Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Table of Contents
INTRODUCTION
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4
SYSTEM DESIGN
D e s ign O ve r v i ew . . . . . . . . . . . . . . . . . . . . . .3.2
K ey p ads an d C on ta ct C l os u re s . . . . . . . . . . . .7.2
European-style . . . . . . . . . . . . . . . . . . .7.4
seeTouch . . . . . . . . . . . . . . . . . . . . . . .7.7
Se r i e s O ve r vi ew . . . . . . . . . . . . . . . . . . . . . . .3.8
Architrave . . . . . . . . . . . . . . . . . . . . . .7.17
COMPONENT OVERVIEW
L ocal C ontrol s
Maestro . . . . . . . . . . . . . . . . . . . . . . . .4.2
GRAFIK Eye . . . . . . . . . . . . . . . . . . . . .4.8
GRAFIK Integrale . . . . . . . . . . . . . . . . . .4.14
Wallbox Power Module . . . . . . . . . . . . . .4.17
Pr oce s s or s . . . . . . . . . . . . . . . . . . . . . . . . . .8.2
8 Series Processors . . . . . . . . . . . . . . . .8.8
4 Series Processors . . . . . . . . . . . . . . . .8.12
L ow-voltage Encl os ur e s . . . . . . . . . . . . . . . . .9.2
W i r e l e s s E q u i p m e nt
Hybrid Signal Repeater . . . . . . . . . . . . . .10.2
Wireless Tabletop Keypads . . . . . . . . . . .10.5
Sivoi a Q ED . . . . . . . . . . . . . . . . . . . . . . . . . .11.2
O t h e r Eq u i p m e n t
Link Extender . . . . . . . . . . . . . . . . . . . .12.2
Auxiliary Power Supply . . . . . . . . . . . . . .12.4
Low-voltage Transformers . . . . . . . . . . . .12.7
Wire Landing Board . . . . . . . . . . . . . . . .12.10
C ol our s and F in is h e s . . . . . . . . . . . . . . . . . . .13.2
1.1
Introduction
2.1
Introduction to HomeWorks
INTRO DUC TIO N
Increased security
Added convenience
Improved aesthetics
ADDED CONVENIENCE
INCREASED SECURITY
2.2
www.lutron.com
Introduction to HomeWorks
IMPROVED AESTHETICS
2.3
Features
INTRO DUC TIO N
LUTRON QUALITY
SECURITY
FA I L - S A F E O P E R AT I O N
AESTHETIC CONSISTENCY
POWER-FAILURE MEMORY
2.4
www.lutron.com
ASTRONOMICAL TIMECLOCK
CONDITIONAL LOGIC
Features
PROGRAMMING FLEXIBILITY
VA C A T I O N M O D E
I N T E G R AT I O N
B AC K L I T K E Y PA D S
2.5
Notes
INTRO DUC TIO N
2.6
www.lutron.com
SYS TE M DE S IG N
System
Design
3.1
Design Overview
System design begins with drawings of the home. The
system design depends on customer requirements and
the homes lighting (load types, wattages and
quantity). HomeWorks has multiple system design
options:
PREWIRE DESIGN
SYS TE M DE S IG N
LOCALISED DESIGN
HYBRID DESIGN
3.2
www.lutron.com
Prewire Design
Prewire design allows homes to be wired for a
HomeWorks system to be added in the future. The
prewire is completed during the construction phase at
a minimal cost. Initially, standard switches are
installed in the home. Later, when the client decides
to add a HomeWorks system, no renovations or
rewiring are required. Simply install Wallbox Power
Modules into the remotely mounted LINCTM (Lutron
INtegrated Control) prewire boxes and replace the
standard switches with keypads, and add a HomeWorks
processor.
SYS TE M DE S IG N
Master Bath
Kitchen
Bath
Bedroom
Family
Room
Study
Foyer
Garage
Dining
Room
Master
Bedroom
Living
Room
3.3
Centralised Design
A centralised design uses Remote Power Modules to
control all lighting loads. The Remote Power Modules
are mounted in power panels, located in equipment
rooms or electrical closets. The clients control the
lights from keypads, providing maximum flexibility
while minimising the number of controls on the wall.
Keypads have the ability to perform any function from
control of a single light to control of every light.
SYS TE M DE S IG N
Master Bath
Kitchen
Bath
Bedroom
Family
Room
Study
Foyer
Master
Bedroom
Garage
Dining
Room
Living
Room
Keypad
Remote Power Module
Processor
3.4
www.lutron.com
Localised Design
SYS TE M DE S IG N
Fail-safe operation
Prewire compatible
Master Bath
Kitchen
Bath
Bedroom
Family
Room
Study
Foyer
Master
Bedroom
Garage
Dining
Room
Keypads
Maestro dimmer
GRAFIK Eye
Living
Room
3.5
Hybrid Design
A hybrid design for HomeWorks combines the benefits
of both centralised and localised designs. Typically,
local lighting controls are used in smaller rooms where
simple controls are desired. In larger rooms, lighting
loads are typically wired to remote dimming
components. Keypads are placed throughout the home,
providing control wherever it is desired.
In this design, areas of the house that have been prewired can be easily added to the system at a later
date. This is ideal for the client who would like to
start with a basic system and then expand it later.
SYS TE M DE S IG N
Master Bath
Kitchen
Bath
Bedroom
Family
Room
Study
Foyer
Master
Bedroom
Garage
Dining
Room
Keypads
Maestro
GRAFIK Eye
3.6
Living
Room
C O MPO NE NTS
Technical Support: hwisupport@lutron.com
3.7
Series Overview
8 SERIES
4 SERIES
SYS TE M DE S IG N
System
designs
supported
Dimming
capability
Control capability
per processor
Integration
capability
Wireless
capability
3.8
8 series
4 series
centralised
yes
no
localised
yes
yes
hybrid
yes
yes
prewire
limited
yes
dimming panels
yes
no
Wallbox
Power Modules
yes
yes
local lighting
controls
yes
yes
typical
zone count
20 to 256
(256 maximum)
20 to 96
(256 maximum)
typical
keypad count
5 to 40
(96 maximum)
5 to 20
(96 maximum)
motor control
direct
thru interface
RS-232 integration
2 ports / processor
1 port / processor
ethernet
1 port / processor
1 port / processor
yes
yes
signal repeaters
5 per processor
5 per processor
tabletop keypads
32 per system
32 per system
www.lutron.com
Dining LINC
Lounge LINC
Lounge LINC
Lounge
Dining
Dining
LINC
Dining
LINC
Lounge LINC
SYS TE M DE S IG N
Dining LINC
Dining LINC
Dining LINC
Master Bedroom LINC
Hall LINC
Lounge LINC
Hall LINC
Master Bedroom LINC
Master Bedroom
Master
Bedroom
LINC
Master
Bedroom
LINC
Master
Bedroom
LINC
Hall LINC
Master Bedroom
LINC
Master
Master
Bedroom
Bedroom
LINC
LINC
Hall
LINC
Kitchen
Hall
Master
Bedroom
LINC
Master
Bedroom
LINC
Hall LINC
Hall LINC
Hall LINC
Hall LINC
Hall LINC
3.9
GRAFIK Eye
SYS TE M DE S IG N
Dimmers
Switches
Ethernet
link
Other equipment
through RS-232
Keypads
Hybrid
Signal
Repeater
Sivoia QED
Shades and Draperies
3.10
Tabletop Keypads
www.lutron.com
8 Series Processor
Wallbox Power Modules
Dimmers
SYS TE M DE S IG N
GRAFIK Eye
Switches
Ethernet
link
Other equipment
through RS-232
Keypads
Hybrid
Signal
Repeater
Sivoia QED
Shades and Draperies
Tabletop Keypads
3.11
4 series
HomeWorks processor
SYS TE M DE S IG N
Connect to
other devices
and home
networks using
standard
ethernet cable.
Wire type B
maximum
15m
(50 feet)
total
point-topoint
Wire type A
maximum
305m
(1,000 feet)
total
daisy-chain
To additional
processors. 16
maximum per
HomeWorks
system.
3.12
www.lutron.com
Tabletop keypad
32 per system
Wire type A
maximum 10 keypads per home run
maximum 305m (1,000 feet) per home
run
maximum 1220m (4,000 feet) total wire
length.
Any configuration.
Wire type A
maximum 610m (2,000
feet) total
daisy-chain
Keypads
HWI-ENC-CC
Contact
Closure
enclosures
SYS TE M DE S IG N
Signal Repeater
5 per processor
To additional keypads/
Contact Closure boards
(maximum 32 devices
per link).
Keypads/
Contact Closure Boards
Dimmer Interfaces/Q96
Wire type A
maximum 305m (1,000
feet) total
daisy-chain
HWI-CCI-8 Contact
Closure Input board
(wire inputs from
driveway sensors,
photocells, security
systems, etc.)
HWI-CCO-8 Contact
Closure Output board
(wire outputs to
shades, screens, gates,
spas, thermostats,
etc.)
Maestro local
lighting controls
HWI-LV17-230
Low-voltage
enclosure
HWI-H48
dimmer
interface
3.13
SYS TE M DE S IG N
Connect to other
devices and home
networks using
standard ethernet
cable.
Wire type B
maximum 15m
(50 feet) total
point-to-point
Wire type A
maximum
305m
(1,000 feet)
total
daisy-chain
To additional
processors. 16
maximum per system.
HWI-PNL-8-CE
Remote
Power Panel
PBK8-40-13-10-CE or
PBK8-40-10-CE Remote
Power Panels
Remote
Power
Modules
HWI-PNL-5-CE
Remote
Power Panel
Wire type A
maximum 305m
(1,000 feet) total
daisy-chain
3.14
HWI-MI-230
Module
Interface
To additional Module
Interfaces. Maximum
per Module Interface
Link is 16
www.lutron.com
Tabletop keypad
32 per system
Link 8 only
Type C: One pair 1.0-0.5mm2 (#18-22 AWG) twisted shielded Class 2/PELV wire.
Wire type A
maximum 10 keypads per home run
maximum 305m (1,000 feet) per home
run
maximum 1220m (4,000 feet) total wire
length.
Any configuration.
Wire type A
maximum 610m (2,000
feet) total
daisy-chain
Keypads
HWI-ENC-CC
Contact
Closure
Enclosures
SYS TE M DE S IG N
Signal Repeater
5 per processor
To additional keypads/
Contact Closure boards
(maximum 32 devices
per link).
Keypads/
Contact Closure Boards
Dimmer Interfaces/Q96
Wire type A
maximum 305m (1,000
feet) total
daisy-chain
HWI-CCI-8 Contact
Closure Input board
(wire inputs from
driveway sensors,
photocells, security
systems, etc.)
HWI-CCO-8 Contact
Closure Output board
(wire outputs to
shades, screens, gates,
spas, thermostats,
etc.)
3.15
Notes
SYS TE M DE S IG N
3.16
www.lutron.com
Local
Controls
4.1
Maestro controls can be mounted together in a multigang wallbox. The load rating for each control must be
derated when ganging with other controls. See page
4.6.
DIMMING CONTROL
L O A D R AT I N G S
SWITCHING CONTROL
L O A D R AT I N G S
I N S TA L L AT I O N N O T E
4.2
www.lutron.com
Input voltage
220-240VAC, 50/60Hz
Regulatory approvals
CE, C-Tick
Environment
One pair twisted shielded 0.5-1.0mm (#18-22 AWG) Class 2/PELV wiring.
Low-voltage wiring
configuration
Daisy-chain, star, T-tap, home run. Each Maestro bus may have a maximum 150m
(500 feet) per wire run but may not exceed 305m (1000 feet) total per bus.
Maximum of eight devices per dimmer interface bus.
Addressing
Via the HomeWorks utility using unique device serial numbers. Units must be
installed prior to addressing. Counts as 1 of 8 addresses on a Maestro bus. The
device may be addressed without removing it from the wall.
