Sei sulla pagina 1di 50

Pgina 1 Reviso5 Maio/2012

MANUAL GERAL





CONTROLE DE SINCRONISMO, PARALELISMO E
TRANSFERNCIA AUTOMTICA DE CARGA
STR-PESA























Pgina 2 Reviso5 Maio/2012


Contedo


1. LAY-OUT DO CONTROLE DO GRUPO GERADOR: .................................................................................... 3
2. LAY-OUT DO PAINEL COM UM DISJUNTOR: .............................................................................................. 5
3. LAY-OUT DO PAINEL COM DOIS DISJUNTORES: ..................................................................................... 7
4. DIAGRAMA DE CONTROLE: ............................................................................................................................ 9
5. DIAGRAMA DE COMANDO DOS DISJUNTORES: ..................................................................................... 15
6. DIAGRAMA DE COMANDO DAS PROTEES: ........................................................................................ 16
7. DIAGRAMA DO EGCP-2: ................................................................................................................................. 17
8. DESCRIO QUADRO DE TRANSFERNCIA EGCP 2 ........................................................................... 18
9. DESCRIO DOS COMPONENTES: ............................................................................................................ 18
10. DESCRIO DAS CHAVES DE COMANDO: .......................................................................................... 19
11. OPERAO EM MODO MANUAL: ............................................................................................................ 19
12. OPERAO EM MODO AUTOMTICO: .................................................................................................. 19
13. PROCEDIMENTOS PARA RECONHECIMENTO DE ALARMES NO EGCP 2: ................................. 20
14. REINICIANDO EVENTOS NO EMCP3 ...................................................................................................... 21
14.1 REINICIANDO EVENTOS INDIVIDUAIS NO EMCP3 ........................................................................ 21
14.2 REINICIANDO TODOS OS EVENTOS PARA UM MDULO NICO ................................................. 22
14.3 REINICIANDO TODOS OS EVENTOS PARA TODOS OS MDULOS ................................................ 24
15. DESCRITIVO DO MANUAL DO EGCP-2: ................................................................................................. 25
16. FALHAS E DIAGNSTICOS: ...................................................................................................................... 25
16.1 COMBUSTVEL: ............................................................................................................................. 25
16.2 FILTRO DE AR: ............................................................................................................................... 25
16.3 FALHA NO SINCRONISMO: ........................................................................................................... 26
16.4 PARALELISMO EM AT (13,8/23/34,5 kV): .................................................................................... 26
16.5 GRUPO FICA EM PARALELO COM A CONCESSIONRIA: .............................................................. 26
17. ALARMES: ...................................................................................................................................................... 27
17.1 SINALIZAO DE ALARMES DO REL PRIMRIO .......................................................................... 27
17.2 SINALIZAES DE ALARMES PARA O DVR .................................................................................... 28
17.1 SINALIZAES DE ALARME PARA O EGCP-2 ..................................................................................... 29
17.2 SINALIZAES DE ALARMES PARA O EMCPII .................................................................................... 30
17.3 SINALIZAES DE ALARMES PARA O EMCP3 .................................................................................... 32
18. MANUAL DE OPERAO DO EGCP-2: ................................................................................................... 34
19. ANOTAES: ................................................................................................................................................ 49

Revises
Reviso 01 2009 Criao - ODG
Reviso 02 2010 Diagramas - ODG
Reviso 03 2011 Sinalizaes Alarmes EMCP3
Reviso 05 2012 Reconhecimento de Alarmes EMCP3, EGCP2
Descrio do quadro de transferncia






Pgina 3 Reviso5 Maio/2012


Este Manual pode ser alterado sem prvio aviso.


1. LAY-OUT DO CONTROLE DO GRUPO GERADOR:





























VISTA FRONTAL EXTERNA SUPERIOR



ITEM QTDE REFERNCIA DESCRIO
10 1 SR1150 Boto de emergncia tipo girar para destravar
9 1 SR1121 Boto pulsar azul
8 3 SR1140 Comutador de duas posies com retorno a zero
7 2 SR1120 Comutador de duas posies fixas
6 4 SR1170 Sinaleiro com led cor vermelho
5 4 SR1161 Sinaleiro com led cor amarelo
4 1 SR1171 Sinaleiro com led cor verde
3 1 SR1075 Controlador Eletrnico EGCP2
2 4 SR3217 Olha para iamento
1 1 SR6002 Painel autosustentvel



