Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
10
5.4.0.1
Introduction
Contents
Installing branch fittings
Overview
This section contains instructions for the installation of the branch joints and fittings which are
included in standard pipe systems with PE outer casings.
Reinforcement plates 5.4.0.2
Steel joints:
Straight taper lock branch 5.4.1
45 branch fitting 5.4.2
90 branch fitting 5.4.3
Branch saddle 5.4.4
Shrink joints:
SXT, branch joints 5.4.5
T2S, branch joints 5.4.6
Weld joints:
Band joint branches 5.4.7
Prefabricated branches 5.4.8
Branch from concrete duct 5.4.9
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.0.2
Application
Installing branch fittings
Reinforcement plates
In connection with branch fittings it may be necessary to reinforce the main pipe when making
cut outs for branches e.g.:
- when the branch dimension and the main pipe dimension are the same
- when the branch dimension is one or two dimensions smaller than the main pipe dimension
- when the level of axial stress in the main pipe is high
This must appear from the design drawing.
In case of doubt please contact a LOGSTOR technician.
Description LOGSTOR supplies reinforcement plates,
adjusted to all relevant combinations of
main pipe and branch pipe. See Product
Catalogue, page 2.4.2.1.
The reinforcement plate is either one plate
or - when the curvature of the plate exceeds
the center line of the pipe - 2-part.
Welding on the
reinforcement
plate
The purpose of the reinforcement plate is to
reinforce the main pipe.
Never weld it on to the branch pipe.
A full weld is not necessary, but as a mini-
mum fillet welding as shown in the illustration
is required.
t = thickness of the reinforcement plate.
The parts of a 2-part reinforcement plate (a)
must be welded together with each other,
but not necessarily with the pipe.
0,3 x d
d
0,3 x d
max. 250
3 x t
a
max. 250
3 x t
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
5.4.0.3
Installing branch fittings
Reinforcement plates
Self-manufacture
of reinforcement
plates
Reinforcement plates can be manufactured
after these measurement and tables, pro-
vided that the stress level is known.
Rectangular plates may be manufactured.
b
d
D
b
s
t
d + 10 mm
= Reinforcement at max. 150 N/mm
2
only necessary in these fields b = 50
mm, t = s
= Reinforcement (b = 50 mm, t = s) at
max. 300 N/mm
2
= Reinforcement (t > s) at max. 300 N/
mm
2
= No reinforcement
Branch
d mm
Main pipe
D x s mm
2
6
.
9
3
3
.
7
4
2
.
4
4
8
.
3
6
0
.
3
7
6
.
1
8
8
.
9
1
1
4
.
3
1
3
9
.
7
1
6
8
.
3
2
1
9
.
1
26.9 x 2.6
33.7 x 2.6
42.4 x 2.6
48.3 x 2.6
60.3 x 2.9
76.1 x 2.9
88.9 x 3.2
114.3 x 3.6
4.1
139.7 x 3.6
4.1 5.0
168.3 x 4.0
4.6 5.6 6.7
219.1 x 4.5
5.1 6.3 7.6 9.9
273 x 5.0
5.7 7.0 8.4 11.0
323.9 x 5.6
6.4 7.8 9.4 12.3
355.6 x 5.6
6.4 7.8 9.4 12.3
406.4 x 6.3
7.2 8.8 10.6 13.8
457 x 6.3
7.2 8.8 10.6 13.8
508 x 6.3
7.2 8.8 10.6 13.8
559 x 6.3
7.2 8.8 10.6 13.8
610 x 7.1
9.1 11.1 13.5 17.5
t
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.1.1
Application
Requirements to
the joint area
Installing branch fittings
Straight taper lock branch
Straight taper lock branches are used in 3
installation cases:
Horizontal/inclined branching from FlexPipe
systems.
Horizontal branching from the steel/plastic
system, including TwinPipes.
Vertical branching from the steel/plastic sys-
tem - primarily in connection with venting
points.
Main pipe dimension: 77-315 mm.
Branch dimension: 77-250 mm.
Space, see section 1.2 Excavation, installation.
Preparation for joint installation, see section 5.1.
