Tdb1 75 F Tdb2 100 F

Twb1 63 F Twb2 75 F
Elevation 11 ft.
AtmPress 14.69 psia
APinHg 29.91 in Hg
HRatio1 0.0095 lbw/lba HRatio2 0.0129 lbw/lba
66.8 Grains 90.4 Grains
RelHum1 51.6 % RelHum2 31.4 %
SpHt1 0.244 Btu/lb-F SpHt2 0.246 Btu/lb-F
Enal1 28.4 Btu/lb Enal2 38.3 Btu/lb
SpVol1 13.69 cu.ft./lb SpVol2 14.41 cu.ft./lb
DewPt1 56.0 F DewPt2 64.4 F
lbpCuFt 0.000697 lb
w
/ft
3
lbpCuFt 0.000896 lb
w
/ft
3
This Psychrometric Processes Program follows equations provided in the 2005 ASHRAE Handbook of
Fundamentals, Chapter 6. The program can replace the Psychrometric chart and users are encouraged to
compare values. It permits the quick calculation of basic HVAC air mixing, cooling, heating and heat recovery
processes. Thanks are extended to Dr. Jim Richardson (CE Department @ UA) and Barbara McCrary of
Hattemer, Hornsby & Bailey, Pratteville, AL for assistance in learning the use of Visual Basic macros in Excel
that permit the calculation of psychrometric values using functions.
See HVAC Simplified (Kavanaugh, 2006) available from ASHRAE for additional details.
Note 1: In these programs,
required input values are in
yellow cells. Output values
are in blue or green.
DRY BULB TEMPERATURE (F)
80
40
40
60 50
50
60
70
75
R
e
lH
u
m
- 4
0
%
80 90 100 120
20 %
8
0
%
6
0
%
90
.004
.016
.012
.008
H
U
M
ID
IT
Y

R
A
T
I
O
(
L
b
v
/
L
b
a
)
.028
.024
.020
40
35
30
45
50
25
20
15
E
n
t
h
a
l
p
y

(
B
t
u
/
l
b
a
)
110
1
5
.0
ft 3
/lb
a
1
4
.5
1
4
.0
S
p
c
V
o
l -
1
3
.5
ft 3
/.
lb
a
1
3
.0
1
2
.5
32
W
e
t B
u
lb
&
D
e
w
P
o
in
t (
F
)
70
65
W
et B
ulb (F
)
Dew Point (F)
E
n
th
a
lp
y
The Psychrometric Chart
Note 2: If Macro security level is set at high, this program will
result in errors in the cells [NAME?]. To reset the security level,
1. Close the PsychProcess program.
2. Click on "Tools" on the main tool bar, select "Macro", select
"Security.
3. Reset security level to Medium (recommended) or Low
4. Exit Excel
5. Re-Open Excel
6. Run program

For 2007 Office products, the terminology "trust" has replaced "security"
and the procedure has been changed (as you might expect). To change
the "trust" settings:

Open Excel
Click the Office Button (top left corner of screen)
Click on "Excel Options" button @ the bottom of the pop-up window
Click on "Trust Center"
Click on "Trust Center Settings"
Click on " Enable all macros.."
Open and Run the programs
An option would be to reset the trust setting by repeating steps 1 thru 5
and,
Click on " Disable macros with notification"