Pgina 4 Reviso5 Maio/2012




VISTA
FRONTAL INTERNA SUPERIOR

ITEM QTDE REFERNCIA DESCRIO
27 2 SR1511 Borne de passagem verde/amarelo
26 2,5 SR0004 Trilho DIN mega
25 7 SR0006 Canaleta PVC 50x50 mm
24 154 SR1500 Borne de passagem
23 7 SR1505 Borne diodos
22 1 SR1230 Bloco temporizado (TY)
21 3 SR1220 Bloco de contatos 2NA2NF (C1, 52Gx, 52Lx)
20 14 SR1200 Contator auxiliar 24 Vcc 2NA2NF (HRT3, C2, C3, FMG,
52T, EG52Lx, EG52Gx, 52DG, 52Lx, MAN, K1, K2)
19 2 SR1210 Contator auxiliar 24 Vcc 4NA (HR, C1)
18 1 Sob Consulta Transdutor de potncia (TR)
17 1 SR1090 Rel de potncia inversa (32L)
16 1 SR1234 Temporizador 30 segundos
15 5 SR1401 Disjuntor monofsico 10 A (24 Vcc, MN/L, MN/G, SY)
14 8 SR1403 Disjuntor monofsico 2 A (TM, K1, K2, EGCP, TRR, 27G,
28G, 28G)
13 1 SR1300 Timer programvel 220 Vca (TM)
2 4 SR3217 Olha para iamento
1 1 SR6002 Painel autosustentvel


Pgina 5 Reviso5 Maio/2012


2. LAY-OUT DO PAINEL COM UM DISJUNTOR:








































VISTA FRONTAL EXTERNA


Pgina 6 Reviso5 Maio/2012


































VISTA FRONTAL EXTERNA INFERIOR
ITEM QTDE REFERNCIA DESCRIO
12 1 SR0050 Placa de advertncia
11 1 Sob Consulta Disjuntor tripolar termomagntico com motorizao (In = em
funo da carga)
01 1 SR6002 Painel autosustentvel




Pgina 7 Reviso5 Maio/2012


3. LAY-OUT DO PAINEL COM DOIS DISJUNTORES:














































VISTA FRONTAL EXTERNA


Pgina 8 Reviso5 Maio/2012















































VISTA FRONTAL
EXTERNA INFERIOR

ITEM QTDE REFERNCIA DESCRIO
12 1 SR0050 Placa de advertncia
11 1 Sob Consulta Disjuntor tripolar termomagntico com motorizao (In = em
funo da carga)
01 1 SR6002 Painel autosustentvel



Pgina 9 Reviso5 Maio/2012


4. DIAGRAMA DE CONTROLE:











































Pgina 10 Reviso5 Maio/2012







































Pgina 11 Reviso5 Maio/2012







































Pgina 12 Reviso5 Maio/2012







































Pgina 13 Reviso5 Maio/2012












































Pgina 14 Reviso5 Maio/2012



























































Pgina 15 Reviso5 Maio/2012


5. DIAGRAMA DE COMANDO DOS DISJUNTORES:
























































Pgina 16 Reviso5 Maio/2012


6. DIAGRAMA DE COMANDO DAS PROTEES:






















































Pgina 17 Reviso5 Maio/2012


7. DIAGRAMA DO EGCP-2:
























































Pgina 18 Reviso5 Maio/2012


8. DESCRIO QUADRO DE TRANSFERNCIA EGCP 2
9. DESCRIO DOS COMPONENTES:


A Sinaleiro ligado: mostra que o painel est pronto para operar em manual;

B Sinaleiro ligado: mostra que o painel est pronto para operar em automtico;

C Sinaleiro ligado: indica que o disjuntor da linha est fechado;

D Sinaleiro ligado: indica que o disjuntor do gerador est fechado;

E Sinaleiro ligado: indica comando para partida do grupo gerador;

F Sinaleiro verde: indica o momento em que o sincronismo est dentro das condies
de fechamento dos disjuntores de transferncia de carga.






Pgina 19 Reviso5 Maio/2012


10. DESCRIO DAS CHAVES DE COMANDO:


G Chave seletora de modo de operao: manual (M) ou automtico (A);

H Chave seletora de comando liga/desliga disjuntor da linha (DL);

I Chave seletora de comando liga/desliga disjuntor do gerador (DG);

J Chave seletora de comando liga/desliga motor (M);

L Chave seletora de comando carga e descarga do gerador: seleciona entrada e sada
automtica do grupo gerador fora do horrio de ponta (Load/Unload);

M Boto de emergncia;

N Boto de reset: tempo mximo de paralelismo (30 segundos) e tempo mximo do
grupo gerador operando a vazio (3 a 5 minutos).

Ateno:

- As chaves H, I e J, s tem funo quando a chave seletora G estiver na posio
manual (M), ou seja, sinaleiro A ligado;

- A chave seletora L somente tem funo em modo automtico (A);


11. OPERAO EM MODO MANUAL:


- O modo manual usado para ligar e desligar o disjuntor da linha, partir o grupo
gerador, testar e calibrar o motor. O disjuntor do gerador no possvel operar em
modo manual;


12. OPERAO EM MODO AUTOMTICO:


- No modo automtico o controle faz todas as funes automaticamente, seja
emergncia ou horrio de ponta. Fora do horrio de ponta pode-se fazer o grupo
gerador tomar carga sem interrupo da energia da concessionria, comandando a
chave de LOAD/UNLOAD" para a posio LOAD, e aps o perodo de operao
retornar para a posio UNLOAD (chave seletora E).




Pgina 20 Reviso5 Maio/2012


13. PROCEDIMENTOS PARA RECONHECIMENTO DE ALARMES NO
EGCP 2:


CLP EGCP-2:



Entrar com a tecla:
Alarme event,
At que, no display da direita mostre quais
falhas ocorreram.