ESD protection
Surge protection
Fail-safe operation
If communication with the processor is interrupted, all Maestro controls will still
provide local control.
Dimensions
Mounting
Ganging
When multiple Maestro controls are located in a single wallbox, the control must
be derated. See page 4.6. If mounting one control above another, leave at least
11.4cm (4-1/2 inch) vertical spacing between them.
Accessory controls
Shipping weight
C O MPO NE NTS
4.3
Maximum load
single-gang: 500W/VA
end gang:
450W/VA
middle gang: 400W/VA
Note: Mixed incandescent and electronic low-voltage loads reduces load capacity
an additional 100 watts.
Minimum load
50W/VA
Line-voltage wiring
See figures 5 and 7, pages 4.6-4.7. Standard single-pole, 2-way, and 3-way wiring.
Maximum load
2A
Minimum load
10W/VA
Line-voltage wiring
See figures 6 and 8, page 4.7. Single-pole, 2-way, and 3-way wiring. A neutral
wire connection is required.
C O MPO NE NTS
HWA-5E-CE, HNA-5E-CE
Maximum load
Minimum load
Line-voltage wiring
See figure 7, page 4.7. Standard single-pole, 2-way, and 3-way wiring.
HWA-2ANS-CE, HNA-2ANS-CE
Maximum load
Minimum load
Line-voltage wiring
See figure 8, page 4.7. Standard single-pole, 2-way, and 3-way wiring.
(1) To reduce the risk of overheating and possibly damaging other equipment, do not install HWA-5E-CE or HNA-5E-CE to control
receptacles, motor-operated appliances, fluorescent lighting, or magnetic low-voltage transformer loads. Do not install HWA-2ANS-CE or
HNA-2ANS-CE to control receptacles or motor-operated appliances.
(2) Because low-voltage transformers vary widely in efficiency, the input VA of each transformer should be measured directly. If this is
not possible, use the maximum lamp wattage figures, which have a built-in safety margin.
4.4
www.lutron.com
A
Low-voltage wiring
Power wiring
B
A
B
C
D
mm
119
75
7.6
34.8
Wallbox
inches
4-11/16
2-15/16
5/16
1-3/8
Figure 2 wire installation
C O MPO NE NTS
Figure 1 dimensions
Wallbox
(Lutron model
241218 may be
used)
Control
Wallplate
adapter
Wallplate
4.5
Minimum
load
Control
all cases
single-gang
end gang
middle gang
HWA-5E-CE
50W/VA
500W/VA
450W/VA
400W/VA
HNA-5E-CE
50W/VA
500W/VA
450W/VA
400W/VA
HWA-2ANS-CE
10W/VA
2A
2A
2A
HNA-2ANS-CE
10W/VA
2A
2A
2A
HA-RD
n/a
n/a
n/a
n/a
HA-RS
n/a
n/a
n/a
n/a
Single gang
MIDDLE of gang
C O MPO NE NTS
LUTRON
PELV
L1 1
Lighting load
Live
220/240 VAC 50 Hz
Neutral
4.6
www.lutron.com
LUTRON
PELV
L 1 1N
Lighting load
Live
220/240 VAC 50 Hz
Neutral
Remote Dimmer
Remote Dimmer
LUTRON
Dimmer
22
LUTRON
LUTRON
PELV
L1 1
L1 1
L1 1
Lighting
load
Live
Neutral
Remote switch
Remote switch
LUTRON
LUTRON
Switch
22
C O MPO NE NTS
220/240 VAC 50 Hz
LUTRON
PELV
L1 1
L1 1
L 1 1N
Lighting
load
Live
220/240 VAC 50 Hz
Neutral
Up to nine Maestro remote dimmers or switches may be connected to the Maestro dimmer or switch. Total distance between
all devices should not exceed 50m (165 feet).
4.7
Fade
Scenes
CONNECTION TO PROCESSOR
ACCESSORY CONTROLS
Handheld Infrared
Remote Control Transmitters
GRX-IT, GRX-8IT (white only)
Controls four or eight scenes plus master
raise/lower and off.
C O MPO NE NTS
4.8
Zones
www.lutron.com
Input voltage
220-240VAC, 50/60Hz
Regulatory approvals
CE, C-Tick
Load types
Incandescent, magnetic low voltage, electronic low voltage (requires Lutron lowvoltage transformers), fluorescent non-dim, neon/cold cathode. The outputs are
also compatible with Lutron Power Boosters and interfaces on in section 6
Minimum load
Environment
Cooling method
Passive cooling.
Line-voltage connections
Two pair [one pair 1.0mm (#18 AWG), one pair 0.5-1.0mm (#18-22 AWG) twisted
shielded] Class 2/PELV wire. Lutron wire model GRX-CBL-346S-500 may be used.
Low-voltage wiring
configuration
Low-voltage connections
One 4-pin removable terminal block. Each of the four terminals will accept up to
two 1.0mm (#18 AWG) wires. Do not connect terminal 2 on processor
communication link connector or between GRX units.
C O MPO NE NTS
Addressing
ESD protection
Surge protection
Air gap
Power-failure memory
Non-volatile RAM.
Fail-safe operation
If communication with the processor is interrupted, all GRAFIK Eye controls will
still provide local control.
Dimensions
Mounting (CE)
All CE-compliant units mount in 4-gang US wallbox 7.0cm (2-3/4 inches) deep
minimum, 8.9cm (3-1/5 inch) deep recommended for ease of wiring. Lutron
model 241400 may be used.
Shipping weight
.9kg (2 pounds)
4.9
Voltage
Maximum watts
per zone
Maximum watts
per control unit
CE
non-CE
CE
non-CE
CE
non-CE
Wallbox
size
(gangs)
2-zone
220-240V
800
1200
1600
1600
3-zone
220-240V
800
1200
2300
2400
4-zone
220-240V
800
1200
2300
3000
6-zone
220-240V
800
1200
2300
3000
C O MPO NE NTS
4.10
www.lutron.com
149mm
15/16"
(49mm) inches)
(1-15/16
CE
4116mm
9/16"
(4-9/16
(116mm)
inches)
2-zone
2-ZONE
3-ZONE
3-zone
4-ZONE
6-ZONE
4-zone
6-zone
Width
NON CE
2-ZONE
141mm
227mm
(8 5/16") (5 9/16")
3-ZONE
184mm
227mm
(8 5/16") (7 5/16")
4-ZONE
227mm
227mm
(8 5/16") (8 5/16")
6-ZONE
227mm
227mm
(8 5/16") (8 5/16")
CE
Width
Width
NON CE
CE
227mm
141mm
227mm
(8 5/16") (5 9/16")
(8-5/16 inches)
227mm
184mm
(8 5/16") (7 5/16")
227mm
227mm
227mm
(8-5/16
inches)
(8 5/16")
(8 5/16")
227mm
227mm
(8 5/16")227mm
(8 5/16")
(A)
ZO N E
ZO N E
ZO N E
ZO N E
ZO N E
ZO N E
FADE
M S
T E MP O R ARFY
ZO N E S
MAST E R
117mm
(4-9/16
117mm
inches)
(4 9/16")
ZO N E
non-CE
141mm
(5-9/16 inches)
ZO N E
ZO N E
ZO N E
ZO N E
ZO N E
FADE
M S
T E MP O R ARFY
ZO N E S
MAST E R
117mm
(4 9/16")
184mm
(7-5/16 inches)
(8-5/16 inches)
227mm
(8-5/16 inches)
227mm
(8-5/16 inches)
227mm
(8-5/16 inches)
Figure 1 dimensions
C O MPO NE NTS
5/16"
8mm
(8mm)
(5/16 inches)
Figure 2 mounting
4.11
Load 2
Load 4
Earth
Load 6
Live
(2) 2.5mm
Neutral
(2)
2
2.5mm
ZONE2
ZONE4
ZONE6
ZONE1
ZONE3
ZONE5
CU
WIREONLY
Class2 USA
SS
2
HOT/LIVE 1 2 34 CLA
IE
CV
PEL
SSA
NEUT
RAL
Load 1
Load 2
Load 3
2
(2) 2.5mm
ZONE2
ZONE4
ZONE6
(2)
2
2.5mm
C O MPO NE NTS
4.12
SSA
PEL
1 V
2 3ONL
4Y
COM 12V
MUX XMU
GRX-3106-CE
230V
~50/60Hz
ZONE
CA
ITY
40-800W
UNI
T CA
PPA
C
ACITY
: : 10A,
2300W
ZONE1
ZONE3
ZONE5
N
(2) 2.5mm
Load 1
Distribution
panel
Load 3
Earth
Load 5
Live
Neutral from
distribution panel
Neutral
2
(2) 2.5mm
www.lutron.com
ZONE 2
ZONE 4
ZONE 1
CU WIRE ONLY
ZONE 3
ZONE 6
ZONE 5
CLASS 2
HOT
SSA
1 2 3 4
USA CLASS 2
IEC PELV
NEUTRAL
Wire to other
WPM/GRX control units
ZONE 2
ZONE 4
CU WIRE ONLY
ZONE 6
HOT
SSA
CLASS 2
1 2 3 4
USA CLASS 2
IEC PELV
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
HOT
NEUTRAL
SSA
ZONE 1
CU WIRE ONLY
ZONE 3
ZONE 5
CLASS 2
USA CLASS 2
IEC PELV
1 2 3 4
NEUTRAL
C O MPO NE NTS
Notes:
Connection between #2 terminals is not made between GRAFIK
Eye control units and the HomeWorks processor.
Connection between #2 terminals is not made between two
GRAFIK Eye control units.
A maximum of 8 GRX and WPM may be wired to one processor
link.
4.13
Fade
Scenes
Zones
C O MPO NE NTS
4.14
www.lutron.com
Control unit
Model
GXI-3104-T-CE, GXI-3504-T-CE
Input voltage
220-240VAC, 50/60Hz
Regulatory approvals
Load types
Minimum load
Environment
Cooling method
Passive cooling.
Line-voltage connections
Two pair [one pair 1.0mm (#18 AWG), one pair 0.5-1.0mm (#18-22 AWG) twisted
shielded] Class 2/PELV wire. Lutron wire model GRX-CBL-346S-500 may be used.
Low-voltage wiring
configuration
Low-voltage connections
One 4-pin removable terminal block. Each of the four terminals will accept up to
two 1.0mm (#18 AWG) wires. Do not connect terminal 2 on processor
communication link connector or between GXI units.
Addressing
ESD protection
Surge protection
Air gap
Power-failure memory
Non-volatile RAM.
Fail-safe operation
Dimensions
Mounting (CE)
All CE-compliant units mount in 4-gang US wallbox 7.0cm (2-3/4 inch) deep
minimum, 8.9cm (3-1/5 inch) deep recommended for ease of wiring. Lutron
model 241400 may be used.
Shipping weight
.9kg (2 pounds)
C O MPO NE NTS
4.15
Load 1
Distribution
panel
Earth
Live
Neutral
Load 2
DL/SL
DL/SL
DL/SL
DL/SL
Live
PELV ONLY
(2) 2.5mm
}
}
}
}
Neutral (2) 2
2.5mm
1
2
3
4
1 2 3 4
- + - + - + - +
Load 3
+
-
(2) 2.5mm
Load 4 -ballast
C O MPO NE NTS
4.16
www.lutron.com
Default scene
status LED
WPM BENEFITS:
C O MPO NE NTS
D E FAU LT S C E N E B U T T O N
4.17
C O MPO NE NTS
4.18
Model
Input voltage
220-240VAC, 50/60Hz
Regulatory approvals
Load types
Incandescent, magnetic low voltage, electronic low voltage (requires Lutron lowvoltage transformers), fluorescent non-dim, neon/cold cathode. The outputs are
also compatible with Lutron Power Boosters and interfaces in section 6.
Minimum load
Environment
Cooling method
Passive cooling.