Tools Use the following tools when installing
straight taper lock branches:
Type: Application:
1. Scissors Sealing strip
2. Hammer (1,5 kg) Taper locks and
plugs
3. Saw Outer casing
4. Scraper Foam remnants
5. Fixing tool Dual plugs
6. Pressure test kit Pressure test
7.Auxiliary tool Pre-installed to facili-
tate installation of
taper locks
1 2 3 4
5
6
7
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
5.4.1.2
Installing branch fittings
Straight taper lock branch
Sealing strip
Removal of foam
from main pipe
Removal of foam
4
4
0
4
4
0
m
m
4
4
0
m
m
Sealing strip is used to seal joint and outer
casing.
Sealing strip is available in coils with two
strips on each.
The sealing strip is on paper, enabling
removal of 1 strip at a time.
The sealing strip should always be cut with a
pair of scissors.
To avoid stretching the sealing strip, espe-
cially at high temperatures, it is recommend-
ed always to keep it on the paper, until it is
applied to the joint.
If the sectional area is reduced, the sealing
will be less efficient.
Sealing strips which are deformed, pasted
together or dirty must be discarded.
1. Excavate or support the pipes so that
there is room for the installation.
2. Mark the position of the branch on the
outer casing. It must be 440 mm.
3. Cut and remove the outer casing.
(See section 1.3 cutting and adjusting pipes.
4. Remove the insulation material from the
uncovered area.
5. Clean the area carefully with a scraper,
especially around the welding area.
It is important to remove the hard film, left by
the foam.
Pipe dimensions < 139.7 are cleaned longi-
tudinally. Major dimensions are cleaned trans-
versely.
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.1.3
Installing branch fittings
Straight taper lock branch
Welding on
branch
6. General: Check whether the branch needs
reinforcement or not. (See section 5.4.0.)
a. In connection with FlexPipes, see
Connection to main pipe of the
respective FlexPipe types in the section.
b. In connection with venting and draining
arrangements, see section 8.2.
Application of
sealing strip on
outer casing
30 mm
30 mm
30 mm
7. Apply sealing strip, still on the paper, to
the clean, dry and ground outer casing
ends.
Remove the paper.
The ends of the sealing strip must over-
lap.
Sealing strip,
branch tee cou-
pling
50 mm
8. Apply sealing strip (on paper) with 50 mm
extra length at each end.
Remove paper.
9. Fold the 50 mm back on the flanges of
the lower half.
Press the sealing strip against the outer
casing where joint and outer casing over-
lap.
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
Tightening
Pressure testing
Insulation
2
6
4
1
5
3
0,2 bar
10. Press the upper part with foaming holes
down onto the outer casings and install
the taper locks manually.
11. Drive the taper locks into position with a
hammer. This operation must be carried
out in sequence (1, 2, 3, 4, 5, 6), so the
taper locks are evenly tightened.
Pressure test the joint with air prior to
insulation.
It is recommended always to do so.
Insulate the joint immediately after installa-
tion or the same day at the latest in order to
eliminate moist from e.g. rain or condensate.
Insulate the joint and insert the venting part
of the dual plugs into the filling holes.
Use a hammer.
See section 7.0 Insulating joints.
5.4.1.4
Installing branch fittings
Straight taper lock branch
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.2.1
Application
Installing branch fittings
45 branch fitting
45 branch fittings are used for branching
from outer casings in dimensions 90-315
mm.
Max. branch dimension: 250 mm.
Requirements to
the joint area
Space, see section 1.2 Excavation, installation.
Preparation for joint installation, see section 5.1.
1 2 3 4
5
6
7
8
9
Tools When installing 45 branch fittings use the
following tools:
Type: Application:
1. Scissors Sealing strip
2. Hammer (1.5 kg) Taper locks and
plugs
3. Saw Outer casing
4. Scraper Foam remnants
5. Ratchet spanner Tightening bolts
and bolt retainer
(17 mm)
(Alternatively an electric bolt spanner may
be used)
6. Fixing tool Dual plugs
7. Pressure test kit Pressure testing
8. Tongs Compressing flang-
es when installing
bolts on steel fit-
tings
9. Auxiliary tool Fitted prior to instal-
lation to facilitate
mounting taper
locks
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
5.4.2.2
Sealing strip
Removing insula-
tion from main
pipe
Removing foam
Installing branch fittings
45 branch fitting
4
4
0
4
4
0
m
m
4
4
0
m
m
Sealing strip is used to seal joint and outer
casing.
Sealing strip is available in coils with two
strips on each.