Entrar com tecla
Enter, at que o led vermelho se apague.




Se ao teclar enter a falha no sair
Entrar com tecla
Config




Entrar com tecla
Enter




Introduzir senha 1112
Atravs das teclas Scroll
(para cima = 1, para direita e para cima = 11,
para direita e para cima = 111, para direita,
para cima e para cima = 1112)





Entrar com tecla
Enter






Entrar com tecla
Alarme event















Pgina 21 Reviso5 Maio/2012






Entrar com tecla
Enter at que o led vermelho se apage.







14. REINICIANDO EVENTOS NO EMCP3


14.1 REINICIANDO EVENTOS INDIVIDUAIS NO EMCP3

H trs caminhos para reiniciar eventos de alarme. Um deles reiniciar
individualmente para o evento desejado no registro de evento.
O segundo caminho, reiniciar todos os eventos no registro de eventos
navegando no registro de eventos ativos.
O terceiro um atalho para reiniciar todos os eventos no mdulo. Para ambos os
mtodos deve-se colocar o motor em STOP.
Para reiniciar eventos individuais no EMCP3 inicie a navegao no registro de
eventos:
Para o topo do menu principal, entre no registro de eventos pressionando a tecla
ESC.

MENU PRINCIPAL

Selecione
REGISTRO DE ENVENTOS

Pressionando a

TECLA ENTER
Navegue para cima , ou para baixo

para selecionar o evento desejado.

Pressione a TECLA ENTER



Navegue para cima , ou para baixo

Prximo, selecione o registro que
contm o evento necessrio a ser
reiniciado.

Nesta imagem, h dois eventos
PRESENTE ou ATIVO, e ambos esto
no registro do CONTROLE DO GRUPO
GERADOR.


Pgina 22 Reviso5 Maio/2012


atravs da lista de eventos e encontre
os eventos ATIVOS que necessitam
ser reiniciados.





Pressione a TECLA ENTER
Para ver o detalhe do evento





Pressionando a TECLA ENTER
Reiniciar o evento.


Os eventos so ordenados pelo status
do evento; eventos PRESENTE so
listados em primeiro lugar, seguido por
eventos ativos, e finalmente os eventos
inativos.

Se o controle estiver no modo STOP, a
mensagem RESET, ser mostrado em
destaque.

NOTA: Se o estado de e evento est
presente, o texto RESET no ser visvel
e o evento no ser reiniciado at a
condio que o causou surgir
novamente.


14.2 REINICIANDO TODOS OS EVENTOS PARA UM MDULO NICO

O segundo mtodo para reiniciar eventos, reiniciar todos os eventos do mdulo
navegando para um dos eventos ativo no registro de eventos.
Para qualquer mtodo, voc deve estar com o motor em STOP.
Eventos so mostrados como ATIVO, se h uma falha afetando o sistema, ou INATIVO
se no h.
Para reiniciar todos os eventos do registro de eventos, comece a navegar pelo registro
de eventos.

MENU PRINCIPAL

Selecione
REGISTRO DE ENVENTOS

Pressionando a

TECLA ENTER
Prximo, selecione o registro que contm
o evento necessrio a ser reiniciado.
Neste exemplo h somente um evento


Pgina 23 Reviso5 Maio/2012




Navegue para cima , ou para
baixo
para selecionar o evento desejado.

Pressione a TECLA ENTER






Pressione a TECLA ENTER
Para ver o detalhe do evento.






Pressionando a TECLA ENTER
Ser aplicado RESET em todos os
eventos.

ATIVO, e est no registro de CONTROLE
DO MOTOR.

Os eventos so ordenados pelo status do
evento; eventos ativos so listados
primeiro, seguido pelos eventos inativos.
V para cima ou para baixo na lista de
eventos e encontre o evento ACTIVO o
qual exige reset.

Se o controle estiver no modo STOP, e a
velocidade do motor esta em zero,
RESET ALL ser mostrado em destaque.

Pressionando a tecla enter ser reiniciado
todos os eventos ATIVO, no registro do
evento do mdulo que pode ser reiniciado.


NOTA: se pressionar a tecla ENTER no RESET ALL no ser reiniciado todos os
eventos, a condio que causa o evento que est sendo visualizada pode ainda estar
presente. Por exemplo, se o motor parar por alta temperatura de refrigerao, ento o
eventos no sero reiniciados at que a temperatura caia abaixo da estabelecida para
desligamento do lquido de arrefecimento.











Pgina 24 Reviso5 Maio/2012


14.3 REINICIANDO TODOS OS EVENTOS PARA TODOS OS MDULOS

A terceira maneira de reiniciar eventos : um atalho para repor todos os eventos para
todas as falhas. Para qualquer mtodo, voc deve estar no modo STOP.
Depois que todos os eventos foram vistos e as condies que causaram os eventos
foram corrigidos, todos os eventos ativos (aqueles em que a condio no est
presente) em todos os mdulos pode ser reiniciado usando o recurso ALL RESET
EVENTOS.
Para fazer isso, o controle deve estar no modo STOP e a velocidade do motor deve ser
zero.

