0 valutazioniIl 0% ha trovato utile questo documento (0 voti)
22 visualizzazioni6 pagine
Polymer insulators generally show superior insulation performance under contaminated and wetted conditions due to hydrophobicity on their Urtace. Presently the same design criteria for ceramic insulators are mostly adopted by considering the hydrophilicity as safety margin.
Polymer insulators generally show superior insulation performance under contaminated and wetted conditions due to hydrophobicity on their Urtace. Presently the same design criteria for ceramic insulators are mostly adopted by considering the hydrophilicity as safety margin.
Polymer insulators generally show superior insulation performance under contaminated and wetted conditions due to hydrophobicity on their Urtace. Presently the same design criteria for ceramic insulators are mostly adopted by considering the hydrophilicity as safety margin.
R. Matsuoka, Fellow, IEEE, K .Naito, Lije Fellow, IEEE, T. Irk, Senior Member, IEEE and K. Kondo, Member, IEEE Abstract- Although polymer insulators generally show superior inaulation performance under contaminated and wetted conditions due to hydrophobicity on their ~Urtace. Owmg to shortage o f their field experience, anti-amtamination design criteria are not yet established. Presently the same design criteria for ceramic insulators are mostly adopted by considering the hydrophobicity as safety margin. In order to establish rationalized insulation design criteria for polymer insulator^. we made fundamental investigation. We found out (1) Roughly t wo times heavier contaminant deposit on hydrophobic polymer insulators than pornlain under slow deposit conditions, while such Merencss become smaller under rapid depoait conditione like typhoon. (2) In spite of smaller leakage cumnta on hydmphohic polymer in~uhtcm, a stiff power 8ource ia stiU necessary for evaluating their contamination hshover voltages. (3) Contamination flashover voltages of hydmphohic polymer ineulat~m should be evaluated under heavy wetting conditions. Combined t est s under heavy f os and rain conditions may be good candidates for evaluating polymer insulators. Index Te- Accumulation 01 Contaminants, Contamination Flashover, Evaluation Methods, Plasbover Voltage, Hydrophobicity, Leakage Current, Polymer Insulston, Power Source, Silicone Rubber, Wetting Conditions 1. INTRODUCTION Polymer insulators generally show superior insulation performance under contaminated and wetted conditions compared with conventional ceramic insulators like porcelain or glass insulators. Such superior Derformance is fundamentallv owing to hydrophobicity on In order to establish rationalized design and maintenance criteria for such insulators, we have conducted fundamental investugation works and some results are shown here. 11. ACCUMULATION OF CONTAMINANTS Contamination flashover voltage of a hydrophobic polymer insulator is also similarly influenced by contamination degree with the case of porcelain insulators, that is, almost proportional to -115 power of SDD(Salt Deposit Density)[ I]. Heavier deposit of contaminants on hydrophobic polymer insulators compared with ceramic insulators has been measured at various sites 12) - C41 . Recently we have also made comparative measurement on porcelain and polymer insulators at the site 50m from seacoast located in the suburbs of Osaka[site A]. Results are shown in Tables 1 and 2. Such heavier deposit of contaminants is partly attributable to oily surface conditions. Once contaminants deposit on such oily surface, they are not easily removed by wind or rain due to adhesive nature of their surface. Under rapid contamination conditions like typhoon, Table 1 ESDD Ratio of Polymer to Porcelain Maximum I 7.44 I 8.17 I 4.79 1 8.17 Minimum I 0.81 1 0.93 I 0.67 I 0.67 Measurement period: March 1998 to January 2002. ESDD measured on 3 month