Qair1 5000 cfm Qair2 1000 cfm
QSair1 4869 scfm QSair2 925 scfm
Stream 1 Stream 2
mflow1 21912 lb/hr mflow2 4164 lb/hr
Stream 3 (mixed)
mflow3 26077 lb/hr
Qair3 6000 cfm
Tdb3 79.0 F
HRatio3 0.0101 lbw/lba
70.5 Grains
Twb3 65.2 F
RelHum3 47.9 %
SpHt3 0.244 Btu/lb-F
Enal3 30.0 Btu/lb
SpVol3 13.80 cu.ft./lb
DewPt3 57.5 F
Mixing - This Worksheet computes the resulting properties of air
(stream 3) when streams 1 and 2 are mixed. Flow rates are
entered below but properties for streams 1 and 2 are entered on
the "Properties" Worksheet.
Note: Input values (Qair1 and Qair2) are in cubic feet per minute.
For additional information purposes, these values are corrected to air
at standard conditions of =0.075 lb/cu.ft. (QSair1 and QSair2).
Stream 2 @
Qair2(cfm),
Tdb2(F),
& Twb2(F)
Stream 1 @
Qair1(cfm),
Tdb1(F),
& Twb1(F)
Stream 3 @
Qair3(cfm),
Tdb3(F),
& Twb3(F)
1
2
3
HRU Effectiveness Room Air
SenEff 70 % TdbRm 75
LatEff 65 % TwbRm 63 F
Outdoor Outdoor Air F
QairOut 10000 cfm TdbOut 96
QSairOut 9307 scfm TwbOut 75 F
mflowOut 41883 lb/hr Elev. 600 ft.
SupFankW 0 kW HRU Outlet
ExFankW 0 kW Capacities MBtu/h Tons Temps.
Exhaust (not req'd) qTotalHru 280.1 23.3 TdbHru 81.3 F
QairEx 2000 cfm qSenHru 151.5 12.6 TwbHru 67.3 F
QSairEx 1851 scfm SHRHru 0.54
Room Air Outdoor Air HRU Outlet
HRatioRm 0.0095 lbw/lba HRatioOut 0.0138 lbw/lba HRatioHru 0.0110 lbw/lba
66.8 Grains 96.9 Grains 77.3 Grains
RelHumRm 51.6 % RelHumOut 38.0 % RelHumHru 48.6 %
SpHtRm 0.244 Btu/lb-F SpHtOut 0.246 Btu/lb-F SpHtHru 0.245 Btu/lb-F
EnalRm 28.4 Btu/lb EnalOut 38.3 Btu/lb EnalHru 31.6 Btu/lb
SpVolRm 13.69 cu.ft./lb SpVolOut 14.33 cu.ft./lb SpVolHru 13.89 cu.ft./lb
DewPtRm 56.0 F DewPtOut 66.3 F DewPtHru 60.0 F
HRU
Outdoor Air
Exhaust Air
This Worksheet computes the properties of air leaving Heat Recovery Units (HRU) used to adsorb or remove heat (and in some u
moisture) from room air that is being exhausted. The heat and moisture are transfered to or from the fresh outdoor air make
capacity of the HRU is also computed. The effects of the HRU supply fan heat are considered.
t(o)
MBtu/h Tons
Total 413.7 34.5
Sensible 216.5 18.0
OALoads
HRU
Room Air
HRU Outlet Air
to room or
HVAC Unit
This Worksheet computes the properties of air leaving Heat Recovery Units (HRU) used to adsorb or remove heat (and in some units
moisture) from room air that is being exhausted. The heat and moisture are transfered to or from the fresh outdoor air make-up air. The
D
t(o)
t(r)
t(hru)
Summer
D
D
Winter
t(hru)
t(o)
Inlet Conditions Outlet Conditions
Without Humidification
QairHin 2000 cfm
qFurn 75 MBtu/h
QSairHin 1983 scfm