Line-voltage connections
Two pair [one pair 1.0mm (#18 AWG), one pair 0.5-1.0mm (#18-22 AWG) twisted
shielded] Class 2/PELV wire. Lutron wire model GRX-CBL-346S-500 may be used.
Low-voltage wiring
configuration
Low-voltage connection
One 4-pin removable terminal block. Each of the four terminals will accept up to
two 1.0mm (#18 AWG) wires. Do not connect terminal 2 on processor
communication link connector or between WPM units.
Addressing
ESD protection
Surge protection
Air gap
Power-failure memory
Non-volatile RAM.
Fail-safe operation
Dimensions
Mounting
4-gang US wallbox, 70mm (2-3/4 inches) deep minimum, 89mm (3-1/2 inches)
deep recommended for ease of wiring. If mounting one control above another,
leave at least 11.4cm (4-1/2 inches) vertical spacing between them. Lutron
model 241400 may be used.
Shipping weight
0.9kg (2 pounds)
www.lutron.com
126mm
(5 inches)
C O MPO NE NTS
126mm
(5 inches)
Faceplate
Figure 3 mounting
4.19
1-8
C O MPO NE NTS
ZONE 2
ZONE 4
ZONE 1
CU WIRE ONLY
ZONE 3
ZONE 6
HOT
SSA
Pin 1 - One 1.0mm (#18 AWG) for common
Pin 2 - Do not connect
Pins 3 and 4 - One pair 1.0-0.5mm (#18-22 AWG)
twisted/shielded for data
ZONE 5
CLASS 2
1 2 3 4
USA CLASS 2
IEC PELV
NEUTRAL
Wire to other
WPM/GRX control units
4.20
www.lutron.com
C O MPO NE NTS
Remote Power
Modules
and
Remote Power
Panels
5.1
MOTOR MODULE
(MODEL HW-RPM-4M-230)
C O MPO NE NTS
5.2
www.lutron.com
Incandescent, magnetic low voltage, electronic low voltage (requires Lutron lowvoltage transformers) neon/cold cathode, fluorescent non-dim. The outputs are
compatible with Lutron Power Boosters and interfaces in section 6.
Maximum load
Wiring
Terminal blocks in the power panel will accept one 1.0-2.5mm (#18-10 AWG)
wire or two 1.0-1.5mm (#18-16 AWG) wires. See figure 1, page 5.6.
1
Technology
Interference
suppression
Air gap
Maximum load
Wiring
Terminal blocks in the power panel will accept one 1.0-2.5mm (#18-10 AWG)
wire or two 1.0-1.5mm (#18-16 AWG) wires.
Technology
Interference suppression
Air gap
C O MPO NE NTS
5.3
Maximum load
1/2 HP per circuit. 5A maximum per circuit for motor loads, 1.5A maximum per
circuit for tungsten loads.
Wiring
Terminal blocks will accept one 1.0-2.5mm (#18-10 AWG) wire or two 1.0-1.5mm
(#18-16 AWG) wires. Requires that four additional terminal blocks be mounted
onto the DIN rail assembly. See figure 2, page 5.6.
Technology
Interference
suppression
Air gap
Non-dim loads.
Maximum load
Wiring
Terminal blocks will accept one 1.0-2.5mm (#18-10 AWG) wire or two 1.0-1.5mm
(#18-16 AWG) wires. Requires the installation of four additional gray terminal
blocks and three additional black terminal blocks to be mounted on to the DIN
rail assembly. Gray terminal blocks accept one 0.75-10mm (#18-8 AWG) wire or
two 1.5-4.0mm (#16-12 AWG) wires. See figure 3, page 5.6.
1
C O MPO NE NTS
5.4
Technology
Patented SoftswitchTM triac arc suppression technology used to extend relay life.
Interference suppression
Air gap
www.lutron.com
Input voltage
Number of outputs
Regulatory approvals
Environment
Cooling method
Passive cooling.
Heat generated
fully loaded
Dimming modules will generate up to 75 BTUs per hour when fully loaded.
Line-voltage connections
Separate line-voltage feeds at the DIN rail terminal blocks for each RPM. Terminal
blocks should be tightened to .40-.57nM (3.5-5.0 inches-pounds).
Low-voltage
communications
Addressing
Diagnostics
ESD protection
Surge protection
Fail-safe operation
Rotary switch on the RPM allows for manual operation of each load.
Dimensions
Mounting
HWI-PNL-8 and the HWBP-8D Remote Power Panels will hold up to 8 RPMs.
HWI-PNL-5 Remote Power Panel will hold up to 5 RPMs.
C O MPO NE NTS
Note: RPMs may hum slightly and internal relays will click when in use. Mount where such
noise is acceptable. Locate at least 1.8m (6 feet) away from sensitive electronic
equipment.
Shipping weight
Minimum load
5.5
Dimmed
Dimmed
Dimmed
Dimmed
hot
hot
hot
hot
DL
1
DL
2
DL
3
DL
4
L
N
N
NN
N
1
2
3
4
Load
Load
Load
Load
neutral
neutral
neutral
neutral
1
2
3
4
Dimensions
A
B
Red 1
Red 2
mm
inches
99
178
3-7/8
7
Red 3
Red 4
Brown
Blue
Lower
Raise
Lower
Raise
Red 4
Brown
C O MPO NE NTS
Blue
Rotary address switch
4-pin connector for
Module Interface
assembly harness
Figure 2 HW-RPM-4M-230
120-240V live
from distribution
panel
Neutral from
distribution
panel
SH
1
H1
N1
SH
2
H2
N2
SH
3
H3
N3
SH
4
H4
N4
Red 1
Black 1
Control power
Control neutral
Red 2
Black 2
Red 3
Black 3
Red 4
Black 4
Rotary address switch
4-pin connector for
Module Interface
assembly harness
Figure 3 HW-RPM-4R
5.6
www.lutron.com
R O TA R Y A D D R E S S S W I T C H P O S I T I O N
FOR HW-RPM-4U, 4E, 4R, 4A
R O TA R Y A D D R E S S S W I T C H P O S I T I O N
FOR HW-RPM-4M
Position
Module output/purpose
Position
Module output/purpose
1-8
Address for
normal operation
1-8
Address for
normal operation
9, A
Not used
9, A-D
Not used
Output 1 ON
use for temporary lighting
and/or zone testing
Output 2 ON
use for temporary lighting
and/or zone testing
Output 3 ON
use for temporary lighting
and/or zone testing
Output 4 ON
use for temporary lighting
and/or zone testing
All outputs ON
use for temporary lighting
and/or zone testing
C O MPO NE NTS
Enlarged view of
rotary address switch
5.7
Module Interface
Module Interfaces control up to eight RPMs and are
available in two configurations: either integral to a
HomeWorks processor or as a stand-alone component.
Each HomeWorks 8 series processor can control up to
16 Module Interfaces.
S TA N D - A L O N E M O D U L E I N T E R FAC E
(MODEL HWI-MI-230)
View of
stand-alone Module Interface
(HWI-MI-230)
M A N U A L O V E R R I D E C A PA B I L I T I E S
C O MPO NE NTS
5.8
www.lutron.com
Module Interface
Specifications apply to HWI-MI-230 stand-alone Module Interfaces and to Module Interfaces
integral to HomeWorks 8 series processors
Model
Input voltage
Regulatory approvals
CE, C-TICK
Environment
Cooling method
Passive cooling.
Two pair [one pair 1.0mm (#18 AWG), one pair 1.0-0.5mm (#18-22 AWG) twisted
shielded] Class 2/PELV wire. Lutron wire model GRX-CBL-346S-500 may be used.
Low-voltage wiring
configuration
Low-voltage connection
One 4-pin removable terminal block. Each of the four terminals will accept up to
two 1.0mm (#18 AWG) wires.
Addressing
Diagnostics
Three LEDs for troubleshooting communications with the processor and the RPMs.
ESD protection
Surge protection
Miswire Protection
All terminal block inputs are over-voltage and miswire protected against wire
reversals and shorts.
Fail-safe operation
The manual override scene is activated for all RPMs connected to the MI by
closing a switch that is wired between the two manual override terminals. The
switch (or relay) contacts must be rated for switching 50 milliamps at 30VDC. A
single switch can be used for multiple MIs wired in parallel, but proper polarity
must be maintained across all units. In this configuration, the switch must be
rated for the sum of the current for all of the MIs connected (e.g., six MIs wired
to a single manual override switch requires a switch rated for 300 milliamps at
30VDC).
C O MPO NE NTS
5.9
Module Interface
Specifications apply to HWI-MI-230 stand-alone Module Interfaces and to Module Interfaces
integral to HomeWorks 8 series processors
Mounting dimensions
Mounting
Shipping weight
1.8kg (4 pounds)
Output
Compatible with HW-RPM-4U dimming module, HW-RPM-4E ELV module, HW-RPM4M motor module, HW-RPM-4R power relay module, and HW-RPM-4A adaptive
dimming module.
C O MPO NE NTS
5.10
www.lutron.com
Module Interface
75mm (3 inches)
333mm
(13-1/8 inches)
C O MPO NE NTS
5.11
F I V E - M O D U L E R E M O T E P O W E R PA N E L
(MODEL HWI-PNL-5-CE)
EIGHT-MODULE
R E M O T E P O W E R PA N E L
(MODEL HWI-PNL-8-CE)
Module Interface
Remote Power
Modules
8 series
processor
Module
Interface
C O MPO NE NTS
Remote
Power
Modules
5.12
Processor (1)
Remote Power Modules
(8 maximum)
www.lutron.com
Capacity
Regulatory approvals
CE, C-TICK
Environment
Cooling method
Passive cooling.
Mount in a place where the vented cover will not be blocked.
Heat generated
fully loaded
Line-voltage
connections
Use copper wire only, supply conductors 60/75C. DIN rail-mounted terminal
blocks provided for line-voltage Remote Power Module (RPM) wiring and
processor/MI power. Terminal blocks should be tightened to .40-.57nM (3.5-5.0
inches-pounds). See page 5.6.
Terminal blocks will accept one 1.0-2.5mm (#18-10 AWG) wire or two 1.0-1.5mm
(#18-16 AWG) wires. Terminal blocks should be tightened to .40-.57 nM (3.5-5.0
inches-pounds). All terminal blocks are shipped with bypass jumpers installed.
After verifying that each circuit is wired correctly, remove the bypass jumpers for
system operation.
Miswire protection
Mounting
Panel must be mounted within 7 degrees from vertical. Allow at least 30cm (12
inches) air space at top and bottom and a minimum of 30cm (12 inches)
clearance in front of panel. Remote Power Panels will hum slightly and internal
relays will click while in use. Locate where such noise is acceptable. Locate the
panel so that line-voltage wiring will be at least 1.8m (6 feet) from audio or
electronic equipment and its wiring.
Dimensions
Construction
Shipping weight
C O MPO NE NTS
5.13
C O MPO NE NTS
5.14
Model
Capacity
Regulatory approvals
CE, C-TICK
Environment
Cooling method
Passive cooling.
Mount in a place where the vented cover will not be blocked.
Heat generated
fully loaded
Line-voltage
connections
Use copper wire only, supply conductors 60/75C. DIN rail-mounted terminal
blocks provided for line-voltage Remote Power Module (RPM) wiring and
processor/MI power. Terminal blocks should be tightened to .40-.57nM (3.5-5.0
inches-pounds). See page 5.6.
Terminal blocks will accept one 1.0-2.5mm (#18-10 AWG) wire or two 1.0-1.5mm
(#18-16 AWG) wires. Terminal blocks should be tightened to .40-.57 nM (3.5-5.0
inches-pounds). All terminal blocks are shipped with bypass jumpers installed.
After verifying that each circuit is wired correctly, remove the bypass jumpers for
system operation.