exposed insulators. - . . their surface. Hydrophobicity, is, however, Sometimes 10s Table2 ESDD Measurement Results under Rai d Contamination by surface discharge or heavy wetting, and recovered with time by the diffusion of low molecular weight silicone onto the surface from the bulk of silicone rubber. Polymer insulators are made of organic materials and so ageing change of surface conditions is not avoidable. In addition, polymer insulators are quite new comers, and so field experience on contamination performance of these insulators is limited. Contamination tlashover/withstand voltage test methods of these insulators in laboratory are not yet established. R. Metsuoka ie with Chubu University 1200 Matsumato-do. Kesugai. K Naito la with Meija University, 1-601 Shiogamaguchi, Tempaku-ku. T. Iris iE \ntb NOK Imulatori, Lld I I 5 5 Tag-, Fulaebm', Komaki. 185-8566. K. Kondo e; \ntb NGK In~ulDtors. Lid. I 155 Tag-, Ful kboi , Komaki. 485-8566, Aiehi,487.8501. Japan (e-mail:mst4uo~se.chubu.aedp) Nagoya 468-8502 Japan (wmsil: kmit&%mfs.meijwu.ae.jp). 1ap.n (e-mail:ir*lak@n&k.~.jp) lopsn(s-mul: kavbk@gkOojp) Conditions 0-7803-7525-4/02/$17.00 0 2002 IEEE. 2197 oily substances are washed off by heavy rain and/or strong wind, and so difference in contamination degree between porcelain and polymer insulators becomes smaller. So, depending on the critical contamination conditions in a given site, rapid or slow accumulation of contaminants, a pertinent correction factor for the design contamination degree of polymer insulators at a given site against the reference contamination degree measured on conventional porcelain insulators must he selected for rationalized design of hydrophobic polymer insulators. Influence of insulator diameter on deposit of contaminants on polymer insulatoi surface was investigated under rapid contamination conditions at sites A and B. Site B i s located near seacoast in Okinawa island. Results are shown in Fig.1. Reduction in ESDD can be found with the increase of average diametei also in the case of polymer insulators 1.2 r I 2 3 4" Pal per Lang-md Regressi on c u we / o f porcel ai n i nsul at ors 12615W"' 7 350- 980- 126150 12 600 1680 166170 9 450 1602 166170 7 350 1246 9 9 0.2 - 1 5 6" 7 Porcelain standard Disc 166, 136137.5 430 1648 166, 126135 365 I445 615 (LonglShon) 515 (LonglShon) 2541- (146) 280 - 0 1 0 200 400 600 800 Average diameter. D. rnm Fig. 1 Influence of Average Diameter of Insulator on Contamination Degree under Rapid Contamination Conditions 111. EFFECT OF POWER SOURCE ON WITHSTAND VOLTAGE In the case of porcelain/ glass insulators, heavy leakage currents flow along the surface of specimen insulators in contamination flashover/ withstand voltage tests especially just before flashover, and so stiff power source is specified for such evaluation tests[fi]. In the case of hydrophobic polymer insulators, however, relatively smaller magnitudes of leakage currents have been measured both in fields and in laboratories. So, it is expected that stiff power source may not be necessary for flashover/withstand voltage tests of contaminated hydrophobic polymer insulators. Weexamined the effect of stiffness of power source on contamination flashover voltages of hydrophobic polymer insulators using a stiff and a weak power sources. A. Test Method Comparative flashover voltage tests were conducted hy using the two power sources shown in Table 3. Dimensional particulars of specimen insulators are shown in Table 4. Table 3 AC Power Sources for Insulator Contamination Tests I Power SauneA I PowerSourceB ( I hour) (Continuous) rnmary ( 1 hour) (Ihour) YO Impedance : 7.0% Rated Voltage : 70kVl26.3kV RatedCapaciiy : I40kVA %Impedance : 2.03% ( 1 hour) Table 4 Dimensional Particulars of Specimen Insulators Speeimen Shed Dial Effective Length NO. I Shedpitch I No'ofSheds [ (ConneetionLength) [ wgeDirtance