Sei sulla pagina 1di 90

ELITE

Sensor
Instruction Manual
July 1999
ELITE

Sensor
Instruction Manual
For technical assistance, phone the Micro Motion Customer
Service Department:
In the U.S.A., phone 1-800-522-6277, 24 hours
Outside the U.S.A., phone 303-530-8400, 24 hours
In Europe, phone +31 (0) 318 549 443
In Asia, phone 65-770-8155
Copyright 1999, Micro Motion, Inc. All rights reserved.
Micro Motion, ELITE, and ProLink are registered trademarks, and ALTUS is
a trademark of Micro Motion, Inc., Boulder, Colorado. HART is a registered
trademark of the HART Communication Foundation, Austin, Texas. Modbus is a
registered trademark of Modicon, Inc., North Andover, Massachusetts. FOUNDATION is
a trademark of the Fieldbus Foundation, Austin, Texas. Hastelloy is a registered
trademark of Haynes International, Inc., Kokomo Indiana. Inconel is a
registered trademark of Inco Alloys International, Inc., Huntington, West Virginia.
ELITE

Sensor Instruction Manual i
Contents
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Your new sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The installation process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Additional information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Step 1. Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Keys for sensor location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Pipe run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cable to transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CMF300A junction box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CMF400 booster amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Hazardous area installations . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 2. Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Keys for sensor orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Flow direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Process fluid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 3. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Keys for sensor mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Optional CMF010 mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CMF300A high-temperature sensors . . . . . . . . . . . . . . . . . . . . . 13
Installing wafer-style sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Optional heat tracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Step 4. Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Hazardous area installations . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Sensor junction box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
CMF400 booster amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Sensor grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Grounding CMF400 sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Flowmeter cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Step 5. Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Zeroing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Configuration, calibration, and characterization . . . . . . . . . . . . . 29
Customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
ii ELITE

Sensor Instruction Manual
Contents continued
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
General information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Zero drift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Erratic flow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Inaccurate flow rate or batch total . . . . . . . . . . . . . . . . . . . . . . . . 34
Inaccurate density reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Inaccurate temperature reading . . . . . . . . . . . . . . . . . . . . . . . . . 36
Troubleshooting at the transmitter . . . . . . . . . . . . . . . . . . . . . . . 37
Troubleshooting at the sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Appendixes
Appendix A ELITE

Sensor Specifications . . . . . . . . . . . . . . 49
Appendix B Ordering Information . . . . . . . . . . . . . . . . . . . . . 63
Appendix C Purge Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Appendix D Rupture Disks . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Appendix E Label Maintenance and Replacement. . . . . . . . 71
Appendix F Return Policy. . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
ELITE

Sensor Instruction Manual iii
Contents continued
Tables
Orientations for measuring liquids . . . . . . . . . . . . . . . . . . . . . . . 8
Orientations for measuring gases. . . . . . . . . . . . . . . . . . . . . . . . 9
Orientations for measuring slurries. . . . . . . . . . . . . . . . . . . . . . . 10
Maximum temperature for heat tracing. . . . . . . . . . . . . . . . . . . . 16
Wire-to-wire connections in CMF300A and CMF400 junction
box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Troubleshooting zero drift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Troubleshooting erratic flow rate . . . . . . . . . . . . . . . . . . . . . . . . 33
Troubleshooting inaccurate flow rate or batch total . . . . . . . . . . 34
Troubleshooting inaccurate density reading. . . . . . . . . . . . . . . . 35
Troubleshooting inaccurate temperature reading. . . . . . . . . . . . 36
Nominal resistance ranges for flowmeter circuits . . . . . . . . . . . . 39
Transmitter terminals for checking flowmeter circuits. . . . . . . . . 39
Time required to purge ELITE sensor cases . . . . . . . . . . . . . . . 67
iv ELITE

Sensor Instruction Manual
Contents continued
Figures
Components of ELITE sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Components of ELITE sensors continued. . . . . . . . . . . . . . . . . . 2
Components of ELITE sensors continued. . . . . . . . . . . . . . . . . . 3
Mounting any ELITE sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CMF010 mounting with bolts. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CMF300A remote-mount junction box . . . . . . . . . . . . . . . . . . . . 13
Wafer-style assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Tightening sensor alignment rings . . . . . . . . . . . . . . . . . . . . . . . 15
Standard ELITE junction box . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
CMF300A sensor cable and junction box . . . . . . . . . . . . . . . . . . 19
CMF400 wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
CMF400 grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Wiring connections at CMF300A and CMF400 sensors . . . . . . . 25
Wiring to RFT9739 field-mount transmitter . . . . . . . . . . . . . . . . . 26
Wiring to RFT9739 rack-mount transmitter . . . . . . . . . . . . . . . . . 26
Wiring to Model 3500 with screw or solder terminals . . . . . . . . . 27
Wiring to Model 3500 with I/O cable . . . . . . . . . . . . . . . . . . . . . . 27
Wiring to Model 3700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Wiring to IFT9701 and Model 5300 transmitters. . . . . . . . . . . . . 28
Wiring to RFT9709 transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Cross-section of cable with drain wires. . . . . . . . . . . . . . . . . . . . 38
Checking ohm levels at a CMF400 sensor . . . . . . . . . . . . . . . . . 40
Cross-section of externally shielded cable . . . . . . . . . . . . . . . . . 42
CMF400 grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
CMF400 booster amplifier housing . . . . . . . . . . . . . . . . . . . . . . . 44
CMF010 dimensions and process fittings . . . . . . . . . . . . . . . . . . 55
CMF025 dimensions and process fittings . . . . . . . . . . . . . . . . . . 56
CMF050 dimensions and process fittings . . . . . . . . . . . . . . . . . . 57
CMF100 dimensions and process fittings . . . . . . . . . . . . . . . . . . 58
CMF200 dimensions and process fittings . . . . . . . . . . . . . . . . . . 59
CMF300 dimensions and process fittings . . . . . . . . . . . . . . . . . . 60
High-temperature CMF300A dimensions and process fittings . . 61
CMF400 dimensions and process fittings . . . . . . . . . . . . . . . . . . 62
Purge fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Rupture disk . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Label number 1003972 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Label number 3002734 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
ELITE

Sensor Instruction Manual v
Using This Manual
Key
Indicates the
main idea to
keep in mind
Topic heading
Section title
Sections in
this manual
Current
section
Title of illustration
or table
Caution statement
Describes hazards that could result in
minor personal injury, product damage,
or property damage
or
Warning statement
Describes hazards that could result in
serious injury or death
I nst al l at i on
Step 3 Mounting
Keys for sensor mounti ng
Install the sensor in accordance with the instructions in this manual
Follow all instructions, to ensure the sensor is properly installed
Installing any sensor The instructions for installing a Micro Motion ELITE sensor are described in detail in
this manual. This is a sample page. Follow all instructions in the manual for a proper
sensor installation. The manual describes how to install an ELITE sensor and get it
ready for operation. In addition, a number of troubleshooting subjects are also
discussed. Specifications for ELITE sensors are provided, as well as dimensions and
Mounting any sensor
CAUTION
A caution statement describes a potential hazard. Bold
text indicates the hazard and the resulting conditions.
The rest of the text describes how to avoid the hazard. Always
read a hazard statement and follow all the instructions included.
ELITE Sensor Instruction Manual 15
B
e
f
o
r
e
Y
o
u

B
e
g
in
L
o
c
a
t
io
n
O
r
ie
n
t
a
t
io
n
M
o
u
n
t
i
n
g
W
i
r
i
n
g
T
r
o
u
b
le
s
h
o
o
t
i
n
g
S
t
a
r
t
u
p
ordering information. Contact Micro Motion if you require information that is not
included in this manual.
vi ELITE

Sensor Instruction Manual
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
b
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 1
Before You Begin
Your new sensor Your new Micro Motion

ELITE

sensor is one part of a Coriolis


flowmetering system. The other component of the flowmeter is a
transmitter.
Transmitter connections
ELITE sensors may be connected to any of these Micro Motion
transmitters:
Model 3500 or 3700
RFT9739
IFT9701
Model 5300
RFT9709
European installations
ELITE sensors comply with EMC directive 89/336/EEC and low-voltage
directive 73/23/EEC, including all amendments, when properly installed
in accordance with the guidelines and instructions described in this
manual.
Sensor components
Components of the sensor are illustrated below. Dimensions are
provided in Appendix A, pages 55-62.
Components of ELITE

sensors
CMF010
Flow direction
arrow
Purge connections or
rupture disks
(optional)
Serial number
tag
Sensor
housing
Junction box
Junction-box side of
sensor
Reverse side
of sensor
Process fitting
Thru-holes for
alternative
mounting
Approvals
tag
2 ELITE

Sensor Instruction Manual
Before You Begin continued
Components of ELITE

sensors continued
CMF025
CMF050
CMF100
Flow direction
arrow
Process fitting
Purge
connections
(optional)
Approvals tag
Sensor
housing
Junction box
Serial number
tag
CMF200
CMF300
Flow direction
arrow
Process fitting
Purge
connections
(optional)
Approvals
tag
Sensor
housing
Junction box
Serial number
tag
ELITE

Sensor Instruction Manual 3
Before You Begin continued
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
b
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
Components of ELITE

sensors continued
CMF300A
Flow direction
arrow
Process fitting
Purge
connections
(optional)
Approvals
tag
Sensor
housing
Remote-mount
junction box
Serial number
tag
CMF400
Flow direction
arrow
Process fitting
Booster
amplifier
Approvals tag
Sensor
housing
Junction box
Serial number
tag
Drain plug
4 ELITE

Sensor Instruction Manual
Before You Begin continued
The installation process Installing your new sensor involves five steps:
Step 1. Location
Determining the proper location for the sensor, taking into account
hazardous areas, process piping, transmitter location, and valves. See
page 5.
Step 2. Orientation
Determining the desired orientation for the sensor in the process
pipeline. See page 7.
Step 3. Mounting
Installing the sensor in the pipeline. See page 11.
Step 4. Wiring
Connecting the flowmeter cable to the sensor and transmitter. See
page 17.
Step 5. Startup
Requirements for flowmeter startup. See page 29.
Additional information In addition to installation instructions, the following subjects are also
covered in this manual:
Troubleshooting for problems that might be attributable to the sensor
begins on page 31.
Product specifications, including sensor dimensions and process
connection options, are listed in Appendix A, page 49.
Ordering information, including complete model numbers and a list of
Micro Motion instruction manuals, is provided in Appendix B, page 63.
Purge fittings are described in Appendix C, page 65.
Rupture disks are described in Appendix D, page 69.
Maintenance of labels is explained in Appendix E, page 71.
Return policy for Micro Motion equipment is described in Appendix F,
page 73.
ELITE

Sensor Instruction Manual 5
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
I nstal l ati on
Step 1 Location
Pipe run Micro Motion sensors do not require a straight run of pipe upstream or
downstream.
Cable to transmitter Total length of cable from the sensor to the transmitter must not exceed
1000 feet (300 meters).
CMF300A junction box The CMF300A high-temperature sensor comes with a 32-inch (812 mm)
pre-installed flexible conduit. This conduit is required for agency
approval (e.g., UL, CSA, CENELEC, etc.). A factory-supplied junction
box is connected to the end of this cable by the factory. The junction box
provides an exterior ground to the sensor and houses the terminal strip
for the flowmeter cable.
CMF400 booster amplifier The CMF400 booster amplifier must remain between 40 and 140F
(40 to 60C). If ambient and radiant heat will cause the CMF400
booster amplifier to fall outside these temperature limits, a remotely
mounted booster amplifier assembly is necessary. Consult the factory
for remote-mount booster amplifier information.
Valves After the sensor and transmitter have been fully installed, you must
perform the zeroing procedure. During the zeroing procedure, flow
through the sensor must be halted and the sensor tubes must be
completely full of process fluid. A shutoff valve, downstream from the
sensor, is recommended to halt flow during the zeroing procedure. For
more information about zeroing, see page 29.
Keys for sensor location
The sensor may be located anywhere in the process line, as long as
the following conditions are met:
Before operation, you must be able to stop flow through the sensor.
(During the zeroing procedure, flow must be stopped completely, and
the sensor must be full of process fluid.)
During operation, the sensor must remain full of process fluid.
The sensor must be installed in an area that is compatible with the
classification specified on the sensor approvals tag. (See
illustrations, pages 1-3.)
6 ELITE

Sensor Instruction Manual
Location continued
Hazardous area installations To comply with requirements for an intrinsically safe (I.S.)
installation, you must use one of the following Micro Motion I.S.
installation instruction manuals, in addition to this manual, when
installing the sensor in a hazardous area. An I.S. manual is shipped with
an approved flowmeter:
UL-D-IS Installation Instructions
For UL-approved flowmeters
UL is a U.S.A. approvals agency
CSA-D-IS Installation Instructions
For CSA-approved flowmeters
CSA is a Canadian approvals agency
SAA-D-IS Installation Instructions
For SAA-approved flowmeters
SAA is an Australian approvals agency
For hazardous area installation in Europe, use standard EN 60079-14 as
a guideline if national standards are not in effect.
To obtain a copy of an I.S. manual, phone the Micro Motion Customer
Service Department:
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277)
Outside the U.S.A., phone 303-530-8400
In Europe, phone +31 (0) 318 549 443
In Asia, phone 65-770-8155
A complete list of UL, CSA, SAA, and European approvals for ELITE
sensors is provided on page 53.
WARNING
Failure to comply with requirements for intrinsic
safety in a hazardous area could result in an
explosion.
Install the sensor in an environment that is compatible
with the hazardous area specified on the sensor
approvals tag. See illustrations, pages 1-3.
For installation in an area that requires intrinsic safety,
use this document with Micro Motion UL, CSA, or SAA
installation instructions.
For hazardous area installations in Europe, refer to
standard EN 60079-14 if national standards do not apply.
ELITE

Sensor Instruction Manual 7
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
I nstal l ati on
Step 2 Orientation
Flow direction Micro Motion sensors measure accurately regardless of flow direction.
Flow direction arrow
The sensor features a flow direction arrow (see illustrations, pages 1-3),
but the sensor will measure flow in either direction.
If the process fluid flows in the direction opposite to the flow direction
arrow, flowmeter outputs might not behave as expected unless the
transmitter is configured appropriately. For more information, including
configuration instructions, refer to any of the following:
Vertical pipeline
If the sensor is installed in a vertical pipeline, liquids and slurries should
flow upward through the sensor. Gases may flow upward or downward.
Process fluid Typical sensor orientations are shown in the tables on the following
pages:
For measuring liquids, see page 8.
For measuring gases, see page 9.
For measuring slurries, see page 10.
Keys for sensor orientation
The sensor will function properly in any orientation if the sensor flow
tubes remain filled with process fluid.
For this transmitter: Refer to:
Model 3500 or 3700 ALTUS

detailed setup manual


RFT9739 HART Communicator manual
ProLink software manual or ProLink on-line help
Modbus manual
AMS software on-line help
IFT9701 IFT9701 transmitter manual
ProLink on-line help
AMS software on-line help
Model 5300 Model 5300 transmitter manual
RFT9709 Contact the factory (phone numbers are listed on page 30)
8 ELITE

