

Data not provided


Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided

Data not provided


Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided

Data not provided


Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided

Data not provided


Bushing
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided

Data not provided


Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided
Data not provided

Data not provided


Data not provided
Data not provided

Data not provided


Data not provided
Data not provided

Data not provided

Yes
Yes

Data not provided

Data not provided


Data not provided

REPLACE POWER GENERATION SYSTEM MARJAN GOSPs BI-10-01247


DATA SCHEDULE FOR POWER TRANSFORMER - R75-XFR(T)-703, R75-XFR(T)-704
Conservator
Pressure (Rate of Rise Type) Relay (63)
Oil Temperature Relay (26)
Winding Over Temperature Relay (49)
Low Oil Level Relay (71)
Magnetic Liquid Level Gauge with volt free contacts

(Yes/No)
(Yes/No)
(Yes/No)
(Yes/No)
(Yes/No)
(Yes/No)

Yes
Yes
Yes
Yes
Yes
Yes

Liquid Temperature Indicator with volt free contacts

(Yes/No)

Yes

Pressure Relief Device

(Yes/No)

Yes

Yes
Yes
Yes
Yes
Yes
Data not provided

Data not provided


Data not provided
Data not provided
Data not provided

Data not provided


Yes

NOTES:
ITEM
No
1

FEED Stage

SIEMENS

A minimum of four dry-contacts, normally closed/normally


open (NO/NC) shall be provided for each relay listed in
section 13 above for field interface. These relay contacts
shall be pre-wired to terminal blocks inside the transformer
control cabinet.

Shorting type terminal blocks shall be used for all CTs


connections.
Only Insulated Ring Tongue crimped type shall be used for
all CTs connections
Insulated ring tongue, locking fork tongue crimped type
shall be used for other control connections
SF6 Terminations for GIB terminations

Buchholz relay 1x alarm 2x trip (hard wired


Winding Temperature Indicator with two contacts (1
contacts) with 4x alarms / 4x trips (by contact
alarm+1 trip)
duplication in control cubicle)
Oil Temperature Indicator with two contacts (1 alarm+1
trip)
Pressure relay (63) 2x trip by change-over
(hard wired contacts) with 4x trips (by contact
Oil Level Indicator for main tank with contacts (2 alarms
duplication in control cubicle); optional 4x trip (Max. & Min) + 1 trip (MinMin))
by no contact (hard wired contacts)
Oil Level Indicator for OLTC with contacts (2 alarms
Oil temperature relay (26) Indicator with 2 x
(Max. & Min) + 1 trip (MinMin))
alarm 2x trip (hard wired contacts) or 1x alarm Buchholz Relay for main tank with two contacts (1
1x trip with 4x alarm 4x trip by contact
alarm+1 trip)
duplication in control cubicle
Pressure relief device for main tank with contacts (2
Winding over temperature relay Indicator with alarms + 2 trips)
2 x alarm 2x trip (hard wired contacts) or 1x
Pressure relief device for each OLTC with two contacts (1
alarm 1x trip with 4x alarm 4x trip by contact
alarm + 1 trip)
duplication in control cubicle
Sudden pressure relay for main tank with two contacts (1
Low oil level relay Indicator with 2 x alarm 2x
alarm + 1 trip)
trip (hard wired contacts) or 1x alarm 1x trip
Pressure relay for each OLTC with two contacts (1 alarm
with 4x alarm 4x trip by contact duplication in
+ 1 trip)
control cubicle
Magnetic or hydraulic liquid level gauge - 2 x
alarm 2x trip (hard wired contacts) or 1x alarm
1x trip with 4x alarm 4x trip by contact
duplication in control cubicle
Sudden pressure relay 2 x alarm 2x trip (hard
wired contacts) or 1x alarm 1x trip with
4x alarm 4x trip by contact duplication in
control cubicle.
Confirmed
Data not provided

3
4
5

ABB

BEST
Data not provided

Data not provided

Confirmed

Data not provided

Data not provided

Confirmed

Data not provided

Data not provided

Oil-SF6 bushings mounted on transformer top

ABB Type GOB 650

Data not provided

REPLACE POWER GENERATION SYSTEM MARJAN GOSPs BI-10-01247


DATA SCHEDULE FOR POWER TRANSFORMER - R75-XFR(T)-703, R75-XFR(T)-704
ITEM
NO.
1
2
3
4

DESCRIPTION

SIEMENS

ABB

BEST

Guaranteed No-Load Loss (rated voltage) (kW)


Guaranteed Load Loss (ONAN at 85 C) (kW)
Forced Cooling Requirements (kW)
Excitation Current at Rated Voltage (%)

121 (+10% tol.)


200 (+10% tol.)
app. 40
< 0.2

104
294
16
0.3

120 @ 1.0 Un
248 @ OA Base
10
0.18