Shed Shape Specimen Insulators I 2198 Tests were conducted according to the clean fog method specified in IEC Pub. 507 except for modified fog density and special pretreatment for uniform contamination layer on hydrophobic insulator surface based on our investigation results [I]. Heavier fog such as 13-15 g/m' gives much lower flashover voltages to hydrophobic polymer insulators compared with the case of thin fog conditions used for ceramic insulators. Special pre-treatment was conducted in order to get uniform and continuous contaminant layer on hydrophobic insulators simulating actual contaminant deposit conditions in fields. Time variations of fog density in both chambers for conventional thin and special dense fogs are shown inFig. 2. In case of polymer insulators, however, discernible differences cannot be found in the flashover voltage between the two power sources under the contamination conditions of 0.03 and 0.12 mp/ cm2 while significant difference can be recognized between the two power sources under heavy Contamination conditions of 0.5 mg/ cm2. 1.6 q 1.4 0 5 1.2 m .. h 1.0 1 0.8 B 0 0 10 20 30 M 50 60 0 1 0 2 0 3 0 1 0 y 1 6 0 Tim b e . min Tim Lapse. min ( i 1 Chamber A (ii) Chamber B Fig. 2 Time Variation of Fog Density B. Test Results Some typical leakage current and applied voltage wave forms at the time of flashover by Power Source A are shown in Fig. 3. In this test facility, in order to minimize the voltage drop of power supply system, protecting resistor of 25 or 50 kn was inserted between testing transformer and specimen. So short circuit current was limited to around 1 A. In the case of porcelain insulators, leakage current increases gradually to flashover while polymer insulators flash over in shorter periods after start of increase of leakage current especially in the case of light contamination conditions. Comparative 50% flashover voltages obtained by Power Source A referenced to the corresponding flashover voltages obtained by Power Source B are shown in Fig. 4. As expected, higher flashover voltages were obtained by weak Power Source A in case of porcelain insulators irrespective of contamination degrees. 02 0 Fig.4 Comparative 50% Flashover Voltage by Two Power Sources IV. CONTAMINATION TEST METHODS In case of artificial contamination tests of ceramic insulators, artificial fog is specified for wetting the contaminated insulators in solid layer methods since it gives lowest flashover/ withstand voltages. In case of hydrophobic polymer insulators, however, heavy wetting conditions such as heavier fog than conventional fog used for ceramic insulators or rain, give lower flashover/ withstand voltages [SI 171. In order to find out the severest wetting conditions giving the lowest flashover voltages for hydrophobic polymer insulators, we investigated the effect of rain conditions on flashover voltages of polymer insulators. A. Test Methoak Based on the investigation results explained in the former section, we installed a new power source stiff enough for contamination tests [ 8] [ 9] . ( i Pomelain/SDD : 0.07mg/cm2 (U) Polymer/SDD 0.03 mg/cmz (id Polymer/SDD 0.6 mg/cm2 Leakage Current and Applied Voltage at the Time of Flashover Fig.3 2199 wetting[5]. Wetting was supplied by simulated rain. Precipitation and size of water droplets were varied by air pressure, water flow rate, distance from nozzles to specimen, etc. A test voltage was applied to the contaminated and dried specimen, and simulated rain was precipitated over the specimen for 15 min. to see flashover or withstand. Test duration of 15 min. was determined by the measurement results of surface resistance as an example is shown in Fig. 5. Dimensional particulars of specimen insulators used for this investigation are shown in Table 5. 