The sealing strip is on paper, enabling
removal of 1 strip at a time.
The sealing strip should always be cut with a
pair of scissors.
To avoid stretching the sealing strip, espe-
cially at high temperatures, it is recommend-
ed always to keep it on the paper, until it is
applied to the joint.
If the sectional area is reduced, the sealing
will be less efficient.
Sealing strips which are deformed, pasted
together or dirty must be discarded.
1. Excavate or support the pipes, so that
there is room for the installation.
2. Mark the position of the branch on the
outer casing. It must be 440 mm.
3. Cut and remove the outer casing.
(See section 1.3 cutting and adapting pipes).
4. Remove the insulation from the cut area.
5. Carefully remove all foam remnants, espe-
cially in the welding area.
It is very important that the hard film which
the foam leaves on the steel pipe is removed
very carefully.
Pipe dimensions < 139.7 are cleaned longi-
tudinally. Major dimensions are cleaned trans-
versely.
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.2.3
Adjusting branch
pipe piece
Installing branch fittings
45 branch fitting
6. The straight part of the branch pipe piece
is shortened by drawing two marks:
L on the inside of the bend, plus actual
insulation thickness, T (and possibly
add x for adjustment to the main pipe).
d is the outside diameter of the branch
pipe piece.
D is measured on the branch pipe
piece of the muff. This compensates for
reducing rings which may be used.
X
T
L
d
M
a
x
.
3
1
5
D
L
R
x
T
L
d
D
20
R 40
L mm
25
R 50
L mm
28
R 56
L mm
26.9
R 54
L mm
33.7
R 67
L mm
42.4
R 85
L mm
48.3
R 97
L mm
60.3
R 121
L mm
76.1
R 95
L mm
88.9
R 114
L mm
114.3
R 152
L mm
139.7
R 190
L mm
168.3
R 229
L mm
77 190 195 195
90 190 195 195 195 195
110 195 195 195 200 200 200 200
125 225 225 225 225 230
140 225 225 230 220
160 235 225 225
180 245 245
200 275 275 275
225 300 300
250 315 315 315
Welding on
branch
440 mm
400 mm
220 mm
45
7. Weld the branch pipe piece on to the
branch pipe at an angle of 45.
(See section 5.4.0, Reinforcement plates for
branch fittings).
Each dimension of 45 branch pipe pieces is delivered long enough to fit all three insulation
series.
They are shortened prior to insulation according to below instructions, which are enclosed with
the parts delivered on the jobsite.
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
5.4.2.4
Sealing strip,
main pipe
Sealing strip,
branch tee cou-
pling
Sealing strip,
branch pipe
Installing branch fittings
45 branch fitting
30 mm
30 mm
50 mm
30 mm
30 mm
8. Apply sealing strip, still on the paper, to
the cleaned, dry and ground outer casing
ends, allowing a slight overlap.
Remove the paper.
9. Apply sealing strip (on paper) with 50 mm
extra length at each end to the flange of
the lower part of the branch tee coupling
and to the branch outlet edges.
Remove the paper.
10. Press the lower part in position up
against the outer casing.
Push the sealing strip against the outer
casing where the branch tee coupling
and the pipe overlap.
11. Mate the upper part with the lower part.
12. Fit the taper locks loosely so the branch
tee coupling is still movable when the
branch bend is installed.
13. Place sealing strip (on paper) around the
branch outlet and the outer casing of the
branch pipe, allowing a slight overlap.
Remove the paper.
Branch angle
15 15
The branch pipe may deviate up to 15 from
right angle.
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.2.5
Tightening
Pressure testing
Insulation
Installing branch fittings
45 branch fitting
0,2 bar
16. Mate the upper part of the branch bend
with the lower part and fit bolts and nuts
into the holes next to the branch tee
coupling.
17. Finger-tighten the nuts crosswise on the
branch bend. Drive the taper locks into
position. Tighten the bolts. See the label
of the branch bend.
18. Check that all four taper locks have
been driven fully home so there is elec-
trical connection between the taper
locks and the branch bend.
19. Install a zinc anode on the end bolt of
the branch bend.
Before insulation the branch bend is pres-
sure tested with air.
It is recommended always to do so.
Insulate the joint immediately after installa-
tion or the same day at the latest in order to
eliminate moisture e.g. rain or condensate.