Sensor Instruction Manual
Orientation continued
Orientations for measuring liquids
Sensor
model
Preferred orientation for
measuring liquids
Alternative orientations for
measuring liquids
CMF010 Tubes flat
Horizontal pipeline
Tubes down
Horizontal pipeline
Flag mount
Vertical pipeline
CMF025
CMF050
CMF100
Tubes down
Horizontal pipeline
Tubes up
Horizontal pipeline
Self-draining
Flag mount
Vertical pipeline
CMF200
CMF300
Tubes down
Horizontal pipeline
Tubes up
Horizontal pipeline
Self-draining
Flag mount
Vertical pipeline
Self-draining
CMF400 Tubes down
Horizontal pipeline
Tubes up
Horizontal pipeline
Self-draining
Flag mount
Vertical pipeline
Self-draining
Flow
Flow
Flow
Flow
ELITE

Sensor Instruction Manual 9
Orientation continued
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
Orientations for measuring gases
Sensor
model
Preferred orientation for
measuring gases
Alternative orientations for
measuring gases
CMF010 Tubes flat
Horizontal pipeline
Tubes up
Horizontal pipeline
Flag mount
Vertical pipeline
CMF025
CMF050
CMF100
Tubes up
Horizontal pipeline
Flag mount
Vertical pipeline
CMF200
CMF300
Tubes up
Horizontal pipeline
Flag mount
Vertical pipeline
CMF400 Tubes up
Horizontal pipeline
Flag mount
Vertical pipeline
10 ELITE

Sensor Instruction Manual
Orientation continued
Orientations for measuring slurries
Sensor
model
Preferred orientation for
measuring slurries
Alternative orientations for
measuring slurries
CMF010 Tubes flat
Horizontal pipeline none
CMF025
CMF050
CMF100
Tubes up
Horizontal pipeline
Self-draining
none
CMF200
CMF300
Flag mount
Vertical pipeline
Self-draining
Tubes up
Horizontal pipeline
Self-draining
CMF400 Flag mount
Vertical pipeline
Self-draining
Tubes up
Horizontal pipeline
Self-draining
Flow
Flow
ELITE

Sensor Instruction Manual 11
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
Mounting any ELITE

sensor
CAUTION
Using the sensor to support piping
can damage the sensor or
cause measurement error.
Do not use sensor to support pipe.
Keys for sensor mounting
Use your common piping practices to minimize:
Torque on process connections
Bending load on process connections
For proper orientation,
see page 7.
Step 3 Mounting
I nstal l ati on
12 ELITE

Sensor Instruction Manual
Mounting continued
Optional CMF010 mounting The CMF010 sensor can be mounted in-line, supported by the process
piping like other sensors, or can be mounted to a wall or another solid
structure using bolts, as illustrated below. The CMF010 sensor weighs
approximately 13 lbs (5.9 kg). Mount the sensor using bolts if the
pipeline will not support the sensor. See illustrated below.
CMF010 mounting with bolts
2 user-supplied bolts for mounting
5/16" (M8) max. diameter
2 1/4" (58 mm) min. length
Junction box can be rotated
by hand (before wiring is attached)
for access to mounting holes
Mounting surface
If pipe supports are used, they
should be rigidly supported by the
same mounting surface as the
sensor
If necessary, rigid standoffs may
be installed (for example: steel
washers are acceptable, rubber
washers are not)
ELITE

Sensor Instruction Manual 13
Mounting continued
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
CMF300A high-temperature
sensors
The CMF300A high-temperature sensor comes with a 32-inch (812 mm)
pre-installed flexible conduit. This conduit is required for agency
approval (e.g., UL, CSA, CENELEC, etc.).
A factory-supplied junction box is connected to the end of the flexible
conduit. The junction box, illustrated below, provides an exterior ground
to the sensor and houses the terminal strip for the flowmeter cable.
Wiring is described starting on page 17.
CMF300A remote-mount junction box
5 1/2
(140)
1/4
(6)
Flexible conduit
from sensor
Conduit length: 32 inches (812 mm)
Min. bend radius: 1 1/2 inches (38 mm)
1/2" NPT female for
wiring to transmitter
2X thru for mounting
Junction
box
2 13/16
(71)
14 ELITE

Sensor Instruction Manual
Mounting continued
Installing wafer-style sensors A wafer-style sensor, which has no flanges or fittings, lets you "clamp"
the sensor between process connections in the pipeline. ELITE
CMF025, CMF050, and CMF100 sensors are available in the wafer
style.
A wafer installation kit is shipped with wafer-style sensors. Kits are
available to fit standard ANSI, DIN, and JIS fittings. (See pages 55-62 for
fitting options.) Wafer kits contain the following pieces:
4 flange bolts
8 flange nuts
2 alignment rings, which help center the sensor between the bolts
To install a wafer-type sensor, follow the five steps below:
1. Make sure the bolts provided in the wafer installation kit fit your
process connections.
2. Slip the sensor alignment rings over each end of the sensor wafer,
then insert the sensor between the process connections in the
pipeline, as illustrated below. Installing gaskets is recommended.
(Micro Motion does not supply gaskets.)
Wafer-style assembly
Process connection
Flange bolt
Sensor wafer
Flange nut
Gasket
(user-supplied)
Alignment ring
Sensor housing
ELITE

Sensor Instruction Manual 15
Mounting continued
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
3. Insert the bolts through both process connections, and thread the
nuts onto the bolts. Tighten nuts as tight as you can with your fingers.
4. Rotate the sensor alignment rings in the direction that pushes the
bolts outward, as illustrated below. Rotate both rings until the
assembly is centered and tight.
5. With a wrench, tighten nuts in an alternating order, to ensure the
process connections are evenly tightened.
Tightening sensor alignment rings
Rotate ring...
...to push
bolts outward
Flange bolt
Sensor
alignment ring
Sensor wafer
16 ELITE

Sensor Instruction Manual
Mounting continued
Optional heat tracing You may install user-supplied heat tracing with any ELITE sensor. Use
either steam or electric heating, up to the sensors maximum
temperature, listed below.
If the sensor carries hazardous area approvals for installation in Europe,
heat tracing will violate the approvals.
Maximum temperature for heat tracing
Sensor model
Temperature
F C
High-temperature CMF300A 650 343
CMF400*
*If ambient and radiant heat will cause the CMF400 booster amplifier to exceed
140F (60C), a remotely mounted booster amplifier assembly is necessary. Consult
the factory for remote-mount booster amplifier information.
140 60
All other ELITE sensors 400 204
ELITE

Sensor Instruction Manual 17
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
I nstal l ati on
Step 4 Wiring
Hazardous area installations To comply with requirements for an intrinsically safe (I.S.) installation,
you must use one of the following Micro Motion I.S. installation
instruction manuals, in addition to this manual, when wiring the sensor in
a hazardous area. An I.S. manual is shipped with an approved
flowmeter:
UL-D-IS Installation Instructions
For UL-approved flowmeters
UL is a U.S.A. approvals agency
CSA-D-IS Installation Instructions
For CSA-approved flowmeters
CSA is a Canadian approvals agency
SAA-D-IS Installation Instructions
For SAA-approved flowmeters
SAA is an Australian approvals agency
For hazardous area installation in Europe, use standard EN 60079-14 as
a guideline if national standards are not in effect.
To obtain a copy of an I.S. manual, phone the Micro Motion Customer
Service Department:
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277)
Outside the U.S.A., phone 303-530-8400
In Europe, phone +31 (0) 318 549 443
In Asia, phone 65-770-8155
A complete list of UL, CSA, SAA, and European approvals for ELITE
sensors is provided on page 53.
WARNING
Failure to comply with requirements for intrinsic
safety in a hazardous area could result in an
explosion.
Make sure the hazardous area specified on the sensor
approvals tag is suitable for the environment in which the
sensor is installed. See illustrations, pages 1-3.
For installation in an area that requires intrinsic safety,
use this document with Micro Motion UL, CSA, or SAA
installation instructions.
For hazardous area installations in Europe, refer to
standard EN 60079-14 if national standards do not apply.
18 ELITE

Sensor Instruction Manual
Wiring continued
Sensor junction box ELITE sensors are shipped with a factory-installed junction box for
wiring to the transmitter.
The CMF300A high-temperature sensor uses a remotely mounted
junction box. See page 19.
The CMF400 has a different junction box than other ELITE sensors,
and requires additional wiring. See pages 19 through 22.
Other ELITE sensors use the junction box described below.
ELITE sensors except CMF300A and CMF400:
Before wiring is attached, the junction box rotates independently from
the terminals inside, as indicated in the illustration below.
If possible, install wiring with the junction-box opening pointed down, to
reduce the risk of condensation or excessive moisture in the junction
box.
Standard ELITE

junction box
3/4" NPT female
Install junction box with
conduit opening pointed
down, if possible
Junction box rotates
(before wiring is installed)
independently from
terminals inside
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 19
Wiring continued
CMF300A high-temperature sensor
The CMF300A high-temperature sensor comes with a 32-inch (812 mm)
pre-installed flexible conduit. This conduit is required for agency
approval (such as UL, CSA, CENELEC, etc.).
A factory-supplied junction box is connected to the end of the flexible
conduit. The junction box, illustrated below, provides an exterior ground
to the sensor and houses the terminal strip for connecting the flowmeter
cable from the transmitter.
The procedure for installing wiring at the CMF300A junction box is
described on page 23.
If possible, install wiring with drip legs in the conduit or cables, to
reduce the risk of condensation or excessive moisture in the junction
box. See illustration, below.
CMF400 sensor
For wiring between the sensor and transmitter, the CMF400 sensor uses
the same junction box as the CMF300A high-temperature sensor. See
illustration, page 21.
The CMF400 also requires power-supply wiring to the booster
amplifier. See pages 20 and 21.
Grounding requirements for the CMF400 are described on page 22.
The procedure for installing flowmeter wiring at the CMF400 junction
box is described on page 23.
If possible, install wiring with drip legs in the conduit or cables, to
reduce the risk of condensation or excessive moisture in the junction
box.
CMF300A sensor cable and junction box
Drip leg
32-inch (812 mm) flexible conduit
Liquid tight to meet CE requirements
for European installations
Permanently attached to sensor
3/4" NPT female
conduit seal or cable gland
for wiring to transmitter
20 ELITE

Sensor Instruction Manual
Wiring continued
CMF400 booster amplifier The CMF400 has a booster amplifier, which requires wiring from an AC
power supply. See illustration, page 21.
Do not open booster amplifier housing cover while the booster amplifier
is energized.
Replace all covers and seal all openings before applying power.
Ground the CMF400 according to the instructions on page 22.
WARNING
Explosion Hazard
In a hazardous area:
Do not open booster amplifier housing cover while
booster amplifier is energized.
Wait at least 8 minutes after power is shut off before
opening.
CAUTION
Improper installation of wiring could cause
measurement error or sensor failure.
Shut off power before installing power-supply wiring.
Follow all instructions to ensure sensor will operate
correctly.
Match power-supply voltage with voltage indicated on the
label inside the booster amplifier housing.
Install drip legs in conduit or cable.
Seal all conduit openings.
Ensure integrity of gaskets, and fully tighten sensor
junction-box cover and all transmitter housing covers.
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 21
Wiring continued
CMF400 wiring
Junction box for
flowmeter wiring
Booster amplifier
in explosion-proof housing
Let the booster amplifier
de-energize; wait at least 8
minutes after power is shut off
before opening housing cover
Flowmeter wiring
to transmitter
Wiring from
power supply
Explosion-proof
Intrinsically safe
Voltage label
Power-supply must match
voltage on label
Power supply connections
Power supply
Terminal
3 2 1
115 VAC, 50/60 Hz G N H
230 VAC, 50/60 Hz G L2 L1
Tighten all covers and seal all
openings before applying power
1/2" NPT female
conduit seal or cable gland
I.S. signal wiring
from sensor
3/4" NPT female
conduit seal or
cable gland
Drive circuit
from sensor
22 ELITE

Sensor Instruction Manual
Wiring continued
Sensor grounding The sensor should be grounded as described below.
ELITE sensors, except the CMF400, can be grounded via the piping if
joints in the pipeline are ground-bonded, or by means of a ground screw
on the outside of the sensor junction box. Ground the CMF400 as
described below.
If the sensor is not grounded via the piping, and if national standards are
not in effect, adhere to these guidelines to ground the sensor via the
junction box:
Use copper wire, 14 AWG (2.5 mm
2
) or larger wire size.
Keep all ground leads as short as possible.
Ground leads must have less than 1 ohm impedance.
Connect ground leads directly to earth, or follow plant standards.
Grounding CMF400 sensors The CMF400 has special grounding requirements. Follow the guidelines
in the illustration below.
CMF400 grounding
CAUTION
Improper grounding could cause measurement error.
To reduce the risk of measurement error:
Ground the flowmeter to earth, or follow ground network
requirements for the facility.
For installation in an area that requires intrinsic safety,
refer to Micro Motion UL, CSA, or SAA installation
instructions for appropriate grounding instructions.
For hazardous area installations in Europe, refer to
standard EN 60079-14 if national standards do not apply.
Explosion-proof
Intrinsically safe
External ground screws
The external ground screws may
be used for supplementary bonding
connections to meet local code
requirements
Barrier safety ground studs
For grounding, connect two individually
shielded 14-gauge wires, one to each
barrier safety ground stud.
Terminate safety ground conductors at
the same earth ground connection as
the equipment ground conductor.
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 23
Wiring continued
Flowmeter cable The instructions in this section explain how to connect a fully prepared
Micro Motion flowmeter cable to the sensor and transmitter.
The procedure for preparing Micro Motion cable and cable glands is
described in the instructions that are shipped with the cable.
Install cable and wiring to meet local code requirements.
Cable connections to CMF300A and CMF400 sensors
To make connections at the CMF300A high-temperature sensor or the
CMF400 sensor junction box, follow these steps:
1. Unscrew junction-box cover, then remove retaining screw and
terminals bracket from junction box.
2. Draw the cable from the transmitter into the junction box. Install a
cable gland or conduit seal to ensure the junction box will remain
sealed after installation.
CAUTION
Failure to seal the sensor junction box and transmitter
housing could cause a short circuit, which would
result in measurement error or flowmeter failure.
To reduce risk of condensation or excessive moisture in
the junction box or transmitter housing:
Seal all conduit openings.
Install drip legs in conduit or cable.
Fully tighten sensor junction-box cover and all transmitter
housing covers.
Junction-box
cover
Terminals
bracket
Junction
box
O-ring
Retaining
screw
24 ELITE

