Kevin Damron & Mike Diedesch Avista Utilities Presented March 17 th , 2014 At the 31 st Annual Hands-On Relay School Washington State University Pullman, Washington 2 Table of Contents System Overview .... 3 Distribution (3-30MVA ) Transformer Protection ...... 14 Relay Overcurrent Curves ... 22 Symmetrical Components .... 8 Distribution Fuse Protection .. 24 Conductors ..... 28 Electromechanical Relays used on Distribution Feeders.. 31 Coordinating Time Intervals . 36 Transformer Relay Settings using Electromechanical Relays . 48 IEEE Device Designations... 51 Transformer & Feeder Protection using Microprocessor Relays . 52 Transformer Differential Protection . 61 Moscow 13.8kV Feeder Coordination Example . 64 3 System Overview - Distribution Protection Objective: Protect people (company personnel and the public) and equipment by the proper application of overcurrent protective devices. Devices include: Relays operating to trip (open) circuit breakers or circuit switchers, and/or fuses blowing for the occurrence of electrical faults on the distribution system. Design tools used: 1 Transformer and conductor damage curves, 2 - Time-current coordination curves (TCCs), fuse curves, and relay overcurrent elements based on symmetrical components of fault current. Documentation: 1 - One-line diagrams and Schematics with standardized device designations as defined by the IEEE (Institute of Electrical and Electronics Engineers) keeps everyone on the same page in understanding how the system works. 2 - TCCs XFMR 12/16/20MVA 115/13.8kV 115kV SYSTEM 13.8 kV BUS 500A, 13.8kV FDR #515 DELTA/WYE LINE RECLOSER P584 3 =5158 SLG =5346 3 =3453 SLG =2762 PT-2B PT-2A 3 =3699 SLG =3060 PT-3B PT-3A PT-4 #4ACSR 1PHASE #4ACSR #4ACSR #4ACSR #2ACSR #4ACSR 2/0ACSR #2ACSR 3 =1907 SLG =1492 3 =322 SLG =271 3-250KVA WYE/WYE PT-8 65T A-172 MOSCOW 1PHASE #4ACSR 3 =558 SLG =463 PT-3C PT-6B PT-6A PT-6C HIGH LEAD LOW 3 =1210 SLG =877 PT-1 PT-5 PT-7 FUSE 556ACSR 556ACSR 13.8 kV FDR #512 500A FDR 4 System Overview Inside the Substation Fence Transformer relays Feeder relay 5 XFMR 12/16/20MVA 115/13.8kV 115kV SYSTEM 13.8kV BUS 500A, 13.8kV FDR #515 DELTA/WYE LINE RECLOSER P584 3 =5158 SLG =5346 3=3453 SLG =2762 PT-2B PT-2A 3=3699 SLG =3060 PT-3B PT-3A PT-4 #4ACSR 1PHASE #4ACSR #4ACSR #4ACSR #2ACSR #4ACSR 2/0ACSR #2ACSR 3=1907 SLG =1492 3 =322 SLG =271 3-250KVA WYE/WYE PT-8 65T A-172 MOSCOW 1PHASE #4ACSR 3=558 SLG =463 PT-3C PT-6B PT-6A PT-6C HIGH LEAD LOW 3=1210 SLG =877 PT-1 PT-5 PT-7 FUSE 556ACSR 556ACSR 13.8kV FDR #512 500A FDR System Overview Outside the Substation Fence Midline recloser relay XFMR 12/16/20MVA 115/13.8kV 115kV SYSTEM 13.8kV BUS 500A, 13.8kV FDR #515 DELTA/WYE LINE RECLOSER P584 3 =5158 SLG =5346 3 =3453 SLG =2762 PT-2B PT-2A 3 =3699 SLG =3060 PT-3B PT-3A PT-4 #4ACSR 1PHASE #4ACSR #4ACSR #4ACSR #2ACSR #4ACSR 2/0ACSR #2ACSR 3 =1907 SLG =1492 3 =322 SLG =271 3-250KVA WYE/WYE PT-8 65T A-172 MOSCOW 1PHASE #4ACSR 3 =558 SLG =463 PT-3C PT-6B PT-6A PT-6C HIGH LEAD LOW 3 =1210 SLG =877 PT-1 PT-5 PT-7 FUSE 556ACSR 556ACSR 13.8kV FDR #512 500A FDR 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage13.8kV HORS 2010 By J DH For Idaho RdFeeder 252inIdaho RdPHASE 12007base.olr No. Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008 TRANSFORMER PROTECTION STATIONVCB 252PROTECTION MAXIMUM FEEDER FUSE HI-SIDE CT'S MIDLINE OCR MAXIMUM MIDLINE FUSE Fault I=5665.9A 1 1. IDR A-77751P 351 SEL-VI TD=1.200 CTR=600/5Pickup=2.A No inst. TP@5=0.3096s Ia= 679.8A (5.7 sec A) T= 0.78s H=8.33 2 2. IDR 25251P 351S SEL-EI TD=1.500 CTR=800/5Pickup=6.A No inst. TP@5=0.4072s Ia=5665.9A (35.4 sec A) T= 0.30s 3. IDR 25250G 351S INST TD=1.000 CTR=800/5Pickup=3.A No inst. TP@5=0.048s 3Io= 0.0A (0.0 sec A) T=9999s 4 4. 252140T FUSE stn S&C Link140T Total clear. Ia=5665.9A T= 0.09s 5 5f 5. Phaseunit of recloser MIDLINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia=5665.9A T(Fast)= 0.03s 6 6. T FUSE S&C Link 50T Minimummelt. Ia=5665.9A T= 0.01s A A. Conductor damagecurve. k=0.06710A=556000.0cmils Conductor AAC FEEDER 252SMALLEST CONDUCTOR TO PROTECT B B. Transf. damage curve. 12.00MVA. Category 3 BaseI=502.00A. Z= 8.2percent. IDAHO RD12/16/20MVA XFMR FAULT DESCRIPTION: Bus Fault on: 0IDR 252 13.8kV 3LG 6 System Overview Each device has at least one curve plotted with current and time values on the Time Coordination Curve. 