Miswire protection
Mounting
Panel must be mounted within 7 degrees from vertical. Allow at least 30cm (12
inches) air space at top and bottom and a minimum of 30cm (12 inches)
clearance in front of panel. Remote Power Panels will hum slightly and internal
relays will click while in use. Locate where such noise is acceptable. Locate the
panel so that line-voltage wiring will be at least 1.8m (6 feet) from audio or
electronic equipment and its wiring.
Dimensions
Construction
Shipping weight
www.lutron.com
20cm
(8 inches)
1cm
(3/8 inches)
6cm
(2-1/2
inches)
Preferred power
wiring entry
8mm diameter
(5/16 inches)
106cm
(41-3/4 inches)
16mm diameter
(5/8 inch)
keyholes for
surface
mounting (4
places)
150cm
(59
inches)
Module locations
(8 maximum)
Terminal blocks
Up
+7
-7
37cm
(14-3/4 inches)
Screws
for recess
mounting
(4 places)
22cm
(11 inches)
Mount panel
vertically
38.5cm
(15-1/8 inches)
Alternate power
wiring entry
36.5cm
(14-3/8
inches)
C O MPO NE NTS
36.5cm
(14-3/8 inches)
18cm
(7 inches)
8mm diameter
(5/16 inches)
74cm
(29
inches)
Preferred power
wiring entry
16mm diameter
(5/8 inch)
keyholes for
surface
mounting (4
places)
81cm
(32")
Up
-7
+7
Mount panel
vertically
Screws
for recess
mounting
(4 places)
Control wiring
entry (Class
2/PELV)
Alternate power
wiring entry
19cm
(7-1/2 inches)
38.54cm
(15-1/8 inches)
5.15
Terminal blocks
Breakers
Module Interface
Main lugs
C O MPO NE NTS
Terminal blocks
Module Interface
5.16
www.lutron.com
PBK8-40-13-CE, PBK8-40-13-10-CE
Capacity
Eight RPMs (HW-RPM-4U and HW-RPM-4A) and one Module Interface or 8 series
processor.
Regulatory approvals
CE, C-TICK
Environment
Cooling method
Passive cooling.
Mount in a place where the vented cover will not be blocked.
Heat generated
fully loaded
Line-voltage
connections
Use copper wire only, supply conductors 60/75C. DIN rail-mounted terminal
blocks provided for line-voltage Remote Power Module (RPM) wiring and
processor/MI power. Terminal blocks should be tightened to .40-.57nM (3.5-5.0
inches-pounds).
Terminal blocks will accept one 1.0-2.5mm (#18-10 AWG) wire or two 1.0-1.5mm
(#18-16 AWG) wires. Terminal blocks should be tightened to .40-.57 nM (3.5-5.0
inches-pounds). All terminal blocks are shipped with bypass jumpers installed.
After verifying that each circuit is wired correctly, remove the bypass jumpers for
system operation.
Miswire protection
Mounting
Panel must be mounted vertically (+/- 7 degrees from vertical). Allow at least
30cm (12 inches) air space at top and bottom and a minimum of 30cm (12
inches) clearance in front of panel. Remote Power Panels will hum slightly and
internal relays will click while in use. Locate where such noise is acceptable.
Locate the panel so that line-voltage wiring will be at least 1.8m (6 feet) from
audio or electronic equipment and its wiring.
Dimensions
Construction
Shipping weight
C O MPO NE NTS
5.17
16mm diameter
(5/8 inch)
keyholes for
surface mounting
(4 places)
111.8cm
(44-1/2 inches)
+7
Mount panel
vertically
MI mounting
screw locations
41.6cm
(16-3/8 inches)
C O MPO NE NTS
Screws
for recess
mounting
(4 places)
Notes:
1. PBK8-40-13-CE has one 3-phase, 4-pole, 40 Amp main input
breaker; eight (8) 13 Amp branch circuit input breakers; and
one (1) 13 Amp input control breaker.
2. PBK8-40-13-10-CE also has thirty two (32) 10 Amp output
breakers.
Terminal blocks
Ground lug
5.18
www.lutron.com
C O MPO NE NTS
Power Boosters
and
Interfaces
6.1
C O MPO NE NTS
E L E C T R O N I C L O W - V O LTAG E
INTERFACE MODELS
NGRX-ELVI-CE AND
NGRX-ELVI-AU (NON-CE)
FLUORESCENT DIMMING
BALLAST INTERFACE MODEL
NGRX-FDBI-AU (NON-CE)
0 10V INTERFACE
MODEL GRX-TVI
T E N V O LT M O D U L E S
MODEL TVM
SYNTHETIC MINIMUM
LOAD INTERFACE
LUT-LBX-CE-WH
6.2
DMX-512 INTERFACE
LUT-DMX
www.lutron.com
Model
Input voltage
220-240VAC, 50/60Hz
Regulatory approvals
Load types
Maximum load
NGRX-PB-AU: 10 amps
NGRX-PB-CE: 8 amps surface mounted, 5.2 amps flush mounted
NGRX-ELVI-: 5 amps (CE and non-CE models)
NGRX-FDBI-AU: 10 amps
Minimum load
25W/VA
Environment
Cooling method
Passive cooling.
Heat generated
fully loaded
Line-voltage
connections
ESD protection
Surge protection
Mounting
2-gang US wallbox, 70mm (2-3/4 inches) deep minimum, 89mm (3-1/2 inches)
deep recommended. (2) Lutron P/N 241218 may be used.
Terminals
Shipping weight
.5kg (1 pound)
C O MPO NE NTS
116mm
(4-5/8 inches)
114mm
(4-1/2 inches)
48mm
(1-15/16
inches)
Figure 1 dimensions
Technical Support: hwisupport@lutron.com
6.3
Neutral N
Zone in
DO NOT USE
LUTRON
PELV
Earth
22
LUTRON
NGRX-PB-AU or NGRX-ELVI-AU
Live ~
Switch
Zone out
~
Remote switch
L 1 1N
L11
Live
220-240VAC
50/60Hz
Neutral
C O MPO NE NTS
L11
Lighting
load
Neutral N
Zone In
Zone Out
~
LUTRON
Earth
22
PELV
NGRX-PB-CE or NGRX-ELVI-CE
Live ~
LUTRON
Switch
DO NOT USE
Remote switch
L 1 1N
Live
220-240VAC
50/60Hz
Neutral
6.4
Up to nine HomeWorks Maestro remote switches may be connected to a HomeWorks Maestro switch. Total wire length between
all devices cannot exceed 50m (165 feet).
www.lutron.com
HW-RPM-4U-240
Neutral N
Zone in
DO NOT USE
Earth
Live ~
Zone out
~
Lighting load
220-240VAC
Neutral
220-240VAC
Neutral
NGRX-PB-CE or NGRX-ELVI-CE
HW-RPM-4U-240
C O MPO NE NTS
Neutral N
Zone in
Zone out
~
Earth
Live ~
DO NOT USE
Lighting load
220-240VAC
Neutral
220-240VAC
Neutral
6.5
NGRX-FDBI-AU
Neutral N
Zone in
SW Live
Earth
Live ~
Zone out
~
220-240VAC
Neutral
220-240VAC
Neutral
LUTRON
Lighting
load
Earth
22
PELV
L11
LUT-LBX
Neutral N
C O MPO NE NTS
LUTRON
Switch
Live ~
Remote switch
L 1 1N
Live
220-240VAC
50/60Hz
Neutral
Figure 7 LUT-LBX
6.6
www.lutron.com
0-10V Interface
Model
GRX-TVI
Input voltage
100-277VAC, 50/60Hz
Regulatory approvals
Load types
Maximum load
10 amps or 1/2 HP
Minimum load
25W/VA
Environment
Cooling method
Passive cooling.
Line-voltage
connections
ESD protection
Surge protection
Mounting
Wall mounted.
Terminals
Shipping weight
COO
ER
SBURG
, PA18036 U.S.A
.
G 2PCB
144-317
Rev. 1.9
Incandescent
Fluorescent
Magnetic Low-voltage
Electronic Low-volta
ge
Neon/ColdCa
thode
Motor
Load Type Swit
ched
Ratings
Switched
Control put:
In
100-120V
, 220240V 0/60Hz
5
SwitchedOutput: 100-277
Con
trolI Rating
16A
GRX-TVI
nput
5A
IIH2 0.02A
16A
DH2 0.1A
16A
16A
0-10V Output Rating
1/4
HP@120
V
Ma
x.
0.
3
A
Clas
s2
1/2 HP
@277V
ACN
003 715 277
10A
5AX
10A
10A
10A
C
A
Con
trolI Rating
GRX-TVI
nput
IIH2 0.02A
DH2 0.1A
0-10V Output Rating
Max. 0.3A PE
LV
wall
Ratings
GRX-TVI
0-10V INTE
RFACE
ONTROL
C
A
B
C
D
E
Dimensions
mm
inches
155
6.10
318
12.50
102
4.0
298
11.75
84
3.30
Figure 1 - dimensions
Technical Support: hwisupport@lutron.com
6.7
Neutral
L
N
N
NN
N
Red 1
Red 2
Red 3
Red 4
Brown
Blue
L2/H2 220-240V
N2
DL2/D
H2
L1/H1
N1
N1
SL
1/SH1
0-10 V
olt
220-240
VAC live
DL
1
DL
2
DL
3
DL
4
220-127V
100- N2 DL2
/DH2
240V
L2/H2
Controlnputs
I
H1
L1/H1 N1 N1 SL1/S
100-V
277
LoadSwitched
0-10V
Max0.3A
Earth
Earth
Earth
C O MPO NE NTS
6.8
www.lutron.com
C O MPO NE NTS
Keypads
and
Contact Closure
Interfaces
7.1
Keypads
HomeWorks keypads are available in many styles,
colours, and finishes. Keypads provide clients with
a simple and elegant way to operate lights, shades,
motorised screens, and many other devices. Keypads
have LEDs that provide status indication. Lutron
provides custom engraving to clearly identify each
buttons function.
Each button on every keypad model can be
programmed to control any lighting load or
device on the HomeWorks system.
Each HomeWorks processor has three or four
configurable links, each capable of controlling
up to 32 keypads and Contact Closure Interfaces.
CONNECTION TO PROCESSOR
C O MPO NE NTS
7.2
www.lutron.com
Keypad Styles
European-style
2-button
Signature SeriesTM
ArchitraveTM
Slim button
C O MPO NE NTS
Web
Large button
Tabletop
(see chapter 10)
Slim button - with insert
7.3
European-style Keypads
E U R O P E A N - S T Y L E K E Y PA D S
E U R O P E A N - S T Y L E K E Y PA D S
2-button
HWI-2SE-XX
Keypad:
Faceplate only: EFP-2B-SL-XX
2-scene
Description:
4-button
HWI-4SE-M-XX
Keypad:
Faceplate only: EFP-4SE-M-XX
4-scene with off
Description:
and raise/lower
HWI-4SE-IR-XX
Keypad:
Faceplate only: EFP-4SE-IR-XX
4-scene with off, raise/lower
Description:
and IR receiver
8-button
HWI-8SE-M-XX
Keypad:
Faceplate only: EFP-8SE-M-XX
8-scene with off
Description:
and raise/lower
C O MPO NE NTS
HWI-8SE-IR-XX
Keypad:
Faceplate only: EFP-8SE-IR-XX
8-scene with off, raise/lower
Description:
and IR receiver
Wallboxes
Model:
Description:
Model:
Description:
7.4
EBB-15-RD
Round plastic wallbox for
European-style keypads
(15 plastic wallboxes)
EBB-15-SQ
Square metal wallbox for
European-style keypads
(15 metal wallboxes)
www.lutron.com
European-style Keypads
B A N G & O L U F S E N C O M PAT I B L E K E Y PA D S
B A N G & O L U F S E N C O M PAT I B L E K E Y PA D S
4-button
HWBO-4SE-M-XX
Keypad:
Faceplate only: EFP-4SE-M-XX
4-scene with off
Description:
and raise/lower
HWBO-4SE-IR-XX
Keypad:
Faceplate only: EFP-4SE-IR-XX
4-scene with off, raise/lower
Description:
and IR receiver
8-button
HWBO-8SE-IR-XX
Keypad:
Faceplate only: EFP-8SE-IR-XX
8-scene with off, raise/lower
Description:
and IR receiver
Green
Yellow
Red
Blue
Colour buttons
Correspond to colour buttons on the
HomeWorks Bang & Olufsen keypad.