Sensor Instruction Manual
Wiring continued
3. Gather each set of wires together and bend back, outside junction
box, in preparation for reinstalling terminals bracket.
The external bonding terminal may be used for supplementary
bonding connections to meet local code requirements.
4. Replace the terminals bracket. Tighten retaining screw to secure
bracket in junction box.
Wires from
booster amplifier
(CMF400 only)
Wires from
sensor
Wires from
transmitter
Junction
box
Cable gland or
conduit seal
External bonding
terminal
CAUTION
Damage to wires could result in measurement error or
flowmeter failure.
Align bracket legs away from wires before pushing the
bracket into position.
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 25
Wiring continued
5. With bracket reinstalled, connect individual wires to terminals. Refer
to the illustration and the table on page 25.
One side of each terminal block is for wires that come from the
sensor (and, if the sensor is a CMF400, from the booster amplifier).
The other side of each terminal block is for connecting wires from
the transmitter.
6. Ensure integrity of gaskets, then reinstall and fully tighten the
junction-box cover.
7. To make wiring connections at the transmitter, follow the instructions
on page 26.
Wiring connections at CMF300A and CMF400 sensors
Wire-to-wire connections in CMF300A and CMF400 junction box
From
transmitter
From CMF300A
sensor
From CMF400
sensor
From CMF400
booster amplifier
Brown 1 Brown
Red 2 Red
Orange 3 Orange
Yellow 4 Yellow
Green 5 Green
Blue 6 Blue
Violet 7 Violet
Gray 8 Gray
White 9 White
Cable from
CMF400 sensor
Cable from CMF400
booster amplifier
Cable from
CMF300A sensor
Orange
Yellow
Green
Blue
Violet
Gray
White
1
2
3
4
5
6
7
8
9
Red
Brown
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Cable from
transmitter
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Cable from
transmitter
7
V
i
o
4
Y
e
l
3
O
r
g
2
R
e
d
8
G
r
a
y
6
B
lu
e
5
G
r
n
9
W
h
t
1
B
r
n
V
i
o
Y
e
l
O
r
g
R
e
d
G
r
a
y
B
lu
e
G
r
n
W
h
t
B
r
n
Junction
box
Junction
box
CMF400
sensor
CMF300A
sensor
26 ELITE

Sensor Instruction Manual
Wiring continued
Cable connections to all other sensors and to transmitter
The wiring procedure is the same for the sensor and transmitter. Refer to
the wiring diagrams below and on pages 2728, and follow these steps:
1. Locate the wires by color.
2. Insert the stripped ends of the individual wires into the terminal
blocks. No bare wires should remain exposed.
At the sensor, connect wiring inside the junction box.
At the transmitter, connect wiring to the transmitters intrinsically safe
terminals for sensor wiring.
3. Tighten the screws to hold the wires in place.
4. Ensure integrity of gaskets, then close the junction-box cover and
tighten all screws. Tightly close all housing covers on the transmitter.
Wiring to RFT9739 field-mount transmitter
Wiring to RFT9739 rack-mount transmitter
Green
White
Brown
Violet
Yellow
Orange
Blue
Gray
Red
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
ELITE

sensor
terminals
Flowmeter
cable
Field-mount
RFT9739 terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Brown
Orange
Green
Violet
White
Gray
Blue
Yellow
Red
Black (Drains)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable
Rack-mount
RFT9739 terminals
Red
Yellow
Orange
White
Gray
Brown
Black (Drains)
Violet
Green
Blue
B2
B4
B6
B8
B10
Z2
Z4
Z6
Z8
Z10
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable
Green
White
Brown
Violet
Yellow
Orange
Blue
Gray
Red
ELITE

sensor
terminals
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 27
Wiring continued
Wiring to Model 3500 with screw or solder terminals
Wiring to Model 3500 with I/O cable
Wiring to Model 3700
Model 3500
with screw-type or
solder-tail terminals
Yellow
Violet
Green
Blue
Brown
Black (Drains)
Orange
White
Gray
Red
c4
c6
c8
c10
c12
a4
a6
a8
a10
a12
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable
Green
White
Brown
Violet
Yellow
Orange
Blue
Gray
Red
ELITE

sensor
terminals
B
r
o
w
n
R
e
d
O
r
a
n
g
e
Y
e
l
l
o
w
G
r
e
e
n
B
l
u
e
V
i
o
l
e
t
G
r
a
y
W
h
i
t
e
B
l
a
c
k

(
d
r
a
i
n
s
)
Connect outer
braid of shielded
or armored cable
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable
Green
White
Brown
Violet
Yellow
Orange
Blue
Gray
Red
ELITE

sensor
terminals
Model 3500
with I/O cable
Not approved for intrinsic safety
in Europe
Model 3700
terminals
Red
Brown
Yellow
Black (drains)
Violet
Orange
Green
White
Blue
Gray
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable
Green
White
Brown
Violet
Yellow
Orange
Blue
Gray
Red
ELITE

sensor
terminals
28 ELITE

Sensor Instruction Manual
Wiring continued
Wiring to IFT9701 and Model 5300 transmitters
Wiring to RFT9709 transmitter
IFT9701 or
Model 5300 terminals
B
l
a
c
k

(
D
r
a
i
n
s
,
r
e
m
o
t
e
-
m
o
u
n
t

o
n
l
y
)
B
r
o
w
n
R
e
d
O
r
a
n
g
e
Y
e
l
l
o
w
G
r
e
e
n
B
l
u
e
V
i
o
l
e
t
G
r
a
y
W
h
i
t
e
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable
Green
White
Brown
Violet
Yellow
Orange
Blue
Gray
Red
ELITE

sensor
terminals
Black (Drains)
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
RFT9709
terminals
No connection
1. In the sensor junction box, identify the violet, yellow, and
orange wires that come from inside the sensor.
2. Disconnect these wires from the terminal block, then tie all
three together with a wire nut to protect exposed wire ends.
3. Connect three wires from the external RTD to the terminals
from Step 2, as illustrated. If the RTD has a fourth wire,
it remains unconnected.
Optional remote temperature detector
(RTD) wiring (required for API)
3-wire or
4-wire RTD
ELITE sensor
terminals
The RFT9709 allows the user to install an optional
external RTD. Requirements for the RTD are as
follows:
The external temperature detector must have
accuracy of 0.1F (0.05C) or better.
Locate the external temperature detector as close
to the sensor as possible.
Use an individually shielded pair of 22 AWG
(0.3 mm) or larger wires to connect the external
temperature detector to the flowmeter.
For more information, see the RFT9709
instruction manual.
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable
Green
White
Brown
Violet
Yellow
Orange
Blue
Gray
Red
ELITE

sensor
terminals
ELITE

Sensor Instruction Manual 29
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
I nstal l ati on
Step 5 Startup
Zeroing After the flowmeter has been fully installed, you must perform the
zeroing procedure. Flowmeter zeroing establishes flowmeter response
to zero flow and sets a baseline for flow measurement. The zeroing
procedure is described in the transmitter instruction manual and in the
manuals listed on page 30.
Configuration, calibration, and
characterization
If the sensor and transmitter are ordered together as a Coriolis
flowmeter, the factory has characterized the meter no additional
characterization is necessary. If either the sensor or transmitter is
replaced, characterization is required.
You can use the transmitter to configure, calibrate, and characterize the
meter. For more information, see any of the manuals listed on page 30.
The following information explains the difference between configuration,
calibration, and characterization. Certain parameters might require
configuration even when calibration is not necessary.
Configuration parameters include such items as flowmeter tag,
measurement units, flow direction, damping values, and slug flow
parameters. If requested at time of order, the meter is configured at the
factory according to customer specifications.
Calibration accounts for the flowmeters sensitivity to flow, density, and
temperature. Field calibration is optional.
Characterization is the process of entering calibration factors for flow,
density, and temperature directly into transmitter memory, instead of
performing field calibration procedures. Calibration factors can be found
on the sensor serial number tag and on the certificate that is shipped
with the sensor.
CAUTION
Failure to zero the flowmeter at initial startup could
cause measurement error.
Zero the flowmeter before putting the meter in operation.
30 ELITE

Sensor Instruction Manual
Startup continued
The following instruction manuals include instructions for flowmeter
configuration, calibration, and characterization:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with the Micro Motion ELITE Model RFT9739
Transmitter
ALTUS Detailed Setup Manual
Model 5300 Transmitter with FOUNDATION fieldbus
Customer Service The Micro Motion Customer Service Department is available for
assistance with flowmeter startup if you experience problems you cannot
solve on your own.
If possible, provide us with the model numbers and/or serial numbers of
your Micro Motion equipment, which will assist us in answering your
questions.
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277), 24 hours
Outside the U.S.A., phone 303-530-8400, 24 hours
In Europe, phone +31 (0) 318 549 443
In Asia, phone 65-770-8155
ELITE

Sensor Instruction Manual 31
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
Troubleshooting
General information Most troubleshooting is performed at the transmitter. However, the
following troubleshooting topics are described in this manual:
Zero drift, page 32
Erratic flow rate, page 33
Inaccurate flow rate or batch total, page 34
Inaccurate density reading, page 35
Inaccurate temperature reading, page 36
If you cannot find the problem you are looking for, check the transmitter
instruction manual or one of the following manuals:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with the Micro Motion ELITE Model RFT9739
Transmitter
ALTUS Detailed Setup Manual
You can also use Fisher-Rosemount

Asset Management Solutions


(AMS) software to troubleshoot Micro Motion flowmeters. For
instructions on using AMS software, refer to the AMS on-line help.
To troubleshoot the flowmeter, you might need a digital multimeter
(DMM) or similar device, the transmitter display, if it has one, and one of
the following:
HART Communicator
ProLink software
AMS software
Modbus master controller (RFT9739 only)
Fieldbus host controller (Model 5300 with FOUNDATION

fieldbus only)
If you cannot find the problem you are looking for, or if troubleshooting
fails to reveal the problem, contact the Micro Motion Customer Service
Department.
If possible, provide us with the model numbers and/or serial numbers of
your Micro Motion equipment, which will assist us in answering your
questions.
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277), 24 hours
Outside the U.S.A., phone 303-530-8400, 24 hours
In Europe, phone +31 (0) 318 549 443
In Asia, phone 65-770-8155
32 ELITE

Sensor Instruction Manual
Troubleshooting continued
Zero drift Symptom
The flowmeter indicates the process fluid is flowing while flow is
stopped; or indicates a flow rate that does not agree with a reference
rate at low flow, but does agree at higher flow rates.
Troubleshooting instructions
To troubleshoot zero drift, you will need a digital multimeter (DMM) and
one of the communications devices listed on page 37. Refer to the table
below for the necessary steps to troubleshoot zero drift.
Troubleshooting zero drift
Procedure Instructions What to do next
1. Check for leaking valves and seals If no leaks are found, go to step 2
If leaks are found, eliminate them, then go to step 15
2. Check the flow units See page 37 If the flow units are OK, go to step 3
If the flow units are wrong, change them, then go to step 15
3. Make sure the flowmeter was
zeroed properly
See page 29 If the flowmeter was zeroed properly, go to step 4
If the flowmeter was not zeroed properly, zero it, then go
to step 15
4. Check for the proper flow
calibration factor
See page 40 If the flow cal factor is correct, go to step 5
If the flow cal factor is incorrect, change it, then go to step 15
5. Check the damping value See page 41 If the damping value is OK, go to step 6
If the damping value is too low, change it, then go to step 15
6. Check for two-phase flow See page 46 If there is no two-phase flow, go to step 7
If there is two-phase flow, fix the problem, then go to step 15
7. Check for moisture in the sensor
junction box
See page 44 If there is no moisture present, go to step 8
If there is moisture in the junction box, dry out and seal the
junction box, then go to step 15
8. Check for faulty or improperly
installed flowmeter wiring
See page 38 If the wiring is OK, go to step 9
If the wiring is faulty, fix or replace it, then go to step 15
9. Check for faulty or improperly
installed grounding
See page 43 If the grounding is OK, go to step 10
If the grounding is incorrect or faulty, fix it, then go to step 15
10. Check for mounting stress on the
sensor
See page 45 If the sensor mount is OK, go to step 11
If there are mounting stresses, fix it, then go to step 15
11. Check for vibration or crosstalk See page 45 If there is no vibration or crosstalk, go to step 12
If there is vibration or crosstalk, eliminate it, then go to
step 15
12. Make sure the sensor is oriented
properly
See page 7 If the sensor is oriented properly, go to step 13
If the sensor is not oriented properly, change the orientation,
then go to step 15
13. Check for plugging or build-up on
the sensor flow tubes
See page 47 If the tubes are not plugged, go to step 14
If there is plugging or build-up, clear the tubes, then go to
step 15
14. Check for RF interference See page 42 If there is no interference, or the source cannot be detected,
go to step 16
If there is interference, eliminate it, then go to step 15
15. Check again for zero drift If there is no longer any zero drift, youve solved the problem
If the zero drifts again, start over at step 3 or go to step 16
16. Contact Micro Motion Phone numbers are
listed on page 31
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 33
Troubleshooting continued
Erratic flow rate Symptom
The flowmeter indicates the flow rate is varying, even though it is steady.
Troubleshooting instructions
To troubleshoot an erratic flow rate, you will need a digital multimeter
(DMM) and one of the communications devices listed on page 37. Refer
to the table below for the necessary steps to troubleshoot an erratic flow
rate.
Troubleshooting erratic flow rate
Procedure Instructions What to do next
1. Check for erratic flow rate at the
transmitter
See page 37 If the signal is stable at the transmitter, go to step 2
If the signal is erratic at the transmitter, go to step 4
2. Check for faulty output wiring See page 37 If the output wiring is OK, go to step 3
If the output wiring is faulty, repair or replace it, then go to
step 13
3. Check the receiving device for
malfunctions
See instruction
manual for the device
If the receiving device is OK, go to step 4
If the receiving device is faulty, contact the manufacturer
4. Check the flow units See page 37 If the flow units are OK, go to step 5
If the flow units are wrong, change them, then go to step 13
5. Check the damping value See page 41 If the damping value is OK, go to step 6
If the damping value is too low, change it, then go to step 13
6. Check for stable drive gain See page 41 If the drive gain is stable, go to step 7
If the drive gain is not stable, go to step 11
7. Check for a stable density reading See page 41 If the density reading is stable, go to step 8
If the density reading is not stable, go to step 11
8. Check for faulty or improperly
installed flowmeter wiring
See page 38 If the flowmeter wiring is OK, go to step 9
If the flowmeter wiring is incorrect or faulty, fix or replace it,
then go to step 13
9. Check for faulty or improperly
installed grounding
See page 43 If the grounding is OK, go to step 10
If the grounding is incorrect or faulty, fix it, then go to step 13
10. Check for vibration or crosstalk See page 45 If there is no vibration or crosstalk, go to step 11
If there is vibration or crosstalk, eliminate it, then go to
step 13
11. Check for two-phase flow See page 46 If there is no two-phase flow, go to step 12
If there is two-phase flow, fix the problem, then go to step 13
12. Check for plugging or build-up on
the sensor flow tubes
See page 47 If the tubes are not plugged, go to step 14
If there is plugging or build-up, clear the tubes, then go to
step 13
13. Check again for erratic flow rate See page 37 If the signal is no longer erratic, youve solved the problem
If the signal is still erratic, start over at step 1 or go to step 14
14. Contact Micro Motion Phone numbers are
listed on page 31
34 ELITE