Insulate the joint and insert dual plugs in the
venting part of the filling holes.
Possibly use hammer.
See section 7.0 Insulating joints.
Sealing strip,
branch bend
50 mm
14. Apply sealing strip along the flange on
the inner side of the bolt holes on the
lower part of the branch bend.
15. Press the lower part up against the outer
casing and outlet.
Push the sealing strip against the outer
casing where the outer casing and outlet
overlap.
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
Requirements to
the joint area
Room, see section 1.2 Excavation, installation.
Preparations for joint installation, see section 5.1.
5.4.3.1
Application
Installing branch fittings
90 branch fitting
90 branch fittings are used when branching
from outer casing dimensions 90-315 mm.
Max. branch dimension: 250 mm.
1 2 3 4
5
6
7
8
9
Tools When installing 90 branch fittings use the
following tools:
Type: Application:
1. Scissors Sealing strip
2. Hammer (1.5 kg) Taper locks and
plugs
3. Saw Outer casing
4. Scraper Foam remnants
5. Ratchet spanner Tightening bolts
and bolt retainer
(17 mm)
(Alternatively an electric bolt spanner may
be used)
6. Fixing tool Dual plugs
7. Pressure test kit Pressure testing
8. Tongs Compressing flang-
es when installing
bolts on steel fit-
tings
9. Auxiliary tool Fitted prior to instal-
lation to facilitate
mounting taper
locks
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.3.2
Sealing strip
Removing insula-
tion from main
pipe
Removing foam
Installing branch fittings
90 branch fitting
4
4
0
4
4
0
m
m
4
4
0
m
m
Sealing strip is used to seal joint and outer
casing.
Sealing strip is available in coils with two
strips on each.
The sealing strip is on paper, enabling
removal of 1 strip at a time.
The sealing strip should always be cut with a
pair of scissors.
To avoid stretching the sealing strip, espe-
cially at high temperatures, it is recommend-
ed always to keep it on the paper, until it is
applied to the joint.
If the sectional area is reduced, the sealing
will be less efficient.
Sealing strips which are deformed, pasted
together or dirty must be discarded.
1. Excavate or support the pipes, so that
there is room for the installation.
2. Mark the position of the branch on the
outer casing. It must be 440 mm.
3. Cut and remove the outer casing.
(See section 1.3 cutting and adapting pipes).
4. Remove the insulation from the cut area.
5. Carefully remove all foam remnants, espe-
cially in the welding area.
It is very important that the hard film which
the foam leaves on the steel pipe is removed
very carefully.
Pipe dimensions < 139.7 are cleaned longi-
tudinally. Major dimensions are cleaned trans-
versely.
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
5.4.3.3
Adjusting branch
pipe piece
Installing branch fittings
90 branch fitting
2
2
0
m
m
A
6. Adjust the branch pipe piece to the steel
pipe dimension of the main pipe.
7. Mark the branch pipe piece on the basis
of the A-measurements in the instructions
or the table and cut the branch pipe piece
in this length.
- d is the outside diameter of the branch
pipe piece.
- D is measured on the branch pipe
piece of the joint. This compensates for
reducing rings which may be used.
d
D
20
R 40
A mm
25
R 50
A mm
28
R 56
A mm
26.9
R 29
A mm
33.7
R 38
A mm
42.4
R 48
A mm
48.3
R 57
A mm
60.3
R 76
A mm
76.1
R 95
A mm
88.9
R 114
A mm
114.3
R 152
A mm
139.7
R 190
A mm
168.3
R 229
A mm
77 50 50 50
90 50 50 50 115 110
110 60 60 60 125 120 110 100
125 140 130 120 110 90
140 150 140 120 100
160 140 120 100
180 140 115
200 150 130 90
225 100 60
250 130 90 50
The straight branch pipe pieces are delivered long enough to fit all three insulation series.
They are shortened prior to insulation according to below instructions, which are enclosed with
the parts delivered on the jobsite.
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.3.4
Installing branch
tee coupling
Installing branch fittings
90 branch fitting
50 mm
30 mm
30 mm
30 mm
10. Apply sealing strip, still on the paper, to
the cleaned, dry and ground outer casing
ends, allowing a slight overlap.
Remove the paper.
11. Apply sealing strip, still on the paper, to
all flanges of the inner part of the branch
tee coupling.
