Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
DH-R
Finned tube duct heaters are most suitable for comfort heating as it provides dampened rate of heating
and cooling, which contributes to more natural and accurate temperature control. Electrical and fire hazard
is also reduced as it is properly insulated. They are more robust, requires little maintenance, and easier to
service.
The duct heater unit is manufactured according to customer duct size, heating capacity, phase, voltage,
and control strategy. Control elements are protected by an enclosure
Heating elements are made from nickel chromium wires insulated with packed refractory material in round
stainless steel tubes. Fins are continuosly wound to ensure robustness and good heat transfer.
Safety controls
Primary over temperature protection is by a sturdy stem type auto reset thermal cutout, secondary over
temperature protection is by a stem type manual reset thermal cutout. DPS (Diffential Pressure Switch) to
verify air flow to allow heater to switch on is optional. All units come with overcurrent protection and
isolator.
Wiring
Plastic (polyamide) plastic threaded cable glands are used to ensure cables are securely fastened, and
strain free at the connection terminals.
Weidmuller earth terminals are mounted on DIN rails to ensure secure earthing. High temperature, leaf
spring protected screw on terminals are used to ensure fast and secure connection.
Mechanical contactors, SSR and other components are mounted onto the DIN rails for secure installation
and easy servicing
1
Duct Heater, Rectangular
DH-R
CONSTRUCTION . DIMENSIONS
110 max
360
B
H + 100 250max
H
Construction
The Breadth (B) and Height (H) is made to suit the customer requirement.
40mm flange is provided.
Heating element covers minimum 70% of duct Breadth, where uncovered area is installed with
50% free area perforated sheet steel, to provide for more uniform air flow across the heating
elements
Materials
Total pressure sensor tube from aluminium (optional item), used with DPS (Differential Pressure
Switch) which is used to verify air flow in duct to permit heater to switch on.
Optional
Insulation cladding from Rockwool, 50mm thick, 40kg/m3
2
Duct Heater, Rectangular
DH-R
Product Order Code
DH-R
Material
- xx SS Stainless Steel 304, 1.0 mm thick
GI Galvanised Sheet Steel, 1.2 mm thick
Heating Element Material - tube
-x C Cladding, 50 mm Rockwool, 40 kg/m3 density
0 No cladding
Heating elements
Connection type
- xx F Flange
S Sleeve
- xxx B Breadth in mm
x xxx H Height in mm
- xx SS Stainless Steel 304 (standard)
GI Aluminium painted Galvanised Steel
- xx F Finned
UF Unfinned
xxx MC Mechanical Contactor
SSR SSR - Solid State Relay
-xx 1…3 Number of Steps
MA Modulating, 4-20 mA Not available for MC
VDC Modulating, 0-10 Vdc
Electrical mains
0.5…40 Heating capacity, kW
1…3 Phases
110… 240 Voltage
Eg.
DH-R-GI-0-F-500x250-SS-F-MC-1-2-1-240-0
Description
Rectangle duct heater to suit duct of 500 x 250 mm, from Galvanised
Sheet Steel 1.2 mm thick. Terminal is uninsulated.
Finned tube heating elements from Stainless Steel 304.
Controls: single step switch by mechanical contactor
2 kW heating capacity, connected to single phase supply, 240Vac
Room module is not supplied.