mflowHin 8924 lb/hr TdbHout 102.6 F
TwbHout 68.2 F
TdbHin 68 F
TwbHin 56 F
ElevH 0 ft. HRatioHout 0.0068 lbw/lba
APpsia 14.70 psia 47.6 Grains
APHg 29.92 in Hg RelHumHout 15.6 %
SpHtHout 0.243 Btu/lb-F
EnalHout 32.1 Btu/lb
HRatioHin 0.0068 lbw/lba SpVolHout 14.33 cu.ft./lb
47.6 Grains DewPtHout 47.0 F
RelHumHin 46.8 %
SpHtHin 0.243 Btu/lb-F
EnalHin 23.7 Btu/lb
SpVolHin 13.45 cu.ft./lb
DewPtHin 47.0 F
t(in)
t(out)
Outlet Conditions
With Humidification*
TdbOutAir 20 F
TwbOutAir 15 F
OAVentInfil 20 % of supply
HRatioOA 0.0007 lbw/lba
5.1 Grains
RelHumOA 32.2 %
SpHtOA 0.240 Btu/lb-F
EnalOA 5.6 Btu/lb
SpVolOA 12.11 cu.ft./lb
DewPtOA -6.8 F
FluidType Sat Steam
FluidTemp 212 F
EnalFluid 1150 Btu/lb
mfluid 10.8 lb/hr
qHumid 0.5 MBtu/h
TdbHumOut 102.8 F
qNet 75.5 MBtu/h
Water
Steam
t(in)
t(out)
*Assumption:
Sufficient moisture is
added in the form of
water or saturated steam
to replace the moisture
lost via the exhaust air,
which is replace with
dryer outdoor air.
Inlet Air Conditions Fan Heat Neglected Fan Heat Included
QairIn 4000 cfm TotalPress 2
TC 120 MBtu/h FanEff 65
SC 100 MBtu/h MotorEff 82
QSairIn 3897 scfm BHP 1.89
SHR 0.83 qFan 5.9
TdbIn 75 F mflowIn 17537 lb/hr qTotNet 114.1
TwbIn 63 F QairOut 3819 cfm qSenNet 94.1
ElevIn 0 ft. QSairOut 3897 scfm SHRNet 0.82
AtmPressIn 14.70 psia
APinHgIn 29.92 in Hg TdbOut 51.7 F TdbNet 53.0
TwbOut 51.7 F TwbNet 52.9
HRatioIn 0.0095 lbw/lba HRatioOut 0.0085 lbw/lba HRatioNet 0.0085
66.7 Grains 59.2 Grains 59.2
RelHumIn 51.6 % RelHumOut 100.0 % RelHumNet 99.4
SpHtIn 0.244 Btu/lb-F SpHtOut 0.244 Btu/lb-F SpHtNet 0.244
EnalIn 28.4 Btu/lb EnalOut 21.6 Btu/lb EnalNet 21.9
SpVolIn 13.69 cu.ft./lb SpVolOut 13.07 cu.ft./lb SpVolNet 13.10
DewPtIn 56.0 F DewPtOut 52.8 F DewPtNet 52.8
In. of Water
%
%
hp
MBtu/h
MBtu/h
F
F
lbw/lba
Grains
%
Btu/lb-F
Btu/lb
cu.ft./lb
F
In
Out
Fan Heat Included
Fan Heat Neglected
Net
By-Pass (BP) Factor
Method
QairRet 4000 cfm mflowRet 17326 lb/hr
Tadp 47 F QairSup 3757 cfm
BPFactor 0.1 QAairSup 3850 scfm
QSairRet 3850 scfm
TdbSup 50.3 F
TdbRet 79.8 F TwbSup 49.5 F
TwbRet 67.1 F HRatioadp 0.0068 lbw/lba
Elev 0 ft.
AtmPress 14.70 psia qTotal 201.0 MBtu/h
APinHg 29.91 in Hg qSensible 125.3 MBtu/h
SHRcoil 0.62
HRatioRet 0.0113 lbw/lba HRatioSup 0.0073 lbw/lba
79.1 Grains 50.8 Grains
RelHumRet 52.0 % RelHumSup 94.7 %
SpHtRet 0.245 Btu/lb-F SpHtSup 0.243 Btu/lb-F
EnalRet 31.5 Btu/lb EnalSup 19.9 Btu/lb
SpVolRet 13.85 cu.ft./lb SpVolSup 13.01 cu.ft./lb
DewPtRet 60.7 F DewPtSup 48.7 F
T(dbRet)
T(wbRet)
T(dbSup)
T(wbSup)
T(adp)
Q(airRet)
Q(airSup)
BPFactor = 1-(TdbRet-TdbSup)/(TdbRet-Tadp)
t(ret)
t(sup)
t(adp)