Gas Stations
Regulations
Introduction
Every attempt has been made to assure these recommendations are in compliance with existing safety
practices and recommendations. However, it is highly
recommended that before any consideration is made
to change an existing chlorine station to make it
comply with these recommendations, the changes and
existing conditions be reviewed by the local, state, or
federal safety compliance agency.
OSHA Regulation
At the writing of this lesson, the new clean air regulations had not been completed. However, it appears
most likely that a chlorine gas release into the
atmosphere will be a violation of the clean-air act and
as such the violator would be required to change the
exhaust practices or face stiff fines.
- 61 -
Article 80
Introduction
WA
ME
ND
MT
MN
OR
ID
VT
MI
WI
SD
NY
WY
MI
IA
NE
NV
PA
UT
IL
CO
CA
DE
MD
WV
KS
VA
KY
NC
AZ
TN
OK
NM
SC
AR
MS
TX
AL
GA
LA
AK
FL
Overlap Between
SBC and BOCA
Physical Hazards
Uniform Building
Code (UBC)
Standard Building
Code (SBC)
Overlap Between
SBC and UBC
Basic Building
Code (BOCA)
- 62 -
NJ
MD
OH
IN
MO
NH
MA
CT
RI
Gas Stations
Health Hazards
Chlorine Hazards
Retroactive Application
Recommendations
- 63 -
Stations
Types of Stations
Five Types
What is Different?
While the basic gas chlorine station is the same for all five
of these types of systems, there are some unique differences. The differences will be noted when appropriate.
Building
Reference
Location
Structure
Materials
Door
Windows
- 64 -
Gas Stations
Electrical
Exterior Switches
Heat
Ventilation System
Vent
Exhaust Rate
Vent Exhaust
Air-Treatment System
- 65 -
VENT
- 66 SPRINKLER SYSTEM
SHOWER
Gas flo
VENT TO SCRUBBER
CHLORINE
LEAK DETECTOR
CAUSTIC SODA
SCRUBBER
EYE WASH
AIR
PACK
VENT
EMERGENCY POWER
Gas Stations
especially true if a pressure header system was being
used with more than one tank in the ON position.
Containment of Scrubber
Negative Pressure
Other Considerations
Eye Wash & Shower
Floor Drains
Sprinkler System
Secondary Containment
Emergency Power
- 67 -
Vandals
DOT & UN ID
POISON
GAS
CHLORINE
1017
2.3
2.3
Approved placard
with DOT identification
Approved placard
Need additional 1017 placard
NFR Placard
Chemical Storage
Blue = Health
Red = Flammability
Yellow = Reactive
White = Special notice
YELLOW DIAMOND
BLUE DIAMOND
OX
WHITE DIAMOND
- 68 -
Gas Stations
Scrubber System Operation
A scrubber system consists of a tank, venturi, pump,
and packed tower.
Air Flow
Treatment
Scrubber System
VENTURI
Caustic Soda
Treated air,
chlorine below
15 ppm
Components
m
Air frorine room
lo
h
c
CAUSTIC SODA
SCRUBBER
2 Venturi - A device used to create a vacuum. The vacuum is created by transferring pressure head to velocity head.
This transfer is the result of a reduction in cross sectional area of the device while maintaining the flow. Named
after G. B. Venturi (1746 - 1822).
- 69 -
Cylinders
Sizes
Cylinder Temperature
Secured
LIQUID
LEVEL
(full)
1" x 12"
Method of securing 100 and 150 pound
chlorine cylinders in an earthquake zone.
- 70 -
GAS
Gas Stations
Storage Space
EMPTY
Impact of Temperature
FULL
- 71 -
Automatic Shutdown
Tied to Leak Detector
Reliquifaction
System Prone to Reliquifaction
Temperature Difference
Use Graph
Prevention
- 72 -
Gas Stations
VAPOR PRESSURE
OF LIQUID CHLORINE
600
CURVE DATA
F
500
PSIG
0
8
14
28
47
71
102
140
187
243
310
389
480
587
-29
-10
0
20
40
60
80
100
120
140
160
180
200
220
400
300
200
LIQUID
GAS
100
0
-20
20
40
60
80
TEMPERATURE F
- 73 -
Piping System
Based on Station Type
LIFE LINE
HEADER
EMPTY
CHLORINATOR
VENT
FULL
PIGTAIL
DISCHARGE
GAUGE
ROOM VENT
SCALES
CHLORINATOR
AUXILIARY PUMP
Y STRAINER
Overview
Basic Components
- 74 -
Gas Stations
FULL
EMPTY
AUXILIARY VALVE
CYLINDER
VALVE
YOKE
- 75 -
PRESSURE
REGULATOR
CYLINDER
VALVE
SUPERIOR
YOKE
The Details
Pigtail
Header
One-ton Containers
Gauges
3 Monel - Also monel metal, an acid resisting alloy of nickel (60 - 70%), copper (25 - 35%), iron, manganese, carbon,
and silicon, used in chemical handling. Named after Ambrose Monel.
- 76 -
Gas Stations
Line to the Injector
- 77 -
CHLORINE
LEAK DETECTOR
CHLORINATOR
SCALES
ow
Gas fl
VENT
Automatic
Switchover
Vacuum
Regulating
Valve
150 LB
CHLORINE
CYLINDER
CAUSTIC SODA
SCRUBBER
VENT
INJECTOR
FROM AUXILIARY
PUMP
The remote vacuum regulator or automatic switchover device is connected directly to the cylinder valve
using a yoke.
