AERCO Gas-Fired Heaters and Hydronic Boilers

Design Choices and Design Tips




Physical Layout
Look at position and access relative to other equipment and piping.
Consider positioning heater to minimize length of flue vent.
Ensure separation from source of chlorine or corrosive chemicals.
Check wall, overhead and service clearance.
See boiler application guide for minimum space requirement. For ease of maintenance, use more than the minimum clearance between units.
Install external regulator at least 3 ft. upstream of heater.
Review gas regulator specification to see if horizontal installation is required.
Do not block access to heater with gas pipe, air duct, or wiring.

Flue Gas Venting
Choose side wall or vertical discharge.
Specify Heat-Fab AL 29-4C vent pipe which will give extended service life.
Slope horizontal vent pipe down toward boiler/heater for condensate drainage.
Consider effect of condensation at vent exit. Do not locate vent discharge over walkways, windows, or paved areas, if possible
Insulate vent pipe up to about 7 ft. height for personnel protection.
Insulate flue piping through walls & floors, or specify recommended clearances.
Multiple units:
Vent individually, if possible.
Allow 3 ft. center to center spacing for roof or wall vents.
If common vent header is required, contact C. J . Michelson Company for recommendations.
CAD drawings of vent pipe system are available when Heat-Fab is specified.

Flue Gas Condensate
Use polypropylene tubing to an appropriate drain. Clear tubing will show condition of condensate.

Combustion Air Ducting
Choose sealed combustion or wall louvers. Consider:
Additional fuel savings with sealed combustion.
Need to isolate gas-fired heating equipment from refrigerant gases, or bear cost of refrigerant sensor/burner shutdown device.
Building aesthetics.
For sealed combustion, specify inlet air adapter for each unit.

Water Piping
Contractor must thoroughly flush system before start-up.

Gas pressure
For new gas service, install the meter as closely as possible to appliances to minimize user piping costs.
Learn range from user or gas company.
Gas pressure to inlet side of AERCO supplied external gas regulator must be no greater than 14" W. C. with standard Maxitrol regulator, or
up to 10 psi with optional regulators. A minimum of 11" W. C. gas pressure to the regulator at maximum firing rate is required for
proper operation.
Note that the Maxitrol RV-81 regulator can be mounted only in the horizontal position.
Vent each regulator individually as required. Regulator vent line sizes vary by model.
Specify only AERCO approved regulators. Contact us for selection assistance for gas pressures above 14" W. C.
Engineering specifications and drawings should indicate the design gas pressure to the AERCO supplied external regulator.

Pressure Relief Valves
Available ratings: 30, 50, 75, 100, 150 psig

Ohio Power Piping Code:
If over 30 psig, a fee plus 2% of project cost is payable to State of Ohio for inspection.

Boiler Nameplate Data
If 30 psig boiler, AERCO will stamp boiler "Boiler designed for 30 psig, and tested to 150 psig".

Interface of Boilers with Building Automation System
Decide whether the BAS will simply enable the AERCO boilers or whether a 4-20 ma signal will be sent from the BAS to provide either a
supply header setpoint temperature for the boilers or a firing percentage for each Aerco boiler.
AERCO is BACnet compatible with RS-485 twisted pair communications (Master Slave / Token Passing). Drivers must be written for BAS.

Control Wiring
Specify which contractor will install wiring from Outside Air Temperature sensors(s), Building Management System, fault sensor, power
level output, etc.

Variable Speed Pumps
A low flow limit should be programmed for the variable speed pumping system, based on minimum boiler flow times number of boilers.

Multiple Boilers
Use AERCO Boiler Management System for 3 or more boilers to obtain maximum efficiency and minimum cycling.
Use individual outdoor sensors and standard controls for indoor/outdoor reset on 2 boilers or less. Consult C. J . Michelson Company for
discussion of operation.

Multiple Domestic Water Heaters - Sequencing
Use differential set points to eliminate short cycling on low load. As an example, set one heater to operate with 124 F setpoint. and second
heater with 120 F setpoint.

If differential setpoint approach results in the temperature swing being too wide, then use customized control system. Contact C. J . Michelson
Company for information.

AERCO Technical References

Benchmark
GF-2030 Gas Components and Supply Design Guide BMK-2.0 (9/98)
GF-2050 Venting and Combustion Air Guide BMK-2.0 (9/00)
GF-2060 Electrical Power Wiring Guide BMK-2.0 (9/98)
GF-2070 Boiler Application Guide BMK-2.0 (9/98)
KC-1000
GF-1030 Gas Components and Supply Design Guide (12/90)
GF-1050 Venting and Combustion Air Guide (5/94)
GF-1060 Electrical Power Wiring Guide (2/90)
GF-1070 Boiler Application Guide (2/91)
GF-1080 Commercial Laundry Sizing Guide (8/92)
(Date in parentheses is printing date as of September 2000)

Please contact C. J . Michelson Company if you need a current version of any bulletin.


2000 C.J . Michelson Company, Inc. All Rights Reserved.
20575 Center Ridge Road, Suite 110 Cleveland, OH 44116 Ph (440) 331-7181 Fax (440) 331-7108
www.cjmichelson.cominfo@cjmichelson.com
F
l
u
e

T
e
m
p
e
r
a
t
u
r
e
A
t

A
p
p
l
i
a
n
c
e

O
u
l
e
t
T
y
p
i
c
a
l

O
u
t
s
i
d
e

S
k
i
n

T
e
m
p
e
r
a
t
u
r
e
S
a
f
-
T

V
e
n
t

C
I

a
n
d

S
a
f
-
T

V
e
n
t

C
I

P
l
u
s
6


D
i
a
m
e
t
e
r

a
t

4

H
o
u
r

C
o
n
t
i
n
u
o
u
s

O
p
e
r
a
t
i
o
n
w
w
w
.
h
e
a
t
-
f
a
b
.
c
o
m

8
0
0
.
7
7
2
.
0
7
3
9
O
u
t
s
i
d
e

S
k
i
n

T
e
m
p
e
r
a
t
u
r
e
a
t

7
2


V
e
r
t
i
c
a
l
O
u
t
s
i
d
e

S
k
i
n

T
e
m
p
e
r
a
t
u
r
e
a
t

9
6


V
e
r
t
i
c
a
l
O
u
t
s
i
d
e

S
k
i
n

T
e
m
p
e
r
a
t
u
r
e
a
t

6
0


V
e
r
t
i
c
a
l
O
u
t
s
i
d
e

S
k
i
n

T
e
m
p
e
r
a
t
u
r
e
a
t

2
4


V
e
r
t
i
c
a
lO
u
t
s
i
d
e

S
k
i
n

T
e
m
p
e
r
a
t
u
r
e
F
r
o
m

9
6


V
e
r
t
i
c
a
l
T
o

6
0


H
o
r
i
z
o
n
t
a
l
O
u
t
s
i
d
e

S
k
i
n

T
e
m
p
e
r
a
t
u
r
e
F
r
o
m

9
6


V
e
r
t
i
c
a
l
T
o

1
2
0


H
o
r
i
z
o
n
t
a
l
F
l
o
w
P
u
b

#

1
1
7
3
2


0
2
1
1
0
5
L
o
c
a
t
i
o
n







L
o
c
a
t
i
o
n






L
o
c
a
t
i
o
n






L
o
c
a
t
i
o
n






L
o
c
a
t
i
o
n






L
o
c
a
t
i
o
n









S
a
f
-
T

V
e
n
t

C
I
3
0
0

F

/

1
4
9

C
7
5

F

/

2
4

C
1
7
0

F

/

7
7

C
1
3
7

F

/

5
8

C
1
4
3

F

/

6
2

C
1
4
8

F

/

6
4

C
1
4
6

F

/

6
3

C
1
3
4

F

/

5
7

C
S
a
f
-
T

V
e
n
t

C
I
3
8
0

F

/

1
9
3

C
7
5

F

/

2
4

C
2
1
2

F

/

1
0
0

C
1
6
8

F

/

7
6

C
1
7
1

F

/

7
7

C
1
7
7

F

/

8
1

C
1
7
3

F

/

7
8

C
1
6
2

F

/

7
2

C
S
a
f
-
T

V
e
n
t

C
I
4
2
0

F

/

2
1
6

C
7
5

F

/

2
4

C
2
2
5

F

/

1
0
7

C
1
7
6

F

/

8
0

C
1
7
6

F

/

8
0

C
1
9
0

F

/

8
8

C
1
7
9

F

/

8
2

C
1
6
9

F

/

7
6

C
S
a
f
-
T

V
e
n
t

C
I

P
l
u
s
3
0
0

F

/

1
4
9

C
7
5

F

/

2
4

C
1
0
0

F

/

3
8

C
1
1
0

F

/

4
3

C
1
2
0

F

/

4
9

C
1
3
5

F

/

5
7

C
1
4
2

F

/

6
1

C
1
3
2

F

/

5
6

C
S
a
f
-
T

V
e
n
t

C
I

P
l
u
s
3
8
0

F

/

1
9
3

C
7
5

F

/

2
4

C
1
3
2

F

/

5
6

C
1
2
4

F

/

5
1

C
1
2
9

F

/

5
8

C
1
4
9

F

/

6
5

C
1
6
4

F

/

7
3

C
1
5
1

F

/

6
6

C
S
a
f
-
T

V
e
n
t

C
I

P
l
u
s
4
2
0

F

/

2
1
6

C
7
5

F

/

2
4

C
1
3
8

F

/

5
9

C
1
3
8

F

/

5
9

C
1
2
6

F

/

5
2

C
1
5
7

F

/

6
9

C
1
7
0

F

/

7
7

C
1
6
1

F

/

7
2

C
9
6
"

V
e
r
t
i
c
a
l

&



1
2
0
"

H
o
r
i
z
o
n
t
a
l
6
0
"

V
e
r
t
i
c
a
l
7
2
"

V
e
r
t
i
c
a
l
9
6
"

V
e
r
t
i
c
a
l
9
6
"

V
e
r
t
i
c
a
l

&

6
0
"

H
o
r
i
z
o
n
t
a
l



M
o
d
e
l

D
o
u
b
l
e

W
a
l
l






6
"

D
i
a
m
e
t
e
r
A
p
p
l
i
a
n
c
e

O
u
t
l
e
t

F
l
u
e

T
e
m
p
e
r
a
t
u
r
e
R
o
o
m

A
m
b
i
e
n
t

T
e
m
p
e
r
a
t
u
r
e
2
4
"

V
e
r
t
i
c
a
l
C
A
B
D
E
F
Heatfab, Div. Selkirk Corp.
Product Specifications subject to change without Notice.
All Rights Reserved.
AL 29-4C is a registered trademark of ATI Properties, Inc..
www.heatfab.com 130 Industrial Blvd., Turners Falls, MA 01376
Pub #11462-030810
The Saf-T Vent