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage13.8kV HORS 2010 By J DH For Idaho RdFeeder 252inIdaho RdPHASE 12007base.olr No. Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008 TRANSFORMER PROTECTION STATIONVCB 252PROTECTION MAXIMUM FEEDER FUSE HI-SIDE CT'S MIDLINE OCR MAXIMUM MIDLINE FUSE Fault I=5665.9A 1 1. IDR A-77751P 351 SEL-VI TD=1.200 CTR=600/5Pickup=2.A No inst. TP@5=0.3096s Ia= 679.8A (5.7 sec A) T= 0.78s H=8.33 2 2. IDR 25251P 351S SEL-EI TD=1.500 CTR=800/5Pickup=6.A No inst. TP@5=0.4072s Ia=5665.9A (35.4 sec A) T= 0.30s 3. IDR 25250G 351S INST TD=1.000 CTR=800/5Pickup=3.A No inst. TP@5=0.048s 3Io= 0.0A (0.0 sec A) T=9999s 4 4. 252140T FUSE stn S&C Link140T Total clear. Ia=5665.9A T= 0.09s 5 5f 5. Phaseunit of recloser MIDLINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia=5665.9A T(Fast)= 0.03s 6 6. T FUSE S&C Link 50T Minimummelt. Ia=5665.9A T= 0.01s A A. Conductor damagecurve. k=0.06710A=556000.0cmils Conductor AAC FEEDER 252SMALLEST CONDUCTOR TO PROTECT B B. Transf. damage curve. 12.00MVA. Category 3 BaseI=502.00A. Z= 8.2percent. IDAHO RD12/16/20MVA XFMR FAULT DESCRIPTION: Bus Fault on: 0IDR 252 13.8kV 3LG 7 System Overview Damage Curves: - transformer - conductor So, what curve goes where? What are the types of curves? Protective Curves: - relay - fuse Damage curves are at the top and to the right of the TCC. Protective curves lowest and to the left on the TCC correspond to those devices farther from the substation where the fault current is less. 8 Transformer Protection - Damage Curve ANSI/IEEE C57.109-1985 The main damage curve line shows only the thermal effect from transformer through-fault currents. It is graphed from data entered below (MVA, Base Amps, %Z ): 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage By For No. Comment Date 1 1. M15 CTR= A A. Transf. damage curve. 12.00 MVA. Category3 Base I=502.00 A. Z= 8.2 percent. The dog leg on the curve is added to allow for additional thermal and mechanical damage from (typically more than 5) through-faults over the life of a transformer serving overhead feeders. Dog leg curve - 10 times base current at 2 seconds. Main curve - 25 times base current at 2 seconds. Time at 50% of the maximum per-unit through fault current = 8 seconds. Avista has Category III size (5-30MVA) Distribution Transformers in service per the above standard. 9 Copper Conductor Damage Curves ACSR Conductor Damage Curves (2/0 damage at 1500A @ 100sec.) (2/0 damage at 900A @ 100sec.) Conductor Damage Curves 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @Voltage13.8kV By DLH For ACSR Conductor DamageCurves No. Comment Date 12/13/05 1 1. M15-515PhaseINST INST TD=1.000 CTR=160Pickup=7.ANoinst. TP@5=0.048s A A. Conductor damagecurve. k=0.08620A=355107.0cmils Conductor ACSR 336.4ACSR B B. Conductor damagecurve. k=0.08620A=167800.0cmils Conductor ACSR AWGSize4/0 4/0ACSR C C. Conductor damagecurve. k=0.08620A=105500.0cmils Conductor ACSR AWGSize2/0 2/0ACSR D D. Conductor damagecurve. k=0.08620A=83690.0cmils Conductor ACSR AWGSize1/0 1/0ACSR E E. Conductor damagecurve. k=0.08620A=52630.0cmils Conductor ACSR AWGSize2 #2ACSR F F. Conductor damagecurve. k=0.08620A=33100.0cmils Conductor ACSR AWGSize4 #4ACSR 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @Voltage13.8kV By DLH For Copper Conductor DamageCurves No. Comment Date 12/13/05 1 1. M15-515PhaseINST INST TD=1.000 CTR=160Pickup=7.ANoinst. TP@5=0.048s A A. Conductor damagecurve. k=0.14040A=105500.0cmils Conductor Copper (bare) AWGSize2/0 2/0Copper B B. Conductor damagecurve. k=0.14040A=83690.0cmils Conductor Copper (bare) AWGSize1/0 1/0Copper C C. Conductor damagecurve. k=0.14040A=52630.0cmils Conductor Copper (bare) AWGSize2 #2Copper D D. Conductor damagecurve. k=0.14040A=33100.0cmils Conductor Copper (bare) AWGSize4 #4Copper E E. Conductor damagecurve. k=0.14040A=20820.0cmils Conductor Copper (bare) AWGSize6 #6Copper 10 Conductor Rating 556 730 336.4 530 4/0 340 2/0 270 1/0 230 #2 180 #4 140 ACSR Ampacity Ratings Conductor Rating 2/0 360 1/0 310 #2 230 #4 170 #6 120 Copper Ampacity Ratings Conductor Ampacities Conductor at 25C