VACUUM
REGULATOR
CYLINDER
VALVE
SUPERIOR
YOKE
Pigtails
Header
- 78 -
Gas Stations
VACUUM GAUGE
BALL
ISOLATION
VALVE
VACUUM REGULATOR
Gauges
Small Systems
One-ton Containers
When a remote
vacuum
device is
used with
the oneton
container,
a one inch
by one foot
VACUUM REGULATOR
long black iron
drip tube must be
HEATER
installed between the
cylinder valve and the
vacuum regulator. The
DRIP LEG
function of the drip tube is to
collect the liquid from the cylinder
eductor tube. Attached to the drip tube is
a 120-volt heater assembly. Its function is to evaporate
any liquid chlorine that exits the container.
Line to the Injector
- 79 -
- 80 -
Gas Stations
Liquid System
Basic Components
EXPANSION TANK
FILTER
HEADER
HEADER VALVE
RUPTURE DISK
CHLORINATOR
CYLINDER VALVE
EVAPORATOR
AUXILIARY VALVE
TRUNNION
Pigtail
Expansion Tanks
- 81 -
Filter
PRV
Vent
Drip Leg
Gauges
- 82 -
Gas Stations
Piping
EXPANSION TANKS
EXPANSION TANKS
RUPTURE DISK
DEW POINT
INDICATOR
AIR
AIR
Cl2 GAS
Cl2 GAS
LIQUID Cl2
FLOW
INDICATOR
LIQUID Cl2
LIQUID Cl2
Cl2 GAS
WATER
TO WASTE
Expansion Tanks
Rupture Disk
- 83 -
Evacuation System
Lighting
Platform
Unloading Piping
Flexible Connection
Air Padding
- 84 -
Gas Stations
Scales
Function
Types
The net weight scales are the most popular. The most
common type used with 100 and 150 pound cylinders
weighs two cylinders separately. This allows the
operator to determine visually the amount of chlorine
left in each cylinder.
Chains
Scales
eight
Net W
10
s
Scale
eam
B
e
c
Balan
- 85 -
1-ton Containers
Most Popular
Restraints
- 86 -
Gas Stations
Chlorinators
Types
There are a wide variety of types and brands of chlorinators in use today. The most common are as follows:
Wallace and Tiernan, Capital Controls, and Fisher
and Porter floor mounted units
The Wallace and Tiernan V-75 wall mounted units
The Wallace and Tiernan V-100 and V-500 wall
mounted units
The Wallace and Tiernan Sonix 100 cylinder
mounted units
The Capital Controls cylinder mounted units
Regal cylinder mounted units
Fisher and Porter cylinder mounted units
Operation
Remote Vacuum
Discussion of Operation
- 87 -
Water Supply
Basic Piping
Types of Pumps
Close Coupled
End-suction Centrifugal Pump
Regenerative Turbine
Configuration
Frame Mounted
- 88 -
Close Coupled
Gas Stations
Two Styles - Frame Mounted
WEAR PLATES
SHAFT
MECHANICAL SEAL
IMPELLER
WEAR PLATE
BEARING
WEAR PLATE
IMPELLER
BEARING
MECHANICAL SEALS
Uses
Self-Priming
Unique Case
- 89 -
Theory of Operation
Water Enters Impeller
discharge
STRIPPER
- 90 -
CONCENTRIC
CASE
Gas Stations
As the water reaches the discharge port, it is
prevented from continuing on by a small metal device
called a stripper, which lies very close to the impeller.
The water is then directed out of the pump.
suction
discharge
stripper
STRIPPER
Comparison/Centrifugal
Subject to Wear
Bypass Valve
- 91 -
Piping System
Not Pump Dependent
Components
Valves
Y Strainer
Check Valve
PUMP DISCHARGE
TO INJECTOR
NEEDLE VALVE
PRESSURE REGULATOR
PUMP SUCTION
Y Strainer
STRAINER AND
BLOW-OFF VALVE
- 92 -
Gas Stations
Pressure Relief
Injector
Gauges
INJECTOR
WATER
DIFFUSER
- 93 -
HOSE CONNECTION
Diffuser
CORPORATION STOP
WELDED COUPLING
(if required)
PIPE LINE
SOLUTION DISTRIBUTION
Tank Diffuser
Contact Time
- 94 -
Gas Stations
Cross Connection
TE
FIL
ION
LAT
NORMAL FLOW
U
CC
FLO
BACKFLOW
FIN
ISH
ED
WA
TE
CLEARWELL
STATIC
MIXER
ER
ER
AT
AT
W
AW
DW
E
ISH
FIN
- 95 -
Normal Operation
Typical Inspection
Routine Testing
Auxiliary Valves
Pigtails - Copper
Pigtail - Plastic
- 96 -
Gas Stations
Safety Equipment
Later Discussion
Respiratory Protection
Regulation Requirements
Emergency Response
Repair Kits
- 97 -
- 98 -
Gas Stations
Operator
Porameter
Position
Month
Residual mg/L
Dosage mg/L
Pounds Used
Cylinder wt.
Production
Day
Meter Reading
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Totals
- 99 -
Month
Day
Operator
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Totals
- 100 -
Gas Stations
Worksheet
1. The most common type of pump used as a booster pump in gas chlorination stations
is the ______________ ______________.
3. What problems can occur when electrical panels and electric motors are placed
inside a gas station?
5. The two most common types of scales used to weigh gas cylinders:
a.
b.
- 101 -
I
A
A.
F.
B.
G.
C.
H.
D.
I.
E.
9. What is the normal life expectancy of each of the following items?
a. Pigtails
b. Auxiliary Valves
c. Black Iron Headers
- 102 -
Gas Stations
10. What are the indicators to determine that the following items need to be replaced?
a. Pigtails
b. Auxiliary Valves
c. Black Iron Headers
11. .. will occur any time chlorine gas is moved from a ____________ temperature to a
___________ temperature. One of the ways to prevent reliquifaction is to place a
____________________ in the gas line.
- 103 -