LIGHT button
Used for initiating all IR commands to
HomeWorks Bang & Olufsen keypad.
GO button
used to select additional scene
C O MPO NE NTS
B A N G & O L U F S E N C O M PAT I B L E K E Y PA D S
and
buttons
Used to control shades
and
buttons
Used to raise/lower lights in current scene
1-9 buttons
Used to select additional 9 scenes.
0 button
Used to select OFF scenes
Colour buttons, GO button,
Figure 2
Beo4 button detail
,
, and
buttons.
See button details.
STOP button
Used to stop Raise/Lower of shades.
Red
Green
Yellow
Blue
Figure 3
keypad button detail (HWBO-8SE-IR shown)
Technical Support: hwisupport@lutron.com
7.5
HWBO-8SE-IR
ON
HWBO-4SE-IR
HWBO-4SE-M
9 1 0
Figure 1
keypad front view (faceplate removed)
C O MPO NE NTS
HomeWorks processor
86mm
(3.38
86mm
(3.38
inches)
German backbox
(40mm deep)
1 234
U.K. backbox
(35mm deep)
s)
inche
Lutron wallbox
model 241-683
9 10
56 78
Adapter plate
Keypad
Faceplate
7.6
www.lutron.com
seeTouch Keypads
s e e To u c h K E Y PA D S
7.7
seeTouch Keypads
s e e To u c h - W I T H O U T I N S E R T
1-button
Keypad:
ST-1B-NI-XX
Button/Faceplate: SK-1B-NI-XX-E
Description:
1-button - without insert
6-button
Keypad:
ST-6B-NI-XX
Button/Faceplate: SK-6B-NI-XX-E
Description:
6-button - without insert
2-button
Keypad:
ST-2B-NI-XX
Button/Faceplate: SK-2B-NI-XX-E
Description:
2-button - without insert
Keypad:
ST-6BRL-NI-XX
Button/Faceplate: SK-6BRL-NI-XX-E
Description:
6-button with raise/lower without insert
3-button
Keypad:
ST-3B-NI-XX
Button/Faceplate: SK-3B-NI-XX-E
Description:
3-button - without insert
7-button
Keypad:
ST-7B-NI-XX
Button/Faceplate: SK-7B-NI-XX-E
Description:
7-button - without insert
Keypad:
ST-3BRL-NI-XX
Button/Faceplate: SK-3BRL-NI-XX-E
Description:
3-button with raise/lower without insert
4-button
Keypad:
ST-4B-NI-XX
Button/Faceplate: SK-4B-NI-XX-E
Description:
4-button - without insert
C O MPO NE NTS
Keypad:
ST-4FS-NI-XX
Button/Faceplate: SK-4FS-NI-XX-E
Description:
4-button favorite scenes without insert
Keypad:
ST-4S-NI-XX
Button/Faceplate: SK-4S-NI-XX-E
Description:
4-scene - without insert
Keypad:
ST-4SIR-NI-XX
Button/Faceplate: SK-4SIR-NI-XX-E
Description:
4-scene with IR receiver without insert
5-button
Keypad:
ST-5B-NI-XX
Button/Faceplate: SK-5B-NI-XX-E
Description:
5-button - without insert
Keypad:
ST-5FS-NI-XX
Button/Faceplate: SK-5FS-NI-XX-E
Description:
5-button favorite scene without insert
Keypad:
ST-5BRL-NI-XX
Button/Faceplate: SK-5BRL-NI-XX-E
Description:
5-button with raise/lower without insert
XX= Colour Code
7.8
www.lutron.com
seeTouch Keypads
s e e To u c h - W I T H I N S E R T
1-button
Keypad:
ST-1B-I-XX
Button/Faceplate: SK-1B-I-XX-E
Description:
1-button - with insert
2-button
Keypad:
ST-2B-I-XX
Button/Faceplate: SK-2B-I-XX-E
Description:
2-button - with insert
3-button
Keypad:
ST-3B-I-XX
Button/Faceplate: SK-3B-I-XX-E
Description:
3-button - with insert
6-button
Keypad:
ST-6B-I-XX
Button/Faceplate: SK-6B-I-XX-E
Description:
6-button - with insert
Keypad:
ST-6BRL-I-XX
Button/Faceplate: SK-6BRL-I-XX-E
Description:
6-button with raise/lower with insert
7-button
Keypad:
ST-7B-I-XX
Button/Faceplate: SK-7B-I-XX-E
Description:
7-button - with insert
Keypad:
ST-3BRL-I-XX
Button/Faceplate: SK-3BRL-I-XX-E
Description:
3-button with raise/lower with insert
s e e To u c h - W I T H O U T B U T T O N S
Keypad:
ST-4FS-I-XX
Button/Faceplate: SK-4FS-I-XX-E
Description:
4-button favorite scenes with insert
No-button
Keypad:
Description:
Keypad:
ST-4S-I-XX
Button/Faceplate: SK-4S-I-XX-E
Description:
4-scene - insert
Keypad:
Description:
ST-NB-NONE
Without buttons
ST-NBIR-NONE
Without buttons with IR
receiver
C O MPO NE NTS
4-button
Keypad:
ST-4B-I-XX
Button/Faceplate: SK-4B-I-XX-E
Description:
4-button - with insert
Keypad:
ST-4SIR-I-XX
Button/Faceplate: SK-4SIR-I-XX-E
Description:
4-scene with IR receiver with insert
5-Button
Keypad:
ST-5B-I-XX
Button/Faceplate: SK-5B-I-XX-E
Description:
5-button - with insert
Keypad:
ST-5FS-I-XX
Button/Faceplate: SK-5FS-I-XX-E
Description:
5-button favorite scene with insert
Keypad:
ST-5BRL-I-XX
Button/Faceplate: SK-5BRL-I-XX-E
Description:
5-button with raise/lower with insert
XX= Colour Code
Technical Support: hwisupport@lutron.com
7.9
seeTouch Keypads
Bang & Olufsen Compatible
B A N G & O L U F S E N C O M PAT I B L E K E Y PA D S
B A N G & O L U F S E N C O M PAT I B L E K E Y PA D S
IR remote
STBO-4SIRI-XXKeypad:
Faceplate only: SKBO-4SIRI-XX-E
4-scene with off, raise/lower,
Description:
IR reciver, with insert
STBO-4SIRN-XXKeypad:
Faceplate only: SKBO-4SIRN-XX-E
4-scene with off, raise/lower,
Description:
IR reciver, no insert
Non IR
STBO-4SI-XXKeypad:
Faceplate only: SKBO-4SI-XX-E
4-scene with off, raise/lower,
Description:
with insert
NOTES
STBO-4SN-XXKeypad:
Faceplate only: SKBO-4SN-XX-E
4-scene with off, raise/lower,
Description:
no insert
Green
Yellow
Red
B A N G & O L U F S E N C O M PAT I B L E K E Y PA D S
Blue
C O MPO NE NTS
Colour buttons
Correspond to colour buttons on the
HomeWorks Bang & Olufsen keypad.
LIGHT button
Used for initiating all IR commands to
HomeWorks Bang & Olufsen keypad.
GO button
used to select additional scene
and
buttons
Used to control shades
and
buttons
Used to raise/lower lights in current scene
1-9 buttons
Used to select additional 9 scenes.
0 button
Used to select OFF scenes
Colour buttons, GO button,
Figure 2
Beo4 button detail
,
, and
buttons.
See button details.
STOP button
Used to stop Raise/Lower of shades.
7.10
Red
Green
Yellow
Blue
Figure 3
keypad button detail (STBO-4SIRI shown)
www.lutron.com
Figure 4
keypad front view (wallplate, wallplate adapter,
and button kit removed) DIP Switches
COM
3
Button 20
Button 19
HomeWorks processor
(8 series shown)
C O MPO NE NTS
Button assembly
Wallplate adapter
Keypad
Wallplate
7.11
S L I M B U T T O N W I T H O U T I N S E R T K E Y PA D S
5-button
HWI-KP5-XX
Keypad:
Faceplate only: HW-B1-NFB-XX
5-button with master on/off
Description:
10-button
HWI-KP10-XX
Keypad:
Faceplate only: HW-B2-NFB-XX
10-button with master on/off
Description:
15-button
HWI-KP15-XX
Keypad:
Faceplate only: HW-B3-NFB-XX
15-button with master on/off
Description:
C O MPO NE NTS
The keypads below will be obsoleted in 2007. Do not use these keypads
for new projects. Contact Lutron Customer Service for availability.
S L I M B U T T O N W I T H I N S E R T K E Y PA D S
S L I M B U T T O N W I T H I N S E R T K E Y PA D S
5-button
HWI-5S-NM-XX
Keypad:
Faceplate only: NT-T7-NFB-XX
5-button
Description:
HWI-5S-M-XX
Keypad:
Faceplate only: NT-T6-NFB-XX
5-button with master
Description:
raise/lower
HWI-5S-IR-XX
Keypad:
Faceplate only: NT-T6-NFB-XX
5-button with IR receiver
Description:
7.12
www.lutron.com
2 - B U T T O N K E Y PA D
L A R G E B U T T O N K E Y PA D S
6-Button
HWI-KP-LB6-XX
Keypad:
Faceplate only: HWI-B4-NFB-XX
6-button
Description:
9-Button
HWI-KP-LB9-XX
Keypad:
Faceplate only: HWI-B5-NFB-XX
9-button
Description:
2 - B U T T O N K E Y PA D
C O MPO NE NTS
L A R G E B U T T O N K E Y PA D S
2-Button
HWI-2B-XX
Keypad:
Faceplate only: NT-T8-NFB-XX
2-button
Description:
Button labels can be engraved on each button. 2button keypads have two contact closure inputs on
the back of the unit which provide independent
functions from the front buttons.
FINISHES AND COLOURS
7.13
1 23 4 5 6
1 2 3 4
1 23 4 5 6
1 23 4 5 6
1 23 4 5 6
C O MPO NE NTS
HomeWorks processor
(8 series shown)
Faceplate
Wallbox model
241218
Control
7.14
www.lutron.com
COM
3
2
1
AP
A
GUE
LA
CORRENTE
MUX
MUX
+15V
COM
ARR
ETEZ
LE
COURANT
LUTRON
3 4
56
COM
Button 23
Button 24
2 31 42 53 6 4 5 6
DIP Switch 6 Down
2 Closure
3 1 4 2 inputs
53 6 4 match
5 6 buttons on front of
keypad.
2 13 24
13
24
35
53
46
64
COM
Button 2
Button 1
DIP Switch 6 Up
Closure inputs separate from buttons on
front of keypad.