ambient taken from the Westinghouse Transmission & Distribution book. 11 Comparing a 140T fuse versus a #4 ACSR Damage curve. The 140T wont protect the conductor below about 550 amps where the curves cross. Conductor Protection Graph 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8kV #4ACSR &140T By Protection For AspenFile: HORS M15EXP.olr No. Comment Date 3/06 1 1. Moscow515Kear 140T Kearney 140T Total clear. A A. Conductor damagecurve. k=0.08620A=33100.0cmils Conductor ACSR AWG Size 4 12 Transformer Protection using 115 kV Fuses 13 Transformer Protection using 115 kV Fuses Used at smaller substations up to 7.5 MVA transformer due to low cost of protection. Other advantages are: - Low maintenance - Panel house & station battery not required There are also several disadvantages to using fuses however which are: Low interrupting rating from 1,200A (for some older models) up to 10,000A at 115 kV. By contrast a circuit switcher can have a rating of 25KAIC and our breakers have normally 40KAIC. The fuses we generally use are rated to blow within 5 minutes at twice their nameplate rating. Thus, a 65 amp fuse will blow at 130 amps. This compromises the amount of overload we can carry in an emergency and still provide good sensitivity for faults. 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8KV ROK 451R2 By J DH For ROK FDR 451, BUS FAULTS: 3LG=3580A, SLG=3782A, L-L=3100A No. Comment ASPEN FILE: ROK NEW XFMR (2005BASE).OLR Date 2-13-07 STATION TRANSFORMER PROTECTION FEEDER VCR PROTECTION MAXIMUM FEEDER FUSE 1 1. LAT RP421150N CO-11 INST TD=1.000 CTR=500/5Pickup=2.A No inst. TP@5=0.048s 2 2. SMD-2B 65E VERY SLOW 176-19-065 Minimummelt. H=8.33 3 3. LAT RP421150P CO-11 INST TD=1.000 CTR=500/5Pickup=3.5A No inst. TP@5=0.048s 4 4. LAT RP421151P CO-11 CO-11 TD=2.000 CTR=500/5Pickup=3.A No inst. TP@5=0.5043s 5 5. LAT RP421151N CO-11 CO-11 TD=4.000 CTR=500/5Pickup=2.A No inst. TP@5=1.0192s 6 6. LAT RP4211FUSE S&C Link 65T Total clear. A A. Transf. damage curve. 7.50MVA. Category 3 Base I=313.78A. Z= 7.3percent. Rockford 13.8kV - ROCKFORD115 115.kV 1T 14 The fuse time current characteristic (TCC) is fixed (although you can buy a standard, slow or very slow speed ratio which are different inverse curves). The sensitivity to detect lo-side SLG faults isnt as good as using a relay on a circuit switcher or breaker. This is because we use DELTA/WYE connected transformers so the phase current on the 115 kV is reduced by the 3 as opposed to a three phase fault. Some fuses can be damaged and then blow later at some high load point. When only one 115 kV fuse blows, it subjects the customer to low distribution voltages. For example the phase to neutral distribution voltages on two phases on the 13.8 kV become 50% of normal. No indication of faulted zone (transformer, bus or feeder). Transformer Protection using 115 kV Fuses - continued A B C a b c 1.0 PU 0.5 PU 0.5 PU 15 Transformer Protection using a Circuit Switcher Showing Avistas present standard using Microprocessor relays. 13.8kV 115kV 16 Transformer Protection using a Circuit Switcher Showing Avistas old standard using Electromechanical relays. 17 Transformer Protection using a Circuit Switcher Some advantages to this over fuses are: Higher interrupting. Relays can be set to operate faster and with better sensitivity than fuses. Three phase operation. Provide better coordination with downstream devices. Some disadvantages would be: Higher cost. Higher maintenance. Requires a substation battery, panel house and relaying. Transformer requires CTs. 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8kV IDR FEEDER 251 By J DH For Idaho RdFeeder 251inIdaho RdPHASE 12007base.olr No. Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008 TRANSFORMER PROTECTION STATION VCB 251PROTECTION MAXIMUM FEEDER FUSE HI-SIDE CT'S LO-SIDE CT'S MINIMUM FAULT TO DETECT: 3LG=2460A, SLG=1833A, L-L=2130A 1 1. IDR A-77751P 351 SEL-VI TD=1.200 CTR=600/5Pickup=2.A No inst. TP@5=0.3096s H=8.33 2 2. IDR A-77751G 351 SEL-VI TD=1.000 CTR=600/5Pickup=1.A No inst. TP@5=0.258s H=8.33 3 3. IDR A-77751N 351 SEL-EI TD=5.700 CTR=1200/5Pickup=3.A No inst. TP@5=1.5473s 4 4. IDR A-77751Q 351 SEL-EI TD=4.200 CTR=600/5Pickup=1.3A No inst. TP@5=1.1401s H=8.33 5 5. IDR A-77751Q 587W2 SEL-EI TD=4.300 CTR=1200/5Pickup=5.4A No inst. TP@5=1.1672s 6 6. IDR 25150P 351S INST TD=1.000 CTR=800/5Pickup=7.A No inst. TP@5=0.048s 7 7. IDR 25151P 351S SEL-EI TD=1.500 CTR=800/5Pickup=6.A No inst. TP@5=0.4072s 8 8. IDR 25150G 351S INST TD=1.000 CTR=800/5Pickup=3.A No inst. TP@5=0.048s 9 9. IDR 25151G 351S SEL-EI TD=3.900 CTR=800/5Pickup=3.A No inst. TP@5=1.0587s 10 10. IDR 25151Q 351S SEL-EI TD=3.500 CTR=800/5Pickup=5.2A No inst. TP@5=0.9501s 11 11. 