0 5 IO 15 20 25 30 Time Lapse. min (SDD: O.Smg/crn*) Fig.5 Time Variation of Surface Resistance i Specimen HTV Silicone Rubber Insulators Shed Shape, rnm 50 Straighr Sheds Allemale Sheds No. of Sheds 12 Large USmall7 Effective Length/ Leakage Distance. 600/1680 470/16W B. Tesl Resulfs Some examples of leakage current and applied voltage waveforms at the time of flashovers are shown in Fig. 6. Flashovers occurred very rapidly after starting of increase of leakage current. Flashover voltage ratios obtained under simulated rain conditions referenced to the corresponding flashover voltage of the same specimen insulator tested under heavy fog conditions are summarized in Fig. 7. There are variations in the results, but some tendencies can be seen. 0.12, 0.5 /O.l SDD/NSDD, Precipitatim, Size of Large: 1.8-3.0 Water Dmpleu, Medium : 0.7-1.5 I I Small : 0.25-0.95 mm In the case of vertical installation, lower flashover voltages were obtained on very heavily contaminated insulators with the SDD of 0.5 mgf cm', while higher flashover voltages were obtained on insulators contaminated with the SDD of 0.12 mp/ cm2 . Under simulated rain conditions, bridging by water drippings behueen the adjacent shed tips was observed as some examples are shown in Fig. 8. Any discernible differences were not obtained in the flashover voltage among the different precipitation and the different sizes o f water droplets within the ranges investigated. In the care of horizontal installation, we estimated much higher flashover voltages under simulated rain conditions compared with the case of heavy fog conditions due to water dripping from individual shed tips without any bridging between the shed tips. Surprisingly, flashover voltages were almost same with those under heavy fog conditions in'the case of very heavily contaminated conditions with SDD of 0.5 mp/ cm'. ( i ) SDD:O.Smg/cmz (Applied V01tage:'iOkV) ( ii )SDD:O.lZmg/cm2 (Applied Vo1tage:SOkV) Fig. 6 Leakage Current and Applied Voltage at the Time of Flashover 2200 Such lower flashover voltages are attributable to the water streams flowing down along individual sheds as illustrated in Fig. 9. Again much higher ratios were obtained on the Such explained by the saturation of salt soluble into the water film deposited on the surface of specimen insulators under heavy fog conditions. Enough quantity of water is, however, supplied under simulated rain conditions even with the SDD of 0.5 mg/cm2. Relationship between SDD and flashover voltage may beexplained qualitatively by two curves shown in Fig. IO. insulators contaminated with SDD of 0.12 mg/ cm2. different ratios between 0.12 and 0.5 mg/ cm may be 2 2 ri I , I 0.03 0.12 0.5 SDD. mgIcm2 Fig. 10 Contamination F.O.V. Characteristics 140 of A Polymer Insulator V. CONCLUSIONS Based on our investigation results, the followings should he taken into consideration at the time of evaluation and design of polymer insulators (I) Heavier contaminant deposit should be considered on hydrophobic polymer insulators compared with conventional ceramic insulators. (2) A stiff power source should be used for evaluation of contamination flashover/withstand voltages of hydrophobic polymer insulators, especially under heavily contaminated conditions, in spite of smaller leakage currents measured both in fields and laboratories. (3) Contamination flashovedwithstand voltages of hydrophobic polymer insulators should be evaluated Fig. 7 Comparative Flashover Voltages under heavy wetting conditions. Both heavy fog and simulated rain tests mav be eood candidates for standard I - contamination flashoveriwithsland voltage test methods for hydrophobic polymer insulators. VI. REFERENCES Il l K. Naito, K. Immi, K. T h u and R. Malsuoka, Performance of Comwsite lnsulalom under Polluted Conditions. ClGRE Session f i )Strai ght Sheds f i i 1 Alternate Sheds PapeiNo. 