CI Plus is an air-insulated double-wall


product designed for commercial applications. It is
approved for use on individual or common vented ANSI
Category I, II, III and IV Gas Burning Appliances, Direct
Vent and for Gas and Oil fired appliances listed for
Type L-Vent applications as approved by the appliance
manufacturer.
The Saf-T Vent CI Plus factory-built Special Gas Vent
system is Tested and Listed by Underwriters
Laboratories to UL 1738/ULC S636 for used with Listed
natural gas or propane burning equipment that produce
continuous flue-gas temperatures not above 550 F.
Also Tested and Listed by Underwriters Laboratories
to UL 641/ULC S609 for use with Listed oil and gas
burning equipment that are suitable for venting with
TypeL vent which produce continuous flue-gas
temperatures not above 570 F. The system is to be
installed and sealed per manufacturers instructions
so all joints are gas tight, preventing leakage of products
of combustion into a building.
The Saf-T Vent CI Plus system is a double-wall product
that consists of a flue-gas conduit fabricated from AL
29-4C

stainless steel, which is highly suited for use


with high-efficiency gas burning equipment, which
produce excessive amounts of condensation in the vent.
The outer jacket of the system is constructed of type
430 stainless steel with a space of approximately 1
between the flue-gas conduit and the jacket.
Note: CI Plus is also available with 1 of insulation in
the annular space.
All joints in the Saf-T Vent CI Plus system are fastened
with a closure system that combines the features of
Heatfabs tapered ends with a mechanical closure
system which consists of tabs and a locking band.
The locking band is tightened from a single location
using a simple hand tool, pulling the two pieces together
making a pressure tight assembly. When installed on
positive pressure or condensing applications, the joints
must be sealed. Diameters 4 through 16 are
manufactured with a factory adhered seal. Diameters
18 through 32 must use an approved sealant on the
job site. This closure system is tested to be gas tight
at two and one-half times the Listed pressure rating of
15 water column.
When properly installed the Saf-T Vent Plus system
may safely and securely be utilized in either interior or
exterior installations. The system is capable of
withstanding reasonable wind and incidental loads as
required by UL standards.
When connected to gas-burning appliances with a
maximum continuous flue-gas temperature of 550 F,
4 through 24 diameter Saf-T Vent CI Plus can be fully
enclosed vertically by combustible materials at 1 or
greater clearance and 2632 diameter by 2 or greater
clearance. For Oil fired Type L-Vent with a maximum
flue-gas temperature of 570, 4 through 8 diameter a
fully enclosed system requires 3 clearance. For
horizontal applications refer to the Clearance Chart
(publication #11724).
The Saf-T Vent CI Plus system is to be sized in
accordance wi th appl i ance manufacturers
specifications, the most current edition of NFPA 211
Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel-Burning Appliances, the most current edition of
NFPA 54 National Fuel Gas Code (ANSI Z223.1),
ASHRAE recommendations, and all applicable local
and regional codes. This proper sizing, based on
information supplied by the consumer, is reflected in
scale drawings of the system provided by Heatfab.
The Saf-T Vent CI Plus system is to be installed only
in accordance with Heatfabs, Installation and
Maintenance Instructions and with all applicable
local, regional, and national codes.
*U.S. Patent No. 6,702,338
Saf-T Vent

CI Plus Specifications for Double Wall Special Gas Vent Applications


TECHNICAL SPECIFICATION
Product Saf-T Vent CI Plus Special Gas Vent
Uses Chimneys and Vents (Horizontal or
Vertical) for ANSI Category I, II, III,
and IV Gas BurningAppliances.
Fuels Natural gas or propane fired equipment
Oi fired low temperature appliances.
Pressure Positive up to 15 wc, negative, or neutral
Standard
Diameters 4-32
Flue-Gas
Conduit AL 29-4C

stainless steel
Jacket 430 stainless steel
Insulation Air Space 1
Available with insulated annular space
Seal Factory adhered seal (4-16)
RTV Sealant ( 18-32)
Saf-T Vent CI Plus
Clearances to Combustibles
For Category I,II,II,IV,
Gas Fired Appliances
And For Gas or Oil Fired Appliances
Listed For L-Vent Venting Systems
The allowed clearances may differ by the appliance manufacturer. The appliance manufacturers
instructions and applicable local codes take precedence over this document.
Combustible Material is defined as material made of or surfaced with wood, compressed paper,
plant fibers, or other materials that are capable of being ignited or burned. Such material shall
be considered combustible even though it is flame-proofed, fire-retardant treated, or plastered.
(Source: NFPA 54/ANSI Z223.1-1999)
Noncombustible Material is defined as material that is not capable of being ignited and burned,
such material consisting entirely of, or of a combination of, steel, iron, brick, tile, concrete,
slate, glass, and plaster. (Source: NFPA 54/ANSI Z223.1-1999.)
www.heatfab.com eng@heat-fab.com
Pub # 11724-120208 413.863.2242 800.772.0739 fax 413.863.4803
130 Industrial Boulevard Turners Falls MA 01376
DIAMETER
CLEARANCE TO
COMBUSTIBLE
MATERIAL
MAXIMUM FLUE
GAS TEMP. (F) ORIENTATION ENCLOSURE
4 - 24" 1"
26" - 32" 2"
4" - 32" Not Allowed 550 Horizontal
Fully enclosed
by combustible
material on
all sides
4" - 8" 1"
9" - 12" 2"
14" 3"
16" - 20" 4"
22" - 24" 5"
26" - 32" 6"
4 - 32" 0 550 Any
Noncombustible
material
Enclosed on a
maximum of 2
sides (ceiling &
sidewall)
Horizontal 550
550 Vertical
Fully enclosed
by combustible
material on
all sides
Gas: Special Gas Vent
Oil: Type L-Vent
4- 8" CI Plus 3" 570 Any Enclosed
4- 32" CI Plus &
ICI Plus
3" 570 Any Un-Enclosed
4"- 24" ICI Plus 3" 570 Any Enclosed
Saf-T Vent CI Plus
Pitched Roof
Tall Cone Flashing
With Rain Cap
Installation Instructions
Directly On Pitched Roof. Prepare a square or round opening per the framing chart. Apply weather-
stripping or outdoor caulk to the bottom of the cone plate. Attach the cone to the roof using common
construction methods. Flash over the cone plate and seal the fastener heads using normal roofing
requirements. When the vent pipe is in place through the Tall Cone, attach the Tall Cone storm collar
around the pipe. Apply RTV sealant around the top of the storm collar and the pipe. On the last section
of pipe before the Rain Cap, install the Ventilation Collar, ordered separately, over the air space between
the inner and outer vent pipes. Install the Rain Cap on the last section of vent per the Rain Cap
installation instructions. Position the Rain Cap Storm Collar 2" above the Ventilation Collar as shown in
the figure below.
PI-CCTCFP 102904 www.heat-fab.com 800.772.0739
CONE PART
NUMBER
VENT
DIAM A
DIAM B
CCM05TCFP 5 9.5
CCM06TCFP 6 10.5
CCM07TCFP 7 11.5
CCM08TCFP 8 12.5
CCM09TCFP 9 13.5
CCM10TCFP 10 14.5
CCM12TCFP 12 16.5
CCM14TCFP 14 18.5
CCM16TCFP 16 20.5
CCM18TCFP 18 22.5
CCM20TCFP 20 24.5
CCM22TCFP 22 26.5
CCM24TCFP 24 28.5
CCM26TCFP 26 30.5
CCM28TCFP 28 32.5
CCM30TCFP 30 34.5
CCM32TCFP 32 36.5
ROOF OPENING FRAMING
DIMENSIONS
COMBUSTIBLE
CHASE
1" CLEARANCE
"B"
SQUARE
2/12
THRU
6/12
PITCH
ROOF
"A"
VENTILATION
COLLAR
(SOLD SEPARATEL
TALL
STORM
COLLAR
APPLY
SEALANT
2"
VENTILATION
SPACE
STORM
COLLAR
APPLY
SEALANT
RAIN
CAP
PITCHED ROOF
TALL CONE
FLASHING
Roof Jack
Apply
Sealant
Roof Structure
Curb Frame
Install the storm collar, supplied with the Roof Jack, around the vent pipe that passes through the Roof Jack.
Tighten the storm collar using the screw clamp. The collar should be sitting on top of the Roof Jack to prevent
the vent pipe from slipping downward (figures 1A and 2A).
Flash over the Roof Jack utilizing normal roofing contractor methods. Flashing materials are not supplied
with the Roof Jack.
Roof Jack
Installation Instructions
for Saf-T Vent CI,
CI Plus, EZ Seal and GC
The Roof Jack Support System is used for all vertical terminations through combustible and non-combustible
roof structures. The Roof Jack supports all wind loading and incidental contact with the flue system as well as
providing vertical support for up to 30 ft of venting (see chart).
Drill or hand punch screw or nail holes around the perimeter of the Roof Jack plate. Apply weather resistant
caulk to the bottom of the Roof Jack plate, gusset side down (fig. 1). Center the Roof Jack over the hole and
secure to the roof deck or curb using screws or roofing nails with neoprene washers.
Prepare the penetration location for the Roof Jack Support System on a flat roof by drilling a small hole up
through the roof at the desired location. Refer to the framing chart dimension B, and figure 1. Cut a square
hole and remove any existing roofing materials to clear the roofjack. If any roof joists must be cut in order to
locate the vent, follow local and national building codes for reframing the opening. If using a raised roof curb
refer to the framing chart, dimension C and figure 2. Roof curbs can be purchased at most building supply
companys and come in many pitches and roof configurations.
Figure 1A Figure 2A
Storm Collar
Storm Collar
Apply Sealant
Apply Sealant
Apply Roof Flashing
Apply Roof Flashing
Figure 2
Roof Jack
Roof Structure
Apply
Sealant
Figure 1
Apply weather resistant sealant around the storm collar to prevent rainwater from entering the Roof Jack.
If the vent pipe protrudes more than 6 feet above the roof, guy sections must be used above and below the
Roof Jack for stabilization. Refer to the Saf-T Vent Guy installation instructions (PI-CIGUY) if necessary.
www.heat-fab.com 800.772.0739 PI-CIRJK 041503
Framing Chart For Saf-T Vent CI, GC and EZ Seal Roof Jacks
Framing Chart For Saf-T Vent CI Plus Roof Jacks
CURB SIZE
FIG. 2
SUPPORT
DISTANCE
VENT DIAM OPENING CURB O.D. VENT HEIGHT
DIM A DIM B DIM C
HEIGHT IN
FEET
CCL06RJ 6 14 X 14 24 30
CCL08RJ 8 16 X 16 24 30
CCL10RJ 10 18 X 18 24 30
CCL12RJ 12 20 X 20 24 30
CCL14RJ 14 22 X 22 27 20
CCL16RJ 16 24 X 24 30 20
CCL18RJ 18 26 X 26 32 15
CCL20RJ 20 28 X 28 34 15
CCL22RJ 22 30 X 30 36 10
CCL24RJ 24 32 X 32 36 10
CCA26RJ 26 34 X 34 36 6
CCL28RJ 28 36 X 36 40 6
CCL30RJ 30 38 X 38 42 6
CCL32RJ 32 40 X 40 44 6
ROOF OPENING
FRAMING DIMS. FIG. 1
PART #
CURB SIZE
FIG. 2
SUPPORT
DISTANCE
VENT DIAM OPENING CURB O.D. VENT HEIGHT
DIM A DIM B DIM C
HEIGHT IN
FEET
5380CI 3 9 X 9 18 30
5480CI 4 10 X 10 18 30
5580CI 5 11 X 11 18 30
5680CI 6 12 X 12 24 30
5780CI 7 13 X 13 24 30
5880CI 8 14 X14 24 30
5980CI 9 15 X 15 24 30
51080CI 10 16 X 16 24 30
51280CI 12 18 X 18 24 30
51480CI 14 20 X 20 24 20
51680CI 16 22 X 22 27 20
51880CI 18 24 X 24 30 15
52080CI 20 26 X 26 32 15
52280CI 22 28 X 28 34 10
52480CI 24 30 X 30 36 10
52680CI 26 32 X 32 36 6
52880CI 28 36 X 36 40 6
53080CI 30 36 X 36 40 6
53280CI 32 38 X 38 42 6
ROOF OPENING
FRAMING DIMS. FIG. 1
PART #
Saf-T Vent CI Plus
Tall Cone Flashing
With Rain Cap
Installation Instructions
APPLICATION 1. Directly On Flat Roof. Prepare a square or round opening 4 1/2" larger than the
inner vent pipe diameter, i.e. an 8" inner vent would have a 12 1/2" opening. Apply weather-stripping or
outdoor caulk to the bottom of the cone plate. Attach the cone to the roof using common construction
methods. Flash over the cone plate and seal the fastener heads using normal roofing requirements.
When the vent pipe is in place through the Tall Cone, attach the Tall Cone storm collar around the pipe
and position at least 2" above the top edge of the cone (figure 1). This 2" air space will release any built
up heat from inside the cone. Apply RTV sealant around the top of the storm collar and the pipe. On the
last section of pipe before the Rain Cap, install the Ventilation Collar over the air space between the
inner and outer vent pipes. Install the Rain Cap on the last section of vent per the Rain Cap installation
instructions. Position the Rain Cap Storm Collar 2" above the Ventilation Collar as shown in Figures 1
& 3. When the Tall Cone is used as a vertical support (figure 1 & 2) screw the self-tapping screws
through the holes in the cone and into the wall of the Outer Vent.
Figure 1
Figure 2
CAUTION: Support screws can only be installed with Saf-T Vent CI Plus venting.
PI-CCTCF 102904
www.heat-fab.com 800.772.0739
APPLICATION 2. On Top Of Roof Curb (figure 3). Before installing, place the cone on top of the curb
and mark the outline of the curb on the bottom of the cone plate. Use snips to notch out the corners of
the plate to match the curb. Bend down the extra material with duckbill pliers to create a cap which fits
over the curb. Attach the cone to the curb using the same methods as described in Application 1.
ROOF OPENING
FRAMING DIMENSIONS
FIGURE 2
Figure 3
CONE
PART
NUMBER
INNER
VENT
DIAM A
OUTER
OPENING
DIM B
SPACING BETWEEN
VERTICAL
SUPPORTS (FIG 2)
CCM05TCF 5 9.5 20
CCM06TCF 6 10.5 20
CCM07TCF 7 11.5 20
CCM08TCF 8 12.5 20
CCM09TCF 9 13.5 20
CCM10TCF 10 14.5 20
CCM12TCF 12 16.5 20
CCM14TCF 14 18.5 12
CCM16TCF 16 20.5 12
CCM18TCF 18 22.5 12
CCM20TCF 20 24.5 10
CCM22TCF 22 26.5 10
CCM24TCF 24 28.5 10
CCM26TCF 26 30.5 6
CCM28TCF 28 32.5 6
CCM30TCF 30 34.5 6
CCM32TCF 32 36.5 6
ROOF OPENING FRAMING DIMENSIONS (FIG 1 & 2)
The Saf-T Vent CI Plus system can be installed through any type of wall using the Saf-T Vent CI Plus
Wall Termination Assembly. The wall termination requires mechanical support from the wall sufficient
to support any incidental loads on the system. If the wall is not sufficient to support the termination
assembly, then appropriate additional framing and/or blocking is required.
Installation Procedure
The Wall Termination Assembly is packed with the screen
cover and end collar (Figure 1). Before beginning, remove this
screen cover. Prepare an opening for the Wall Termination
Assembly in the wall. The opening must be 7 inches larger than
the Inner Vent pipe diameter. The opening may be either round
or square so long as allowance for proper clearance to
combustible material is made. When passing through solid,
noncombustible construction, clearances may be reduced if
necessary. If there are not sufficient support members to
secure the Wall Termination Assembly or if there is a semi-rigid
foam insulation layer under the sheathing, the opening must be
blocked out or framed to provide support.
Position the Wall Termination Assembly into the enlarged hole from the outside (Figure 2). Secure the
assembly using common construction methods. Seal under the screw heads with caulking. The
assembly may be painted to match the exterior decor.
Saf-T Vent CI Plus
Wall Termination
Installation Instructions
Figure 2
FLOW
FLOW
Figure 1
www.heatfab.com 800.772.0739 PI-CCWL 110607
Figure 3
Figure 4
Finished Assembly
FLOW
FLOW
Proceed with the installation of Saf-T Vent CI Plus sections
and terminate it through the Wall Termination Assembly
(Figure 3). Install the End Collar on the last section to
close off the 1" air space around the inner vent. Seal
between the vent and the End Collar for weather conditions.
The assembly is constructed to allow for 2 degrees (1/4"
per foot) of pitch in the vent sections. Seal the gap between
the vent and the end plate of the Assembly using silicone
caulk suitable for extended exposure to the elements.
The vent section must protrude at least 2 inches into the
screened area beyond the end plate of the Wall Termination
Assembly (Figure 4). Attach the screen cover using the
stainless screws. Align the hole in the top (solid) portion of
the screen cover with the top of the assembly and securely
screw the two together. The screen cover may be easily
removed for inspection of the venting system.
FLOW
PI-VSPINS 082208