Sensor Instruction Manual
Troubleshooting continued
Inaccurate flow rate or batch total Symptom
The flowmeter indicates a flow rate or batch total that does not agree
with a reference rate or total.
Troubleshooting instructions
To troubleshoot an inaccurate flow rate or batch total, you will need a
digital multimeter (DMM) and one of the communications devices listed
on page 37. Refer to the table below for the necessary steps to
troubleshoot an inaccurate rate or total.
Troubleshooting inaccurate flow rate or batch total
Procedure Instructions What to do next
1. Check for the proper flow
calibration factor
See page 40 If the flow cal factor is correct, go to step 2
If the flow cal factor is incorrect, change it, then go to step 15
2. Check the flow units See page 37 If the flow units are OK, go to step 3
If the flow units are wrong, change them, then go to step 15
3. Make sure the flowmeter was
zeroed properly
See page 29 If the flowmeter was zeroed properly, go to step 4
If the flowmeter was not zeroed properly, zero it, then go
to step 15
4. Is the flow measurement
configured for mass or volume?
See page 37 If the configuration is for mass, go to step 6
If the configuration is for volume, go to step 5
5. Check for the proper density
calibration factor
See page 40 If the dens cal factor is correct, go to step 6
If the dens cal factor is incorrect, change it, then go to
step 15
6. Make sure the density reading is
accurate for the fluid
See page 41 If the density reading is correct, go to step 7
If the density reading is wrong, go to step 11
7. Make sure the temperature
reading is accurate for the fluid
See page 41 If the temperature reading is correct, go to step 8
If the temperature reading is wrong, go to step 14
8. Is the flow measurement
configured for mass or volume?
See page 37 If the configuration is for mass, go to step 11
If the configuration is for volume, go to step 9
9. Is the reference total based on a
fixed density value?
If the total is based on a fixed value, go to step 10
If the total is not based on a fixed value, go to step 11
10. Change flow units to mass flow
units
See page 37 Go to step 15
11. Check for faulty or improperly
installed grounding
See page 43 If the grounding is OK, go to step 12
If the grounding is incorrect or faulty, fix it, then go to step 15
12. Check for two-phase flow See page 46 If there is no two-phase flow, go to step 13
If there is two-phase flow, fix the problem, then go to step 15
13. Check the scale (or reference
measurement) for accuracy
Use your plant
procedures
If the scale is accurate, go to step 14
If the scale is not accurate, fix it, then go to step 15
14. Check for faulty or improperly
installed flowmeter wiring
See page 38 If the flowmeter wiring is OK, go to step 16
If the flowmeter wiring is incorrect or faulty, fix or replace it,
then go to step 15
15. Run a new batch and check again
for an inaccurate rate or total
If the rate or total is correct, youve solved the problem
If the rate or total is wrong, start over at step 2 or go to
step 16
16. Contact Micro Motion Phone numbers are
listed on page 31
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 35
Troubleshooting continued
Inaccurate density reading Symptom
The flowmeter density measurement is erratic, or is lower or higher than
the density of the fluid.
Troubleshooting instructions
To troubleshoot an inaccurate density reading, you will need a digital
multimeter (DMM) and one of the communications devices listed on
page 37. Refer to the table below for the necessary steps to
troubleshoot an inaccurate density reading.
Troubleshooting inaccurate density reading
Procedure Instructions What to do next
1. Check for stable density reading at
the transmitter
See page 41 If the density reading is stable, go to step 2
If the density reading is not stable, go to step 3
2. Check for the proper density
calibration factor
See page 40 If the dens cal factor is correct, go to step 4
If the dens cal factor is incorrect, change it, then go to
step 11
3. Check for faulty or improperly
installed flowmeter wiring
See page 38 If the flowmeter wiring is OK, go to step 4
If the flowmeter wiring is incorrect or faulty, fix or replace it,
then go to step 11
4. Check for faulty or improperly
installed grounding
See page 43 If the grounding is OK, go to step 5
If the grounding is incorrect or faulty, fix it, then go to step 11
5. Check to see if the density reading
is low or high
See page 41 If the density reading is low, go to step 6
If the density reading is high, go to step 10
6. Run a quality check on the
process fluid
Use your plant
procedures
If the product quality is OK, go to step 7
If the product quality is not OK, fix it, then go to step 11
7. If you checked the wiring in step 3,
go to step 8, otherwise, check for
faulty or improperly installed
flowmeter wiring
See page 38 If the flowmeter wiring is OK, go to step 8
If the flowmeter wiring is incorrect or faulty, fix or replace it,
then go to step 11
8. Check for two-phase flow See page 46 If there is no two-phase flow, go to step 9
If there is two-phase flow, fix the problem, then go to step 11
9. Check for vibration or crosstalk See page 45 If there is no vibration or crosstalk, go to step 12
If there is vibration or crosstalk, eliminate it, then go to
step 11
10. Check for plugging or build-up on
the sensor flow tubes
See page 47 If the tubes are not plugged, go to step 12
If there is plugging or build-up, clear the tubes, then go to
step 11
11. Check again for inaccurate density
reading at the transmitter
See page 41 If the reading is correct, youve solved the problem
If the reading is still wrong, start over at step 1 or go to
step 12
12. Contact Micro Motion Phone numbers are
listed on page 31
36 ELITE

Sensor Instruction Manual
Troubleshooting continued
Inaccurate temperature reading Symptom
The flowmeter temperature reading is different than expected.
Troubleshooting instructions
To troubleshoot an inaccurate density reading, you will need a digital
multimeter (DMM) and one of the communications devices listed on
page 37. Refer to the table below for the necessary steps to
troubleshoot an inaccurate density reading.
Troubleshooting inaccurate temperature reading
Procedure Instructions What to do next
1. Check for faulty or improperly
installed flowmeter wiring
See page 38 If the flowmeter wiring is OK, go to step 2
If the flowmeter wiring is faulty, fix or replace it, then go to
step 3
2. Check for the proper temperature
calibration factor
See page 40 If the temp cal factor is correct, go to step 4
If the temp cal factor is incorrect, change it, then go to step 3
3. Check again for inaccurate
temperature reading at the
transmitter
See page 41 If the reading is correct, youve solved the problem
If the reading is still wrong, start over at step 1 or go to step 4
4. Contact Micro Motion Phone numbers are
listed on page 31
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 37
Troubleshooting continued
Troubleshooting at the
transmitter
The tables in the preceding sections refer you to this section for
instructions on troubleshooting at the transmitter. To troubleshoot at the
transmitter, you might need a digital multimeter (DMM) or similar device,
the transmitter display, if it has one, and one of the following:
HART Communicator
ProLink software
AMS software
Modbus master controller (RFT9739 only)
Fieldbus host controller (Model 5300 with FOUNDATION

fieldbus only)
Checking the flow units
Check or change the flow units (unit of measure) configuration at the
transmitter. If necessary, refer to the instruction manual (or on-line help
for software) for the method you choose.
Use the Model 3500 or 3700 display
Use a HART Communicator, ProLink software, or AMS software
Use the host controller
Make sure the configured units of measure are the ones you want. Also,
make sure you know what the abbreviations mean. For example, g/sec is
grams per second, not gallons per second.
Checking for erratic flow rate at the transmitter
Before troubleshooting erratic flow rate, you must first determine
whether it is a result of the transmitter or a connected output device.
Check for an erratic flow signal at the transmitter using any of the
following methods. If necessary, refer to the instruction manual (or on-
line help for software) for the method you choose.
Use the transmitter display, if it has one
Use a HART Communicator, ProLink software, or AMS software
Use the host controller
Use a DMM on the transmitters 4-20 mA or frequency output terminals
If the flow rate or output signal is not erratic at the transmitter outputs,
the problem is not with the transmitter.
Checking for faulty output wiring
Having already checked the output at the transmitter end (above), use a
DMM to check the signal at the other end (the receiving end) of the
output wiring. If the signal is not erratic, the problem is not with the
output wiring.
38 ELITE

Sensor Instruction Manual
Troubleshooting continued
Checking for faulty flowmeter wiring
Wiring problems are often incorrectly diagnosed as a faulty sensor.
Examine wiring between the sensor and transmitter as follows:
1. Check the cable preparation. The flowmeter cable must be
prepared correctly. The most common problem is improperly
prepared drain wires. See illustration, below. The drains are clipped at
the sensor end. They should not be connected to any terminals in the
sensor junction box. See wiring diagrams, pages 2628.
2. Check wire terminations. Check to be sure wires are secured tightly
in the terminal blocks, and making good connections. Make sure no
wires remain exposed at either end of the flowmeter cable.
3. Check ohm levels. If the cable was properly prepared and terminal
connections are good, check resistance across wire pairs to
determine whether the flowmeter cable is faulty. The procedure is
performed first at the transmitter, then at the sensor. Follow these
steps:
a. Disconnect the transmitters power supply.
b. Disconnect sensor wiring from the transmitters flowmeter
terminals.
c. Use a DMM to measure resistance across wire pairs at the
transmitter end of the cable. See tables on page 39.
If the measured value is within the range listed in the table,
reconnect wiring and restore power to the transmitter.
If the measured resistance is outside the range listed in the table,
repeat the measurements at the sensor junction box.
- If the sensor is a not a CMF400, refer to the "Nominal resistance
ranges" table on page 39.
- If the sensor is a CMF400, refer to the table on page 39, and the
illustration on page 40.
- If resistance values measured at the sensor are also outside the
range listed in the table, the sensor might be faulty.
Cross-section of cable with drain wires
Cable jacket
Wire sets
Wire sets
Drain wire
(one for each wire set)
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 39
Troubleshooting continued
Nominal resistance ranges for flowmeter ci rcuits
Notes
Temperature-sensor value increases 0.38675 ohms per C increase in temperature.
Nominal resistance values will vary 40% per 100C. However, confirming an open coil or shorted coil is more important than
any slight deviation from the resistance values presented below.
Resistance across blue and gray wires (right pickoff circuit) should be within 10% of resistance across green and white wires
(left pickoff circuit).
Actual resistance values depend on the sensor model and date of manufacture.
Reading across wire pairs should be steady.
Circuit Wire colors* Nominal resistance range
Drive coil Brown to red 8 to 2650
Left pickoff Green to white 16 to 300
Right pickoff Blue to gray 16 to 300
Temperature sensor Orange to violet 100 at 0C + 0.38675 / C
Lead length compensator Yellow to violet 100 at 0C + 0.38675 / C
*For transmitter terminal designations, refer to the table below. For CMF400 sensors, also see the illustration on page 40.
Transmitter terminals for checking flowmeter circuits
Wire colors
Transmitter terminals
Model 3500 with I/O cable
RFT9739 field-mount
IFT9701
Model 5300
RFT9709 RFT9739 rack-mount
Model 3500 with
screw-type or solder-tail
terminals Model 3700
Brown to red 1 to 2 CN1-Z2 to CN1-B2 c12 to a12 12 to 11
Green to white 5 to 9 CN1-Z8 to CN1-B8 c8 to a8 17 to 18
Blue to gray 6 to 8 CN1-Z10 to CN1-B10 c10 to a10 19 to 20
Orange to violet 3 to 7 CN1-B6 to CN1-Z6 a6 to c6 16 to 15
Yellow to violet 4 to 7 CN1-B4 to CN1-Z6 c4 to c6 13 to 15
40 ELITE

Sensor Instruction Manual
Troubleshooting continued
Checking ohm levels at a CMF400 sensor
Checking the calibration factors
Check or change the flow, density, or temperature calibration factors at
the transmitter. The temperature cal factor is for the RFT9739, Model
3500, 3700, and 5300 only. If necessary, refer to the instruction manual
(or on-line help for software) for the method you choose.
Use the Model 3500 or 3700 display
Use a HART Communicator, ProLink software, or AMS software
Use the host controller
Enter the calibration factors that are listed on the flowmeter serial
number tag. (Calibration factors are also listed on the certificate that was
shipped with the meter.) If the calibration factors at the flowmeter are
already correct, the problem is not with the calibration factors.
Check all circuits, except
drive coil circuit (brown to red
wires), here
Check drive coil circuit
(brown to red wires) here
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 41
Troubleshooting continued
Checking the damping value
Check or change the damping value at the transmitter. If necessary, refer
to the instruction manual (or on-line help for software) for the method
you choose.
Use the Model 3500 or 3700 display
Use a HART Communicator, ProLink software, or AMS software
Use the host controller
In almost all applications, the damping value should be greater than
or equal to 0.8 seconds. If the damping value is already greater than or
equal to 0.8 seconds, the problem is probably not with the damping
value.
Damping values less than 0.8 seconds are used in very few applications.
After troubleshooting is complete, if you have a question about whether
your application might require a lower damping value, contact the Micro
Motion Customer Service Department. Phone numbers are listed on
page 31. The two most common applications affected by a damping
value that is too high are:
Very short batching applications
Very short-pass proving applications
Checking the drive gain
Contact Micro Motion to check the drive gain. Phone numbers are listed
on page 31.
If the transmitter is a Model 3500 or 3700, you can use the display to
view drive gain. For more information, refer to the ALTUS Detailed Setup
Manual.
Checking the density or temperature reading
View the flowmeter density or temperature measurement in any of
several ways:
Use the transmitter display, if it has one
Use a HART Communicator, ProLink software, or AMS software
Use the connected output device, if there is one
Use the host controller
If necessary, test the process fluid to confirm the flowmeter
measurement is correct.
42 ELITE

Sensor Instruction Manual
Troubleshooting continued
Checking for RF interference
Radio-frequency (RF) interference can affect the input or output signals
at the transmitter. If you suspect RF interference, and can eliminate the
source, do so before checking the alternatives described below.
Output wiring. Output wiring can be affected by RF interference. Make
sure output wiring from the transmitter is properly grounded in
accordance with the instructions in the transmitter manual. Also make
sure no wires remain exposed at either end of output wiring.
Flowmeter cable. If the flowmeter cable does not have an external
shield (see illustration, below), and is not installed in conduit, it could be
affected by RF interference. Also make sure no wires remain exposed at
either end of the flowmeter cable.
Cross-section of externally shielded cable
External shield
(braided wire)
Cable jacket
Individual wire sets
with drain wires
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 43
Troubleshooting continued
Troubleshooting at the sensor The tables in the preceding sections refer you to this section for
instructions on troubleshooting at the sensor. To troubleshoot at the
sensor, you might need a digital multimeter (DMM) or similar device. For
some procedures, you might also need the transmitter manual.
Checking flowmeter grounding
The sensor can be grounded via the piping, as long as joints in the
pipeline are ground-bonded, or by means of a ground screw on the
outside of the sensor junction box.
For CMF400 sensors, see illustration, below.
Transmitter grounding is described in the transmitter instruction
manual.
If the sensor is not grounded via the piping, and if national standards are
not in effect, adhere to these guidelines to ground the sensor via the
junction box:
Use copper wire, 14 AWG (2.5 mm
2
) or larger wire size.
Keep all ground leads as short as possible.
Ground leads must have less than 1 ohm impedance.
Connect ground leads directly to earth, or follow plant standards.
For hazardous area installation in Europe, use standard EN 60079-14 as
a guideline if national standards are not in effect.
CMF400 grounding
Explosion-proof
Intrinsically safe
External ground screws
The external ground screws may
be used for supplementary bonding
connections to meet local code
requirements
Barrier safety ground studs
For grounding, connect two individually
shielded 14-gauge wires, one to each
barrier safety ground stud.
Terminate safety ground conductors at
the same earth ground connection as
the equipment ground conductor.
44 ELITE