3
2
1
3
2
1
3
2
1
C O MPO NE NTS
Control
Faceplate
adapter
Faceplate
7.15
S I G N AT U R E S E R I E S K E Y PA D S
3-button Monaco
(blue status indicators)
HWS-3B-B-XX
Keypad:
Button Kit: HKS-3B-BL-E
Description: 3-button
4-button Monaco
(blue status indicators)
HWS-4B-B-XX
Keypad:
Button Kit: HKS-4B-BL-E
Description: 4-button
3-button Monterey
(green status indicators)
HWS-3B-G-XX
Keypad:
Button Kit: For white Monterey keypads only
HKS-3B-WH-E
Button Kit: For non-white Monterey keypads
HKS-3B-BL-E
Description: 3-button
4-button Monterey
(green status indicators)
HWS-4B-G-XX
Keypad:
Button Kit: For white Monterey keypads only
HKS-4B-WH-E
Button Kit: For non-white Monterey keypads
HKS-4B-BL-E
Description: 4-button
Wallbox
WBOX-SA1-Q1
Model:
Description: Signature Series wallbox
7.16
www.lutron.com
Keypads Architrave
TM
A R C H I T R AV E K E Y PA D S
5-button
HWI-KP5-DN-XX
Keypad:
Faceplate only: AR-M4-DN-XX
Door narrow 5-button
Description:
with master on/off
HWI-KP5-DW-XX
Keypad:
Faceplate only: AR-M4-DW-XX
Door wide 5-button
Description:
with master on/off
HWI-LB5-DC1-XX
Keypad:
Faceplate only: Custom
5 large buttons
Description:
with raise/lower
Wallboxes
241-399
Wallbox for HWI-KP5-DW
241-663
Wallbox for HWI-LB5-DC1
C O MPO NE NTS
A R C H I T R AV E K E Y PA D S
7.17
TM
1 2 3 4 5 6
ON
1 23 4
COM
+15VDC
MUX
MUX
C O MPO NE NTS
HomeWorks processor
(8 series shown)
7.18
www.lutron.com
TM
Wall
Door
trim
114mm
(4-1/2 inches)
91mm
(3.6
inches)
41mm
(1.6 inches)
36mm
(1-2/5
inches)
Wallbox model
WBOX-SA1-Q1
Button kit
Keypad
Button kit
Faceplate
Keypad
Faceplate
Control
90mm
(3-1/2 inches)
32mm
(1-1/4 inches)
C O MPO NE NTS
Faceplate
Faceplate
Control
Control
Faceplate
Faceplate
102mm
(4 inches)
Wallbox model
241399
29mm
(1-1/8 inches)
7.19
C O N TAC T C L O S U R E I N P U T I N T E R FAC E
(MODEL HWI-CCI-8)
C O MPO NE NTS
7.20
www.lutron.com
C O MPO NE NTS
Web Keypads
The web keypads allow the homeowner to control
the HomeWorks system from a computer using a web
browser. The homeowner will be able to monitor and
control selected keypads in the system. Web keypads
can simulate actual keypads in the home or provide
special functions only possible from the computer.
The web keypads can be accessed from most popular
web browsers including Internet Explorer 6.0, Mozilla
Firefox, and Safari. The web keypads will work on
any browser that supports Javascript 1.2, Cascading
Style Sheets and a screen with a minimum resolution
of 800x600. Palm Pilots and Pocket PCs are not
currently supported.
7.21
HWI-WCI
C O N TAC T C L O S U R E I N P U T S
C O MPO NE NTS
7.22
www.lutron.com
Wallbox
Switch
settings
Address
number
Switch
settings
HWI-WCI
Third party low-voltage
contact closure switch
Input 1
Common
Set DIP switches 1-5 to give the Wallbox Closure Interface a unique
HomeWorks system address from 1 to 32.
ON
HWI-WCI
1 2 3 4 5 6 7 8 9 10
Power LED
DIP switches 1-5 for setting address. DIP switches 6-10 do not affect
Wallbox Closure Interface address.
C O MPO NE NTS
Figure 3 addressing
HWI-WCI
1234
HWI-WCI
1234
HomeWorks keypad
Wallbox Closure
Interfaces can be
connected to any
link configured as
an HomeWorks
Keypad Link.
2
HomeWorks processor
Each HWI-WCI counts as seven LEDs toward the capacity of the power
supply for the link.
7.23
C O MPO NE NTS
Model
All keypads.
Input voltage
Environment
Two pair [one pair 1.0mm (#18 AWG), one pair 1.0-0.5mm (#18-22 AWG) twisted
shielded] Class 2/PELV wire. Lutron wire model GRX-CBL-346S-500 may be used.
Low-voltage
wiring configuration
Daisy-chain, star, T-tap. Termination not required. Total length of wire on any
link cannot exceed 305m (1,000 feet) per wire run. Total length of wire on that
link cannot exceed 1220m (4,000 feet). Maximum of 32 devices per processor link
that has been configured for keypads.
Low-voltage connections
One 4-pin removable terminal block. Terminal block will accept up to four 1.0mm
(#18 AWG) wires.
Addressing
Via DIP switch located on unit. Units should be addressed before mounting in
wall.
Diagnostics
ESD protection
Surge protection
Miswire protection
All terminal block inputs are over-voltage and miswire-protected against wire
reversals and shorts.
Mounting
Engraving
IR keypads
Shipping weight
Address
#
Switch
setting
Address
#
Switch
setting
Address
#
Switch
setting
Address
#
17
25
10
18
26
11
19
27
12
20
28
13
21
29
14
22
30
15
23
31
16
24
32
Switch
setting
On - Up
Off - Down
7.24
www.lutron.com
Control
LED Count
Wallboxes Required
HWI-2SE
European-style (241683)
HWI-4SE
European-style (241683)
4SE-IR
European-style (241683)
HWI-8SE
European-style (241683)
HWBO-4SE
European-style (241683)
HWBO-8SE-IR
European-style (241683)
15
1-gang US (241218)
HWI-KP5
1-gang US (241218)
HWI-KP10
10
1-gang US (241218)
HWI-KP15
15
2-gang US (241218)
HWI-LB6
1-gang US (241218)
HWI-LB9
2-gang US (241218)
HWI-KP5-DN
Not required
HWI-KP5-DW
(241399)
HWI-5S-M
1-gang US (241218)
HWI-5S-NM
1-gang US (241218)
HWI-5S-IR
1-gang US (241218)
HWI-2B
10
1-gang US (241218)
HWS-3B-G
10
WBOX-SA1-Q1
HWS-4B-G
10
WBOX-SA1-Q1
HWS-3B-B
10
WBOX-SA1-Q1
HWS-4B-B
10
WBOX-SA1-Q1
HWI-CCI-8
10
n/a
HWI-CCO-8
10
n/a
HWI-WCI
n/a
HWI-HHP-LD
45
n/a
HR-REP-
15
n/a
C O MPO NE NTS
Specifications
7.25
Notes
C O MPO NE NTS
7.26
www.lutron.com
C O MPO NE NTS
Processors
8.1
P5 Processors
HomeWorks Processors comprise the major
communication hub of a HomeWorks system. Each
processor has communication links, which allow the
processor to interact with various system components.
System components communicate with a processor
through low-voltage wiring or radio frequency. Some
components must be connected to the processor
through a interface. These interfaces are available as
stand-alone components or as built-in components in
specific models of processors.
8 SERIES
8 Series Processor
(H8P5-MI-H48-CE shown)
4 SERIES
C O MPO NE NTS
4 AND 8 SERIES
4 Series Processor
(H4P5-H48-HRL-CE shown)
8.2
www.lutron.com
Model
Number
Module
Interface
H48
Dimmer
Interface
#
Configurable
Links
Hybrid
Signal
Repeater
Link
#
RS232
Ports
#
Keypad
LEDs
#
Integral
CCIs
Panel/
Enclosure
H8P5-CE
External
External
Yes
350
HWI-LV32-CE
H8P5-MI-CE
Included
External
Yes
350
HWI-PNL-8-CE
H8P5-H48-CE
External
Included
Yes
350
HWI-LV32-CE
H8P5-MI-H48-CE
Included
Included
Yes
350
HWI-PNL-8-CE
H4P5-CE
Not
Available
External
No
150
HWI-LV24-CE
H4P5-HRL-CE
Not
Available
External
Yes
150
HWI-LV24-CE
H4P5-H48-CE
Not
Available
Included
No
150
HWI-LV24-CE
H4P5-H48-HRL-CE
Not
Available
Included
Yes
150
HWI-LV24-CE
C O MPO NE NTS
P5 Processors
H8P5-MI-H48-CE
220-240VAC Operating Voltage
With H48 Dimmer Interface
With Module Interface
P5 Processor
HomeWorks 8 Series
8.3
P5 Processors
PROCESSOR LINKS
C O MPO NE NTS
8.4
www.lutron.com
P5 Processors
Non-configurable
links
Function
Link capacity
Wiring
configuration
Terminators?
Maximum wire
length and type
link 1
(8 series only)
link to Remote
Power Modules
16 Module
Interfaces, each
controlling
maximum 8 RPMs
daisy-chain
at last Module
2
Interface
link 2
link to other
processors
16 processors
daisy-chain
links 3 and 7
(7 available on the
8 series only)
RS-232 port
n/a
point-to-point
No
Configurable links
Possible function
Link capacity
Wiring
configuration
Terminators?
Maximum wire
length and type
link to keypads
and Contact
Closure Interfaces
32 devices
any (Daisy-chain,
Star, T-tap, etc.)
no
daisy-chain
at processor and
last Dimmer
2
Interface
8 GRAFIK
Eye/WPMs
daisy-chain
no
any function of
link 4, 5, 6
see above
see above
see above
see above
no
link 8 (8 series)
or hybrid signal
repeater link
any
link 8 (4 series)
hybrid signal
repeater link
any
no
link 9
ethernet
point-to-point
no
C O MPO NE NTS
8.5
P5 Processors
Notes from previous page
2
C O MPO NE NTS
8.6
www.lutron.com
P5 Processors
DB9 female connector for RS-232 communication
Required for
Hardware
Handshaking
Required for
Simple
Communications
(Hardware
Handshaking
Disabled)
RXD
DSR
GND
Ground
DTR
CTS
RTS
RI
Pin
Name
Description for
Processor Connector
DCD
TXD
Processor
Ethernet Hub/Switch
Transmit +Ve
Receive +Ve
Transmit -Ve
Receive -Ve
Receive +Ve
Transmit +Ve
No Connection
No Connection
No Connection
No Connection
Receive -Ve
Transmit -Ve
No Connection
No Connection
No Connection
No Connection
1
2
3
4 NC
5 NC
6
7 NC
8 NC
C O MPO NE NTS
Pin
Number
1
2
3
NC 4
NC 5
6
NC 7
NC 8
8.7
8 Series P5 Processors
C O MPO NE NTS
8.8
Model Numbers
H8P5-CE:
H8P5-MI-CE:
H8P5-H48-CE:
H8P5-MI-H48-CE:
Input Voltage
220-240VAC, 50/60Hz
Regulatory Approvals
Environment
Cooling Method
Passive cooling.
Line-Voltage
Connections
Mates with Lutron-provided 2-pin pigtail on DIN-rail terminal block. Power switch
provided on top left of processor. Terminal blocks should be tightened to .40-.57nM
(3.5-5.0 inches-pounds).
Low-Voltage
Wire Type
Two pair [one pair 1.0mm (#18 AWG), one pair 1.0-0.5mm (#18-22) twisted
shielded] Class 2 cable.
Low-Voltage
Wiring Configuration
All processors on the same system must have the inter-processor communication
links connected in a daisy-chain configuration.
Low-Voltage
Connections
One 4-pin removable terminal block. Each of the four terminals will accept up to two
1.0mm (#18 AWG) wires. Up to two standard female DB-9 serial RS-232 connections.
ESD Protection
Surge Protection
Miswire
Protection
All terminal block inputs are over-voltage and miswire protected against wire
reversals and shorts. 15V communications link power is short-circuit protected.