Application Information
The Support Plate is used to provide support for vertically
installed vent. The Support Plate can be installed at the base
of the stack or at various other locations throughout the stack
when additional vertical support is required.

To Install:
1. Refer to Table 1 for Minimum Vertical Spacing
between Supports. Note: A Wall Band is required at
10 intervals to provide lateral support for the vent (See Fig. 2).
2. Determine the appropriate location for mounting the Support Plate. The Support Plate should be
mounted to solid framing members (by others) capable of supporting the weight of the vent.
3. Secure the Support Plate to the framing members by installing the appropriate fastener through
the pilot hole in the plate and into the framing members (See Figs. 1 & 2).
4. Once the plate is securely mounted, connect additional vent sections to the Support Plate by
using the standard joint attachment method.




Support Plate (CI-Plus, GC & EZ Seal)
Installation Instruction Supplement

Part Inner
Number Vent Dia. (in.) EZ & GC CI-Plus
CCA04VSP 4 300 150
CCA05VSP 5 300 150
CCA06VSP 6 300 150
CCA07VSP 7 300 150
CCA08VSP 8 200 100
CCA09VSP 9 200 100
CCA10VSP 10 200 75
CCA12VSP 12 200 75
CCA14VSP 14 100 75
CCA16VSP 16 100 50
CCA18VSP 18 100 50
CCA20VSP 20 100 50
CCA22VSP 22 100 30
CCA24VSP 24 50 30
CCA26VSP 26 50 30
CCA28VSP 28 50 20
CCA30VSP 30 50 20
CCA34VSP 32 50 20
Vert. Spacing (Ft.)
Table 1. Total Height for Support Plate
Plate supports may be used in these different applications:
Note: Framework and support lines are by others
CCA04VSP 4 8
CCA05VSP 5 9
CCA06VSP 6 10
CCA07VSP 7 11
CCA08VSP 8 12
CCA09VSP 9 13
CCA10VSP 10 14
CCA12VSP 12 16
CCA14VSP 14 18
CCA16VSP 16 20
CCA18VSP 18 22
CCA20VSP 20 24
CCA22VSP 22 26
CCA24VSP 24 28
CCA26VSP 26 30
CCA28VSP 28 32
CCA30VSP 30 34
CCA32VSP 32 36
PART NO. DIM. A
VENT
DIM. B
PLATE
"B"
"B"
1.0
1.0
0.50
"A"
4.50"
INSTALLED
1/8"
THICK
304ss
Figure 2: Support
Stack Inside A Chase
Figure 1: Support
Stack Along A Wall
Figure 3: Support
Stack Below A Floor
Figure 4: Support
Stack Above A Floor
Saf-T Vent CI Plus
Vent Support With Plate
Saf-T Vent

CI Plus
Technical and Dimensional Data
130 Industrial Boulevard
Turners Falls, MA 01376-1607
Call (800) 772-0739
Fax (413) 863-4803
www.heat-fab.com
Copyright 2006 Selkirk Corp.
Saf-T Vent is a registered trademark of Selkirk Corp.
AL 29-4C is a registered trademark of ATI Properties, Inc.
UL and the UL Mark are registered trademarks of
Underwriters Laboritories, Inc.
Pub # 11720 120308
Double Wall
AL 29-4C

Stainless Steel
Special Gas Vent and Type L Vent
For Venting Commercial & Industrial Appliances
Condensing Appliances
Category I,II,III,IV Appliances
For Use on Positive, Neutral, and Negative Pressures up to 15" W.C.
Also For Venting Listed Gas or Oil Fired Appliances Listed as Suitable For Venting
With Type L Vent Low-Temperature Venting Systems
Sizes: 4"- 32" Diameters.
Tested and Listed to
UL 1738/ULC S636
by Underwriters Laboratories, Inc
Also Listed to UL 641, ULC/ORD-C441-M1990
and CAN-ULC-S609-M89
2
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Introduction
Accessories
Boot Tees &
Covers
Increasers
Reducer
Elbows
Straight Lengths
Supports &
Hangers
Terminations
Termination
Accessories
TABLE OF CONTENTS
CATEGORY PART DESCRIPTION PAGE
Introduction
Part Numbering System
Surface Temeratures
Material Thickness
RTV Sealant
Silicone Lubricant
Universal Boiler Adapter
Adapter, From / To Saf-T Vent CI Plus
Double Male Adapter
Flanged Adapter
Fire Stop
Condensate Drain Tube Kit
In-Line Damper Section
Vent Flow Regulator
In-Line Probe Section
In-Line Drain Section
Tee Cover with Drain Fitting
Tee Cover
Boot Tees
Boot Tees with Reducing Tap
Square Tee
Barometric Tee
Increaser
Reducer
15 Elbow
30 Elbow
45 Elbow
90 Elbow
Tight Radius 90 Elbow
6" Length, 9" Length
12" Length, 18" Length
24"' Length, 36" Length
Long Adjustable Length
Short adjustable Length
Guy Support Section
Floor Support
Vertical Support Plate
Vertical Support
Horizontal Support
Support Clamp
Roof Jack Support System
Tall Cone Flashing and Support
Pitched Tall Cone Flashing
Wall Termination/Penetration
Wall Penetration
Rain Cap
Screened Termination
Exit Cone
Finish Collar
Ventilation Collar
3
3
4
5
5
5
6
6
7
7
8
8
9
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
31
32
33
33
34
35
36
37
38
39
39
40
41
41
3
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Saf-T Vent CI Plus is an AL29-4C superferritic stainless steel conduit with a one-inch air space and a type
430 stainless steel outer jacket. It is ideal for close clearance installation within building chases.
Saf-T Vent CI Plus combines the tight fit of the tapered male and female expands with a patented* closure system
which consists of tabs and a locking strap. The locking strap provides a mechanical connection between the two
assembled sections. It also serves to pull together the two pieces, making a pressure-tight assembly. The locking
strap is tightened from a single location using a simple hand tool. This single-point fastening system allows one
installer to complete an assembly without rotating the sections or rotating himself around the sections.
The double-wall construction allows for an insulating blanket of 1" air space between the inner wall and the outer
wall. This air insulation has the advantage of keeping the flue gases warmer as well as making the skin temperature
of the outer wall cooler. The reduced skin temperature allows the product to be installed in closer proximity to
combustible materials. Refer to the installation instructions for Heat-fab's Saf-T Vent CI Plus system (PI-CCINS).
*Patent No. 6,702,338
Introduction:
Part Numbering System for CI Plus Saf-T Vent CI Plus parts are identified by the following numbering
system which describes the composition, use, diameter and length of each part.
1. The Product Code, or Model, is comprised of two letters. CC designates CI Plus, which has a one inch air
space insulation.
2. The Material Code is one letter and designates the type of steel or steel combination from which the part is
made. A stands for AL-29-4C inner/ 430SS outer. Other outer jacket materials are available; contact your Heat-fab
sales representative.
3. The Diameter of the inner vent is designated by two numbers, for example, a 6 inch diameter would be 06.
4. The Part shape description is 1 to 4 letters and are as follows: AD adapter, AJ adjustable, BT Boot Tee,
CV cover, DCV drain cover, E elbow, FC finish collar, FS firestop, GUY guy section, HZS horizontal support,
L for length, NCR for increaser, RC for raincap, RDC reducer, RJ roof jack, TCF tall cone flashing, TM for
termination, VTS vertical support, WP wall penetration.
5. The Qualifying description is 2 numbers and designates the length of a section, the angle of an elbow, or the
second diameter size as on increasers and reducers and boot tees with a different diameter tap. Examples are
12 for a 12" long section or 90 for a 90 degree elbow.
An example of a part number is CCA14E90, which would be a CI Plus, CC; made from AL29-4C inner and 430SS
outer, A; 14 inch diameter, 14; an elbow, E; 90 degree, 90.
Locking Strap
4
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Typical Outside Skin Temperature
Saf-T Vent CI and Saf-T Vent CI Plus
6 Diameter at 4 Hour Continuous Operation
Flue Temperature
At Appliance Oulet
Outside Skin Temperature
at 72 Vertical
Outside Skin Temperature
at 96 Vertical
Outside Skin Temperature
at 60 Vertical
Outside Skin Temperature
at 24 Vertical
Outside Skin Temperature
From 96 Vertical
To 60 Horizontal
Outside Skin Temperature
From 96 Vertical
To 120 Horizontal
8'
B
C
D E F
A
Flow
5
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Accessories:
RTV Sealant In order to have a UL Listed system, Saf-T Vent CI Plus parts without a factory adhered
sealed must be installed with one of the following approved RTV sealants:
Approximate Coverage
Note: In planning the RTV required for an installation, please be aware that certain fittings require additional RTV in
order to achieve a proper positive-pressure seal. The following types of parts should be counted as 2 joints toward the
RTV coverage table:
Boiler Starters Adjustable Sections Flue Collar Adapters Boot Tees
The table below shows the approximate number of installed joints that can be completed with a container of
RTV sealant. These figures are based on a bead of sealant. Actual coverage may vary.
Maximum Appliance
Flue Gas Temperature
Sealant Size
Heat-fab Part
Number
General Electric (GE) RTV 106 2.8 oz tube 7000RTV
or 10.1 oz cartridge 7000RTVL
Dow Corning 736
550 F.
*Diameters 4" thru 16" are manufactured with a factory adhered seal on the inside of the female end
and will not need sealant in the joint.
Approximate Number of Joints
Inner Vent
Diameter, Inches
3 oz Tube 10 oz Cartridge
18 4 14
20 4 13
22 3 12
24 3 11
26 3 10
28 3 9
30 2 9
32 2 8
Material Thickness:
Inner Vent
Diameter
Wall Thickness
Inner Vent
Wall Thickness
Outer Jacket
4 8 0.015 (28 ga)
9 16 0.020 (26 ga)
18 24 0.025 (24 ga)
24 32 0.035 (20 ga) 0.030 (22 ga)
0.024 (24 ga)
Use as an aid when assembling Saf-T Vent CI Plus double wall, Saf-T Vent EZ Seal single wall and
Saf-T Vent SC sealed combustion joints which have the silicone seal installed in the female end. Apply
a very thin film of silicone compound lubricant directly to gasket on inside of female end or to the
leading edge of outside surface on male end.
Silicone Lubricant:
6
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Accessories:
Universal Boiler Adapter Used horizontally or vertically to adapt Saf-T Vent CI Plus to nominal diameter flue
collars, it can also adapt to boiler collars that are slightly out of round. The adapter comes with a joint locking strap, boiler collar
clamp and a coupler band.
Part Number DIM - A DIM - B
Nominal Nominal Diameter
Inner Diameter Outer Jacket
CCA04ADUV 4 6.3
CCA05ADUV 5 7.3
CCA06ADUV 6 8.3
CCA07ADUV 7 9.3
CCA08ADUV 8 10.3
CCA09ADUV 9 11.3
CCA10ADUV 10 12.3
CCA12ADUV 12 14.3
CCA14ADUV 14 16.3
CCA16ADUV 16 18.3
CCA18ADUV 18 20.3
CCA20ADUV 20 22.3
CCA22ADUV 22 24.3
CCA24ADUV 24 26.3
CCA26ADUV 26 28.3
CCA28ADUV 28 30.3
CCA30ADUV 30 32.3
CCA32ADUV 32 34.3
B
A
4.0
FLOW
Universal
Boiler Adapter
Part Number DIM - A
Nominal Vent Diameter
CCA04ADSV 4
CCA05ADSV 5
CCA06ADSV 6
CCA07ADSV 7
CCA08ADSV 8
CCA09ADSV 9
CCA10ADSV 10
CCA12ADSV 12
CCA14ADSV 14
CCA16ADSV 16
Vent Adapter
To Saf-T Vent CI & EZ Seal
Adapter From CI Plus to EZ Seal / EZ Seal To CI Plus Used horizontally or vertically to adapt to
or from Saf-T Vent CI Plus nominal diameter to Saf-T Vent EZ Seal. The adapter consists of a joint locking strap with tabs for
connecting to the Saf-T Vent EZ Seal ring.
7
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