33-301, 1996. H.l rnapawa R. Matsuoka S. 110. K. SAanishi. K. Kondo. N. Okada 121 ., ~ ~~ . ~ . and T. Yonezawa, Comparative Contaminatio Degrees on Porcelain and Siliwne Rubber Insulators in Fields, ClGRE SC33 Colloquium, Paper No. 33- 43, Toronto, September IW7. Y. Hi&whimori, 2. Nakao, S. Nishimura, J . X. Zhu, 2. Iha, T. Tmaki, I. Kat. R. Kimata T. Mugushima and T. Kohayashi, Studies on Salt Conrnminalian and Leakage Current of Silicone Rubber InsuIafors, ICE. pp.744-748, Beijing, China, 1996. K. Kondo, M. Ishiwari, S. Ito, I. Irie, Y. Suzuki and K. Amkawa. Pollution Performance of Polymer Insulaon under The Marine Conditions in Japan. ISH-2001. Paper No. 5-19, Bangalore, India, August 2001. IEC Pub. 507. * Artificial Pollution Tests on High-Voltape lrrsulamn lo beUsed on A. C. Systems, 1991. A. de l a 0 and R. S . Gorur. Flashover of Conlaminated Nonceramic Outdoor lnsulator~ in A Wet Alrnosphcre, IEEE Trans. On DEI, Vol . 5, No. 6, December 1998. M. Ishiwirri. S. 110, K. Arakawa, T. Nakachi and K. Kondo. Various Altificial Contamination Withstand Voltsge Test Methods and A Fig. 8 Dripping of Water at the Tips of Sheds (Precipitation: 4mmlmin) [3] 141 (51 16) [7] q? ( i )Vertical Installation ( li 1 Horizontal lnatallation Fig. 9 Flashover Paths in Simulated Rain Tests 2201 Comparison of Their Results on Polymer and Porcelain Insulalops, paper presented at the I IISH, London, A U~USI 1%. [SI N. 0- K. Ikeda, S. Sumi, R Matsuaka K. Kondo and S. Ito, Contamination Withstand Voltage Chamcleristics of Hydrophobic Polymer Insulators under Simulated Rain Conditions, Paper to be presented at lSEl inBoston, April 2002. K. Ikeda, N. Okada, S. Sumi, R. Mauuoka, K. Takemato, T. Ito, T. Ono and Y. Komiya A New Power Source for Insulator Contamination Tests, h. of the Twelfth Annual Conference of Power & Energy Society, IEE of Japan, Vol. B. P a p No. 493, 2001 ( In Japanex ). [ 9] VII. BIOGRAPHIES Rymuke Mabuoks (SMW- F96) was born inGifu Prefecture, J a m in 1941.He received the BS, MS and the Ph.D. degrees, dl in Elsuical Engineering fmm the Nagoya University in 1964, 1966 and 1994, respectively. He joined NGK Insulators, Ltd. in 1966. He served as General Manager of NGK High VoltageLaboratory. He w e d also as manager of Insulate(. Engineering, in h k c Insulators Inc. fmm 1981 to 1986. He retired NGK and joined Chubu University as a full-time pmfessor in 1598. Pmf. Mauuoha is a Member of CERE and IEE of J apan, Katsuhiko N d o (M66SM8C-FW) was born i n Aichi Prefenm, J apan, in 1934.He received the EIS, MS and the Ph.D. de- al l in Electrical Engineering fmm the Nagoya University in 1958, 1%0 and 1976 respectively. He joined NGK Insulators, Ltd. in 1964. He served as General Manager of Design Deparunent, Gend Manager of NGK, High Voltage Laboratory, and later as Executive Chief Engineer of Power Business Group of the Company. He joined Nagoyalnstiate afTechnalogy in 1991 BS a full-time Professor. In 1998, he &red fmm Nagoya Institute of Technology and joined Meijo University as a full-tim Fmfessor. Prof. Naito is a Member o f CIGRE and B Fellow of IEEE of U.S.A. He is a Member of Insulator and Lightning Arrester Subsomminee of IEEE. Takarbl l ri r (SM91) was born in Tottori Prefecture, Japan. in 1944. He received the BSc. and Ph.D. de- both in elenrical engineering from YokohamaNational University in 1968 and 1995, respectively. In 1968 he joined NGK Insulators, Lid. He is now the General Manager of NGK High Voltage Labamtory, Power Buincss Gmup. His fields of interest include insulator contamination, lightning arrester and insulation smength of large air W. Kunhki Kondo ( MY8) WBS barn in Aichi Prefechue, Japan in 1967. He received the B. Sc., M. Sc., and Ph. D. d e p s in electrical engineering fmmNagoya lnstitutc of Technology in IWO, IW2 and 1997. respectively. In 1992 hejoined NGK Insulators, Lld. He has been engaged in rereareh of insulator commination. He is now a Supervisor of NGK High Voltage I.aboratory, Power Business Gmup. 2202