251140T FUSE stn S&C Link140T Total clear. A A. Conductor damage curve. k=0.08620A=133100.0cmils Conductor ACSR AWG Size2/0 FEEDER 251SMALLEST CONDUCTOR TO PROTECT B B. Transf. damage curve. 12.00MVA. Category 3 Base I=502.00A. Z= 8.2percent. IDAHO RD12/16/20MVA XFMR 18 Transformer Protection using a Breaker This is very similar to using a circuit switcher with a couple of advantages such as: Higher interrupting 40kAIC for the one shown below. Somewhat faster tripping than a circuit switcher (3 cycles vs. 6 8 cycles). Possibly less maintenance than a circuit switcher. The CTs would be located on the breaker so it would interrupt faults on the bus section up to the transformer plus the transformer high side bushings. 19 SEL Various Relay Overcurrent Curves. Extremely Inverse steepest Very Inverse Inverse Moderately Inverse Short Time Inverse least steep The five curves shown here have the same pickup settings , but different time dial settings. These are basically the same as various E-M relays. Avista uses mostly extremely inverse on feeders to match the fuse curves. Relay Overcurrent Curves 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage By For No. Comment Date 1 1. EXTREMELY INVERSE SEL-EI TD=15.000 CTR=800/5Pickup=6.A No inst. TP@5=4.0718s 2 2. INVERSE SEL-I TD=2.000 CTR=800/5Pickup=6.A No inst. TP@5=0.8558s 3 3. MODERATELY INVERSE SEL-2xx-MI TD=1.000 CTR=800/5Pickup=6.A No inst. TP@5=0.324s 4 4. SHORT TIME INVERSE SEL-STI TD=1.000 CTR=800/5Pickup=6.A No inst. TP@5=0.1072s 5 5. VERY INVERSE SEL-VI TD=6.000 CTR=800/5Pickup=6.A No inst. TP@5=1.5478s 20 Time dial - at what time delay will the relay operate to trip the breaker - the larger time dial means more time delay - also known as lever from the electromechanical relay days - Instantaneous elements have a time dial of 1 and operate at 0.05 seconds. - Instantaneous curves are shown as a flat horizontal line starting at the left at the pickup value and plotted at 0.05 seconds. Relay Overcurrent Curves - Pickups & Time Dials Pickup - the current at which the relay will operate to trip the breaker. - also known as tap from the electromechanical relay days -expressed in terms of the ratio of the current transformer (CTR) that the relay is connected to, - e.g., a relay with a CTR of 120 and a pickup (or tap) of 4 will operate to trip the breaker at 480 amps 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8kV IDR FEEDER 251 By J DH For Idaho RdFeeder 251inIdaho RdPHASE 12007base.olr No. Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008 TRANSFORMER PROTECTION STATIONVCB 251PROTECTION MAXIMUMFEEDER FUSE HI-SIDE CT'S LO-SIDE CT'S MINIMUM FAULT TO DETECT: 3LG=2460A, SLG=1833A, L-L=2130A 1 1. IDR A-77751P 351 SEL-VI TD=1.200 CTR=600/5Pickup=2.A No inst. TP@5=0.3096s H=8.33 2 2. IDR A-77751G 351 SEL-VI TD=1.000 CTR=600/5Pickup=1.A No inst. TP@5=0.258s H=8.33 3 3. IDR A-77751N351 SEL-EI TD=5.700 CTR=1200/5Pickup=3.A No inst. TP@5=1.5473s 4 4. IDR A-77751Q 351 SEL-EI TD=4.200 CTR=600/5Pickup=1.3A No inst. TP@5=1.1401s H=8.33 5 5. IDR A-77751Q 587W2 SEL-EI TD=4.300 CTR=1200/5Pickup=5.4A No inst. TP@5=1.1672s 6 6. IDR 25150P 351S INST TD=1.000 CTR=800/5Pickup=7.A No inst. TP@5=0.048s 7 7. IDR 25151P 351S SEL-EI TD=1.500 CTR=800/5Pickup=6.A No inst. TP@5=0.4072s 8 8. IDR 25150G 351S INST TD=1.000 CTR=800/5Pickup=3.A No inst. TP@5=0.048s 9 9. IDR 25151G 351S SEL-EI TD=3.900 CTR=800/5Pickup=3.A No inst. TP@5=1.0587s 10 10. IDR 25151Q 351S SEL-EI TD=3.500 CTR=800/5Pickup=5.2A No inst. TP@5=0.9501s 11 11. 251140T FUSE stn S&C Link140T Total clear. A A. Conductor damagecurve. k=0.08620A=133100.0cmils Conductor ACSR AWG Size 2/0 FEEDER 251SMALLEST CONDUCTOR TO PROTECT B B. Transf. damage curve. 