A
6"
3"
Accessories:
Part Number DIM - A
Diameter Installed Length
CCA04MM 4 3
CCA05MM 5 3
CCA06MM 6 3
CCA07MM 7 3
CCA08MM 8 3
CCA09MM 9 3
CCA10MM 10 3
CCA12MM 12 3
CCA14MM 14 3
CCA16MM 16 3
CCA18MM 18 3
CCA20MM 20 3
CCA22MM 22 3
CCA24MM 24 3
CCA26MM 26 3
CCA28MM 28 3
CCA30MM 30 3
CCA32MM 32 3
Double Male Adapter This adapter is to be used in conjugation with an universal adapter when attaching to an
in-line draft inducing fan that has a collar at the inlet.
Double Flange Adapter This adapter can be used to attach a flanged in-line damper or balancing baffle to
Saf-T Vent products. Adapter comes in two sections, a male and a female end connection.
Part Number DIM - A
Diameter Installed Length
CCA04PS 4 4.5
CCA05PS 5 4.5
CCA06PS 6 4.5
CCA07PS 7 4.5
CCA08PS 8 4.5
CCA09PS 9 4.5
CCA10PS 10 4.5
CCA12PS 12 4.5
CCA14PS 14 4.5
CCA16PS 16 4.5
CCA18PS 18 4.5
CCA20PS 20 4.5
CCA22PS 22 4.5
CCA24PS 24 4.5
CCA26PS 26 4.5
CCA28PS 28 4.5
CCA30PS 30 4.5
CCA32PS 32 4.5
6"
6"
A
8
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Part Number DIM - A Vent DIM - B DIM - C
Hole Outer Jacket Plate Plate
Diameter Diameter Length Width
CCS04FS 6.4 6.3 20 20
CCS05FS 7.4 7.3 20 20
CCS06FS 8.4 8.3 20 20
CCS07FS 9.4 9.3 26 26
CCS08FS 10.4 10.3 26 26
CCS09FS 11.4 11.3 26 26
CCS10FS 12.4 12.3 26 26
CCS12FS 14.4 14.3 26 26
CCS14FS 16.4 16.3 26 26
CCS16FS 18.4 18.3 26 26
CCS18FS 20.4 20.3 32 32
CCS20FS 22.4 22.3 32 32
CCS22FS 24.4 24.3 32 32
CCS24FS 26.4 26.3 32 32
CCS26FS 28.4 28.3 36 36
CCS28FS 30.4 30.3 36 36
CCS30FS 32.4 32.3 40 40
CCS32FS 34.4 34.3 40 40
Fire Stop A firestop may be required anytime Saf-T Vent CI Plus penetrates combustible floors, walls, or ceilings.
Remove any insulating material from the floor, wall or ceiling cavity for at least 1" around the vent for diameters 4" - 24" and
2" around the vent for diameters 26" - 32". Review fire codes and consult with local building code officials to determine the
necessity for a firestop. The stainless steel firestop may be trimmed provided the required clearances are maintained.
Fire Stop
Accessories:
A
B
C
Side View
Clearance Spacer
Condensate Drain Tube Kit This kit contains a length of high temperature silicone rubber tubing, a clamp,
and two cable ties. The silicone tubing is rated for 500F, and is translucent to allow inspection of the P-trap. Larger diameter
drains can be plumbed directly into a drain system.
Part Number: 7000TUBE 5 feet of 3/8 diameter tubing
7000TUBE-10 10 feet of 3/8 diameter tubing
7001TUBE 10 feet of 1/2 diameter tubing
9
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Accessories:
In-Line Damper Section Use to adjust the flow in positive pressure applications. Can also be used to restrict
back flow when the appliance is off. Each damper comes with an 18" long coupler, a locking strap, a rotating clamp, and a
motor platform. The shaft is 3/8" diameter.
10.5
INSTALLED
LENGTH
A
B
Part Number DIM - A DIM - B
Nominal Nominal Diameter
Inner Diameter Outer Jacket
CCA04DMP 4 6.3
CCA05DMP 5 7.3
CCA06DMP 6 8.3
CCA07DMP 7 9.3
CCA08DMP 8 10.3
CCA09DMP 9 11.3
CCA10DMP 10 12.3
CCA12DMP 12 14.3
CCA14DMP 14 16.3
CCA16DMP 16 18.3
CCA18DMP 18 20.3
Vent Flow Regulator Use only in conjuction with an in-line or termination fan to balance the flow of the exhaust
gases when inducing a draft.
Part Number DIM - A
Nominal
Inner Diameter
CCA04BG 4
CCA05BG 5
CCA06BG 6
CCA07BG 7
CCA08BG 8
CCA09BG 9
CCA10BG 10
CCA12BG 12
CCA14BG 14
A
4"
INSTALLED
LENGTH
Vent Flow Regulator
LOCKING
BOLT
SLIDE
PLATE
Side View Top View
10
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
B
A
4-1/2"
INSTALLED
LENGTH
In-Line Probe Section Use to attach probes to the vent system by means of a 1/4" NPT female fitting. Can be
used vertically or horizontally. Comes standard with a coupler made of 430 stainless steel with an outlet for the probe fitting,
a 1/4" NPT plug, a locking strap and a rotating clamp for directonal changes.
Part Number DIM - A DIM - B
Nominal Nominal Diameter
Inner Diameter Outer Jacket
CCA04PRB 4 6.3
CCA05PRB 5 7.3
CCA06PRB 6 8.3
CCA07PRB 7 9.3
CCA08PRB 8 10.3
CCA09PRB 9 11.3
CCA10PRB 10 12.3
CCA12PRB 12 14.3
CCA14PRB 14 16.3
CCA16PRB 16 18.3
CCA18PRB 18 20.3
CCA20PRB 20 22.3
CCA22PRB 22 24.3
CCA24PRB 24 26.3
CCA26PRB 26 28.3
CCA28PRB 28 30.3
CCA30PRB 30 32.3
CCA32PRB 32 34.3
1/4" NPT
COUPLER
Accessories:
11
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


A
C
D
B
Accessories:
Horizontal/Vertical In-Line Drain Section Use to drain away condensate from the vent system. The
unique design of this part allows it to be installed in a horizontal, vertical or inclined orientation. Continuous horizontal runs in
excess of 30 feet require a condensate drain. High temperature silicone tubing is available separately. The outer jacket consists
of an 12" long coupler made of 430 stainless steel with an outlet for the drain and also comes standard with a locking strap and
a rotating clamp.
Part Number DIM - A DIM - B DIM - C DIM - D
Nominal Diameter Nominal Diameter Installed Drain
Inner Diameter Outer Jacket Length Diameter OD
CCA04DRN 4 6.3 4.5 0.5
CCA05DRN 5 7.3 4.5 0.5
CCA06DRN 6 8.3 4.5 0.5
CCA07DRN 7 9.3 4.5 0.5
CCA08DRN 8 10.3 4.5 0.5
CCA09DRN 9 11.3 4.5 0.5
CCA10DRN 10 12.3 4.5 0.5
CCA12DRN 12 14.3 4.5 0.5
CCA14DRN 14 16.3 4.5 0.5
CCA16DRN 16 18.3 4.5 0.5
CCA18DRN 18 20.3 4.5 0.5
CCA20DRN 20 22.3 4.5 0.5
CCA22DRN 22 24.3 4.5 0.5
CCA24DRN 24 26.3 4.5 0.5
CCA26DRN 26 28.3 4.5 0.5
CCA28DRN 28 30.3 4.5 0.5
CCA30DRN 30 32.3 4.5 0.5
CCA32DRN 32 34.3 4.5 0.5
Coupler (included)
In-Line Drain Section
Drain Tube Kit (sold separately)
12
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Part Number DIM - A DIM - B DIM - C DIM - D
Nominal Diameter Nominal Diameter Height Drain
Inner Diameter Outer Jacket Diameter OD
CCA04DCV 4 6.3 1.62 0.375
CCA05DCV 5 7.3 1.62 0.375
CCA06DCV 6 8.3 1.62 0.375
CCA07DCV 7 9.3 1.62 0.375
CCA08DCV 8 10.3 1.62 0.375
CCA09DCV 9 11.3 1.62 0.5
CCA10DCV 10 12.3 1.62 0.5
CCA12DCV 12 14.3 1.62 0.5
CCA14DCV 14 16.3 1.62 0.5
CCA16DCV 16 18.3 1.62 0.5
CCA18DCV 18 20.3 1.62 0.5
CCA20DCV 20 22.3 1.62 .62
CCA22DCV 22 24.3 1.62 .62
CCA24DCV 24 26.3 1.62 .62
CCA26DCV 26 28.3 1.62 .75 female NPT
CCA28DCV 28 30.3 1.62 .75 female NPT
CCA30DCV 30 32.3 1.62 .75 female NPT
CCA32DCV 32 34.3 1.62 .75 female NPT
Tee Cover with Drain Fitting Use at the base of a Boot Tee to drain away condensate from a vent system.
High temperature silicone tubing is available separately. The drain cover comes standard with a locking strap and finish coupler.
Other drain options are available on larger diameters upon request, contact Heatfab's EngineeringTeam.
Drain Cover
Boot Tees & Covers:
D
C
A
13
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