Sensor Instruction Manual
Troubleshooting continued
Checking for moisture in the sensor junction box
The sensor junction box must be sealed to prevent a short circuit. A
short would result in measurement error or flowmeter failure. The
CMF400 has a junction box and a booster amplifier housing. See below.
Do not open the CMF400 booster amplifier housing while the booster
amplifier is energized. See the warning statement below.
Replace all covers and seal all openings before applying power to a
CMF400 sensor.
Open the junction box (and, for a CMF400, the booster amplifier
housing) to check for moisture. If moisture is present, dry out the
junction box or housing. Do not use contact cleaner. Follow these
guidelines to avoid risk of condensation or excessive moisture from
accumulating:
Seal all conduit openings.
Install drip legs in conduit or cable.
If possible, install wiring with the junction-box opening pointed down.
Check integrity of gaskets.
Close and fully seal all housing covers.
CMF400 booster amplifier housing
WARNING
Explosion Hazard
In a hazardous area:
Do not open booster amplifier housing cover while
booster amplifier is energized.
Wait at least 8 minutes after power is shut off before
opening.
Booster amplifier
housing
Flowmeter wiring
junction box
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 45
Troubleshooting continued
Checking for mounting stress on the sensor
Because each installation is unique, it is not possible to offer a definitive
solution for mounting problems. However, mounting stresses can be
caused by one or more of the following conditions:
The pipeline is being supported by (hung from) the sensor.
Misaligned piping was drawn together by the sensor.
An unsupported pipeline is not sturdy enough to support the sensor.
If you are unable to determine whether the process connections are
being subjected to mounting stress, contact Micro Motion for additional
assistance. Phone numbers are listed on page 31.
Checking for vibration and crosstalk
Micro Motion sensors have been designed to minimize the effect of
vibration. In very rare cases, however, vibration or crosstalk can affect
flowmeter operation. Crosstalk is the transfer of resonant vibration from
one sensor to another, and sometimes occurs when two like-size
sensors are installed in close proximity to each other and are operating
on the same fluid.
Micro Motion meters are rarely affected by vibration, so vibration or
crosstalk is probably not the problem. If you are not sure whether
vibration or crosstalk is affecting the sensor, contact Micro Motion for
additional assistance. Phone numbers are listed on page 31.
46 ELITE

Sensor Instruction Manual
Troubleshooting continued
Checking for 2-phase flow
Two-phase flow occurs when air or gas is present in a liquid process
stream, or when liquid is present in a gas process stream. Two-phase
flow has several causes, as described below.
Leaks. Leaks can occur at process connections, valve seals, and pump
seals, resulting in air being introduced into a liquid stream. Air might also
be drawn in at the system inlet. Check the system for leaks, and repair
any leaks that are found.
Cavitation and flashing. Cavitation and flashing are caused by
operating the system at or near the process fluid vapor pressure,
resulting in pockets of air or gas being introduced into the process fluid.
If the sensor is near a device that causes pressure drop, such as a
control valve, locating the sensor upstream from the device can
decrease the risk of flashing. Alternatively, increasing back pressure
downstream from the sensor can also reduce the risk of cavitation and
flashing.
Cascading. Cascading of the fluid can occur when the flow rate
diminishes to the point where the sensor tube is only partially filled.
Often, this occurs because fluid is flowing downward through a sensor
installed in a vertical pipeline. (When a sensor is mounted this way, it is
called the flag-mount orientation).
To help eliminate cascading, fluids should flow upward through a flag-
mounted sensor. Mounting the sensor in the preferred orientation often
reduces cascading. (See Orientation, page 7.) Increasing back pressure
downstream from the sensor can also reduce or eliminate cascading.
High points in the system. When measuring liquids, entrained air
(pockets of non-condensable gas) can collect in high points of a fluid
system. If the fluid velocity is low, and/or the high points are very high
relative to the system, entrained air pockets can grow and persist. If the
air pocket releases and passes through the sensor, measurement error
could occur. One possible solution is to install vent valves or air
eliminators at a high point in the system, upstream from the sensor. Use
your common plant practices if you choose to install vent valves or air
eliminators.
Low points in the system. When measuring gases, liquid condensate
can collect in low points of a fluid system. If the fluid velocity is low,
and/or the low points are very low relative to the system, condensates
can accumulate and persist. If the liquid passes through the sensor,
measurement error could occur. One possible solution is to install
condensate valves at a low point in the system, upstream from the
sensor. Use your common plant practices if you choose to install
condensate valves.
W
i
r
i
n
g
S
t
a
r
t
u
p
T
r
o
u
l
e
s
h
o
o
t
i
n
g
B
e
f
o
r
e

Y
o
u

B
e
g
i
n
L
o
c
a
t
i
o
n
O
r
i
e
n
t
a
t
i
o
n
M
o
u
n
t
i
n
g
ELITE

Sensor Instruction Manual 47
Troubleshooting continued
Checking for plugging or build-up
If the process fluid tends to build up in the piping, the sensor can
become plugged or partially plugged due to build-up of material inside
the sensor flow tubes. To determine whether plugging or build-up has
occurred, check at the transmitter for a high drive gain and high density
reading (see below).
If the drive gain and the density reading are both high, flush or clean
the sensor, then check for an accurate density reading on water (or
some other fluid with a known density). If the density is still wrong,
plugging of the tube is probably not the problem.
If either the drive gain or the density reading is not high, plugging of the
tube is probably not the problem.
Checking the drive gain. Contact Micro Motion to check the drive gain.
Phone numbers are listed on page 31.
If the transmitter is a Model 3500 or 3700, you can use the display to
view drive gain. Refer to the ALTUS Detailed Setup Manual.
Checking the density reading. View the flowmeter density
measurement in any of several ways:
Use the transmitter display, if it has one
Use a HART Communicator, ProLink software, or AMS software
Use the connected output device, if there is one
Use the host controller
48 ELITE

Sensor Instruction Manual
ELITE

Sensor Instruction Manual 49
Appendi x
A ELITE

Sensor Specifications
Performance specifications
Fl ow
Nominal flow range
1
1
Micro Motion has adopted the terminology "nominal flow range." The upper limit of this range is the flow rate at which water at
reference conditions causes approximately 15 psid (1 bar) of pressure drop for ELITE sensors.
lb/min kg/h
CMF010 0 to 3 0 to 82
CMF025 0 to 40 0 to 1090
CMF050 0 to 125 0 to 3400
CMF100 0 to 500 0 to 13,600
CMF200 0 to 1600 0 to 43,550
CMF300 0 to 5000 0 to 136,080
CMF400 0 to 15,000 0 to 409,000
Maximum flow rate lb/min kg/h
CMF010 4 108
CMF025 80 2180
CMF050 250 6800
CMF100 1000 27,200
CMF200 3200 87,100
CMF300 10,000 272,160
CMF400 20,000 545,500
Accuracy
2
2
Flow accuracy includes the combined effects of repeatability, linearity, and hysteresis. All specifications for liquids are based on
reference conditions of water at 68 to 77F (20 to 25C) and 15 to 30 psig (1 to 2 bar), unless otherwise noted.
All models liquid 0.10% [(zero stability/ flow rate) x 100]% of rate
gas 0.50% [(zero stability/ flow rate) x 100]% of rate
Repeatability
2
All models liquid 0.05% [(zero stability/ flow rate) x 100]% of rate
gas 0.25% [(zero stability/ flow rate) x 100]% of rate
Zero stability lb/min kg/h
CMF010 0.00015 0.004
CMF025 0.001 0.027
CMF050 0.006 0.163
CMF100 0.025 0.680
CMF200 0.08 2.18
CMF300 0.25 6.80
CMF400 1.50 40.91
50 ELITE

Sensor Instruction Manual
ELITE

Sensor Specifications continued


Performance specifications continued
Density
with 3500 or
3700
with RFT9739,
5300, or RFT9709 wi th IFT9701
g/cc g/cc g/cc
Accuracy High-pressure CMF010P liquid 0.002 0.002 0.008
gas 0.008 0.008 0.08
All other models liquid 0.0005 0.0005 0.002
gas 0.002 0.002 0.02
Repeatability High-pressure CMF010P liquid 0.001 0.001 0.004
gas 0.004 0.004 0.04
All other models liquid 0.0002 0.0002 0.001
gas 0.001 0.001 0.01
Range All models 0 to 5 0 to 5 0 to 5
Temperature
Accuracy All models 1C 0.5% of reading in C
Repeatability All models 0.2C
Range F C
High-temperature CMF300A sensor 32 to 650 0 to 343
junction box 40 to 248 40 to 120
CMF400
1
1
Ambient temperature limits for CMF400 booster amplifier are 40 to 140F (40 to 60C). Maximum temperature limit for
CENELEC-approved CMF400 booster amplifier is 55C. If ambient temperature and radiant heat will cause the booster amplifier
to exceed these limits, a remotely mounted booster amplifier assembly is necessary. Consult the factory for remote-mount
booster amplifier information.
40 to 140 40 to 60
All other models 400 to 400 240 to 204
ELITE

Sensor Instruction Manual 51
ELITE

Sensor Specifications continued


Performance specifications continued
Pressure ratings
Flow tube rating
1
1
Flow tube and housing pressure ratings at 77F (25C), according to ASME B31.3. For higher operating temperatures, tube
pressure needs to be derated as follows:
Flow tubes Flow tubes Housing
316L sensors nickel alloy sensors all sensors
All sensors 201 to 300F (94 to 148C) none 2% derating none
301 to 400F (149 to 204C) 7.2% derating 9.2% derating 7.2% derating
High-temperature CMF300A 401 to 500F (205 to 260C) 13.8% derating not applicable 11.4% derating
501 to 600F (261 to 316C) 19. 2% derating not applicable 16. 2% derating
601 to 650F (317 to 343C) 20. 1% derating not applicable 18. 0% derating
psi bar
Stainless steel sensors 1450 100
Nickel alloy sensors 2160 148
High-pressure CMF010P 6000 413
High-temperature CMF300A
2,3
2
High-temperature CMF300A pressure rating at 650F (343C), according to ASME B31.3.
3
Maximum pressure, 1450 psi (100 bar) at 77F (25C), according to ASME B31.3.
1145 343
Housing rating
1
psi bar
CMF010
4
4
Optional rupture disks for high-pressure CMF010 will burst if pressure inside sensor housing reaches 400 psi (27 bar).
425 29
CMF025 850 58
CMF050 850 58
CMF100 625 43
CMF200 550 38
CMF300 275 19
High-temperature CMF300A
2
225 15
CMF400 250 17
Short-term housing
rating
1,5
5
Housing pressure rating for 10 hours or less, according to ASME B31.3.
psi bar
CMF010
4
565 38
CMF025 1130 78
CMF050 1130 78
CMF100 830 57
CMF200 730 50
CMF300 365 25
High-temperature CMF300A
2
299 20
CMF400 325 22
52 ELITE

Sensor Instruction Manual
ELITE

Sensor Specifications continued


Functional specifications
Environmental effects
Process
temperature effect
Process temperature effect is defined as the worst-case zero offset for flow rate due to process fluid
temperature change away from the zeroing temperature.
Process temperature effect
1
1
Nominal flow rate is the upper limit of the nominal flow range.
% of nominal flow rate per C
CMF010 0.00025
CMF025 0.00025
CMF050 0.00025
CMF100 0.00025
CMF200 0.001
CMF300 0.004
CMF400 0.001
Pressure effect Pressure effect is defined as the change in sensor flow and density sensitivity due to process pressure
change away from the calibration pressure. Pressure effect can be corrected.
Pressure effect
on flow accuracy
Pressure effect
on density accuracy
% of rate per psi g/cc per psi
CMF010 none none
CMF025 none 0.000004
CMF050 none 0.000002
CMF100 0.0002 0.000006
CMF200 0.0008 0.000001
CMF300 0.0006 0.0000002
CMF400 0.002 0.000007
ELITE

Sensor Instruction Manual 53
ELITE

Sensor Specifications continued


Functional specifications continued
Power supply options
A power supply is required for the CMF400 booster amplifier.
CMF400 only 115 VAC, 50/60 Hz
230 VAC, 50/60 Hz
Hazardous area classifications
ELITE sensors are Intrinsically safe when properly connected to an approved transmitter. Approval
agency on sensor approval tag must match agency on transmitter approval tag.
UL is a U.S.A. approvals agency, CSA is a Canadian approvals agency, CENELEC is a European
standards organization, and SAA is an Australian approvals agency.
UL and CSA Class I, Div. 1, Groups C and D
Class I, Div. 2, Groups A, B, C, and D
Class II, Div.1, Groups E, F, and G
CENELEC
1
1
CENELEC "T" rating depends on the maximum temperature of the process fluid flowing through the sensor.
Maximum fluid temperature, C
T1 T2 T3 T4 T5 T6
CMF010 EEx ib IIC T1...T6 204 204 150 85 45 35
CMF025 EEx ib IIC T1...T6 204 204 150 85 45 35
CMF050 EEx ib IIC T1...T6 204 204 150 85 45 35
CMF100 EEx ib IIC T1...T6 204 204 160 95 55 45
CMF200 EEx ib IIB T1...T6 204 204 170 105 65 55
CMF300 EEx ib IIB T1...T6 204 204 178 113 73 63
High-temperature CMF300A EEx ib IIB T1...T6 343 268 173 108 73 58
CMF400
2
2
Maximum temperature limit for CENELEC CMF400 booster amplifier is 55C. If ambient temperature and radiant heat will cause
the booster amplifier to exceed this limit, a remotely mounted booster amplifier assembly is necessary. Consult the factory for
remote-mount booster amplifier information.
EEx d [ib] IIB T1...T6 200 200 185 120 85 70
SAA CMF025 Ex ib IIC T5
CMF050 Ex ib IIC T5
CMF100 Ex ib IIC T6
CMF200 Ex ib IIB T6
CMF300
3
3
Standard-temperature model only. CMF300A high-temperature model is not SAA approved.
Ex ib IIB T6
54 ELITE

Sensor Instruction Manual
ELITE

Sensor Specifications continued


Physical specifications
Materials of construction
Wetted parts
1
1
General corrosion guides do not account for cyclical stress, and therefore should not be relied upon when choosing a wetted
material for your Micro Motion sensor. Please refer to Micro Motions corrosion guide for proper material compatibility information.
Stainless steel Nickel alloy
CMF010 316L Inconel

alloy 686
CMF025 316L Hastelloy

C-22
CMF050 316L Hastelloy C-22
CMF100 316L Hastelloy C-22
CMF200 316L Hastelloy C-22
CMF300 316L Hastelloy C-22
High-temperature CMF300A 316L not available
CMF400 316L not available
Housing 304L stainless steel
Junction box Epoxy-coated aluminum
Weight
2
2
Weight of sensor with ANSI 150 lb weld neck raised face flanges.
lb kg
CMF010 13 5.9
CMF025 8 3.6
CMF050 12 5.5
CMF100 29 13.2
CMF200 60 27.2
CMF300 162 73.5
CMF400 550 250
ELITE