12.00MVA. Category 3 BaseI=502.00A. Z= 8.2percent. IDAHO RD12/16/20MVA XFMR 21 Same Time Dial =9 Right curve picks up at 960 Amps Left curve picks up at 320Amps Relay Overcurrent Curves - Example of Different Pickup & Time Dial Settings 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage By For No. Comment Date 1 1. EXT INV 1 SEL-EI TD=15.000 CTR=800/5Pickup=6.A No inst. TP@5=4.0718s 2 2. ~EXT INV 1 SEL-EI TD=12.000 CTR=800/5Pickup=6.A No inst. TP@5=3.2574s 3 3. ~EXT INV 2 SEL-EI TD=9.000 CTR=800/5Pickup=6.A No inst. TP@5=2.4431s 4 4. ~EXT INV 3 SEL-EI TD=6.000 CTR=800/5Pickup=6.A No inst. TP@5=1.6287s 5 5. ~EXT INV 4 SEL-EI TD=2.000 CTR=800/5Pickup=6.A No inst. TP@5=0.5429s 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage By For No. Comment Date 1 1. EXT INV 1 SEL-EI TD=9.000 CTR=800/5Pickup=6.A No inst. TP@5=2.4431s 2 2. ~EXT INV 1 SEL-EI TD=9.000 CTR=800/5Pickup=5.A No inst. TP@5=2.4431s 3 3. ~EXT INV 2 SEL-EI TD=9.000 CTR=800/5Pickup=4.A No inst. TP@5=2.4431s 4 4. ~EXT INV 3 SEL-EI TD=9.000 CTR=800/5Pickup=3.A No inst. TP@5=2.4431s 5 5. ~EXT INV 4 SEL-EI TD=9.000 CTR=800/5Pickup=2.A No inst. TP@5=2.4431s Same Pickup =960 Amps Top curve Time Dial =15 Bottom curve Time Dial =2 22 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8 kV INT 12F1 By J DH For Indian Trail feeder 12F1 in INT 2007base.olr No. Comment AT SUB: 3LG=5719A, LL=4951A, SLG=5880A Date 1-29-08 TRANSFORMER PROTECTION STATION VCB 12F1 PROTECTION 1 1. INT A-742 51P 351 SEL-VI TD=10.000 CTR=600/5 Pickup=0.8A No inst. TP@5=2.5797s H=8.33 2 2. INT 12F1 51P 351S SEL-VI TD=1.800 CTR=800/5 Pickup=3.A No inst. TP@5=0.4643s 3 3. INT 12F1 51G 351S SEL-VI TD=0.900 CTR=800/5 Pickup=3.A No inst. TP@5=0.2322s 4 4. INT 12F1 51Q351S SEL-VI TD=0.500 CTR=800/5 Pickup=3.A No inst. TP@5=0.129s 5 5. INT A-742 51G 351 SEL-VI TD=5.000 CTR=600/5 Pickup=0.8A No inst. TP@5=1.2898s H=8.33 6 6. INT A-742 51Q351 SEL-VI TD=3.000 CTR=600/5 Pickup=0.8A No inst. TP@5=0.7739s H=8.33 A A. Transf. damage curve. 12.00 MVA. Category3 Base I=502.00 A. Z= 8.4 percent. INDIAN TRAIL 12/16/20 MVA XFMR B B. Conductor damage curve. k=0.06710 A=556000.0 cmils Conductor AAC 556 kCMil AAC Microprocessor relays have different types of curves based on the type of fault current being measured: 51P phase time overcurrent 51N or 51G ground time overcurrent 51Q negative sequence time overcurrent Transformer relay curves Feeder relay curves 51P phase time overcurrent 51N or 51G ground time overcurrent 51Q negative sequence time overcurrent This brings us to a brief discussion of: 23 Symmetrical Components Symmetrical Components for Power Systems Engineering, J . Lewis Blackburn, There are three sets of independent components in a three-phase system: positive, negative and zero for both current and voltage. Positive sequence voltages (Figure 1) are supplied by generators within the system and are always present. A second set of balanced phasors are also equal in magnitude and displaced 120 degrees apart, but display a counter-clockwise rotation sequence of A-C-B (Figure 2), which represents a negative sequence. The final set of balanced phasors is equal in magnitude and in phase with each other, however since there is no rotation sequence (Figure 3) this is known as a zero sequence. 24 Symmetrical Components Three phase (3LG) fault - Positive sequence currents for setting phase elements in relays. Phase -Phase (L-L) fault - Negativesequence currents for setting negative sequence elements in relays. Single phase (1LG or SLG) fault - Zerosequence currents for setting ground elements in relays. Symmetrical Components Notation: Positive Sequence current =I + =I1 Negative Sequence current =I - =I2 Zero Sequence current =I 0 =I0 Phase Current notation: IA High side Amps Ia Low side Amps 8.33=115/13.8 =transformer Voltage (turns) ratio Phasor diagram from Fault-study Software. Examples of three 13.8kV faults showing the current distribution through a Delta-Wyehigh-lead-low transformer bank : 25 Symmetrical Components Positive Sequence, 3LG 13.8 kV Fault You have only positive sequence voltage and current since the system is balanced. A B C a b c R R IA =619 -88 Ia=5158 -118 IB =619 152 Ib =5158 122 IC =619 32 Ic=5158 2 Phase current =Sequence current That is; Ia=I + . Phase currents and voltages for the 115kV side. IA =Ia/ 8.33 =5158A / 8.33 IA =619A 26 Symmetrical Components Negative Sequence, L-L 13.8 kV Fault 115kV side sequence currents and voltages 13.8kV side sequence currents and voltages A B C a b c R R IA =309 -28 Ia =0 0 IB =619 152 Ib =4467 152 IC =309 -28 Ic =4467 -28 3LG 13.8kV fault =5158A, Ib=Ic=4467 A, 4467/5158 =86.6%=3/2 IB 3LG =IB LL =619A IA & IC =IB or Ia& Ic=Ib I 2 =the phase current/3 =4467/3 =2579 Digital relays 50Q/51Q elements set using 3I2. 