C
B
A
Tee Cover Use to cap off the male end of a Boot Tee body that is installed horizontally. The tee cover / boot tee
combination allows for the future addition of appliances to a common-vent system. The cover comes with a locking strap and
a finish coupler that is made of the same 430 stainless steel as the outer jacket to give a finished look to the installation.
Part Number DIM - A DIM - B DIM - C
Nominal Nominal Diameter Height
Inner Diameter Outer Jacket
CCA04CV 4 6.3 1.62
CCA05CV 5 7.3 1.62
CCA06CV 6 8.3 1.62
CCA07CV 7 9.3 1.62
CCA08CV 8 10.3 1.62
CCA09CV 9 11.3 1.62
CCA10CV 10 12.3 1.62
CCA12CV 12 14.3 1.62
CCA14CV 14 16.3 1.62
CCA16CV 16 18.3 1.62
CCA18CV 18 20.3 1.62
CCA20CV 20 22.3 1.62
CCA22CV 22 24.3 1.62
CCA24CV 24 26.3 1.62
CCA26CV 26 28.3 1.62
CCA28CV 28 30.3 1.62
CCA30CV 30 32.3 1.62
CCA32CV 32 34.3 1.62
Boot Tees & Covers:
Cover
Coupler
Locking Band
14
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Boot Tee Use vertically or horizontally to add appliances into a common-vent system. When installed horizontally, the
male end of the tee body may be capped off with a tee cover to allow for future appliances. When used in conjunction with
a drain tee cover, the boot tee will effectively transition a vent system from a horizontal to a vertical orientation while allowing
for proper condensate drainage. The pressure drop through the tap for this fitting is equivalent to 15 feet of horizontal vent.
Both inlet connections rotate to accommodate direction changes. Each Boot Tee comes standard with a coupler, one joint
locking strap and two rotating clamps.
Boot Tees:
Part Number DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F DIM- G
Out In Tap Installed Centerline Installed Nominal Diameter
Nominal Diameters Length of Tap to from Tap to Outer Jacket
Vent Pipe Outlet Outlet Centerline
CCA04BT 4 4 4 16.5 11 12.5 6.3
CCA05BT 5 5 5 17.5 11.5 13 7.3
CCA06BT 6 6 6 18.5 12 13.5 8.3
CCA07BT 7 7 7 19.5 12.5 14 9.3
CCA08BT 8 8 8 20.5 13 14.5 10.3
CCA09BT 9 9 9 21.5 13.5 15 11.3
CCA10BT 10 10 10 22.5 14 15.5 12.3
CCA12BT 12 12 12 24.5 15 16.5 14.3
CCA14BT 14 14 14 26.5 16 17.5 16.3
CCA16BT 16 16 16 28.5 17 18.5 18.3
CCA18BT 18 18 18 30.5 18 19.5 20.3
CCA20BT 20 20 20 32.5 19 20.5 22.3
CCA22BT 22 22 22 34.5 20 21.5 24.3
CCA24BT 24 24 24 36.5 21 22.5 26.3
CCA26BT 26 26 26 38.5 22 23.5 28.3
CCA28BT 28 28 28 40.5 23 24.5 30.3
CCA30BT 30 30 30 42.5 24 25.5 32.3
CCA32BT 32 32 32 44.5 25 26.5 34.3
F
E
1.50
D
1.50
A
B
E
D
C
G
Boot Tee
15
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Boot Tees with Reducing Tap:
Boot Tee Use vertically or horizontally to add appliances into a common-vent system. When installed horizontally, the
male end of the tee body may be capped off with a tee cover to allow for future appliances. When used in conjunction with
a drain tee cover, the boot tee will effectively transition a vent system from a horizontal to a vertical orientation while allowing
for proper condensate drainage. The pressure drop through the tap for this fitting is equivalent to 15 feet of horizontal vent.
Both inlet connections rotate to accommodate direction changes. Each boot tee comes standard with a coupler,one joint
locking strap, and two rotating clamps. Other diameter configurations may be available. Please contact Heatfabs Engineering
Team to discuss your special needs.
Part Number DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F DIM- G
Out In Tap Installed Centerline Installed Nominal Diameter
Nominal Diameters Length of Tap to from Tap to Outer Jacket
Vent Pipe Outlet Outlet Centerline
CCA08BT06 8 8 6 18.5 12.0 14.5 10.3
CCA10BT06 10 10 6 18.5 12.0 15.5 12.3
CCA10BT08 10 10 8 20.5 13.0 15.5 12.3
CCA12BT06 12 12 6 18.5 12.0 16.5 14.3
CCA12BT08 12 12 8 20.5 13.0 16.5 14.3
CCA12BT10 12 12 10 22.5 14.0 16.5 14.3
CCA14BT06 14 14 6 18.5 12.0 17.5 16.3
CCA14BT08 14 14 8 20.5 13.0 17.5 16.3
CCA14BT10 14 14 10 22.5 14.0 17.5 16.3
CCA16BT14 16 16 14 26.5 16.0 18.5 18.3
CCA18BT16 18 18 16 28.5 17.0 19.5 20.3
CCA20BT18 20 20 18 30.5 18.0 20.5 22.3
CCA22BT10 22 22 10 22.5 14.0 21.5 24.3
CCA24BT12 24 24 12 24.5 15.0 22.5 26.3
D
B
1.50
A
E
D
F
1.50
G
C
Boot Tee
16
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Square Tees:
Square Tee Due to the significant pressure drop of this fitting, Heat-fab recommends it be used as an inspection
port only. Use vertically or horizontally to add appliances into a common-vent system. When installed horizontally, the male
end of the tee body may be capped off with a tee cover to allow for future appliances. When used in conjunction with a drain
tee cover, the square tee will effectively transition a vent system from a horizontal to a vertical orientation while allowing for
proper condensate drainage. The pressure drop through the tap for this fitting is equivalent to 45 feet of horizontal vent. Both
inlet connections rotate to accommodate direction changes. Each Square Tee comes standard with a coupler, one joint
locking strap, and two rotating clamps.
Part Number DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F
Nominal Installed Centerline of Tap ID Centerline to Nominal
Diameter Length Tap to Inlet Edge of Tap Diameter
Inner vent OuterJacket
CCA04ST 4 11.5 5 4 6 6.3
CCA05ST 5 12.5 5.5 5 7 7.3
CCA06ST 6 13.5 6 6 8.5 8.3
CCA07ST 7 14.5 6.5 7 9 9.3
CCA08ST 8 15.5 7 8 10 10.3
CCA09ST 9 16.5 7.5 9 11 11.3
CCA10ST 10 17.5 8 10 12 12.3
CCA12ST 12 19.5 9 12 14 14.3
CCA14ST 14 21.5 10 14 16 16.3
CCA16ST 16 23.5 11 16 18 18.3
CCA18ST 18 25.5 12 18 20 20.3
E
C
B
A
F
D
Square Tee
17
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Barometric Tees:
Barometric Tee Use to attach a standard barometric damper (supplied by others) to the vent system. Use only
if recommended by the appliance manufacturer and a qualified designer of vent systems. Each barometric tee comes
standard with a coupler and a joint locking strap.
Part Number DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F
Nominal Installed Centerline of Tap ID Centerline to Nominal
Diameter Length Tap to Inlet Edge of Tap Diameter
Inner vent OuterJacket
CCA04BAR 4 11.5 5.0 4 5 6.3
CCA05BAR 5 12.5 5.5 5 5 7.3
CCA06BAR 6 13.5 6.0 6 6 8.3
CCA07BAR 7 14.5 6.5 7 7 9.3
CCA08BAR 8 15.5 7.0 8 8 10.3
CCA09BAR 9 16.5 7.5 9 9 11.3
CCA10BAR 10 17.5 8.0 10 10 12.3
CCA12BAR 12 19.5 9.0 12 12 14.3
CCA14BAR 14 21.5 10.0 14 14 16.3
CCA16BAR 16 23.5 11.0 16 16 18.3
CCA18BAR 18 25.5 12 .0 18 18 20.3
C
B
E
A
F
D
Barometric Tee
18
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Part Number DIM - A DIM - B DIM - C
Inlet Diameter Outlet Diameter Installed Length
CCA04NCR06 4 6 10.5
CCA05NCR07 5 7 10.5
CCA06NCR08 6 8 10.5
CCA07NCR09 7 9 10.5
CCA08NCR10 8 10 10.5
CCA09NCR10 9 10 10.5
CCA10NCR12 10 12 10.5
CCA12NCR14 12 14 10.5
CCA14NCR16 14 16 10.5
CCA16NCR18 16 18 10.5
CCA18NCR20 18 20 10.5
CCA20NCR22 20 22 10.5
CCA22NCR24 22 24 10.5
CCA24NCR26 24 26 10.5
CCA26NCR28 26 28 10.5
CCA28NCR30 28 30 10.5
CCA30NCR32 30 32 10.5
Increasers:
Increaser Use to upsize a vent system. The term increaser is based on an increase in vent diameter in the direction
of flue gas motion. Increasers are eccentric to allow for proper drainage of condensate when installed horizontally. Each
increaser comes standard with a coupler that will fit the outlet diameter. Other diameter configurations may be available; please
contact Heat-fabs Engineering Team to discuss your special needs.
Increaser
C
A
B
19
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Part Number DIM - A DIM - B DIM - C
Inlet Diameter Outlet Diameter Installed Length
CCA06RDC04 6 4 10.5
CCA08RDC06 8 6 10.5
CCA10RDC08 10 8 10.5
CCA12RDC10 12 10 10.5
CCA14RDC12 14 12 10.5
CCA16RDC14 16 14 10.5
CCA18RDC16 18 16 10.5
Reducers:
Reducer Use to downsize the vent system when adding a fan to the system. The term reducer is based on an
reduction in vent diameter in the direction of flue gas motion. Reducers are eccentric to allow for proper drainage of condensate
when installed horizontally. Each reducer comes standard with a coupler that will fit the outlet diameter. Other diameter
configurations may be available; please contact Heat-fabs Engineering Team to discuss your special needs.
Reducer
A
B
C
20
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
15 Elbow Use to achieve offsets or changes in the direction of the vent system. The degree of these welded seam
elbows is not adjustable. The pressure drop for this fitting is equivalent to 3 feet of horizontal vent. The inlet connection rotates
to accommodate direction changes. Each elbow comes standard with a coupler, joint locking strap, and a rotating clamp.
Elbows:
Part Number DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F
Nominal Nominal Rise Run Combined Offset
Diameter Diameter Installed Height
Inner vent Outer Jacket
CCA04E15 4 6.3 4.3 4.43 16.7 2.3
CCA05E15 5 7.3 4.4 4.4 16.9 2.3
CCA06E15 6 8.3 4.4 4.4 17.2 2.3
CCA07E15 7 9.3 4.5 4.5 17.5 2.3
CCA08E15 8 10.3 4.5 4.5 17.8 2.4
CCA09E15 9 11.3 4.6 4.6 18.1 2.4
CCA10E15 10 12.3 4.7 4.7 18.3 2.4
CCA12E15 12 14.3 4.8 4.8 18.8 2.5
CCA14E15 14 16.3 4.9 4.9 19.3 2.6
CCA16E15 16 18.3 5.0 5.0 19.9 2.6
CCA18E15 18 20.3 5.2 5.2 20.4 2.7
CCA20E15 20 22.3 5.3 5.3 20.9 2.8
CCA22E15 22 24.3 5.4 5.4 21.4 2.8
CCA24E15 24 26.3 5.6 5.6 21.9 2.9
CCA26E15 26 28.3 5.7 5.7 22.5 3.0
CCA28E15 28 30.3 5.8 5.8 23.0 3.1
CCA30E15 30 32.3 6.0 6.0 23.5 3.1
CCA32E15 32 34.3 6.1 6.1 24.0 3.2
A
B
C
D
15
F
E
21
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