Pressione e segure

Reconhecimento de alarme
por aproximadamente 5 segundos.


Pressione a
TECLA ENTER


Pressione a
TECLA ESC .


Uma tela de confirmao aparecer

Continuar e reiniciar todos os eventos
em todos os mdulos



Cancelar a operao de RESET.
























Pgina 25 Reviso5 Maio/2012


15. DESCRITIVO DO MANUAL DO EGCP-2:


- Ver manual 26174 do fabricante do controle.



16. FALHAS E DIAGNSTICOS:


16.1 COMBUSTVEL:


1. Falta de diesel;
2. Qualidade do diesel;
3. Filtros de diesel.

Soluo:

4. Escorvar via bomba instalado no sistema;
5. Verificar distribuidor e separador gua / combustvel;
6. Substituir.

Sintomas:

No EGCP-2, indica Low Frequency e no EMCP-II indicar AL-8, parada do motor;
Motor falha, pode alarmar Low Frequency no EGCP-2 ou AL-8 no EMCP-II, rpida
queda na energia, com ou sem abertura do disjuntor do grupo gerador;
Idem ao item 2.


16.2 FILTRO DE AR:


1. Filtro de ar sujo.

Soluo:

2. Passar ar ou substituir (recomendvel).

Sintoma:

3. Limita potncia do motor, o grupo gerador toma carga parcial, o sistema fica em
paralelo (mximo 30 segundos), abre o disjuntor do grupo gerador, fica a carga
na concessionria, o grupo gerador opera durante 3 minutos e depois desliga.



Pgina 26 Reviso5 Maio/2012


16.3 FALHA NO SINCRONISMO:


1. Falha no sincronismo.

Soluo:

2. Verificar alteraes na voltagem da concessionria ou grupo.
3. Ajustar valores.

Sintoma:

4. Grupo no consegue fechar disjuntor, lmpada verde no painel de controle pisca,
o grupo gerador far tentativas, (trs a cinco tentativas), o sistema bloqueia o
sincronismo.
- Resetar boto no painel controle (boto amarelo).

16.4 PARALELISMO EM AT (13,8/23/34,5 kV):


1. Rel de proteo secundria atuado.
Quando ocorrer atuao do rel na cabine de mdia ocorre bloqueio no
automatismo do grupo gerador. Inspecionar defeito, reconhecer a falha, resetar o rel.
operar o grupo em modo manual.


16.5 GRUPO FICA EM PARALELO COM A CONCESSIONRIA:


1. Reduo dos HPs do motor.

Soluo:

2. Verificar sistema de combustvel, filtro de ar e restrio no escapamento.

Sintoma:

3. Grupo gerador no consegue tomar toda a carga, fica em paralelo com a
concessionria por 30 segundos, abre o disjuntor do grupo, entra em tempo de
resfriamento e desliga. Resetar o boto no controle.







Pgina 27 Reviso5 Maio/2012


17. ALARMES:

17.1 SINALIZAO DE ALARMES DO REL PRIMRIO



- 51 Sobrecorrente temporizado de fase Led 1;
- 50 Sobrecorrente instantneo de fase Led 1 + Led 9;
- 51N Sobrecorrente temporizado de neutro Led 2;
- 50N Sobrecorrente instantneo de neutro Led 2 + Led 9;
- 50BF Falha do disjuntor Led 1 a Led 9 ligados;
- 46 Sobrecorrente temporizado seqncia negativa Led 3;
- 46I Sobrecorrente instantneo seqncia negativa Led 3 + Led 9;
- 67T Direcional temporizado de corrente de fase Led 4;
- 67I Direcional instantneo de corrente de fase Led 4 + Led 9;
- 67NT Direcional temporizado de corrente de neutro Led 5;
- 67NI Direcional instantneo de corrente de neutro Led 5 + Led 9;
- 32 Potncia reversa Led 6;
- 27P Subtenso trifsica Led 7;
- 27M Subtenso monofsica Led 7 + Led 9;
- 59P Sobretenso trifsico Led 7 + Led 8;
- 59P Sobretenso monofsico Led 7 + Led 8 + Led 9;
- 59N Falha a terra nvel baixo Led 6 + Led 7;
- 59NI Falha a terra nvel alto Led 6 + Led 7 + Led 9;


Pgina 28 Reviso5 Maio/2012


- 47 Sobretenso seqncia negativa Led 4 + Led 5 + Led 6 + Led 7;
- 81A1 Sobrefrequencia nvel baixo Led 1 + Led 7;
- 81A2 Sobrefrequencia nvel alto Led 2 + Led 8;
- 81B1 Subfrequencia nvel baixo Led 3 + Led 7;
- 81B2 Subfrequencia nvel alto Led 4 + Led 8.