Sensor Instruction Manual 55
ELITE

Sensor Specifications continued


CMF010 dimensions and process fittings
Fittings for stainless steel sensors
Fitting
code
Dim. A
Face-to-face
Dim. B
Outside diameter
1/2-inch 150 lb ANSI weld neck raised face flange 313 7 27/32 (199) 3 1/2 (89)
1/2-inch 300 lb ANSI weld neck raised face flange 314 8 7/32 (209) 3 3/4 (95)
1/2-inch 600 lb ANSI weld neck raised face flange 315 8 23/32 (221) 3 3/4 (95)
1/2-inch sanitary fitting 321 6 31/32 (177) 1 (25)
15mm DIN PN40 weld neck, DIN 2526 type C face 300 7 13/32 (188) 3 3/4 (95)
15mm DIN PN100 weld neck, DIN 2526 type E face 302 7 31/32 (202) 4 1/8 (105)
15mm JIS 10K weld neck, JIS face 304 7 3/16 (183) 3 3/4 (95)
15mm JIS 20K weld neck, JIS face 305 7 3/16 (183) 3 3/4 (95)
1/4-inch NPT female union fitting 323 6 15/32 (164) ---
1/4-inch tube compression fitting 324 6 15/32 (164) ---
6mm tube compression fitting 325 6 15/32 (164) ---
Fittings for nickel alloy sensors
1/2-inch 150 lb ANSI lap joint flange 520 7 27/32 (199) 3 1/2 (89)
1/2-inch 300 lb ANSI lap joint flange 521 8 7/32 (209) 3 3/4 (95)
15mm DIN PN40 lap joint, DIN 2526 type C face 523 7 13/32 (188) 3 3/4 (95)
15mm JIS 10K lap joint flange 522 8 3/16 (208) 3 3/4 (95)
1/4-inch NPT female union fitting 323 6 15/32 (164) ---
Dimensions in
inches
(mm)
Weld neck
raised face
flange
Union
fitting
Dim. A
face to face
Dim. A
face to face
1 3/8
(35)
1 3/8
(35)
3 5/16
(84)
8 3/4
(222)
2 13/16
(71)
9
(229)
3/4" NPT female
2 13/16
(71)
1 13/16
(47)
7 3/16
(182)
7 3/4
(197)
2X 1/2" NPT female
purge fittings (optional)
1 7/8
(48)
3 3/16
(81)
4 5/8
(117)
3 3/8
(86)
2X

5/16
(8)
thru
1/4" NPT female
Dim. B
FLOW
2X rupture disks
(optional)
Alternate side view
with rupture disk
4 3/8
(111)
56 ELITE

Sensor Instruction Manual
ELITE

Sensor Specifications continued


CMF025 dimensions and process fittings
Fittings for stainless steel sensors
Fitting
code
Dim. A
Face-to-face
Dim. B
Outside diameter
Wafer style, 1/2" ANSI (150 lb, 300 lb, 600 lb bolt kit) 009 2 3/8 (60) 1 13/16 (46)
Wafer style, 15 mm DIN 2526, type C facing (PN40 bolt kit) 016 2 3/8 (60) 1 13/16 (46)
Wafer style, 15 mm DIN 2512, type N grooved facing (PN40 bolt kit) 017 2 3/8 (60) 1 13/16 (46)
Wafer style, 15 mm DIN 2526, type E facing (PN100 bolt kit) 018 2 3/8 (60) 1 13/16 (46)
Wafer style, 15 mm DIN 2512, type N grooved facing (PN100 bolt kit) 019 2 3/8 (60) 1 13/16 (46)
Wafer style, 15 mm, standard JIS facing (10K, 20K bolt kit) 029 2 3/8 (60) 1 13/16 (46)
1/2" ANSI 150 lb weld neck raised face flange 313 6 3/4 (171) 3 1/2 (89)
1/2" ANSI 300 lb weld neck raised face flange 314 7 1/8 (181) 3 3/4 (95)
1/2" ANSI 600 lb weld neck raised face flange 315 7 5/8 (194) 3 3/4 (95)
1/2" NPT female union fitting 319 4 11/16 (119) ----
1/2" sanitary fitting 321 4 11/16 (119) 1 (25)
15 mm DIN PN40 weld neck, DIN 2526, type C facing 300 6 5/16 (160) 3 3/4 (95)
15 mm DIN PN40 weld neck, DIN 2512, type N grooved facing 301 6 5/16 (160) 3 3/4 (95)
15 mm DIN PN100 weld neck, DIN 2526, type E facing 302 6 15/16 (176) 4 1/8 (105)
15 mm DIN PN100 weld neck, DIN 2512, type N grooved facing 303 6 15/16 (176) 4 1/8 (105)
15 mm JIS 10K weld neck, JIS facing 304 6 1/8 (156) 3 3/4 (95)
15 mm JIS 20K weld neck, JIS facing 305 6 1/8 (156) 3 3/4 (95)
Fittings for nickel alloy sensors
1/2" ANSI 150 lb lap joint flange 520 6 3/4 (171) 3 1/2 (89)
1/2" ANSI 300 lb lap joint flange 521 7 1/8 (181) 3 3/4 (95)
15 mm DIN PN40 lap joint flange, DIN 2526, type C facing 523 7 5/16 (186) 3 3/4 (95)
15 mm JIS 10K lap joint flange, JIS facing 522 7 1/8 (181) 3 3/4 (95)
Dimensions in
inches
(mm)
Weld neck
raised face
flange
Union
fitting
Wafer
style
Dim. A
face to face
Dim. A
face to face
1 13/16
(46)
3 5/16
(84)
10 9/32
(261)
2 13/16
(71)
10 1/64
(254)
3/4" NPT female 3 59/64
(100)
8 1/64
(204)
2 9/32
(58)
9 9/64
(232)
1/2" NPT female
purge fittings
(optional)
3 7/64
(79)
0.410 (10.4)
inside dia.
1 13/16
(46)
1/2" NPT female
Dim. B
FLOW
Dim. B
Dim. A
face to face
2X
ELITE

Sensor Instruction Manual 57
ELITE

Sensor Specifications continued


CMF050 dimensions and process fittings
Fittings for stainless steel sensors
Fitting
code
Dim. A
Face-to-face
Dim. B
Outside diameter
Wafer style, 1/2" ANSI (150 lb, 300 lb, 600 lb bolt kit) 009 3 1/2 (89) 1 13/16 (46)
Wafer style, 15 mm DIN 2526, type C facing (PN40 bolt kit) 016 3 1/2 (89) 1 13/16 (46)
Wafer style, 15 mm DIN 2512, type N grooved facing (PN40 bolt kit) 017 3 1/2 (89) 1 13/16 (46)
Wafer style, 15 mm DIN 2526, type E facing (PN100 bolt kit) 018 3 1/2 (89) 1 13/16 (46)
Wafer style, 15 mm DIN 2512, type N grooved facing (PN100 bolt kit) 019 3 1/2 (89) 1 13/16 (46)
Wafer style, 15 mm, standard JIS facing (10K, 20K bolt kit) 029 3 1/2 (89) 1 13/16 (46)
1/2" ANSI 150 lb weld neck raised face flange 313 7 15/16 (202) 3 1/2 (89)
1/2" ANSI 300 lb weld neck raised face flange 314 8 5/16 (211) 3 3/4 (95)
1/2" ANSI 600 lb weld neck raised face flange 315 8 13/16 (224) 3 3/4 (95)
3/4" NPT female union fitting 320 6 1/2 (165) ----
3/4" sanitary fitting 322 6 1/2 (165) 1 (25)
15 mm DIN PN40 weld neck, DIN 2526, type C facing 300 7 1/2 (191) 3 3/4 (95)
15 mm DIN PN40 weld neck, DIN 2512, type N grooved facing 301 7 1/2 (191) 3 3/4 (95)
15 mm DIN PN100 weld neck, DIN 2526, type E facing 302 8 1/16 (205) 4 1/8 (105)
15 mm DIN PN100 weld neck, DIN 2512, type N grooved facing 303 8 1/16 (205) 4 1/8 (105)
15 mm JIS 10K weld neck, JIS facing 304 7 1/4 (184) 3 3/4 (95)
15 mm JIS 20K weld neck, JIS facing 305 7 1/4 (184) 3 3/4 (95)
Fittings for nickel alloy sensors
1/2" ANSI 150 lb lap joint flange 520 7 15/16 (202) 3 1/2 (89)
1/2" ANSI 300 lb lap joint flange 521 8 5/16 (211) 3 3/4 (95)
15 mm DIN PN40 lap joint flange, DIN 2526, type C facing 523 8 1/2 (216) 3 3/4 (95)
15 mm JIS 10K lap joint flange, JIS facing 522 8 1/4 (210) 3 3/4 (95)
Weld neck
raised face
flange
Dimensions in
inches
(mm)
Union
fitting
Wafer
style
Dim. A
face to face
Dim. A
face to face
1 15/16
(49)
4 3/8
(111)
12 59/64
(328)
5
(127)
14 21/64
(364)
3/4" NPT female
4 19/64
(109)
10 13/16
(275)
2 5/32
(63)
11 3/4
(298)
1/2" NPT female
purge fittings
(optional)
3 19/64
(84)
0.645 (16.4)
inside dia.
2
(51)
1/2" NPT female
Dim. B
FLOW
Dim. B
Dim. A
face to face
2X
58 ELITE

Sensor Instruction Manual
ELITE

Sensor Specifications continued


CMF100 dimensions and process fittings
Fittings for stainless steel sensors
Fitting
code
Dim. A
Face-to-face
Dim. B
Outside diameter
Wafer style, 1" ANSI (150 lb bolt kit) 010 4 (102) 2 1/2 (64)
Wafer style, 1" ANSI (300 lb, 600 lb bolt kit) 011 4 (102) 2 1/2 (64)
Wafer style, 25 mm DIN 2526, type C facing (PN40 bolt kit) 020 4 (102) 2 1/2 (64)
Wafer style, 25 mm DIN 2512, type N grooved facing (PN40 bolt kit) 021 4 (102) 2 1/2 (64)
Wafer style, 25 mm DIN 2526, type E facing (PN100 bolt kit) 022 4 (102) 2 1/2 (64)
Wafer style, 25 mm DIN 2512 type N grooved facing (PN100 bolt kit) 023 4 (102) 2 1/2 (64)
Wafer style, 25 mm, standard JIS facing (10K, 20K, 30K bolt kit) 030 4 (102) 2 1/2 (64)
1" ANSI 150 lb weld neck raised face flange 328 9 1/4 (235) 4 1/4 (108)
1" ANSI 300 lb weld neck raised face flange 329 9 3/4 (248) 4 7/8 (124)
1" ANSI 600 lb weld neck raised face flange 330 10 1/4 (260) 4 7/8 (124)
1 1/2" ANSI 600 lb weld neck raised face flange 331 10 7/8 (276) 6 1/8 (155)
1" sanitary fitting 339 8 3/8 (213) 2 (51)
25 mm DIN PN40 weld neck, DIN 2526, type C facing 306 8 5/16 (211) 4 1/2 (114)
25 mm DIN PN40 weld neck, DIN 2512, type N grooved facing 307 8 5/16 (211) 4 1/2 (114)
25 mm DIN PN100 weld neck, DIN 2526, type E facing 308 9 11/16 (246) 5 1/2 (140)
25 mm DIN PN100 weld neck, DIN 2512, type N grooved facing 309 9 11/16 (246) 5 1/2 (140)
25 mm JIS 10K weld neck, JIS facing 317 8 5/16 (211) 4 15/16 (125)
25 mm JIS 20K weld neck, JIS facing 318 8 5/16 (211) 4 15/16 (125)
Fittings for nickel alloy sensors
1" ANSI 150 lb lap joint flange 530 9 1/4 (235) 4 1/4 (108)
1" ANSI 300 lb lap joint flange 531 9 3/4 (248) 4 7/8 (124)
25 mm DIN PN40 lap joint flange, DIN 2526, type C facing 533 9 9/16 (243) 4 1/2 (114)
25 mm JIS 10K lap joint flange, standard JIS facing 532 9 5/16 (237) 4 15/16 (125)
Dimensions in
inches
(mm)
Weld neck
raised face
flange
Wafer
style
0.900 (22.9)
inside dia.
3 9/32
(83)
4 3/32
(104)
1/2" NPT female
purge fittings
(optional)
15 13/16
(402)
15 43/64
(398)
Dim. B
FLOW
Dim. A
face to face
2 51/64
(71)
5 57/64
(150)
3/4" NPT female
21 1/2
(546)
5 59/64
(150)
17 13/32
(442)
5 3/8
(137)
Dim. B
Dim. A
face to face
ELITE

Sensor Instruction Manual 59
ELITE

Sensor Specifications continued


CMF200 dimensions and process fittings
Fittings for stainless steel sensors
Fitting
code
Dim. A
Face-to-face
Dim. B
Outside diameter
1 1/2" ANSI 150 lb weld neck raised face flange 341 22 7/8 (581) 5 (127)
1 1/2" ANSI 300 lb weld neck raised face flange 342 23 3/8 (594) 6 1/8 (156)
1 1/2" ANSI 600 lb weld neck raised face flange 343 23 7/8 (606) 6 1/8 (156)
2" ANSI 150 lb weld neck raised face flange 418 22 7/8 (581) 6 (152)
2" ANSI 300 lb weld neck raised face flange 419 23 3/8 (594) 6 1/2 (165)
2" ANSI 600 lb weld neck raised face flange 420 23 5/8 (600) 6 1/2 (165)
1 1/2" sanitary fitting 351 21 3/8 (543) 2 (51)
2" sanitary fitting 352 21 3/8 (543) 2 17/32 (64)
40 mm DIN PN40 weld neck, DIN 2526, type C facing 381 21 11/16 (551) 5 15/16 (151)
40 mm DIN PN40 weld neck, DIN 2512, type N grooved facing 383 21 11/16 (551) 5 15/16 (151)
40 mm DIN PN100 weld neck, DIN 2526, type E facing 377 23 1/8 (587) 6 11/16 (170)
40 mm DIN PN100 weld neck, DIN 2512, type N grooved facing 379 23 1/8 (587) 6 11/16 (170)
50 mm DIN PN40 weld neck, DIN 2526, type C facing 382 21 15/16 (557) 6 1/2 (165)
50 mm DIN PN40 weld neck, DIN 2512, type N grooved facing 384 21 15/16 (557) 6 1/2 (165)
50 mm DIN PN100 weld neck, DIN 2526, type E facing 378 23 9/16 (598) 7 11/16 (195)
50 mm DIN PN100 weld neck, DIN 2512, type N grooved facing 380 23 9/16 (598) 7 11/16 (195)
40 mm JIS 10K weld neck, JIS facing 385 21 9/16 (548) 5 1/2 (140)
40 mm JIS 20K weld neck, JIS facing 387 21 9/16 (548) 5 1/2 (140)
50 mm JIS 10K weld neck, JIS facing 386 21 13/16 (554) 6 1/8 (156)
50 mm JIS 20K weld neck, JIS facing 388 21 13/16 (554) 6 1/8 (156)
Fittings for nickel alloy sensors
1 1/2" ANSI 150 lb lap joint flange 540 22 7/8 (581) 5 (127)
1 1/2" ANSI 300 lb lap joint flange 541 23 3/8 (594) 6 1/8 (156)
2" ANSI 150 lb lap joint flange 544 22 7/8 (581) 6 (152)
2" ANSI 300 lb lap joint flange 545 23 3/8 (594) 6 1/2 (165)
40 mm DIN PN40 lap joint flange, DIN 2526, type C facing 543 21 11/16 (551) 5 15/16 (151)
50 mm DIN PN40 lap joint flange, DIN 2526, type C facing 547 21 15/16 (557) 6 1/2 (165)
40 mm JIS 10K lap joint flange, standard JIS facing 542 21 9/16 (548) 5 1/2 (140)
50 mm JIS 10K lap joint flange, standard JIS facing 546 21 13/16 (554) 6 1/8 (156)
Dimensions in
inches
(mm)
FLOW
27 9/32
(693)
3/4" NPT
female
3 51/64
(96)
4 5/16
(110)
2X 1/2" NPT female
purge fittings (optional)
8 51/64
(223)
5 3/32
(129)
7 57/64
(200)
11 7/8
(302)
28 25/32
(731)
Dim. A
face to face
Dim. B
14
(356)
19 37/64
(497)
60 ELITE