30 Elbow Use to achieve offsets or changes in the direction of the vent system. The degree of these welded seam
elbows is not adjustable. The pressure drop for this fitting is equivalent to 5 feet of horizontal vent. The inlet connection rotates
to accommodate direction changes. Each elbow comes standard with a coupler, joint locking strap, and a rotating clamp.
Elbows:
Part Number DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F
Nominal Nominal Rise Run Combined Offset
Diameter Diameter Installed Height
Inner vent Outer Jacket
CCA04E30 4 6.3 4.3 4.8 17 4.5
CCA05E30 5 7.3 4.4 5.0 17.3 4.6
CCA06E30 6 8.3 4.5 5.1 18 4.8
CCA07E30 7 9.3 4.7 5.2 18.3 5.0
CCA08E30 8 10.3 4.8 5.3 19 5.0
CCA09E30 9 11.3 4.9 5.5 19.3 5.2
CCA10E30 10 12.3 5.0 5.6 20 5.3
CCA12E30 12 14.3 5.3 5.9 21 5.6
CCA14E30 14 16.3 5.6 6.1 22 5.9
CCA16E30 16 18.3 5.8 6.4 23 6.1
CCA18E30 18 20.3 6.1 6.7 24 6.4
CCA20E30 20 22.3 6.4 7.0 25 6.7
CCA22E30 22 24.3 6.6 7.2 26 7.0
CCA24E30 24 26.3 6.9 7.5 27 7.2
CCA26E30 26 28.3 7.2 7.8 28 7.5
CCA28E30 28 30.3 7.4 8.0 29 7.7
CCA30E30 30 32.3 7.7 8.3 30 8.0
CCA32E30 32 34.3 8.0 8.6 31 8.3
C
D
B
A
30
E
F
22
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
45 Elbow Use to achieve offsets or changes in the direction of the vent system. The degree of these welded seam
elbows is not adjustable. The pressure drop for this fitting is equivalent to 8 feet of horizontal vent. The inlet connection rotates
to accommodate direction changes. Each elbow comes standard with a coupler, joint locking strap, and a rotating clamp.
Elbows:
Part Number DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F
Nominal Nominal Rise Run Combined Offset
Diameter Diameter Installed Height
Inner vent Outer Jacket
CCA04E45 4 6.3 6.2 6.7 22.1 9.2
CCA05E45 5 7.3 6.4 7.0 23.3 9.4
CCA06E45 6 8.3 6.6 7.2 23.6 9.7
CCA07E45 7 9.3 6.8 7.4 24.3 10.0
CCA08E45 8 10.3 7.0 7.6 24.9 10.3
CCA09E45 9 11.3 7.2 7.8 25.2 10.6
CCA10E45 10 12.3 7.4 8.0 26.5 10.9
CCA12E45 12 14.3 7.8 8.4 27.7 11.6
CCA14E45 14 16.3 8.0 8.8 29.0 12.0
CCA16E45 16 18.3 8.7 9.3 30.4 12.6
CCA18E45 18 20.3 9.1 9.7 32.0 13.3
CCA20E45 20 22.3 9.5 10.1 33.3 13.8
CCA22E45 22 24.3 9.9 10.5 34.8 14.4
CCA24E45 24 26.3 10.3 10.9 36.3 15.1
CCA26E45 26 28.3 11.1 11.1 37.5 15.6
CCA28E45 28 30.3 11.2 11.7 39.1 16.2
CCA30E45 30 32.3 11.6 12.1 40.4 16.8
CCA32E45 32 34.3 12.0 12.6 41.9 17.3
A
B
D
C
E
F
45
23
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


90 Elbow Use to achieve offsets or changes in the direction of the vent system. The degree of these welded seam
elbows is not adjustable. The pressure drop for this fitting is equivalent to 15 feet of horizontal vent. The inlet connection
rotates to accommodate direction changes. Each elbow comes standard with a coupler, joint locking strap, and a rotating
clamp. For diameters above 24" use two 45 elbows.
Part Number DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F
Nominal Nominal Rise Run Combined Offset
Diameter Diameter Installed Height
Inner vent Outer Jacket
CCA04E90 4 6.3 11.7 11.3 2 3 23
CCA05E90 5 7.3 12.3 11.8 24 24
CCA06E90 6 8.3 12.8 12.3 25 25
CCA07E90 7 9.3 13.3 12.8 26 26
CCA08E90 8 10.3 13.8 13.3 27 27
CCA09E90 9 11.3 14.3 13.8 28 28
CCA10E90 10 12.3 14.8 14.3 29 29
CCA12E90 12 14.3 15.8 15.3 31 31
CCA14E90 14 16.3 16.8 16.3 33 33
CCA16E90 16 18.3 17.8 17.3 35 35
CCA18E90 18 20.3 18.8 18.3 37 37
CCA20E90 20 22.3 19.8 19.3 39 39
CCA22E90 22 24.3 20.8 20.3 41 41
CCA24E90 24 26.3 21.8 21.3 43 43
Elbows:
B
A
90
D
C
F
E
24
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Tight Radius 90 Elbow Use to achieve offsets or changes in the direction of the vent system where a
conventional long radius 90 degree elbow will not fit. The degree of these welded seam elbows is not adjustable. The
pressure drop for this fitting is equivalent to 15 feet of horizontal vent. The inlet connection rotates to accommodate direction
changes. Each elbow comes standard with a coupler, joint locking strap, and a rotating clamp.
Part Number DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F
Nominal Nominal Rise Run Combined Offset
Diameter Diameter Installed Height
Inner vent Outer Jacket
CCA04E90TR 4 6.3 7.3 6.8 14 14
CCA05E90TR 5 7.3 7.8 7.5 15 15
CCA06E90TR 6 8.3 8.3 7.8 16 16
CCA07E90TR 7 9.3 8.8 8.3 17 17
CCA08E90TR 8 10.3 9.3 8.8 18 18
CCA09E90TR 9 11.3 9.8 9.3 19 19
CCA10E90TR 10 12.3 10.3 9.8 20 20
Elbows:
F
E
C
D
A
B
90
25
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Horizontal and Vertical When used horizontally, install vent with a continuous pitch of 1/4" per foot, sloping
upward toward the termination (unless otherwise specified by the appliance manufacturer). It is important to provide adequate
support to a Saf-T Vent CI Plus system, refer to installation instructions for support specifications. Each section comes with a
coupler and a joint locking strap.
Straight Lengths:
A
B
C
6" Length
Part Number DIM - A DIM - B DIM - C
Nominal Nominal Installed Length
Vent Pipe Outer Jacket
Diameter Diameter
CCA04L6 4 6.3 4.5
CCA05L6 5 7.3 4.5
CCA06L6 6 8.3 4.5
CCA07L6 7 9.3 4.5
CCA08L6 8 10.3 4.5
CCA09L6 9 11.3 4.5
CCA10L6 10 12.3 4.5
CCA12L6 12 14.3 4.5
CCA14L6 14 16.3 4.5
CCA16L6 16 18.3 4.5
CCA18L6 18 20.3 4.5
CCA20L6 20 22.3 4.5
CCA22L6 22 24.3 4.5
CCA24L6 24 26.3 4.5
CCA26L6 26 28.3 4.5
CCA28L6 28 30.3 4.5
CCA30L6 30 32.3 4.5
CCA32L6 32 34.3 4.5
9" Length
CCA04L9 4 6.3 7.5
CCA05L9 5 7.3 7.5
CCA06L9 6 8.3 7.5
CCA07L9 7 9.3 7.5
CCA08L9 8 10.3 7.5
CCA09L9 9 11.3 7.5
CCA10L9 10 12.3 7.5
CCA12L9 12 14.3 7.5
CCA14L9 14 16.3 7.5
CCA16L9 16 18.3 7.5
CCA18L9 18 20.3 7.5
CCA20L9 20 22.3 7.5
CCA22L9 22 24.3 7.5
CCA24L9 24 26.3 7.5
CCA26L9 26 28.3 7.5
CCA28L9 28 30.3 7.5
CCA30L9 30 32.3 7.5
CCA32L9 32 34.3 7.5
26
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Horizontal and Vertical When used horizontally, install vent with a continuous pitch of 1/4" per foot, sloping
upward toward the termination (unless otherwise specified by the appliance manufacturer). It is important to provide adequate
support to a Saf-T Vent CI Plus system, refer to installation instructions for support specifications. Each section comes with a
coupler and a joint locking strap.
Straight Lengths:
A
B
C
18" Length
CCA04L18 4 6.3 16.5
CCA05L18 5 7.3 16.5
CCA06L18 6 8.3 16.5
CCA07L18 7 9.3 16.5
CCA08L18 8 10.3 16.5
CCA09L18 9 11.3 16.5
CCA10L18 10 12.3 16.5
CCA12L18 12 14.3 16.5
CCA14L18 14 16.3 16.5
CCA16L18 16 18.3 16.5
CCA18L18 18 20.3 16.5
CCA20L18 20 22.3 16.5
CCA22L18 22 24.3 16.5
CCA24L18 24 26.3 16.5
CCA26L18 26 28.3 16.5
CCA28L18 28 30.3 16.5
CCA30L18 30 32.3 16.5
CCA32L18 32 34.3 16.5
12" Length
Part Number DIM - A DIM - B DIM - C
Nominal Nominal Installed Length
Vent Pipe Outer Jacket
Diameter Diameter
CCA04L12 4 6.3 10.5
CCA05L12 5 7.3 10.5
CCA06L12 6 8.3 10.5
CCA07L12 7 9.3 10.5
CCA08L12 8 10.3 10.5
CCA09L12 9 11.3 10.5
CCA10L12 10 12.3 10.5
CCA12L12 12 14.3 10.5
CCA14L12 14 16.3 10.5
CCA16L12 16 18.3 10.5
CCA18L12 18 20.3 10.5
CCA20L12 20 22.3 10.5
CCA22L12 22 24.3 10.5
CCA24L12 24 26.3 10.5
CCA26L12 26 28.3 10.5
CCA28L12 28 30.3 10.5
CCA30L12 30 32.3 10.5
CCA32L12 32 34.3 10.5
27
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Horizontal and Vertical When used horizontally, install vent with a continuous pitch of 1/4" per foot, sloping
upward toward the termination (unless otherwise specified by the appliance manufacturer). It is important to provide adequate
support to a Saf-T Vent CI Plus system, refer to installation instructions for support specifications. Each section comes with a
coupler and a joint locking strap.
Straight Lengths:
36" Length
CCA04L36 4 6.3 36.0
CCA05L36 5 7.3 36.0
CCA06L36 6 8.3 36.0
CCA07L36 7 9.3 36.0
CCA08L36 8 10.3 36.0
CCA09L36 9 11.3 36.0
CCA10L36 10 12.3 34.5
CCA12L36 12 14.3 34.5
CCA14L36 14 16.3 34.5
CCA16L36 16 18.3 34.5
CCA18L36 18 20.3 34.5
CCA20L36 20 22.3 34.5
CCA22L36 22 24.3 34.5
CCA24L36 24 26.3 34.5
CCA26L36 26 28.3 34.5
CCA28L36 28 30.3 34.5
CCA30L36 30 32.3 34.5
CCA32L36 32 34.3 34.5
A
B
C
24" Length
Part Number DIM - A DIM - B DIM - C
Nominal Nominal Installed Length
Vent Pipe Outer Jacket
Diameter Diameter
CCA04L24 4 6.3 22.5
CCA05L24 5 7.3 22.5
CCA06L24 6 8.3 22.5
CCA07L24 7 9.3 22.5
CCA08L24 8 10.3 22.5
CCA09L24 9 11.3 22.5
CCA10L24 10 12.3 22.5
CCA12L24 12 14.3 22.5
CCA14L24 14 16.3 22.5
CCA16L24 16 18.3 22.5
CCA18L24 18 20.3 22.5
CCA20L24 20 22.3 22.5
CCA22L24 22 24.3 22.5
CCA24L24 24 26.3 22.5
CCA26L24 26 28.3 22.5
CCA28L24 28 30.3 22.5
CCA30L24 30 32.3 22.5
CCA32L24 32 34.3 22.5
28
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Part Number DIM - A DIM - B DIM - C DIM - D
Nominal Nominal Maximum Minimum
Vent Pipe Coupler Installed Length Installed Length
Diameter Diameter
CCA04AJ 4 6.3 20 13
CCA05AJ 5 7.3 20 13
CCA06AJ 6 8.3 20 13
CCA07AJ 7 9.3 20 13
CCA08AJ 8 10.3 20 13
CCA09AJ 9 11.3 20 13
CCA10AJ 10 12.3 20 13
CCA12AJ 12 14.3 20 13
CCA14AJ 14 16.3 20 13
CCA16AJ 16 18.3 20 13
CCA18AJ 18 20.3 20 13
CCA20AJ 20 22.3 20 13
CCA22AJ 22 24.3 20 13
CCA24AJ 24 26.3 20 13
CCA26AJ 26 28.3 20 13
CCA28AJ 28 30.3 20 13
CCA30AJ 30 32.3 20 13
CCA32AJ 32 34.3 20 13
Adjustable Length:
Long Adjustable Length The Saf-T Vent CI Plus Adjustable Section serves as a variable length between other
components when specific lengths cannot be utilized. The installed length of the adjustable is 13" to 20 ". Each adjustable
section comes with a joint locking strap and a coupler, which can be field cut. It is important to provide adequate support to a
Saf-T Vent CI Plus system, refer to installation instructions for support specifications.
Maximum Length Minimum Length
Coupler
Inner Vent
Outer Vent
A
C
D
B
29
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Short Adjustable Length The Saf-T Vent CI Plus Adjustable Section serves as a variable length between other
components when specific lengths cannot be utilized. The installed length of the adjustable is 7" to 11 ". Each adjustable section
comes with a joint locking strap and a coupler, which can be field cut. It is important to provide adequate support to a Saf-T Vent
CI Plus system, refer to installation instructions for support specifications.
Part Number DIM - A DIM - B DIM - C DIM - D
Nominal Nominal Maximum Minimum
Vent Pipe Coupler Installed Length Installed Length
Diameter Diameter
CCA04AJSM 5 6.3 11 7
CCA05AJSM 5 7.3 11 7
CCA06AJSM 6 8.3 11 7
CCA07AJSM 7 9.3 11 7
CCA08AJSM 8 10.3 11 7
CCA09AJSM 9 11.3 11 7
CCA10AJSM 10 12.3 11 7
CCA12AJSM 12 14.3 11 7
CCA14AJSM 14 16.3 11 7
CCA16AJSM 16 18.3 11 7
CCA18AJSM 18 20.3 11 7
CCA20AJSM 20 22.3 11 7
CCA22AJSM 22 24.3 11 7
CCA24AJSM 24 26.3 11 7
CCA26AJSM 26 28.3 11 7
CCA28AJSM 28 30.3 11 7
CCA30AJSM 30 32.3 11 7
CCA32AJSM 32 34.3 11 7
Maximum Length Minimum Length
Coupler
Inner Vent Outer Vent
A
C
D
B
Adjustable Length:
30
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
B
A
Guy Support Section Provides vertical support using a part that is a flue-gas-carrying component of the vent
system. Guy sections are primarily installed in long, inaccessible chases or used to provide support to systems with extended
lengths above the roofline. Attach the guy section using stainless steel or galvanized cables or chain (supplied by others). Each
guy section comes with a coupler and a joint locking strap.
Supports:
Part Number DIM - A DIM - B DIM - C
Nominal Diameter Installed Height Hole Diameter
CCA04GUY 4 4.5 0.38
CCA05GUY 5 4.5 0.38
CCA06GUY 6 4.5 0.38
CCA07GUY 7 4.5 0.38
CCA08GUY 8 4.5 0.38
CCA09GUY 9 4.5 0.38
CCA10GUY 10 4.5 0.38
CCA12GUY 12 4.5 0.38
CCA14GUY 14 4.5 0.38
CCA16GUY 16 4.5 0.38
CCA18GUY 18 4.5 0.38
CCA20GUY 20 4.5 0.38
CCA22GUY 22 4.5 0.38
CCA24GUY 24 4.5 0.38
CCA26GUY 26 4.5 0.38
CCA28GUY 28 4.5 0.38
CCA30GUY 30 4.5 0.38
CCA32GUY 32 4.5 0.38
Guy Support Section
3/8" Diameter Cable
Holes
31
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