17.2 SINALIZAES DE ALARMES PARA O DVR


Alarm Faults (Parameter 95):

0000 No fault present;
601 Internal memory failure;
602 Internal Watchdog failure;
603 Rotating diode fault;

Active Shutdown Faults (Parameter 92):

0000 No fault present;
701 Under voltage;
702 Over voltage;
703 Over excitation;
704 Loss of excitation;
705 Reserve power;
801 Instantaneous trip;
802 Loss of Sensing;
803 Loss of Frequency.



















Pgina 29 Reviso5 Maio/2012


17.1 SINALIZAES DE ALARME PARA O EGCP-2


















Cada setpoint do alarme pode ser ajustado para:

Disable;
Warning LED on control flashes;
Visual alarm LED flashes, and visual alarm relay energize;
Audible alarm LED flashes, visual and audible alarm relays energize;
Soft Shutdown LED turns on, visual and audible alarm relays energize;
Hard Shutdown Same as above, but immediately opens generator
breaker and de-energizes the fuel solenoid.

Voltage range alarm;
Generator volt high limit;
Generator volt low limit;
Generator high/low volt limit alarm;
Voltage alarm delay;
Generator frequency high limit;
Generator frequency Low limit;
Generator high/low frequency limit alarm;
Speed/frequency mismatch alarm;
Overcurrent level;
Overcurrent delay;
Overcurrent alarm;
Reverse power level;
Reverse power delay;
Minimum reverse power;
Reverse kVAr limit;
Reverse kVAr delay;
Remote faults #3.


Pgina 30 Reviso5 Maio/2012



17.2 SINALIZAES DE ALARMES PARA O EMCPII




- 100 Presso do leo do motor;
- 110 Temperatura do lquido arrefecedor do motor;
- 111 Perda de lquido arrefecedor do motor;
- 168 Voltagem da bateria;
- 175 Temperatura do leo do motor;
- 190 Sensor de rotao do motor;
- 248 Link de dados CAT (antes 560);
- 268 Parmetros programados;
- 269 Suprimento de potncia do sensor;
- 333 Sada do anunciador;
- 334 Sada extra;
- 336 Int. de controle do motor;
- 441 Rel do governador eletrnico;
- 442 Rel de falha do grupo gerador;
- 443 Rel de terminar a partida;
- 444 Rel do motor de partida;
- 445 Rel de operao;
- 446 Rel de parada do ar;
- 447 Rel de controle de combustvel;


Pgina 31 Reviso5 Maio/2012


- 448 Rel extra programvel;
- 475 Mdulo do rel do operador;
- 500 Controle + do grupo gerador (GSC+);
- 566 Componente externo sem identificao;
- 590 Comunicao perdida do ADEM;
- 859 Rel de nvel de kW;
- AL1 Alarme temperatura alta de lquido arrefecedor do motor;
- AL2 Alarme temperatura baixa do lquido arrefecedor do motor;
- AL3 Alarme presso baixa do leo do motor;
- AL4 Falha detectada pela ECM do motor;
- AL5 Falha de nvel baixo ded lquido arrefecedor do motor;
- AL6 Falha de temperatura alta do leo do motor;
- AL7 Falha de voltagem excessivo do gerador;
- AL8 Falha de falta de voltagem do gerador;
- AL9 Falha de freqncia excessivo do gerador;
- AL10 Falha de falta de freqncia do gerador;
- AL11 Falha de potncia invertida do gerador;
- AL12 Falha de fase de tenso excessivo total do gerador;
- AL13 Falha de tenso excessivo total do gerador;
- AL14 Falha de fase A sem entrada de voltagem;
- AL15 Erro de configurao GSC+;
- SP1 Falha extra de entrada 1;
- SP2 Falha extra de entrada 2;
- SP3 Falha extra de entrada 3;
- SP4 Falha extra de entrada 4;
- 2 Fora da faixa, dados errticos ou estado indefinido;
- 3 Curto a +bateria, voltagem excessiva ou circuito aberto;
- 4 Curto a terra ou falta de voltagem;
- 7 Atualizao anormal;
- 12 Componente falhando.



















Pgina 32 Reviso5 Maio/2012



17.3 SINALIZAES DE ALARMES PARA O EMCP3







- 38 Sensor de nvel do tanque de combustvel externo;
- 82 Sensor de presso de ar de partida;
- 95 Alarme do filtro diferencial de presso;
- 96 Alarme de nvel de combustvel;
- 98 Alarme do nvel de leo;
- 99 Alarme do filtro diferencial de presso;
- 100 Alarme de presso de leo do motor;
- 107 Sensor diferencial de presso do filtro de ar;
- 110 Alarme de temperatura do liquido de arrefecimento do motor;
- 111 Sensor de nvel do liquido de arrefecimento do motor;
- 137 Sensor de presso de extino de fogo;
- 167 Alarme do sistema de carregador de bateria;
- 168 Alarme de tenso de bateria;
- 171 Sensor de temperatura do ar ambiente;
- 173 Sensor de temperatura de exausto;
- 175 Sensor de nvel de temperatura do leo do motor;
- 190 Sensor de velocidade do motor;
- 625 Alarme falta de link de dados Scada;