Remove the paper.
Always add 50 mm at the ends to be
folded back as shown.
12. Press the inner part in position up
against the outer casing.
Push the sealing strip against outer cas-
ing where the branch tee coupling and
the pipe overlap.
13. Mate the outer part with the inner part.
14. Fit the taper locks loosely so the branch
tee coupling is still movable when the
branch bend is installed.
Welding on
branch
1
2
3
8. First weld a 90 weld elbow, 1.5 x D, on
to the branch pipe and then to the branch
pipe piece.
9. Then weld the branch on to the main pipe.
(See section 5.4.0, Reinforcement plates at
branch fittings).
Branch angles
1 15 15
2
Branch pipe perpendicular to the main pipe
(1) can deviate up to 15 from right angle.
In connection with expansion absorption a
parallel installation is applied (2).
See Design manual.
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
5.4.3.5
Pressure testing
Installing branch fittings
90 branch fitting
0,2 bar
Before insulation pressure test the joint with
air.
It is recommended always to do so.
15. Place sealing strip (on paper) around the
branch outlet and the outer casing of the
branch pipe, allowing a slight overlap.
16. Apply sealing strip (on paper) to the
flanges of the branch bend.
Add 50 mm to the ends to be folded
back.
Do not forget possible internal hook, see
below.
17. Place the bend in position and finger-
tighten it, so joint and bend fit together.
18. Finger-tighten the nuts crosswise on the
branch bend. Drive the taper locks into
position. Tighten the bolts. See the label
of the branch bend.
19. Check that all four taper locks have been
driven fully home so there is electrical
connection between the taper locks and
the branch bend.
20. Install a zinc anode on the end bolt of the
branch bend.
Installing branch
bend
Installing internal
retainer
Branch bends in dimensions 180 - 250
mm are supplied with an internal hook on
one of the halves.
The hook prevents the internal pressure in
the joint during foaming from pushing of the
bend. Fasten the hook to the retainer in the
joint.
Do not tighten too hard, just enough to keep
the hook in place during foaming.
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
Insulation Insulate the joint immediately after installa-
tion or the same day at the latest in order to
eliminate moisture e.g. rain or condensate.
Insulate the joint and insert the venting part
of the dual plugs in the filling holes.
Possibly use hammer.
See section 7.0 Insulating joints.
5.4.3.6
Installing branch fittings
90 branch fitting
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
5.4.4.1
Application
Requirements to
joint area
Installing branch fittings
Branch saddle
Branch saddles make it possible to make a
branch from 90-315 mm anywhere on a
pipeline with outer casing dimension 355-
780 mm.
Room, see section 1.2 Excavation, installation.
Preparations for joint installation, see section 5.1.
1 2 3
4 5 6
7
8
Tools When installing branch saddle use the follow-
ing tools:
Type: Application:
1. Scissors Sealing strip
2. Hammer (1.5 kg) Taper locks and
plugs
3. Jig saw Outer casing
4. Scraper Foam remnants
5. Ratchet spanner Tightening bolts
and bolt retainer
(17 mm)
(Alternatively an electric bolt spanner may
be used)
6. Fixing tool Dual plugs
7. Pressure test kit Pressure testing
8. Tongs Compressing flang-
es when installing
bolts on steel fit-
tings
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.4.2
Sealing strip
Mark where to
remove insula-
tion
Installing branch fittings
Branch saddle
d
L
R
45
d
R
L
90
A
A
A
X
T
L
Each branch pipe piece is delivered long enough to fit all three insulation series.
They are shortened prior to insulation in accordance with below instructions.
Shorten the straight part by marking two measurements:
- L on the inside of the bend
- T for the actual insulation thickness of the main pipe
(Possibly with the addition of x for adjustment of the main pipe)
d, mm
20
R125
L mm
25
R125
L mm
28
R160
L mm
26.9
R140
L mm
33.7
R140
L mm
42.4
R140
L mm
48.3
R140
L mm
60.3
R150
L mm
76.1
R190
L mm
45 310 310 320 300 295 295 290 390 385
90 275 275 300 250 245 240 235 310 315
Installation equip-
ment
Control of the
welding process
Use a LOGSTOR trailer containing generator,
compressor, welding machine, straps and all
necesssary tools for the installation work.