5.00
DIM. A
ALSO OD
OF VENT
DIM. B
DIM. C OPENING
DIM. A
FLOOR
TOP VIEW
OPENING IN FLOOR
FLOOR
VENT PIPE
Floor Support Use as a support between floors. Can also be used inside an accessible chase with the addition of site
designed support brakets.
Supports:
Vertical Support Plate Use as a vertical stack support. Can be used horizontally if needed. Framework is by
others, utilizing typical construction components such as angle iron or unistrut type material. Support section is fully assembled and
includes a joint band.
Part Number DIM-A DIM - B
Vent Diameter Plate
CCA04VSP 4 8
CCA05VSP 5 9
CCA06VSP 6 10
CCA07VSP 7 11
CCA08VSP 8 12
CCA09VSP 9 13
CCA10VSP 10 14
CCA12VSP 12 15
CCA14VSP 14 16
CCA16VSP 16 18
CCA18VSP 18 20
CCA20VSP 20 22
CCA22VSP 22 24
CCA24VSP 24 26
CCA26VSP 26 28
CCA28VSP 28 30
CCA30VSP 30 32
CCA32VSP 32 34
Part Number DIM-A DIM - B DIM -C
Vent Diameter Plate Max. Floor Opening
FLSUP06 6 14.68 11.68
FLSUP07 7 15.68 12.68
FLSUP08 8 16.68 13.68
FLSUP09 9 17.68 14.68
FLSUP10 10 18.68 15.68
FLSUP11 11 19.68 16.68
FLSUP12 12 20.68 17.68
FLSUP14 14 22.68 19.68
FLSUP16 16 24.68 21.68
FLSUP18 18 26.68 23.68
FLSUP20 20 28.68 25.68
FLSUP22 22 30.68 27.68
FLSUP24 24 32.68 29.68
FLSUP26 26 34.68 31.68
FLSUP28 28 36.68 33.68
FLSUP30 30 38.68 35.68
FLSUP32 32 40.68 37.68
A
B
B
32
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Vertical Support Use to support Saf-T Vent CI Plus systems, the part number CCA_VTS4 maintains a 4" clearance
to combustible materials and the CCA_VTS maintains a 1" clearance to combustible materials. Refer to the installation
instructions for placement of supports.
Supports:
Part Number DIM - A
Inner Vent Nominal Outer
Diameter Jacket Diameter
CCA04VTS4 4 6.3
CCA05VTS4 5 7.3
CCA06VTS4 6 8.3
CCA07VTS4 7 9.3
CCA08VTS4 8 10.3
CCA09VTS4 9 11.3
CCA10VTS4 10 12.3
CCA12VTS4 12 14.3
CCA14VTS4 14 16.3
CCA16VTS4 16 18.3
CCA18VTS4 18 20.3
CCA20VTS4 20 22.3
CCA22VTS4 22 24.3
CCA24VTS4 24 26.3
CCA26VTS4 26 28.3
CCA28VTS4 28 30.3
CCA30VTS4 30 32.3
CCA32VTS4 32 34.3
Part Number DIM - A
Inner Vent Nominal Outer
Diameter Jacket Diameter
CCA04VTS 4 6.3
CCA05VTS 5 7.3
CCA06VTS 6 8.3
CCA07VTS 7 9.3
CCA08VTS 8 10.3
CCA09VTS 9 11.3
CCA10VTS 10 12.3
CCA12VTS 12 14.3
CCA14VTS 14 16.3
CCA16VTS 16 18.3
CCA18VTS 18 20.3
CCA20VTS 20 22.3
CCA22VTS 22 24.3
CCA24VTS 24 26.3
4"
A
8"
A
1"
8"
33
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


HANGERS
BY OTHERS
CLAMP
HORIZONTAL
SUPPORT
Support Clamp Typical for smaller diameter support. For use on horizontal systems to provide support at the
required 6-foot intervals. Support clamps by themselves do not maintain the necessary clearances to combustible materials; be sure
to consider clearances when planning the system. Support clamps are sold in pairs, with two half-shells, and two 1/4-20 nuts and
bolts. This part is made from 18-gauge Type 304 stainless steel and should not be installed in the direct path of flue gases.
Can also be used as guy support clamps, vertically as well as horizontally.
Part Number Inner DIM - A
Vent Nominal Diameter
4627SS 6 8
4727SS 5 7
4827SS 6 8
4927SS 7 9
41027SS 8 10
41127SS 9 11
41227SS 10 12
41427SS 12 14
41627SS 14 16
41827SS 16 18
42027SS 18 20
42227SS 20 22
42427SS 22 24
Support Clamp
Used in pairs to clamp around
the vent and suspend from a
single rod or cable.
Support Clamp
Used singularly as a saddle
to rest the vent in; suspend
from two rods or cables.
A
A
Horizontal Support for Large Diameter Typical for large diameter support. Provides horizontal
support for the Saf-T Vent CI Plus system. Diameters 24" thru 32" must have support every 6 feet of horizontal run. The support
may be attached from the center of the bracket or from the sides
of the support bracket. Support hangers by themselves do not
maintain the necessary clearances to combustible materials; be
sure to consider clearances when planning the system.
Support Hangers:
CLAMP
HANGERS
BY OTHERS
HORIZONTAL
SUPPORT
Center Attached Support
Side Attached Support
Part Number DIM - A DIM - B
Inner Vent Diameter Outer Jacket
CCM24HZS 24 26.3
CCM26HZS 26 28.3
CCM28HZS 28 30.3
CCM30HZS 30 32.3
CCM32HZS 32 34.3
A
A
B
B
34
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
A
B
E
D
B
C
A
E
Supports:
Roof Jack Support System For use with vertical terminations. Use to pass through combustible and
non-combustible roof structures. The roof jack support system must be installed on a flat roof or a level curb only. Each roof
jack support system includes a storm collar that provides support and when sealed, acts as a water barrier. Cannot be used
in a chase with a 1" clearance to vent. Refer to Tall Cone Flashing.
Part Number Inner DIM - A DIM - B DIM - C DIM - D DIM - E
Vent I D OD Height Above Height Below Plate Size
Diameter of Roof Jack of Roof Jack Roof Line Roof Line
CCL04RJ 4 6.5 9.1 7.25 15 24
CCL05RJ 5 7.5 10.1 7.25 15 24
CCL06RJ 6 8.5 11.1 7.25 15 24
CCL07RJ 7 9.5 12.1 7.25 15 24
CCL08RJ 8 10.5 13.1 7.25 15 24
CCL09RJ 9 11.5 14.5 7.25 15 24
CCL10RJ 10 12.5 15.1 7.25 15 24
CCL12RJ 12 14.5 17.1 7.25 15 24
CCL14RJ 14 16.5 19.1 7.25 15 27
CCL16RJ 16 18.5 21.1 7.25 15 30
CCL18RJ 18 20.5 23.1 7.25 15 32
CCL20RJ 20 22.5 25.1 7.25 15 34
CCL22RJ 22 24.5 27.1 7.25 15 36
CCL24RJ 24 26.5 29.1 7.25 15 36
CCL26RJ 26 28.5 31.1 7.25 15 36
CCL28RJ 28 30.5 33.1 7.25 15 40
CCL30RJ 30 32.5 35.1 7.25 15 42
CCL32RJ 32 34.5 37.1 7.25 15 44
Roof Jack Support System
35
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Tall Cone Flashing and Support Use as a vertical roof penetration/support in conjunction with a combus-
tible chase. Can be used with a roof curb if needed. Can be used on metal roofs with a 2-12 pitch. This part comes with a
storm collar and support screws and is of all stainless steel construction. A Vented Termination Collar must be used when
installed in a combustible chase and must be ordered separately. CAUTION: the support screws can only be installed with
Saf-T Vent CI Pus venting.
Supports:
Part Number Inner Vent DIM-A DIM - B DIM - C DIM - D DIM-E
Diameter Top of Cone Bottom of Cone Face Plate Overall Quantity
Opening Opening (Square) Height of Holes
CCM04TCF 4 6.5 9.75 18 12 4
CCM05TCF 5 7.5 10.75 20 12 4
CCM06TCF 6 8.5 11.75 20 12 4
CCM07TCF 7 9.5 12.75 22 12 4
CCM08TCF 8 10.5 13.75 22 12 4
CCM09TCF 9 11.5 14.75 24 12 4
CCM10TCF 10 12.5 15.75 24 12 4
CCM12TCF 12 14.5 17.75 26 12 4
CCM14TCF 14 16.5 19.75 28 12 6
CCM16TCF 16 18.5 21.75 30 16 6
CCM18TCF 18 20.5 23.75 32 12 6
CCM20TCF 20 22.5 25.75 34 12 6
CCM22TCF 22 24.5 27.75 36 12 6
CCM24TCF 24 26.5 29.75 38 12 8
CCM26TCF 26 28.5 31.75 40 12 8
CCM28TCF 28 30.5 33.75 42 12 8
CCM30TCF 30 32.5 35.75 44 12 8
CCM32TCF 32 34.5 37.75 46 12 8
Tall Cone Flashing and Support
.25
SPACED
HOLE
EQUALLY
E
D
B
A
C
36
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
18
1.8"
A
12"
B
Part Number Inner Vent DIM-A DIM - B
Diameter Top of Cone Face Plate
Opening (Square)
CCM04TCFP 4 6.5 24
CCM05TCFP 5 8.5 24
CCM06TCFP 6 9.5 24
CCM07TCFP 7 10.5 26
CCM08TCFP 8 11.5 26
CCM09TCFP 9 12.5 26
CCM10TCFP 10 13.5 28
CCM12TCFP 12 15.5 30
CCM14TCFP 14 17.5 34
CCM16TCFP 16 19.5 34
CCM18TCFP 18 21.5 36
CCM20TCFP 20 23.5 38
CCM22TCFP 22 25.5 40
CCM24TCFP 24 27.5 42
CCM26TCFP 26 29.5 44
CCM28TCFP 28 31.5 46
CCM30TCFP 30 33.5 48
CCM32TCFP 32 35.5 48
Pitched Tall Cone Flashing Use as a vertical roof penetration in conjunction with a combustible chase. Can
be used on roofs with a 2/12 - 6/12 pitch. This part comes with a storm collar and is of all stainless steel construction. A
Vented Termination Collar must be used when installed in a combustible chase and must be ordered separately. Can be used
with Saf-T Vent CI vent when clearance to combustibles are maintained.
Pitched Tall Cone Flashing
Supports:
37
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