Power-Failure Memory
Internal Timeclock
Shipping Weight
(all model numbers)
4.1kg (9 pounds)
www.lutron.com
Preferred Power
Wiring Entry
H
H
N
N
N
G
C O MPO NE NTS
HomeWorks
Processor
HomeWorks
Processor
Control Wiring
Entry
(Class 2/PELV)
Alternate Power
Wiring Entry
8.25cm
(3-1/4
inches)
Control Wiring
Entry
(Class 2/PELV)
8.9
8 Series P5 Processors
RPM harness
(MI models only)
Power Cord
Mounting
Hole
Power Switch
Processor
#24-16 AWG
(0.5mm2-1.5mm2) Wiring
Processor Board
Dimmer Hub
(H8P5-H48-CE
and
H8P5-MI-H48-CE
Mounting Keyhole
C O MPO NE NTS
Contact Closure
Inputs
Configuration
Switch
Mounting Keyhole
Manual Override
Switch
Ethernet Port
OFF - Left
ON -Right
8.10
DIP
Switch
OFF
ON
Normal Mode
Boot Mode
User-Configured
Baud Rate
9600 Baud
3-6
Address
www.lutron.com
C O MPO NE NTS
Technical Support: hwisupport@lutron.com
8.11
4 Series P5 Processors
C O MPO NE NTS
8.12
Model Numbers
H4P5-CE:
H4P5-HRL-CE:
H4P5-H48-CE:
H4P5-H48-HRL-CE:
Input Voltage
220-240VAC, 50/60Hz
Regulatory Approvals
Environment
Cooling Method
Passive cooling.
Line-Voltage
Connections
Mates with Lutron-provided 2-pin pigtail on DIN-rail terminal block. Power switch
provided on top left of processor. Terminal blocks should be tightened to .40-.57nM
(3.5-5.0 inches-pounds).
Low-Voltage
Wire Type
Two pair [one pair 1.0mm (#18 AWG), one pair 1.0-0.5mm (#18-22) twisted
shielded] Class 2 cable.
Low-Voltage
Wiring Configuration
All processors on the same system must have the inter-processor communication
links connected in a daisy-chain configuration.
Low-Voltage
Connections
One 4-pin removable terminal block. Each of the four terminals will accept up to two
#18 AWG (1.0mm ) wires. Up to two standard female DB-9 serial RS-232 connections.
ESD Protection
Surge Protection
Miswire
Protection
All terminal block inputs are over-voltage and miswire protected against wire
reversals and shorts. 15V communications link power is short-circuit protected.
Power-Failure Memory
Internal Timeclock
Shipping Weight
www.lutron.com
4 Series P5 Processors
Mounting
Keyhole (4 places)
Processor
Label
Processor
Board
RS-232 Port
DIP
Switch
Function
3-6
C O MPO NE NTS
High-voltage
enclosure
(shown with
cover
installed).
8.13
8 series processor
8 series processor
3 4
LT-1 Link
terminator
LT-1 link
terminator
1 2 43
LT-1 link
terminator wiring
detail
8.14
www.lutron.com
System Specifications
8 series processor communication link specifications
Link type
Maximum per
processor
Baud
rates
Wiring
configuration
Termination
required
1
1
3
2
3
1
125K
125K
31.25K
9600-115.2K
10.42K-41.67K
125K
daisy-chain
daisy-chain
daisy-chain
point-to-point
any
daisy-chain
62.5K
no
Module Interface
inter-processor
GRAFIK Eye/WPM
RS-232
keypad
H48 and Q96
interface
Hybrid Signal
Repeater
1
Baud
rates
Wiring
configuration
Termination
required
1
1
3
3
1
125K
9600-115.2K
10.42-41.67K
31.25K
125K
daisy-chain
point-to-point
point-to-point
daisy-chain
daisy-chain
62.5K
no
inter-processor
RS-232
keypads
GRAFIK Eye/WPM
H48 and Q96
interface
Hybrid Signal
Repeater
1
16
1
128
256
16
C O MPO NE NTS
Link type
15
3
24
45
16
2,048
384
4,096
720
8.15
System Specifications
Wired Keypad capacities
48
32
3
96
16
1,536
192
1
Wireless capacities
192
16
32
3,072
C O MPO NE NTS
8.16
96
Maximum number of
Sivoia QED drives per system
4096
www.lutron.com
C O MPO NE NTS
Low-voltage
Enclosures
9.1
Low-voltage Enclosures
Low-voltage enclosures are available in four different
sizes. The number of enclosures and the types of
components within them are customised to fit the
size, lighting plan, and design of a home. Low-voltage
enclosures can be distributed throughout the home
near the rooms they are controlling to provide
maximum flexibility.
Transformer
(for dimmer
interface)
8 series
processor
8 series
processor
Dimmer
interface
Contact
Closure
Interfaces
(up to 2)
8 1 C M ( 3 2 I N C H E S ) L O W - V O LTAG E
ENCLOSURE (MODEL HWI-LV32-CE)
C O MPO NE NTS
C O N TAC T C L O S U R E I N T E R FAC E S U B P L AT E
(MODEL HWI-SUB32-CC9)
Subplate
mounting
locations (5)
Contact
Closure
Interfaces
Contact
Closure
Interface
subplate
9.2
Contact Closure
Interfaces
(9 maximum)
www.lutron.com
Low-voltage Enclosures
6 1 C M ( 2 4 I N C H E S ) L O W - V O LTAG E
ENCLOSURE (MODEL HWI-LV24-CE)
4 series processor
The 61cm (24 inches) low-voltage enclosure accommodates several components including 4 series processors,
Contact Closure Interfaces and Wire Landing Boards.
Low-voltage enclosures cannot accommodate Remote
Power Modules.
C O MPO NE NTS
9.3
Low-voltage Enclosures
4 4 C M ( 1 7 I N C H E S ) L O W - V O LTAG E
ENCLOSURE (MODEL HWI-LV17-230)
Transformer for
dimmer interface
C O MPO NE NTS
2 5 C M ( 1 0 I N C H E S ) L O W - V O LTAG E
ENCLOSURE (MODEL HWI-ENC-CC)
9.4
www.lutron.com
Important Note:
Regulations for products with radio frequency change from country to
country. Therefore, HomeWorks products with radio frequency are not
available in all countries. You should consult Lutron to understand
which products with radio frequency are available in your country.
C O MPO NE NTS
Wireless
Equipment
10.1
C O MPO NE NTS
RF SYSTEM
C O M M U N I C AT I O N
Hybrid
Signal Repeater
4 Series
Processor
10.2
www.lutron.com
Input Voltage
Regulatory Approvals
Environment
Two pair [one pair 1.0mm (#18 AWG), one pair 1.0-0.5mm (#18-22 AWG)
twisted shielded] Class 2/PELV wire. Lutron wire model # GRX-CBL-346S500 may be used.
Low-Voltage
Wiring Configuration
Low-Voltage Connections
One 4-pin removable terminal block. Terminal block will accept up to four
1.0mm (#18 AWG) wires. Pin 2 should not be connected if using included
transformer.
Diagnostics
ESD Protection
Surge Protection
Coverage
Each wireless table keypad must be within 9m (30 feet) of a hybrid signal
repeater.
Shipping Weight
C O MPO NE NTS
Addressing
34.8mm
(1-3/8 inches)
Status LEDs
Buttons
75mm
(2-15/16
inches)
119mm
(4-11/16 inches)
7.6mm
(5/16 inches)
10.3
UP
MUX
MUX
+15 V
COM
UP
Figure 13 Mounting
RF TX/RX LEDs
WIRED TX/RX LEDs
STATUS Button
TEST Button
TM
C O MPO NE NTS
STATUS LED
Indicates the status of the HomeWorks
system. Note: When the Hybrid Repeater is
powered, but has not yet been assigned an
address from the HomeWorks Illumination
Software, the STATUS and TEST LEDs will be
dimly illuminated.
TEST LED
A slow flash indicates RF communications
tests are in progress
Figure 14 Operation
HomeWorks
Processor
(8 Series shown)
Tabletop Keypads
Hybrid
signal
repeater
9m
(30 feet)
maximum
9m
(30 feet)
maximum
18m (60 feet)
maximum
9m
(30 feet)
maximum
10.4
www.lutron.com
SLIM BUTTON
5-Button
Keypad:
HRT-5RL-434-xx
HRT-5RL-868-xx
Faceplate only: HKT-5RL-xx-E
5-button with master
Description:
on/off and raise/lower
10-Button
Keypad:
HRT-10RL-434-xx
HRT-10RL-868-xx
Faceplate only: HKT-10RL-xx-E
10-button with master
Description:
on/off and raise/lower
15-Button
Keypad:
HRT-15RL-434-xx
HRT-15RL-868-xx
Faceplate only: HKT-15RL-xx-E
15-button with master
Description:
on/off and raise/lower
LARGE BUTTON
6-Button
Keypad:
HRT-6LRL-434-xx
HRT-6LRL-868-xx
Faceplate only: HKT-6LRL-xx-E
6-button with raise/lower
Description:
C O MPO NE NTS
10.5
Input Voltage
Regulatory Approvals
Frequency of Operation
Environment
Cooling Method
Passive cooling.
Addressing
Diagnostics
ESD Protection
Surge Protection
Mounting
Shipping Weight
C O MPO NE NTS
25mm
(1 inch)
82mm
(3-1/4
inches)
91mm
18mm
(3-9/16 inches)
(3/4
inches)
Figure 19 Dimensions
10.6
www.lutron.com
Model Numbers
Input Voltage
Output Voltage
9 VDC regulated
Output Current
300 mAmps
Regulatory Approvals
CE
Environment
Shipping Weight
Cord Length
42mm
(1.654
inches)
37mm
(1.457
inches)
42mm
(1.654
inches)
C O MPO NE NTS
48mm
(1.89
inches)
59mm
(2.323
inches)
UK Plug
European Plug
Figure 20 Dimensions
10.7
Notes
C O MPO NE NTS
10.8
www.lutron.com
C O MPO NE NTS
Sivoia
QED
11.1
TM
76mm (3 inches)
C O MPO NE NTS
to HomeWorks
processor link
11.2
www.lutron.com
TM
Model Number
HWI-Q96
Input Voltage
Regulatory Approvals
Environment
Two pair [one pair 1.0mm (#18 AWG), one pair 1.0-0.5mm (#18-22 AWG) twisted
shielded] Class 2/PELV wire. For connection to Sivoia QED link, the 1.0mm (#18 AWG)
wire must be used for +12V and Common. HWI-Q96 get its power from the Sivoia QED
Link.
2
Low-Voltage Wiring
Configuration
Line-Voltage Connections
Between processor and HWI-Q96: One 4-pin removable terminal block. Terminal block
will accept up to two 1.0mm (#18 AWG) wires.
Between HWI-Q96 and Sivoia QEDs: One 4-pin removable terminal block. Terminal
block will accept up to two 1.0mm (#18 AWG) wires.
2
Addressing
Via DIP Switch. Set DIP switches 5-6 to give HWI-Q96 a unique address from 1 to 4.
DIP Switches 1-4 should always be in the down position. Counts as one address on
the H48/Q96 link.
Diagnostics
Between processor and HWI-Q96: The HomeWorks heartbeat LED will be flashing to
denote communication with the processor. If the LED is off, check the connections
Between HWI-Q96 and Sivoia QEDs: The Sivoia QED TX and RX Communication LEDs
are normally off. After limits have been set for each QED, Use the All Open or All
Closed button and check the Sivoia QED Communications LEDs (TX and RX) for
flashing after the button is pressed.
ESD Protection
Surge Protection
Mounting
Shipping Weight
C O MPO NE NTS
11.3
TM
To processor
or next
H48 or Q96
Interface
C O MPO NE NTS
Sivoia QED Fe atu re s an d Be n e f its :
Ultra-quiet operation: will not exceed 44dBA
measured 3 feet from the EDU.
11.4
www.lutron.com
C O MPO NE NTS
Other
Equipment
www.lutron.com
12.1
Link Extender
C O MPO NE NTS
12.2
Model
LUT-LINK-EXT: extends the total wire length allowed for use on the
inter-processor and Module Interface links from 305m (1,000 feet) to 610m
(2,000 feet).
Input voltage
Regulatory approvals
Environment
Line-voltage
One pair twisted shielded 1.0-0.5mm (#18-22 AWG) Class 2/PELV wiring.
Low-voltage
wiring configuration
Low-voltage
connections
Addressing
Not required.