Pgina 33 Reviso5 Maio/2012


- 639 Alarme falta de link de dados Primrio;
- 970 Parada de emergncia;
- 1122 Alarme de temperatura no rolamento do gerador;
- 1231 Alarme de falta do acessrio de link de dados;
- 1239 Alarme de ruptura no tanque de combustvel;
- 1664 Falha na partida do motor;
- 2433 Alarme de temperatura de exausto;
- 2436 Alarme de freqncia do gerador;
- 2440 Alarme de tenso do gerador;
- 2448 Alarme falta de corrente do gerador;
- 2452 Alarme de potncia reversa no gerador;
- 2648 Alarme de intervalo de manuteno para servio;
- 4000 - Damper de ar fechado;
- 4001 ATS em posio normal;
- 4002 ATS em posio de emergncia;
- 4003 Falha no carregador de bateria;
- 4004 Disjuntor do circuito do gerador fechado;
- 4005 Disjuntor do circuito de utilidades fechado;
- 4006 Motor em Cooldown;
- 4007 Alarme de gerador no em automtico;
- 4008 Desligamento inesperado do motor;




























Pgina 34 Reviso5 Maio/2012


18. MANUAL DE OPERAO DO EGCP-2:


















Pgina 35 Reviso5 Maio/2012



H um total de 19 teclas no teclado. Cada uma delas possui as seguintes funes:


TECLAS DE REISTRO DE ALARME/EVENTO:


ALARM / EVENT



ALARM CLEAR













TECLAS DE NAVEGAO E AJUSTES:


SCROLL




TECLAS DE MENU DE ESTADO:

Os contedos dos diversos menus de estado so descritos na seo de Telas de
Estado abaixo:


A tecla de ALARM/EVENT (Alarme/Evento) utilizada para acessar o
menu de alarme e eventos na tela de display do lado direito. Quando
pressionada, esta tecla mostrar no display LCD direito o estado de
atual de alarmes e eventos do grupo gerador.
A tecla de ALARM CLEAR (Limpar Alarme) utilizada para
reconhecimento dos eventos de alarme a partir do registro de eventos,
e limp-los (apag-los). Ao ser pressionada, esta tecla reconhecer o
alarme selecionado. Ao pression-la pela segunda vez, esta tecla far
com que o tem selecionado do evento de alarme seja removido do
registro de eventos. Se o evento de alarme selecionado foi um evento
de alarme ativo, a ao associada com o evento de alarme tambm
ser eliminada da lgica de controle. Se uma sada de ALARME
SONORO est ativa (energizada), a tecla de ALARM CLEAR tambm
ir remover a sada do ALARME SONORO quando for pressionada
pela primeira vez. Exige-se um cdigo de segurana de Nvel de
Operador ou maior para reconhecer e limpar alarmes.
A tecla de SCROLL (Rolagem) utilizada para movimentar o cursor
para cima, para baixo, para a direita e para a esquerda. Tambm
utilizada para incrementar e diminuir valores dentro dos menus de
configurao.


Pgina 36 Reviso5 Maio/2012




SYSTEM




ENGINE



GEN



I/O



SYNC



KW LOAD




PF / KVAR

Ao apertar-se a tecla SYSTEM (SISTEMA) so exibidas informaes
de estado do sistema. O display de estado tambm a tela de display
de estado padro ( sempre o primeiro display a aparecer aps a
ativao do controle). Este display mostra informaes gerais sobre a
operao do grupo motor gerador.
A tecla ENGINE (MOTOR), ao ser pressionada, exibe informaes de
estado sobre as funes e operao do motor.
A tecla GEN (GERADOR), quando pressionada, mostra os parmetros
das trs fases do gerador.
A tecla I/O (ENTRADAS E SADAS) fornece o estado de todas as
entradas e sadas discretas, bem como informaes sobre as entradas
e sadas analgicas.
A tecla SYNC (SINCRONISMO) mostra informaes de estado
referentes ao sincronismo via disjuntor do grupo e da rede.
A tecla KW LOAD (CARGA ATIVA) quando pressionada, mostra as
informaes de estado para o controle de carga em kW do EGCP-2.
Pressione a tecla PF/KVAR para exibir informaes do Mode de
controle VAR/PF, bem como as tenses e correntes das trs fases do
gerador.


Pgina 37 Reviso5 Maio/2012




SEQUENCE



ATS


































A tecla SEQUENCE (SEQUENCIA) oferece informao sobre
sequenciamento para sistemas de unidades mltiplas. Nesta tela no
haver informao sobre estado de sistemas de unidades nicas, e
unidades que no estiverem no modo AUTO (automtico)
A tecla ATS (CHAVE DE TRANSFERENCIA AUTOMATICA), ao ser
pressionada exibe informaes de estado sobre funes da Chave de
Transferncia Automtica.