B
E
G
A
F
D
B
A
C
Terminations:
Wall Termination / Penetration Use to penetrate any combustible or non-combustible wall. This part is a
thimble only and does not include any vent. Order enough vent to pass through the thimble and extend 4-8 inches beyond the
building sheathing. Includes an AL 29-4C

screen cover and a vent finish collar to terminate the vent system.
Part Number Inner DIM - A DIM - B DIM - C DIM - D DIM - E DIM - F DIM - G
Vent Outer Jacket Outer Thimble Face Plate Face Plate Overall Exterior Wall
Diameter Diameter Diameter Width Height Length Length Opening
CCE04WP 4 6.3 9 16 15 21.5 6 11
CCE05WP 5 7.3 10 17 16 23.5 8 12
CCE06WP 6 8.3 11 18 17 23.5 8 13
CCE07WP 7 9.3 12 18 17 23.5 12 14
CCE08WP 8 10.3 13 19 18 27.5 12 15
CCE09WP 9 11.3 14 20 19 27.5 12 16
CCE10WP 10 12.3 15 22 21 27.5 12 17
CCE12WP 12 14.3 17 24 23 27.5 12 19
CCE14WP 14 16.3 19 25 24 27.5 12 21
CCE16WP 16 18.3 21 27 26 27.5 12 23
CCE18WP 18 20.3 23 29 28 27.5 12 25
CCE20WP 20 22.3 25 31 30 27.5 12 27
CCE22WP 22 24.3 27 33 32 27.5 12 29
CCE24WP 24 26.3 29 35 34 27.5 12 31
CCE26WP 26 28.3 31 37 36 27.5 12 33
CCE28WP 28 30.3 33 39 38 27.5 12 35
CCE30WP 30 32.3 35 41 40 27.5 12 37
CCE32WP 32 34.3 37 43 42 27.5 12 39
WallTermination / Penetration
38
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Terminations:
Wall Penetration Use to penetrate any combustible or non-combustible wall. This part is a thimble only and does
not include any vent. Order enough vent to pass through the thimble and extend 4-8 inches beyond the building sheathing.
Includes a finish collar.
A
B
G
E
D
B
A
C
Part Number Inner DIM - A DIM - B DIM - C DIM - D DIM - E DIM - G
Vent Outer Jacket Outer Thimble Face Plate Face Plate Overall Wall
Diameter Diameter Diameter Width Height Length Opening
CCL04WPNS 4 6.3 9 16 15 18.5 11
CCL05WPNS 5 7.3 10 17 16 18.5 12
CCL06WPNS 6 8.3 11 18 17 18.5 13
CCL07WPNS 7 9.3 12 18 17 18.5 14
CCL08WPNS 8 10.3 13 19 18 18.5 15
CCL09WPNS 9 11.3 14 20 19 18.5 16
CCL10WPNS 10 12.3 15 22 21 18.5 17
CCL12WPNS 12 14.3 17 24 23 18.5 19
CCL14WPNS 14 16.3 19 25 24 18.5 21
CCL16WPNS 16 18.3 21 27 26 18.5 23
CCL18WPNS 18 20.3 23 29 28 18.5 25
CCL20WPNS 20 22.3 25 31 30 18.5 27
CCL22WPNS 22 24.3 27 33 32 18.5 29
CCL24WPNS 24 26.3 29 35 34 18.5 31
CCL26WPNS 26 28.3 31 37 36 18.5 33
CCL28WPNS 28 30.3 33 39 38 18.5 35
CCL30WPNS 30 32.3 35 41 40 18.5 37
CCL32WPNS 32 34.3 37 43 42 18.5 39
Wall Penetration
39
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Terminations:
Rain Cap Use as a termination on vertical systems. Category I and II appliances require a raincap or other device to
prevent rainwater from entering the vent. Vent systems for positive pressure appliances may omit the raincap if there are
other provisions for draining rainwater from the system. The raincap may also be used as a horizontal termination. Each
raincap includes a joint locking strap as well as a storm collar. Call Heat-fab to inquire about larger diameters.
Part Number DIM - A DIM - B DIM - C DIM - D
Nominal Cap Storm Collar Cap
Vent Pipe Installed OD OD
Diameter Height
CCA04RC 4 8.5 12 12
CCA05RC 5 8.5 14 14
CCA06RC 6 8.5 14 14
CCA07RC 7 9.5 18 18
CCA08RC 8 9.5 18 18
CCA09RC 9 9.5 20 20
CCA10RC 10 9.5 20 20
CCA12RC 12 9.5 24 24
CCA14RC 14 11.5 28 28
CCA16RC 16 13.5 32 32
CCA18RC 18 15.5 36 36
CCA20RC 20 17.5 36 36
CCA22RC 22 19.5 44 44
CCA24RC 24 19.5 48 48
B
C
A
D
Rain Cap
Screened Termination Use as a termination on horizontal or vertical systems, as specified or allowed by the
appliance manufacturer. The screened termination comes with a joint locking strap and a finish collar. Made of AL29-4C.
Part Number DIM - A DIM-B
Diameter Installed Length
CCK04TM 4 4.5
CCK05TM 5 4.5
CCK06TM 6 4.5
CCK07TM 7 4.5
CCK08TM 8 4.5
CCK09TM 9 4.5
CCK10TM 10 4.5
CCK12TM 12 4.5
CCK14TM 14 4.5
CCK16TM 16 4.5
CCK18TM 18 4.5
CCK20TM 20 4.5
CCK22TM 22 4.5
CCK24TM 24 4.5
CCK26TM 26 4.5
CCK28TM 28 4.5
CCK30TM 30 4.5
CCK32TM 32 4.5
A
B
Screened Termination
40
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Terminations:
Exit Cone Use as a termination to increase the velocity of the flue gases exiting the stack. The exit cone may also
help to reduce ice buildup in cold climates where a rain cap may normally be used. A narrow Finish Collar is included to seal
off the 1" air space of the CI Plus vent. The Exit Cone can be attached to EZ Seal vent systems with the addition of an adapter
strap, CCA__ADSV
Part Number DIM - A DIM-B
CCA06EX04 4 6
CCA07EX05 5 7
CCA08EX06 6 8
CCA09EX07 7 9
CCA10EX08 8 10
CCA126EX10 10 12
CCA14EX12 12 14
CCA16EX14 14 16
CCA18EX16 16 18
CCA20EX18 18 20
CCA22EX20 20 22
CCA24EX22 22 24
CCA26EX24 24 26
CCA28EX26 26 28
CCA30EX28 28 30
CCA32EX30 30 32
41
Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Termination Accessories:
Finish Collar The collar is used to close off air space between inner vent and outer jacket. For use on horizontal or
vertical systems.
Part Number DIM-A DIM - B DIM - C
Inner Vent Outer Jacket Outer Collar
Diameter Diameter Diameter
CCK04FC 4 6.3 7
CCK05FC 5 7.3 8
CCK06FC 6 8.3 9
CCK07FC 7 9.3 10
CCK08FC 8 10.3 11
CCK09FC 9 11.3 12
CCK10FC 10 12.3 13
CCK12FC 12 14.3 15
CCK14FC 14 16.3 17
CCK16FC 16 18.3 19
CCK18FC 18 20.3 21
CCK20FC 20 22.3 23
CCK22FC 22 24.3 25
CCK24FC 24 26.3 27
CCK26FC 26 28.3 29
CCK28FC 28 30.3 31
CCK30FC 30 32.3 33
CCK32FC 32 34.6 35
A
C
B
Ventilation Collar The ventilation collar is installed over the air space between the inner vent and outer jacket and
allows any built up heat to escape. The ventilation collar must be used on Tall Cone Flashing installations with a combustible
chase . For use on horizontal and vertical systems.
Part Number DIM-A DIM - B DIM - C
Inner Vent Outer Jacket Outer Collar
Diameter Diameter Diameter
CCK04FCV 4 6.3 7
CCK05FCV 5 7.3 8
CCK06FCV 6 8.3 9
CCK07FCV 7 9.3 10
CCK08FCV 8 10.3 11
CCK09FCV 9 11.3 12
CCK10FCV 10 12.3 13
CCK12FCV 12 14.3 15
CCK14FCV 14 16.3 17
CCK16FCV 16 18.3 19
CCK18FCV 18 20.3 21
CCK20FCV 20 22.3 23
CCK22FCV 22 24.3 25
CCK24FCV 24 26.3 27
CCK26FCV 26 28.3 29
CCK28FCV 28 30.3 31
CCK30FCV 30 32.3 33
CCK32FCV 32 34.3 35
C
A
B
42
Saf-T Vent

CI

Plus
DOUBLE WALL AL 29-4C

SPECIAL GAS VENT


Heatfab Division, Selkirk Corp.
130 Industrial Boulevard Turners Falls, MA 01376
Phone 800 772 0739 Fax 413 863 4803 www.heat-fab.com
Notes:

Potrebbero piacerti anche