Diagnostics
ESD protection
Surge protection
Dimensions
Mounting
Shipping weight
Special wire can be used to extend the total wire length on the inter-processor
and Module Interface links from 305m (1,000 feet) to 1220m (4,000 feet)
without the use of a Link Extender, and to 2240m (8,000 feet) with the use of
a Link Extender. Refer to HomeWorks application note #62 for details and wire
specifications.
Link Extender
105mm x 105mm
(4 inches x 4 inches)
junction box
Live
Black
Link Extender
White
Green
220/240VAC
50/60Hz
Earth
Class 2/PELV connections
Line-voltage connections
Neutral
LT-1
termination
resistor at
each end
(terminals 3
and 4)
LT-1 termination
resistor at each end
(terminals 3 and 4)
C O MPO NE NTS
ADDRESS
LT-1 included
on the MI link
of processor
COM
+15
MUX
ADDRESS
MUX
COM
+15
MUX
ADDRESS
MUX
COM
+15
MUX
MUX
LT-1
termination
resistor at each
end (terminals
3 and 4)
www.lutron.com
12.3
C O MPO NE NTS
12.4
Model
Input voltage
220-240VAC, 50/60Hz
Regulatory approvals
CE, C-Tick
Line-voltage
connections
Use copper wire only, supply conductors 60/75C. DIN rail-mounted terminal
blocks for power supply feed located at top left corner of panel. Terminal blocks
should be tightened to .40-.57nM (3.5-5.0 inches-pounds).
DIN rail
terminal blocks
Terminal blocks will accept one 1.0-2.5mm (#18-10 AWG) wire or two 1.0-1.5mm
(#18-16 AWG) wires. Terminal blocks should be tightened to .40-.57nM (3.5-5.0
inches-pounds).
Output voltage
15VDC
Output current
2A maximum, powers 350 LEDs on the keypad link. See page 7.25 for LED counts
for the different keypad and Contact Closure Interface models.
Dimensions
Mounting
Construction
Shipping weight
17cm
(6-3/4 inches)
3.2cm
(1-1/4 inches)
8mm
diameter
(5/16 inch)
16mm
diameter
(5/8 inch)
44cm
(17-1/4
inches)
Screws for
recess mounting
36cm
(14
inches)
41cm
(16
inches)
25cm
(10 inches)
Power supply
Do not connect
terminal 2
C O MPO NE NTS
www.lutron.com
12.5
Input voltage
220-240VAC, 50/60Hz
Regulatory approvals
CE, C-Tick
Line-voltage
connections
Output voltage
15VDC
Output current
900mA maximum, powers 150 LEDs on the keypad link. See page 7.25 for LED
counts for the different keypad and Contact Closure Interface models.
Dimensions
Shipping weight
Cut the plug end off of transformer wire and strip the ends. The black wire
should be connected to common and the black/white wire should be
connected to +15V.
HomeWorks processor
C O MPO NE NTS
Keypad link
1 2 3 4
COM MUX
+15 MUX
N/C
Keypad back
Plug-in
power supply
15VDC
Black/white wire
from transformer
4
4
3
3
2
2
Black/white
Plug-in
power supply
15VDC
black
Keypad back
12.6
Input voltage
230-240VAC, 50/60Hz
Regulatory approvals
Environment
Output voltage
Protection
Connections
Input screw terminal block accepts 2.5mm wire maximum and output screw
terminal block accepts 4.0mm wire. Torque 0.34nM (3 inches-pounds). Flying
leads are 2 x 0.75mm PVC/PVC 105C wires 0.5m long.
2
Standards
Safety: EN 61347.2.2
Performance: EN 61047
EMC: EN 55015
Transient: EN 61547
Harmonics: EN 61000.3.2
Mounting
Single screw
Shipping weight
C O MPO NE NTS
www.lutron.com
12.7
6 0 WA T T E L E C T R O N I C
L O W - V O LTAG E T R A N S F O R M E R
C O MPO NE NTS
1 0 5 WA T T E L E C T R O N I C
L O W - V O LTAG E T R A N S F O R M E R
12.8
Restrictions
HWI 4E modules
none
HWI 4U modules
none
HWA-5E
none
HNA-5E
none
TM-ELV500-__
none
TIR-ELV500-__
none
TM-MLV500-__
TIR-MLV500-__
GXI-3___-_-CE-__
none
NTGRX-ELVI-CE-WH
none
LP 4E modules
none
GRX-3___-_-CE-__
none
NTGRX-PB-CE-WH
none
LP 4U modules
none
GP modules
none
Note: Do not mix electronic and magnetic transformers on the same circuit.
C O MPO NE NTS
WIRING
Dimmer
22
LUTRON
PELV
L1 1
Live
Lighting load
220/240 VAC 50 Hz
Neutral
12.9
Section 1
A
B
Section 2
A
B
Section 3
C O MPO NE NTS
HomeWorks
Processor
To processor
keypad link
To Dimmer bus 1
Bus 2
Bus 1
To Dimmer bus 2
Bus 2
Bus 1
Connection to
HomeWorks
Processor
or
Dimmer
Interface
Connection to
HomeWorks Devices
12.10
www.lutron.com
C O MPO NE NTS
Colours
and Finishes
www.lutron.com
13.1
white (WH)
black (BL)
black (BL)
beige (BE)
beige (BE)
ivory (IV)
ivory (IV)
gray (GR)
gray (GR)
brown (BR)
C O MPO NE NTS
Metallic
Plastic
white (WH)
brown (BR)
taupe (TP)
taupe (TP)
13.2
Metallic
Plastic
Metal Finishes
European-style Faceplates
(replacement faceplates)
ArchitraveTM Keypads
Metallic
Metallic
white (WH)
www.lutron.com
13.3
Patents
These products may be covered by one or more of the following U.S. patents:
4,449,074
4,797,599
4,889,999
4,954,768
5,105,336
5,180,886
5,237,207
5,399,940
5,555,150
5,808,417
5,909,087
6,005,308
6,188,181
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
4,663,570
4,803,380
4,893,062
5,001,386
5,144,205
5,187,655
5,237,264
5,430,356
5,633,540
5,838,226
5,942,727
6,037,721
6,225,760
227,577
254,001
302,543
308,647
311,485
319,429
335,867
344,068
370,663
391,924
412,315
428,855
437,834
453,742
463,382
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
4,689,547
4,816,628
4,894,587
5,017,837
5,144,278
5,191,265
5,248,919
5,463,286
5,637,930
5,841,239
5,949,200
6,046,550
6,310,140
241,853
271,373
302,544
310,349
311,678
325,567
336,744
344,264
378,814
395,037
421,246
431,199
439,220
456,783
465,460
4,728,866
4,833,339
4,924,151
5,038,081
5,146,153
5,191,971
5,262,678
5,467,266
5,637,964
5,848,054
5,962,979
6,091,205
6,313,588
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
DES.
249,141
285,066
303,657
311,170
313,738
325,728
337,755
353,798
387,736
396,448
421,399
436,579
442,723
457,863
465,770
4,737,609
4,835,343
4,924,349
5,041,763
5,170,068
5,196,782
5,309,068
5,499,930
5,671,387
5,848,634
5,982,103
6,100,659
4,745,351
4,835,816
4,939,383
5,055,742
5,173,643
5,207,317
5,357,170
5,510,679
5,736,965
5,864,212
5,987,205
6,111,368
4,783,581
4,876,498
4,947,054
5,099,193
5,178,350
5,224,029
5,359,231
5,530,322
5,798,581
5,905,442
5,990,635
6,169,377
These products may be covered by one or more of the following U.K. patents:
2190804; 2182493; 0293569; 0427709; 2225872B; 0341805; 2221345B;
2251727B; 2239568; 2246034; 2234862B; 0531079; 0587878; 0637401;
EP 95906117.7; 2326768;
and by one or more of the following design registrations:
1048019; 1048020; 1048021; 1048792; 1048794; 1048793; 1045560; 1055178;
2001301; 1056587; 2021252; 2023658; 2023659; 2023660; 2028662; 2058358;
2063408; 2063409; 2063410; 2083226; 2083227; 2083228; 2083229; 2083230;
2083231; 2083232; 2083233; 2083234; 2083235; 2084666; 2084667;
and corresponding patents of other countries.
US and foreign patents pending. Lutron, Ampion, Ariadni, Attach, Aurora,
Centurion, Claro, Credenza, Dimming by Lutron, Diva, Earn & Learn, Earn & Learn
Express, Euro Maestro, Fandial, Glyder, GRAFIK Eye, GRAFIK 6000, Hi-lume,
HomeWorks, Hyperion, Luma, Luma 2, Lutron Dimmers Save Energy, Maestro,
microWATT, Nova, Nova Ta, Orion, Paesar, PerSONNA, Powerdial, RadioRA, Save
Energy and design, Sivoia, Skylark, Solaris, Spacer, Speedial, the Sunburst logo,
Telume, Ta, The Ultimate Home Theater Experience, The Ultimate Home Theater
and Design, Toggler, Tu-Wire, Vareo, Versaplex, and US Trademarks 1,617,349;
1,624,489; 1,624,490; 1,626,714, and 1,638,913
are registered trademarks of Lutron Electronics Co., Inc.
Architrave, Athena, Classico, Designer, Digital microWATT, Dim-N-Glo, Diva Duo,
Eco-10, FASS, Faedra, FASS, FasTrak, Favorite Scene, GRAFIK 5000, GRAFIK Eye
Designer, GRAFIK Eye Liaison, GRAFIK Integral, hand, Harmony, Hi-lume Compact,
Hi-lume Compact SE, Hi-Power 246, Liaison, LuMaster, Lustra, Maestro Duo,
microOS, microPS, microWATT-SC, Millennium, NeTwork, Omnislide, One Spec,
Piedra, Pre-Pack, RadioTouch, Ranax, RTISS, Satin Colours, seeTouch, Serena,
Softswitch, Spacer System, Sunata, Symphony, TapSwitch, Viseo, Vibrato, Zone
Capture and 2Link are trademarks of Lutron Electronics Co., Inc.
To Contact Lutron:
WORLD HEADQUARTERS
EUROPEAN HEADQUARTERS
Lutron EA Ltd.
6 Sovereign Close
London, E1W 3JF
United Kingdom
Tel:
+44-(0)20-7702-0657
Fax:
+44-(0)20-7480-6899
CUSTOMER SERVICE/ORDERING
UK
USA
CUSTOMER SERVICE/E-MAIL
custsvc@lutron.com
TECHNICAL SUPPORT & SERVICES
UK
USA
INTERNET
www.lutron.com/europe
A D D I T I O N A L L U T R O N S A L E S O F F I C E S L O C AT E D I N :
United Kingdom
Germany
France
Spain-Madrid
Spain-Barcelona
Hong Kong
Beijing
Shanghai
Singapore
Japan
Brasil
Tel:
Tel:
Tel:
Tel:
Tel:
Tel:
Tel:
Tel:
Tel:
Tel:
Tel:
+44-(0)20-7702-0657
+49-309-710-4590
+33-(0)1-41-05-42-80
+34-91-567-84-79
+34-93-496-57-42
+852-2104-7733
+86-10-5877-1817
+86-21-62881473
+65-6220-4666
+81-3-5575-8411
+55-11-3885-5152
Fax:
Fax:
Fax:
Fax:
Fax:
Fax:
Fax:
Fax:
Fax:
Fax:
+44-(0)20-7480-6899
+49-309-710-4591
+33-(0)1-44-70-70-97
+34-91-567-84-78
+34-93-496-57-50
+852-2104-7633
+86-10-5877-1816
+86-21-62881751
+65-6220-4333
+81-3-5575-8420
FREEPHONE
FREEPHONE
FREEPHONE
FREEPHONE
FREEPHONE
(UK) 0800-282-107
00800-5887 6635
0800-90-12-18
0900-948-944
0900-948-944
01/2007 Lutron Electronics Co. Inc. | Made and printed in the U.S.A. | P/N 367-1029/EA Rev. G