Sensor Instruction Manual
ELITE

Sensor Specifications continued


CMF300 dimensions and process fittings
Fittings for stainless steel sensors
Fitting
code
Dim. A
Face-to-face
Dim. B
Outside diameter
3" ANSI 150 lb weld neck raised face flange 355 33 11/16 (856) 7 1/2 (191)
3" ANSI 300 lb weld neck raised face flange 356 34 7/16 (875) 8 1/4 (210)
3" ANSI 600 lb weld neck raised face flange 357 35 3/16 (894) 8 1/4 (210)
4" ANSI 150 lb weld neck raised face flange 425 34 1/16 (865) 9 (229)
4" ANSI 300 lb weld neck raised face flange 426 35 (889) 10 (254)
4" ANSI 600 lb weld neck raised face flange 427 36 11/16 (932) 10 3/4 (273)
3" sanitary fitting 361 32 (813) 3 9/16 (90)
80 mm DIN PN40 weld neck, DIN 2526, type C facing 391 32 7/8 (835) 7 7/8 (200)
80 mm DIN PN40 weld neck, DIN 2512, type N grooved facing 393 32 7/8 (835) 7 7/8 (200)
80 mm DIN PN100 weld neck, DIN 2526, type E facing 395 34 9/16 (878) 9 1/16 (230)
80 mm DIN PN100 weld neck, DIN 2512, type N grooved facing 397 34 9/16 (878) 9 1/16 (230)
100 mm DIN PN40 weld neck, DIN 2526, type C facing 392 33 7/16 (849) 9 1/4 (235)
100 mm DIN PN40 weld neck, DIN 2512, type N grooved facing 394 33 7/16 (849) 9 1/4 (235)
100 mm DIN PN100 weld neck, DIN 2526, type E facing 396 35 9/16 (903) 10 7/16 (265)
100 mm DIN PN100 weld neck, DIN 2512, type N grooved facing 398 35 9/16 (903) 10 7/16 (265)
80 mm JIS 10K weld neck, JIS facing 400 33 3/8 (848) 7 5/16 (186)
80 mm JIS 20K weld neck, JIS facing 402 33 3/8 (848) 7 7/8 (200)
100 mm JIS 10K weld neck, JIS facing 401 33 9/16 (852) 8 1/4 (210)
100 mm JIS 20K weld neck, JIS facing 403 33 9/16 (852) 8 7/8 (225)
Fittings for nickel alloy sensors
3" ANSI 150 lb lap joint flange 550 33 11/16 (856) 7 1/2 (191)
3" ANSI 300 lb lap joint flange 551 34 7/16 (875) 8 1/4 (210)
80 mm DIN PN40 lap joint flange, DIN 2526, type C facing 553 32 7/8 (835) 7 7/8 (200)
80 mm JIS 10K lap joint flange, JIS facing 552 33 3/8 (848) 7 5/16 (186)
Dimensions in
inches
(mm)
FLOW
36 1/2
(927)
3/4" NPT
female
5 7/64
(130)
5 5/8
(137)
2X 1/2" NPT female
purge fittings (optional)
11 1/4
(286)
6 11/32
(161)
10 29/64
(266)
13 13/16
(351)
39 1/2
(1003)
Dim. A
face to face
Dim. B
22
(559)
30 3/16
(767)
ELITE

Sensor Instruction Manual 61
ELITE

Sensor Specifications continued


High-temperature CMF300A dimensions and process fittings
Fittings for stainless steel sensors
Fitting
code
Dim. A
Face-to-face
Dim. B
Outside diameter
3" ANSI 150 lb weld neck raised face flange 355 33 11/16 (856) 7 1/2 (191)
3" ANSI 300 lb weld neck raised face flange 356 34 7/16 (875) 8 1/4 (210)
3" ANSI 600 lb weld neck raised face flange 357 35 3/16 (894) 8 1/4 (210)
3" ANSI 900 lb weld neck raised face flange 358 36 11/16 (932) 9 1/2 (241)
4" ANSI 150 lb weld neck raised face flange 425 34 1/16 (865) 9 (229)
4" ANSI 300 lb weld neck raised face flange 426 35 (889) 10 (254)
4" ANSI 600 lb weld neck raised face flange 427 36 11/16 (932) 10 3/4 (273)
4" ANSI 900 lb weld neck raised face flange 428 37 3/16 (945) 11 1/2 (292)
80 mm DIN PN40 weld neck, DIN 2526, type C facing 391 32 7/8 (835) 7 7/8 (200)
80 mm DIN PN40 weld neck, DIN 2512, type N grooved facing 393 32 7/8 (835) 7 7/8 (200)
80 mm DIN PN100 weld neck, DIN 2526, type E facing 395 34 9/16 (878) 9 1/16 (230)
80 mm DIN PN100 weld neck, DIN 2512, type N grooved facing 397 34 9/16 (878) 9 1/16 (230)
100 mm DIN PN40 weld neck, DIN 2526, type C facing 392 33 7/16 (849) 9 1/4 (235)
100 mm DIN PN40 weld neck, DIN 2512, type N grooved facing 394 33 7/16 (849) 9 1/4 (235)
100 mm DIN PN100 weld neck, DIN 2526, type E facing 396 35 9/16 (903) 10 7/16 (265)
100 mm DIN PN100 weld neck, DIN 2512, type N grooved facing 398 35 9/16 (903) 10 7/16 (265)
80 mm JIS 10K weld neck, JIS facing 400 33 3/8 (848) 7 5/16 (186)
80 mm JIS 20K weld neck, JIS facing 402 33 3/8 (848) 7 7/8 (200)
100 mm JIS 10K weld neck, JIS facing 401 33 9/16 (852) 8 1/4 (210)
100 mm JIS 20K weld neck, JIS facing 403 33 9/16 (852) 8 7/8 (225)
FLOW
11
(279)
Junction
box
8 3/16
(208)
30 3/16
(767)
2X 1/2" NPT female
purge fitting (optional)
5 1/2
(140)
11
(280)
45 13/16
(1163)
Remote-mount
junction box
1/4
(6)
Dim. A
face to face
Dim. B
36 15/16
(937)
32 (812) flexible conduit
Minimum bend radius: 1 1/2 (38)
Dimensions in
inches
(mm)
1/2" NPT
female
2X thru for mounting
5 5/8
(143)
2X
13 13/16
(351)
3 5/16
(84)
2X
2 13/16
(71)
62 ELITE

Sensor Instruction Manual
ELITE

Sensor Specifications continued


CMF400 dimensions and process fittings
Fittings for stainless steel sensors
Fitting
code
Dim. A
Face-to-face
Dim. B
Outside diameter
4" ANSI 150 lb weld neck raised face flange 435 40 5/16 (1025) 9 (229)
4" ANSI 300 lb weld neck raised face flange 436 41 1/8 (1044) 10 (254)
4" ANSI 600 lb weld neck raised face flange 437 42 13/16 (1088) 10 3/4 (273)
6" ANSI 150 lb weld neck raised face flange 451 40 7/16 (1028) 11 (279)
6" ANSI 300 lb weld neck raised face flange 452 41 7/16 (1053) 12 1/2 (318)
6" ANSI 600 lb weld neck raised face flange 453 43 5/8 (1107) 14 (356)
100 mm DIN PN40 weld neck, DIN 2526, type C facing 460 39 7/16 (1002) 9 1/4 (235)
100 mm DIN PN40 weld neck, DIN 2512, type N facing 462 39 7/16 (1002) 9 1/4 (235)
100 mm DIN PN100 weld neck, DIN 2526, type E facing 464 41 7/16 (1052) 10 7/16 (265)
100 mm DIN PN100 weld neck, DIN 2512, type N facing 466 41 7/16 (1052) 10 7/16 (265)
150 mm DIN PN40 weld neck, DIN 2526, type C facing 461 39 3/4 (1010) 11 13/16 (300)
150 mm DIN PN40 weld neck, DIN 2512, type N facing 463 39 3/4 (1010) 11 13/16 (300)
150 mm DIN PN100 weld neck, DIN 2526, type E facing 465 42 1/16 (1068) 14 (355)
150 mm DIN PN100 weld neck, DIN 2512, type N facing 467 42 1/16 (1068) 14 (355)
100 mm JIS 10K weld neck, JIS facing 470 39 7/16 (1002) 8 1/4 (210)
100 mm JIS 20K weld neck, JIS facing 472 39 15/16 (1014) 8 7/8 (225)
150 mm JIS 10K weld neck, JIS facing 471 39 3/4 (1010) 11 (280)
150 mm JIS 20K weld neck, JIS facing 473 40 1/4 (1022) 12 (305)
Dimensions in
inches
(mm)
FLOW
11 5/8
(295)
3/4" NPT female
for flowmeter wiring
7 9/16
(192)
32 3/4
(832)
3/8
(10)
8 13/16
(224)
9 15/16
(253)
Dim. A
face to face
Dim. B
5 3/8
(137)
38 1/4
(971)
10 3/4
(274)
1/2" NPT female
for power wiring
14 13/16 (376)
clearance for
removal of cover
4 7/8
(123)
5 1/16 (129)
Power NPT
14 5/8 (371)
clearance for
removal of cover
ELITE

Sensor Instruction Manual 63
Appendi x
B Ordering Information
ELITE

sensor model number matrix


Code Sensor model
CMF010 ELITE 1/8-inch sensor
CMF025 ELITE 1/4-inch sensor
CMF050 ELITE 1/2-inch sensor
CMF100 ELITE 1-inch sensor
CMF200 ELITE 2-inch sensor
CMF300 ELITE 3-inch sensor
CMF400 ELITE 4-inch sensor
Code Pressure, temperature, and wetted material
M Standard pressure, standard temperature, 316L stainless steel
H Standard pressure, standard temperature, Hastelloy

C-22 nickel alloy


Not available with CMF010 or CMF400
N Standard pressure, standard temperature, Inconel

686 nickel alloy CMF010 only


A Standard pressure, high temperature, 316L stainless steel CMF300 only
P High pressure, standard temperature, Inconel

686 nickel alloy and 316L stainless steel CMF010 only


Code Process connections
### See fittings tables on pages 55-62
Code Case option
N Standard pressure containment
P Purge fittings 1/2" NPT female, not available with CMF400
D Rupture disks CMF010 with pressure/material code P only
Code Approvals
M Micro Motion standard no approvals
U UL intrinsically safe U.S.A. approvals agency
C CSA Canadian approvals agency
B CENELEC European standards organization
S SAA Australian approvals agency, not available with CMF400
or temperature code A
Code Booster amplifier power voltage CMF400 only
1 110/115 VAC
2 220/230 VAC
Example*
CMF300 M 355 N U
*Example: CMF300 M 355 N U = ELITE CMF300 3-inch sensor; standard pressure, 316L stainless steel; 3-inch ANSI 150 lb
weld neck raised face flanges; standard pressure containment; UL approved for intrinsically safe installations
64 ELITE

Sensor Instruction Manual
Ordering Information continued
Micro Motion instruction
manuals
To obtain any of the Micro Motion instruction manuals listed below,
contact the Micro Motion Customer Service Department:
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277)
Outside the U.S.A., phone 303-530-8400
In Europe, phone +31 (0) 318 549 443
In Asia, phone 65-770-8155
Sensors ELITE

Sensor Instruction Manual


T-Series Sensor Instruction Manual
R-Series Flowmeter Instruction Manual
R-Series Flowmeter with FOUNDATION

fieldbus
F-Series Sensor Instruction Manual
Model D and DT Sensors Instruction Manual
Model DL Sensor Instruction Manual
Transmitters ALTUS

Installation Manual
ALTUS

Detailed Setup Manual


ALTUS

Discrete Batch Control Applications Manual


ALTUS

HFCS/Brix Applications Manual


ALTUS

Net Oil Computer Applications Manual


Installing Relays for the ALTUS

Applications Platform
Printer Setup for the ALTUS

Applications Platform
ELITE

Model RFT9739 Field-Mount Transmitter Instruction Manual


ELITE

Model RFT9739 Rack-Mount Transmitter Instruction Manual


BASIS

Model IFT9701 Transmitter Instruction Manual


Model 5300 Transmitter with FOUNDATION

fieldbus
Model RFT9709 Transmitter Instruction Manual
Model RFT9712 Remote Flow Transmitter Instruction Manual
Communications Using ProLink

Software with Micro Motion

Transmitters
Using the HART

Communicator with Micro Motion

Transmitters
Using Modbus

Protocol with the Micro Motion

ELITE

Model
RFT9739 Transmitter
RFT9739 Transmitter-Specific Command Specification
RFT9709 Transmitter-Specific Command Specification
RFT9712 Transmitter-Specific Command Specification
Peripheral products DMS Density Monitoring System Instruction Manual
DRT Digital Rate Totalizer LCD Instruction Manual
DRT Digital Rate Totalizer LED Instruction Manual
FMS-3 Flow Monitoring System LCD Instruction Manual
FMS-3 Flow Monitoring System LED Instruction Manual
NFC Net Flow Computer Instruction Manual
NOC Net Oil Computer Instruction Manual
PI 4-20 Process Indicator
Wiring instructions 9-Wire Flowmeter Cable Preparation and Installation
Cable Gland Assembly Instructions
UL-D-IS Installation Instructions
CSA-D-IS Installation Instructions
SAA-D-IS Installation Instructions
Power-Supply Wiring for the D600 Sensor
Input Signal Wiring for Peripheral Devices
ELITE

Sensor Instruction Manual 65
Appendi x
C Purge Fittings
Keeping purge fittings sealed If the sensor has purge fittings, they should remain sealed at all times.
After a purge plug is removed, the sensor case should be purged with a
dry, inert gas (such as argon or nitrogen), and resealed. See Case
purging procedure, page 66.
Purging the case protects internal components. Before Micro Motion
ships a sensor from the factory, it purges the sensor case. If you never
loosen or remove the fittings, you do not have to be concerned about
them.
For more information, contact the Micro Motion Customer Service
Department:
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277)
Outside the U.S.A., phone 303-530-8400
In Europe, phone +31 (0) 318 549 443
In Asia, phone 65-770-8155
Using purge fittings The primary reason for having purge fittings is to monitor pressure inside
the sensor case. Some users, such as those measuring highly volatile
fluids, install a pressure transmitter across the sensor purge fittings. A
control device, connected to the pressure transmitter, shuts down the
process if a change in pressure is detected. This provides additional
protection should a rupture occur inside the sensor.
Purge fittings
1/2" NPT female
purge fitting
Purge plug
Sensor
case
Front
view
Side
view
66 ELITE