3I2 =Ib x 3 =4467 x 1.732 =7737, 27 Symmetrical Components Zero Sequence, 1LG 13.8 kV Fault 115kV side sequence currents and voltages A B C a b c R R 3I0 is the sum of the 3 phase currents and since Ib & Ic =0, then 3I0 =Ia. This means the phase and ground overcurrent relays on the feeder breaker see the same amount of current. 5346/(8.33*3) =370 amps. So the high side phase current is the 3 less as compared to the 3 fault. Digital relays ground elements set using 3I0. 13.8kV side sequence currents and voltages IA =370 -118 Ia=3I0=5346 -118 IB =0 0 Ib =0 0 IC =370 62 Ic=0 0 Ia=3Va/(Z1 +Z2 +Z0) 28 Symmetrical Components - Summary of 13.8 kV Faults 3LG positive sequence current SLG zero sequence current L-L negative sequence current IA =619 Ia=5158 IB =619 Ib =5158 IC =619 Ic=5158 5158 / 8.33 =619 Ia=5158 =I1 5346/(8.33x3) =370 Ia=5346 =3I0 If you have a Delta-Wye transformer bank, and you know the voltage ratio and secondary phase current values for 13.8kV 3LG (5158) and SLG (5346) faults, you can find the rest: IA =309 Ia =0 IB =619 Ib =4467 IC =309 Ic =4467 5158 x 3/2 =4467 Ib x 3 =7737 =3I2 4467/(8.33x 3) =309 309 x 2 =619 IA =370 Ia=5346 IB =0 Ib =0 IC =370 Ic=0 29 Symmetrical Components - Summary of 13.8 kV Faults Youve heard of a Line-to-Line fault, how about an Antler-to-Antler fault? 30 Electromechanical Relays used on Distribution Feeders Avistas standard distribution relay package (until the mid-1990s) included the following: 3 phase 50/51 CO-11 relays, 1 reclosing relay 1 ground 50/51 CO-11 relay . 31 Objectives: Protect the feeder conductor Detect as low a fault current as possible (PU =50% EOL fault amps) Other than 51P, set pickup and time dial as low as possible and still have minimum Coordinating Time Interval (CTI) to next device. CTI is minimum time between operation of adjacent devices. Carry normal maximum load (phase overcurrent only). Pickup the feeder in a cold load condition ( 2 times maximum normal load) or pickup of the next feeder load 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8KV By For No. Comment Date TRANSFORMER PROTECTION FEEDER VCB PROTECTION MAXIMUM FEEDER FUSE 1 1. SMD-2B 65E VERY SLOW 176-19-065 Minimummelt. H=8.33 2 2. LAT42150P CO-9 INST TD=1.000 CTR=600/5Pickup=4.6A No inst. TP@5=0.048s 3 3. LAT42151P CO-9 CO-9 TD=1.900 CTR=600/5Pickup=4.A No inst. TP@5=0.4618s 4 4. LAT42150N CO-9 INST TD=1.000 CTR=600/5Pickup=3.A No inst. TP@5=0.048s 5 5. LAT42151N CO-9 CO-9 TD=3.000 CTR=600/5Pickup=3.A No inst. TP@5=0.7228s 6 6. LAT421FUSE S&C Link100T Total clear. A A. Transf. damagecurve. 7.50MVA. Category 3 Base I=313.78A. Z= 6.9percent. LatahJ ct 13.8kV - LATAHJ CT115 115.kV T B B. Conductor damage curve. k=0.08620A=105500.0cmils Conductor ACSR AWG Size 1/0 Electromechanical Relays used on Distribution Feeders 32 13 kV BUS MIN FAULT 3LG =2000 A 1LG =1000 A FEEDER SETTINGS 51P =2000 / 2 =1000 A 51N =1000 / 2 =500 A Electromechanical Relays used on Distribution Feeders Pickup setting criteria of 2/1 ratio of end of line fault duty / pickup - ensures that the relay will see the fault and operate when needed. 33 13 kV BUS FAULT at MIDLINE 3LG =2000 A 1LG =1000 A FEEDER SETTINGS 51P =2000 / 2 =1000 A 51N =1000 / 2 =500 A MIN FAULT at END OF LINE 3LG =1000 A 1LG =500 A MIDLINE SETTINGS 51P =1000 / 2 =500 A 51N =500 / 2 =250 A Electromechanical Relays used on Distribution Feeders 34 Electromechanical Relays used on Distribution Feeders 13 kV BUS 500A FEEDER SETTINGS 51P =960 A 51N =480 A SECTION LOAD =500 A 35 Electromechanical Relays used on Distribution Feeders 13 kV BUS 500A FEEDER SETTINGS 51P =960 A 51N =480 A N.O. SECTION LOAD =250 A SECTION LOAD =500 A SECTION LOAD =250 A 36 Most overhead feeders also use reclosing capability to automatically re-energize