Pgina 38 Reviso5 Maio/2012



TECLAS DE ESTADOS - SYSTEM:




Viso Geral das entradas do motor fora da linha

A tela contm as seguintes informaes:


Alarmes: Numero de alarmes ativos na unidade.
Unidade #: O endereo da unidade na rede.
Alimentao de Rede (Mains): Display grfico da condio da tenso de alimentao da rede.
Dois smbolos de menos (- -) indicam que a tenso da rede est fora de especificao; um
smbolo de mais (+) indica que a tenso da rede est dentro da especificao, mas no
considerada como estvel (+ -); dois smbolos de mais (+ +) indicam que a tenso da rede
est dentro da especificao e estvel.
Gerador: Display grfico do estado do gerador. Dois smbolos de menos indicam que o
gerador est fora de especificao; um smbolo de mais indica que o gerador est dentro da
especificao mas no determinado como estvel (+ - ); dois smbolos de mais (+ +) indicam
que o gerador est dentro da especificao e estvel.
Motor: Estado de operao do motor.

Estados de Controle do Motor:
- DESLIGADO
- PR INCANDESCNCIA
- PARTIDA
- FUNCIONANDO


Pgina 39 Reviso5 Maio/2012


- RESFRIANDO
- REDUO DE ROTAO
- RETENTATIVA

Estado de Operao: Mostra se o EGCP-2 est no modo AUTO (automtico) ou MAN
(manual).

Estado de Controle: Mostra o estado da lgica do controle de carga do EGCP-2. Os
estados do controle de carga so:

Estados de Controle de Carga:
- DESLIGADO
- DROOP
- ISCRONO
- BASE DE CARGA
- PROCESSO

kW: A carga total, em kW do gerador.

Hz: A frequncia, em Hertz, do grupo gerador.

FP: O Fator de Potencia mdio das trs fases do grupo gerador.

kWH: O total de kW-horas acumulado produzido pelo grupo gerador. Este display muda
automaticamente para mW-horas quandoo valor de kWH ultrapassa 10.000.

Tempo de Execuo (Runtime): O tempo de funcionamento total acumulado do grupo
gerador.

Toda informao do display ser automaticamente atualizada medida que os modos e
condies de operao para EGCP-2 se alterem.


















Pgina 40 Reviso5 Maio/2012



ENGINE - MOTOR


Viso geral do motor


HH:MM: Visor de relgio de 24 horas (horas, minutos).
MM-DD: Data (ms-dia)
Engine: Motor. O estado da funo de controle do motor.
RPM: RPM do motor.
Battery Volts: Tenso da Bateria em Volts CC.
H2O Temp: Temperatura da gua em graus Celcius ou Fahrenheit, dependendo da
unidade de medida selecionada na configurao.
OIL Press: Presso do leo em Bar, ou PSI (libras /pol
2
), dependendo da unidade de
medida selecionada na configurao.
Gen Breaker: Estado do disjuntor do gerador conforme providenciada na entrada
discreta auxiliar.
Gen: O estado do gerador. Dois smbolos menos (- - ) indicam que o gerador est fora
de especificao, um smbolo mais (+) indica que o gerador est dentro da
especificao, mas no considerado estvel (+ -), dois smbolos mais (+ +) indicam
que o gerador est dentro da especificao e estvel.








Pgina 41 Reviso5 Maio/2012



GEN GERADOR


Estados do gerador


A B C: Litura das trs fases do gerador.
KVA: Leitura de kVA das trs fases.
KW: Leitura de kW das trs fases.
KVR: Leituras de KVAR das trs fases.
V: Tenso em cada fase do gerador.
A: Corrente por fase para o gerador.
PF: Fator de Potencia para cada fase do gerador.

Nota
A indicao de tenso do gerador (VLL ou VLN) mudar automaticamente dependendo
do ajuste da configurao de tenso de entrada. Ver a seo do menu de configurao
deste manual para mais detalhes.

Nota
As leituras e indicaes de tenso mudaro automaticamente de V (volts) pra KV
(quilovolts) quando a tenso ultrapassar 9999 V nessa entrada.






Pgina 42 Reviso5 Maio/2012


I/O ENTRADAS E SADAS


Estados das entradas / sadas



DI: Entradas discretas 1 a 16.
DO: Sadas discretas 1 a 12.
Volt Bias: Sada % bias (ajuste) de tenso (+- 100% da faixa).
Speed Bias: Sada % bias (ajuste) de velocidade (+- 100% da faixa).
Process In: Entrada de processo em miliampres (mA).


Entradas Discretas
1. Modo Automatico
2. Modo Teste
3. Modo de Operao com Carga
4. Aumentar Tenso
5. Diminuir Tenso
6. Aumentar Velocidade
7. Diminuir velocidade
8. Contato Auxiliar do Disjuntor do Gerador
9. Contato Auxiliar do Disjuntor da Rede
10. Controle de Processo
11. -16. Entradas Remotas de Alarme / Desligamento




Pgina 43 Reviso5 Maio/2012


Sadas Discretas

1. Fechar Disjuntor / Contator da Rede
2. Fechar Disjuntor / Contator do Gerador
3. Pr Incandescencia do Motor
4. Solenoide de Combustivel
5. Motor de partida
6. Rel de Alarme visual
7. Conexo do TP da rede
8. Desconexo do TP da rede
9. Abre disjuntor da rede
10. Abre do Disjuntor do gerador
11. Alarme sonoro
12. Chave de carga em kVA, ou chave Lenta / Nominal dependendo da
configurao.


