Carry out the welding process with a compu-
ter controlled welding machine which auto-
matically controls the welding and checks
that the welding temperature and the pres-
sure between the welding surfaces are cor-
rect.
(See also section 5.4.0., Reinforcement plates at branch fittings).
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.7.3
Installing branch fittings
Band joint branch
Fitters The installation is carried out by certified fitters who have been specially educated and trained
at LOGSTOR. An education and training which are kept up by follow-up courses at least every
second year.
Installation
instructions
The certified fitters must use the authorized installation equipment and follow the instructions
in the Trailer Manual, which can be ordered at LOGSTOR.
Other branch
band joints
Perpendicular band joint branch for venting/
draining or as a reference point for the sur-
veillance system
Main pipe, 125-800 mm
Branch, 110-225 mm
Straight band joint branch (Twin - Twin).
Main pipe (outer casing):
125 - 630 mm
Branch (outer casing):
90 - 225 mm
Straight branch with branch band joint
(Twin - single pipe):
Main pipe (outer casing):
125 - 630 mm
Branch (outer casing):
77 - 110 mm
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
5.4.8.1
Application
Installation
instructions
Installing branch fittings
Prefabricated branch
Use preinsulated T-pieces when the branch
fittings systems cannot be used for dimen-
sional limiting reasons.
Especially in connection with under-crossing
branch pipes they are advantageous to use
as there is no foaming problem.
Weld prefabricated branches like normal pre-
fabricated pieces of pipe.
They are always delivered with 3 embed-
ded alarm wires. The middle wire, i.e. the
tinned one, has connection to the connecting
branch.
The two through-going wires are blank
copper wires.
Regarding connection of alarm wires, see the
alarm drawing.
LOGSTOR A/S Tel. +45 99 66 10 00 Handling and Installation 2009.10
5.4.9.1
Application
Branch with
outer casing
dimensions 90-
140 mm
Branch with
outer casing
dimensions >
140 mm
Installing branch fittings
Branching from concrete duct
750
M
1-2 min.
1. Make a hole in the concrete wall of
approx. 750 mm where the branch will be
established.
Prior to installation, the duct is extended.
See section 4.4 Design, Branching from
concrete duct and section 10.1 Installing
sealing ring as well as 10.3 Installing end-
cap.
2. Pull the shrink sleeve and branch adaptor
in over the branch pipe.
3. Adjust the height and length of the two
branch pipes.
4. Shrink end-caps on. See section 10.3.1
Installation of end-cap
5. Weld the branch on to the main pipe
6. Pull the branch adaptor into position flush
with the concrete wall.
It is very important to pay attention to the
temperature conditions and the position
of anchors to ensure that the branch can
expand.
7. Pull the shrink sleeve over the end of the
branch adaptor and shrink the sleeve.
Wait 1-2 minutes before shrinking on the
outer casing.
Now the installation is complete and the con-
crete wall can be repaired.
When branches are made with pipes from a concrete duct, a branch adaptor is used to
ensure a watertight entry into the duct and to allow the main pipe to expand with the branch.
Handling and Installation 2009.10 LOGSTOR A/S Tel. +45 99 66 10 00
5.4.9.2
Branching with
FlexPipe
Installing branch fittings
Branching from concrete duct
1. Pull the shrink sleeve and the branch
adaptor in over the branch pipe.
2. Adjust the 90 bend (200 x 300 mm) to
fit horizontally and vertically in the installa-
tion. Cut the bend at right angles using a
hacksaw with small saw teeth.
3. Weld the adjusted bend and the welding
stub together.
4. Weld the bend pipe on to the reduction
piece. See section 12 FlexPipes.
5. Shrink the end-cap on the FlexPipe end.
(See section 10.3 Installing end-cap).
6. Shrink the shrink tubing around the
reduction piece and the free end of the
FlexPipe.
7. Pull the shrink tubing on to the FlexPipe,
while it is still warm.
8. Weld the branch on to the main pipe.
9. Pull the branch adaptor in position flush
with the concrete wall.
It is very important to pay attention to the
temperature conditions and the position of
the anchors to ensure that the branch can
expand.
10. Pull the shrink sleeve in over the branch
adaptor end and shrink the sleeve.
Wait 1-2 minutes before shrinking the outer
casing.
The installation is now complete and the
concrete wall can be repaired.
1-2 min.