Sensor Instruction Manual
Purge Fittings continued
Removing a purge plug If you remove a purge plug from the sensor case, it is necessary to
re-purge the case.
Case purging procedure Read all instructions before performing the case purging procedure. It is
not necessary to perform this procedure unless a purge plug has been
removed.
1. Shut down the process, or set control devices for manual operation.
2. Remove both purge plugs from the sensor case. If purge lines are
being used, open the valve in the purge lines.
WARNING
Removing a purge plug will require the sensor case to
be re-purged with a dry inert gas. Improper
pressurization could result in serious personal injury.
Follow all instructions for re-purging the sensor case. See
Case purging procedure, below.
WARNING
Explosion hazard
The CMF400 has drain plugs, which look similar to purge
fittings. The drain plugs must remain sealed at all times.
Do not remove or damage CMF400 drain plugs.
CMF400 drain
plugs
CAUTION
Performing the purge procedure while the flowmeter is
operating could affect measurement accuracy,
resulting in inaccurate flow signals.
Before performing the case purging procedure, shut down
the process, or set control devices for manual operation.
ELITE

Sensor Instruction Manual 67
Purge Fittings continued
3. Connect the supply of dry, inert gas to the inlet purge connection or
open inlet purge line. Leave the outlet connection open.
Exercise caution to avoid introducing dirt, moisture, rust, or other
contaminants into the sensor case.
If the purge gas is heavier than air (such as argon), locate the inlet
lower than the outlet, so the purge gas will displace air from bottom
to top.
If the purge gas is lighter than air (such as nitrogen), locate the inlet
higher than the outlet, so the purge gas will displace air from top to
bottom.
4. Make sure there is a tight seal between the inlet connection and
sensor case, so air cannot be drawn by suction into the case or purge
line.
5. The purge time is the amount of time required for full exchange of
atmosphere to inert gas. For each sensor size, the purge time is
different. Refer to the table below. If purge lines are being used,
increase the purge time to fill the additional volume of the purge line.
6. Avoid pressurizing the sensor case. At the appropriate time, shut off
the gas supply, then immediately seal the purge outlet and inlet
connections. If pressure inside the case elevates above atmospheric
pressure during operation, the flowmeter density calibration will be
inaccurate.
Time required to purge ELITE

sensor cases
Sensor model
Purge rate
cubic ft/hr (l/hr)
Time*
minutes
*If purge lines are being used, increase purge time to fill the additional volume.
CMF010 20 (566) 1
CMF025 20 (566) 1
CMF050 20 (566) 2
CMF100 20 (566) 5
CMF200 20 (566) 12
CMF300 20 (566) 30
68 ELITE

Sensor Instruction Manual
ELITE

Sensor Instruction Manual 69
Appendi x
D Rupture Disks
Keeping the rupture disks sealed If the sensor has rupture disks, they are installed in the sensor purge
fitting openings. The rupture disks should remain installed at all times. If
you remove a rupture disk from the sensor case, it is necessary to
re-purge the case. See Appendix C, page 65.
For more information, contact the Micro Motion Customer Service
Department:
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277)
Outside the U.S.A., phone 303-530-8400
In Europe, phone +31 (0) 318 549 443
In Asia, phone 65-770-8155
Rupture disk
Rupture disk
assembly
Sensor
case
Front
view
Side
view
1/2" NPT female
purge fitting
70 ELITE

Sensor Instruction Manual
Rupture Disks continued
Using the rupture disks The primary reason for having rupture disks is to vent process fluid from
inside the sensor case, should the sensor flow tube rupture in a high-
pressure application. Some users, such as those measuring high-
pressure gases, connect a pipeline to the rupture disk fittings, to help
contain escaping process fluid. This provides additional protection
should a rupture occur.
Removing a rupture disk The rupture disks are installed in the sensor purge fitting openings. If
you remove a rupture disk from the sensor case, it is necessary to
re-purge the case. See Case purging procedure, page 66, for
instructions.
WARNING
Pressure Relief Zone.
Escaping high-pressure fluid can cause severe injury
or death.
Stay clear of rupture disk pressure-relief area.
WARNING
Removing a rupture disk will require the sensor case
to be re-purged with a dry inert gas. Improper
pressurization could result in serious personal injury.
Follow all instructions for re-purging the sensor case. See
Case purging procedure, page 66.
ELITE

Sensor Instruction Manual 71
Appendi x
E Label Maintenance and
Replacement
Micro Motion product safety labels have been designed in accordance
with the voluntary standard, ANSI Z535.4. If either of the labels
illustrated below is illegible, damaged, or missing, promptly have a new
one installed. The sensor includes the safety labels illustrated below.
Contact Micro Motion for replacement labels:
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277)
Outside the U.S.A., phone 303-530-8400
In Europe, phone +31 (0) 318 549 443
In Asia, phone 65-770-8155
Label number 1003972
For additional information, see Removing a purge plug and Case
purging procedure, page 66.
Label number 3002734
For additional information, see Appendix D, page 69.
CAUTION: Removal of plugs will require sensor case to
be repurged with a dry inert gas.
! WARNING: Improper pressurization may result in
injury. Refer to sensor manual for repurging instructions.
Part No. 1003972, Rev. B
ELITE sensor with
purge fittings
Part No. 3002734
WARNING
Pressure Relief Zone.
Escaping pressure
can cause severe
injury or death.
Stay clear of vent.
CMF010 sensor with
rupture disks
72 ELITE

Sensor Instruction Manual
ELITE

Sensor Instruction Manual 73
General guidelines Micro Motion return procedures must be followed for you to meet the
legal requirements of applicable U.S. Department of Transportation
(DOT) regulations. They also help us provide a safe working
environment for our employees. Failure to follow these requirements will
result in your equipment being refused delivery.
To return equipment, phone the Micro Motion Customer Service
Department for information on the return procedures and required
documentation forms:
In the U.S.A., phone 1-800-522-6277 or 1-303-530-8422 between
6:00 a.m. and 5:30 p.m. (Mountain Standard Time), Monday through
Friday, except holidays.
In Europe, phone +31 (0) 318 549 549, or contact your local sales
representative.
In Asia, phone (65) 777-8211, or contact your local sales
representative.
Information on return procedures and forms are also available on-line at
www.micromotion.com.
New and unused equipment Only equipment that has not been removed from the original shipping
package will be considered new and unused. New and unused
equipment includes sensors, transmitters, or peripheral devices which:
Were shipped as requested by the customer but are not needed, or
Were shipped incorrectly by Micro Motion.
Used equipment All other equipment is considered used. This equipment must be
completely decontaminated and cleaned before being returned.
Document all foreign substances that have come in contact with the
equipment.
F Return Policy
Appendi x
74 ELITE

Sensor Instruction Manual
Return Policy continued
Domestic shipping and billing
addresses
International shipping and billing
addresses
Shipping address: Billing/correspondence:
Attn: RMA# _____________
Chemical Waste Management
Sensor Department
9131 East 96 Avenue
Henderson CO 80640
Micro Motion Inc.
7070 Winchester Circle
Boulder, CO 80301
Attn: Repairs
Shipping address: Billing/correspondence:
Attn: RMA# _____________
Micro Motion Inc.
c/o Chemical Waste Management
Sensor Department
9131 East 96 Avenue
Henderson CO 80640
Micro Motion Inc.
7070 Winchester Circle
Boulder CO 80301
Attn: Repairs
ELITE

Sensor Instruction Manual 75


Page numbers in bold indicate illustrations.
A
Air eliminators 46
AMS software 31, 37
Approvals tag
CMF010 1
CMF025, CMF050, and CMF100 2
CMF200 and CMF300 2
CMF300A 3
CMF400 3
keys for sensor location 5
B
Batch total 34
Before you begin 14
additional information 4
installation process 4
your new sensor 1
Booster amplifier
sensor location 5
sensor wiring 20, 21
C
Cable. See also Flowmeter cable; Wiring
CMF300A 5
glands 23
wiring instruction manuals 64
Calibration
certificate 40
startup 29
troubleshooting 40
Cascading 46
Cavitation 46
CENELEC. See European installations
Certificate of conformance 40
Characterization 29
Condensate valves 46
Configuration 29
Coriolis flowmeter 1. See also Flowmeter
Crosstalk 45
CSA
grounding 22
instruction manual 64
sensor location 6, 17
Customer Service 30
Customer service 31
D
Damping 41
Density
checking 41
inaccurate density reading 35
Dimensions 5562
DMM 31, 37
Drain plug 66
Drive gain 41
E
EMC directive. See European installations
EMI. See European installations
Entrained air or gas 46
European installations 1
hazardous area installation 6, 17
F
Fieldbus host 37
Flashing 46
Flow direction 7
Flow direction arrow
CMF010 1
CMF025, CMF050, and CMF100 2
CMF200 and CMF300 2
CMF300A 3
CMF400 3
sensor orientation 7
Flow rate
erratic flow rate 33
inaccurate flow rate 34
Flowmeter
cable. See also Wiring
cross-section 38
instruction manual for cable preparation 64
maximum length 5
RF interference 42, 42
sensor wiring 23
troubleshooting 3839
components of 1
grounding 22
startup 2930
zeroing 29
FOUNDATION fieldbus. See Fieldbus host
G
Grounding
troubleshooting 43
wiring 22
H
HART Communicator
instruction manual 64
troubleshooting with 37
Hazardous area installations
sensor location 6
wiring 17
Heat tracing 16
Index
76 ELITE

Sensor Instruction Manual


Index continued
I
IFT9701. See Transmitter
Installation
step 1: location 56. See also Location
step 2: orientation 710. See also Orientation
step 3: mounting 1116. See also Mounting
step 4: wiring 1728. See also Wiring
step 5: startup 2930. See also Startup
Installation process 4
Instruction manuals
list of 64
Intrinsically safe
grounding 22
instruction manuals 64
J
Junction box 1819
CMF300A 13, 13
sealing 23
troubleshooting 44
K
Keys for installation
sensor location 5
sensor mounting 11
sensor orientation 7
L
Labels 71
Location 56
booster amplifier 5
cable to transmitter 5
CMF300A junction box 5
CMF400 5
hazardous area installations 6
keys for installation 5
pipe run 5
valves 5
M
Modbus
instruction manual 64
troubleshooting with 37
Model 5300. See Transmitter
Model number matrix 6364
Mounting 1116
CMF010 optional mounting 12, 12
CMF300A junction box 13, 13
heat tracing 16
keys for installation 11
mounting any sensor 11
wafer-style alignment rings 15
wafer-style assembly 14
wafer-style sensors 1415
O
Ordering information 6364
Orientation 710
flow direction 7
flow direction arrow 7
keys for installation 7
measuring gases 9
measuring liquids 8
measuring slurries 10
process fluids 7
vertical pipeline 7
P
Pipe run 5
Plugging 47
Process fittings. See Specifications
Process fluid
flow direction 7
sensor orientation 7
measuring gases 9
measuring liquids 8
measuring slurries 10
ProLink program
instruction manual 64
ProLink software 31, 37
Purge fittings 65. See also Rupture disk
CMF010 1
CMF025, CMF050, and CMF100 2
CMF200 and CMF300 2
CMF300A 3
instructions 6567
R
Resistance ranges for flowmeter circuits 39
Return policy 73
RF interference 42, 42
RFT9709. See Transmitter
RFT9739. See Transmitter
Rupture disk 6970, 69
S
SAA
grounding 22
instruction manual 64
sensor location 6, 17
Sensor
approvals tag 1, 2, 3
booster amplifier 21
location 5
wiring 20
components 13
CMF010 1
CMF025, CMF050, and CMF100 2
CMF200 and CMF300 2
CMF300A 3
CMF400 3
dimensions 5562
flow direction arrow 1, 2, 3
grounding 22
heat tracing 16
instruction manuals 64
junction box 1819
CMF300A 19
sealing 23
labels 71
location 56. See also Location
CMF400 5
mounting 1116. See also Mounting
ordering information 6364
orientation 710. See also Orientation
purge fittings 6567, 65. See also Rupture disk
rupture disk 6970, 69
serial number tag 1, 2, 3
specifications 4962. See also Specifications
startup 2930
ELITE

Sensor Instruction Manual 77


Index continued
troubleshooting 3147. See also Troubleshooting
wafer-style alignment rings 15
wafer-style assembly 14
wiring 1728. See also Wiring
Serial number tag
CMF010 1
CMF025, CMF050, and CMF100 2
CMF200 and CMF300 2
CMF300A 3
CMF400 3
troubleshooting 40
Specifications 4962
dimensions 5562
process fittings
CMF010 55
CMF025 56
CMF050 57
CMF100 58
CMF200 59
CMF300 6061
CMF400 62
Startup 2930
zeroing 29
T
Temperature
checking 41
inaccurate temperature reading 36
Transmitter
compatible models 1
maximum distance from sensor 5
terminals. See Wiring
troubleshooting 3147
Troubleshooting 3147
air eliminators 46
AMS software 31, 37
at the sensor 4347
at the transmitter 3742
cascading 46
cavitation 46
checking
calibration factors 40
crosstalk 45
damping value 41
density reading 41
drive gain 41
faulty flowmeter wiring 3839
faulty output wiring 37
flowmeter grounding 43
junction box 44
mounting stress 45
plugging 47
RF interference 42
temperature reading 41
2-phase flow 46
vibration 45
condensate valves 46
customer service 31
DMM 31, 37
Fieldbus host 37
flashing 46
general information 31
HART Communicator 37
high points in system 46
low points in system 46
procedures
erratic flow rate 33
inaccurate batch total 34
inaccurate density reading 35
inaccurate flow rate 34
inaccurate temperature reading 36
zero drift 32
ProLink software 31, 37
vent valves 46
wiring
resistance ranges 39
transmitter terminals 39
U
UL
grounding 22
instruction manual 64
sensor location 6, 17
Using this manual v
V
Valves
sensor location 5
Vent valves 46
W
Wafer kit 14
Wiring 1728
CMF300A 19, 2324
CMF400 1920, 212324
flowmeter cable 23, 38
grounding 22
hazardous area installations 17
instruction manuals 64
junction box 1819, 23
CMF300A 19
transmitter 2328
IFT9701 28
Model 3500 27
Model 3700 27
Model 5300 28
RFT9709 28
RFT9739 field-mount 26
RFT9739 rack-mount 26
troubleshooting 3839
output wiring 42
RF interference 42
Z
Zero drift 32
Zeroing
flowmeter startup 29
keys for sensor location 5
78 ELITE

Sensor Instruction Manual


Index continued
recycled paper
Micro Motion Inc. USA
Worldwide Headquarters
7070 Winchester Circle
Boulder, Colorado 80301
Tel (303) 530-8400
(800) 522-6277
Fax (303) 530-8459
Micro Motion Europe
Groeneveldselaan 8
3903 AZ Veenedaal
The Netherlands
Tel +31 (0) 318 549 549
Fax +31 (0) 318 549 559
Micro Motion Asia
1 Pandan Crescent
Singapore 128461
Republic of Singapore
Tel (65) 777-8211
Fax (65) 770-8003
Visit us on the Internet at www.micromotion.com
1999, Micro Motion, Inc.
All rights reserved
P/N 3002708, Rev. C

Potrebbero piacerti anche