Pgina 44 Reviso5 Maio/2012


SYNC - SINCRONZAO


Estados do sincronismo

Slip: Diferena de frequncia em Hz do gerador com relao ao barramento ou a rede
qual est em paralelo.
Phase: Diferena de ngulo de fase em graus entre o gerador e o barramento ou rede
com qual est em paralelo.
Volts: Diferena de potencial percentual entre o gerador e o barramento ou rede com a
qual est em paralelo.
Mains/Bus: Entrada de TP ativa monitorada pelo EGCP-2.
Dead Bus: Indica se a entrada TP (rede ou barramento) que est sendo medida est
inativa.
Syncronizer Status: Exibe os estado do sincronizador. Estes so os seguintes:
Fechar Disjuntor do Gerador Abrir Disjuntor do Gerador
Fechar Disjuntor da Rede Abrir Disjuntor da rede
Temporizador do Sincronizador
VB: Sada de Bias (ajuste) de tenso (%)
SB: Sada de Bias (ajuste) de velocidade (%)
GEN A: Tenso do gerador.
MAINS: Tenso da entrada de TP ativa monitorada pelo sincronizador.
NOTA
A indicao de tenso do gerador (VLL ou VLN) mudar automaticamente dependendo
do ajuste da configurao de tenso de entrada. Ver a seo do menu de configurao
deste manual para mais detalhes.


Pgina 45 Reviso5 Maio/2012


kW LOAD


Estados da carga Ativa (kW)


Generator kW: A soma da potncia em kW das trs fases do Gerador.
Load Reference: A referencia de carga, em kW para o gerador.
System Load: A carga de sistema calculada para todas as unidades operando no modo
iscrono de diviso de carga. Esta leitura ativa somente nas unidades em diviso de
carga.
Control: O modo de controle de carga atual em operao.
Process in: O valor medido da entrada de peocesso em 4-20 mA ou 1-5 VCC

NOTA
A leitura de entrada de processo ser sempre escalada em mA. Se for usada uma
entrada de tenso, a leitura da entrada de processo multiplicada por 243 converter a
leitura de mA diretamente para a tenso na entrada.

Process Ref: A referencia de processo para o controle de processo.
Master Sync Cmd: O comando mestre de bias (ajuste) para o sincronizador e o
controle de carga (%).
Master Volt Cmd: O comando mestre de bias (ajuste) de tenso (%).





Pgina 46 Reviso5 Maio/2012


PF kVAR


Estados da controle de FP/KVAR


VAR/PF MODE: O modo de controle VAR/PF configurado.
PF REFERENCE: O valor referencia de controle de fator de potencia

NOTA
A referencia do Fator de Potencia (FP) muda para KVAR REF quando se opera em
controle de VAR.

PF: O FP mdio das trs fases do gerador.
ABC: Indicao da leitura das fases A,B,C do gerador.
V: Leituras de tenso das trs fases do gerador.
A: Leituras da corrente das trs fases do gerador.
KVAR: Leitura do KVAR total para o gerador.











Pgina 47 Reviso5 Maio/2012


SEQUENCE - SEQUNCIA


Menu de sequenciamento

UNIT: Endereo de Rede de todas as unidades em Auto na rede RS-485.
OPER: Unidade em Auto, e na rede com seus disjuntores fechados e sob carga.
PRTY: Prioridade de Rede pra todas as unidades em Auto na rede.
MASTER UNIT: Unidade com maior prioridade (numero mais baixo de prioridade) que
est na rede e em Auto.
NEXT ON: Endereo de Rede da prxima unidade que, na sequencia, entrar na rede.
NEXT OFF: Endereo de rede da prxima unidade que, na sequencia sair da rede.
TOTAL ON LOAD: Nmero total de unidades em diviso de carga operando em modo
iscrono.
GEN BREAKER: Estado do disjuntor do gerador como determinado pela entrada
discreta gen CB aux.













Pgina 48 Reviso5 Maio/2012


ATS SISTEMA DE TRANSFERENCIA AUTOMATICA


Menu de sequenciamento Unidades Multiplas


Como mostrado na tela de sequenciamento:

UNITS 1,3 e 5 esto em carga e com os disjuntores do gerador fechados.
NEXT ON a unidade numero 2, que possui prioridade de rede 4.
NEXT OFF a unidade nmero 5, que possui prioridade de rede 3.
MASTER UNIT neste sistema a unidade com a prioridade mais alta, que a unidade
nmero um.
NOTA
Os estados de sequenciamento so exibidos quando a unidade est em Auto e
configurada para Unidades Mltiplas.

NOTA
As unidades com parada (shutdowns) ativos sairo elas mesmas do menu de
sequenciamento at que a condio de parada seja solucionada.







Pgina 49 Reviso5 Maio/2012


19. ANOTAES:

____________________________________________________________________________________________-
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________























Pgina 50 Reviso5 Maio/2012










PROTOCOLO DE RECEBIMENTO