the feeder for temporary faults. Most distribution reclosing relays have the capability of providing up to three or four recloses. -- Avista uses either one fast or one fast and one time delayed reclose to lockout. The reclosing relay also provides a reset time generally adjustable from about 10 seconds to three minutes. This means if we run through the reclosing sequence and trip again within the reset time, the reclosing relay will lockout and the breaker will have to be closed by manual means. The time to reset from the lockout position is 3 to 6 seconds for EM reclosing relays. -- Avista uses reset times ranging from 90 to 180 seconds. Lockout only for faults within the protected zone. That is; wont lockout for faults beyond fuses, line reclosers etc. Most distribution reclosing relays also have the capability of blocking instantaneous tripping. -- Avista normally blocks the INST tripping after the first trip to provide for a Fuse Protecting Scheme. Electromechanical Relays used on Distribution Feeders Reclosing 37 13 kV BUS RECLOSING SEQUENCE Closed Open 0.5" 12" LOCKOUT RESET =120" (INST Blocked during Reset Time) Electromechanical Relays used on Distribution Feeders Reclosing Sequence shown for a permanent fault 38 Distribution Fusing Fuse Protection/Saving Scheme Fault on fused lateral on an overhead feeder: - Station or midline 51 element back up fuse. - Station or midline 50 element protects fuse. During fault: Trip and clear the fault at the station (or line recloser) by the instantaneous trip before the fuse is damaged for a lateral fault. Reclose the breaker. That way if the fault were temporary the feeder is completely re-energized and back to normal. During the reclose the reclosing relay has to block the instantaneous trip from tripping again. That way, if the fault still exists you force the time delay trip and the fuse will blow before you trip the feeder again thus isolating the fault and re-energizing most of the customers. Of course if the fault were on the main trunk the breaker will trip to lockout. 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8kV M1551551Nto 140T By Protection For AspenFile: HORS M15EXP.olr No. Comment Date 3/06 STATIONFEEDER RELAYING MAXIMUM FEEDER FUSE 1 1. M15515GNDTIME CO-11 TD=4.000 CTR=160Pickup=3.A No inst. TP@5=1.0192s 2 2. Moscow515Kear 140T Kearney 140T Total clear. 3 3. M1550NCO-11 INST TD=1.000 CTR=160Pickup=3.A Noinst. TP@5=0.048s 39 Shows the maximum fault current for which S&C type T fuses can still be protected by a recloser/breaker instantaneous trip for temporary faults (minimum melt curve at 0.1 seconds): 6T 120 amps 8T 160 amps 10T 225 amps 12T 300 amps 15T 390 amps 20T 500 amps 25T 640 amps 30T 800 amps 40T 1040 amps 50T 1300 amps 65T 1650 amps 80T 2050 amps 100T 2650 amps 140T 3500 amps 200T 5500 amps 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage By For No. Comment Date 1 1. BR1S&C 140T S&C Link140T Minimummelt. 2 2. ENDTAP S&C 40T S&C Link 40T Minimummelt. 3 3. M15515S&C 80T S&C Link 80T Minimummelt. Distribution Fusing Fuse Protection for Temporary Faults 40 NOTE: These values were taken from the S&C data bulletin 350-170 of March 28, 1988 based on no preloading and then preloading of the source side fuse link. Preloading is defined as the source side fuse carrying load amps equal to its rating prior to the fault. This means there was prior heating of that fuse so it doesnt take as long to blow for a given fault. 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage By For No. Comment Date 1 1. T FUSE S&C Link100T Minimummelt. 2 2. 251140T FUSE stn S&C Link140T Total clear. Distribution Fusing Fuse to Fuse Coordination 41 Typical continuous and 8 hour emergency rating of the S&C T rated silver fuse links plus the 140T and 200T. 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage By For No. Comment Date 1 1. BR1 S&C 140T S&C Link140T Minimummelt. Distribution Fusing S&C T-Fuse Current Ratings General Rule: Fuse Blows at 2X Rating in 5 Minutes 42 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. DEVICES: CTI (Sec.) Relay Fuse Total Clear 0.2 Relay Series Trip Recloser 0.4 Relay Relayed Line Recloser 0.3 Lo Side Xfmr Relay Feeder Relay 0.4 Hi Side Xfmr Relay Feeder Relay 0.4 Xfmr Fuse Min Melt Feeder Relay 0.4 Coordinating Time Intervals 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8kV HORS 2010 By J DH For Idaho RdFeeder 252inIdaho RdPHASE 12007base.olr No. Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008 TRANSFORMER PROTECTION STATION VCB 252PROTECTION MAXIMUM FEEDER FUSE HI-SIDE CT'S MIDLINE OCR MAXIMUM MIDLINE FUSE Fault I=5665.9A 1 1. IDR A-77751P 351 SEL-VI TD=1.200 CTR=600/5Pickup=2.A Noinst. TP@5=0.3096s Ia= 679.8A (5.7 sec A) T= 0.78s H=8.33 2 2. IDR 25251P 351S SEL-EI TD=1.500 CTR=800/5Pickup=6.A Noinst. TP@5=0.4072s Ia=5665.9A (35.4 sec A) T= 0.30s 3. IDR 25250G 351S INST TD=1.000 CTR=800/5Pickup=3.A No inst. TP@5=0.048s 3Io= 0.0A (0.0 sec A) T=9999s 4 4. 252140T FUSE stn S&C Link140T Total clear. Ia=5665.9A T= 0.09s 5 5f 5. Phase unit of recloser MIDLINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia=5665.9A T(Fast)= 0.03s 6 6. T FUSE S&C Link 50T Minimummelt. Ia=5665.9A T= 0.01s A A. Conductor damage curve. k=0.06710A=556000.0cmils Conductor AAC FEEDER 252SMALLEST CONDUCTOR TO PROTECT B B. Transf. damage curve. 12.00MVA. Category 3 Base I=502.00A. Z= 8.2percent. IDAHO RD12/16/20MVA XFMR FAULT DESCRIPTION: Bus Fault on: 0IDR 252 13.8kV 3LG 43 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. DEVICES: CTI (Sec.) Relay Fuse Total Clear 0.2 Relay Series Trip Recloser 0.4 Relay Relayed Line Recloser 0.3 Lo Side Xfmr Relay Feeder Relay 0.4 Hi Side Xfmr Relay Feeder Relay 0.4 Xfmr Fuse Min Melt Feeder Relay 0.4 Coordinating Time Intervals 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8kV HORS 2010 By J DH For Idaho RdFeeder 252inIdaho RdPHASE 12007base.olr No. Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008 TRANSFORMER PROTECTION STATION VCB 252PROTECTION MAXIMUM FEEDER FUSE HI-SIDE CT'S MIDLINE OCR MAXIMUM MIDLINE FUSE Fault I=5665.9A 1 1. IDR A-77751P 351 SEL-VI TD=1.200 CTR=600/5Pickup=2.A Noinst. TP@5=0.3096s Ia= 679.8A (5.7 sec A) T= 0.78s H=8.33 2 2. IDR 25251P 351S SEL-EI TD=1.500 CTR=800/5Pickup=6.A Noinst. TP@5=0.4072s Ia=5665.9A (35.4 sec A) T= 0.30s 3. IDR 25250G 351S INST TD=1.000 CTR=800/5Pickup=3.A No inst. TP@5=0.048s 3Io= 0.0A (0.0 sec A) T=9999s 4 4. 252140T FUSE stn S&C Link140T Total clear. Ia=5665.9A T= 0.09s 5 5f 5. Phase unit of recloser MIDLINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia=5665.9A T(Fast)= 0.03s 6 6. T FUSE S&C Link 50T Minimummelt. Ia=5665.9A T= 0.01s A A. Conductor damage curve. k=0.06710A=556000.0cmils Conductor AAC FEEDER 252SMALLEST CONDUCTOR TO PROTECT B B. Transf. damage curve. 12.00MVA. Category 3 Base I=502.00A. Z= 8.2percent. IDAHO RD12/16/20MVA XFMR FAULT DESCRIPTION: Bus Fault on: 0IDR 252 13.8kV 3LG 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @Voltage13.8kV RAT 231MIDC390R By J DH For Huetterfeeder142(2008)Ratfeeder231(2009+)MidlineRecloserC390R No. Comment Savedin: HUE142-RAT231MIDC390R 2007base.olr Date 2-25-08 HUETTER FDR 142PROTECTION RATHDRUMFDR 231PROTECTION HUE 142MIDC270R PROTECTION MIDLINE 390R PROTECTION CALLED"HUE 142LINE"INPOWERBASE RECLOSE IS 1SEC, 12SEC, LO, 120SEC RESET RECLOSE IS 1SEC, 12SEC, LO, 180SEC RESET LARGEST DOWNSTREAMFUSE FROM390R MIDLINE 1 1. C390R MID51P CO-9 CO-9 TD=2.500 CTR=300/5Pickup=5.A Noinst. TP@5=0.6037s 2 2. C390R MID50P CO-9 INST TD=1.000 CTR=300/5Pickup=6.A Noinst. TP@5=0.048s 3 3. C390R MID50NCO-9 INST TD=1.000 CTR=300/5Pickup=5.A Noinst. TP@5=0.048s 4 4. C390R MID51NCO-9 CO-9 TD=2.500 CTR=300/5Pickup=5.A Noinst. TP@5=0.6037s 5 5. HUE 14250P 251 INST TD=1.000 CTR=160Pickup=7.A Noinst. TP@5=0.048s 6 6. HUE 14251P 251 SEL-EI TD=1.500 CTR=160Pickup=6.A Noinst. TP@5=0.4072s 7 7. HUE ML C270R 50P INST TD=1.000 CTR=400/5Pickup=8.1A Noinst. TP@5=0.048s 8 8. HUE ML C270R 51P CO-11 TD=1.500 CTR=400/5Pickup=7.A Noinst. TP@5=0.3766s 9 9. HUE 14250N251 INST TD=1.000 CTR=160Pickup=3.A Noinst. TP@5=0.048s 10 10. HUE 14251N251 SEL-EI TD=4.000 CTR=160Pickup=3.A Noinst. TP@5=1.0858s 11 11. HUE 14251Q251 SEL-EI TD=4.000 CTR=160Pickup=5.2A Noinst. TP@5=1.0858s 12 12. HUE ML C270R 50N INST TD=1.000 CTR=400/5Pickup=3.A Noinst. TP@5=0.048s 13 13. HUE ML C270R 51N CO-11 TD=7.000 CTR=400/5Pickup=3.A Noinst. TP@5=1.8052s 14 14. RAT 23150NCO-11 INST TD=1.000 CTR=800/5Pickup=3.A Noinst. TP@5=0.048s 15 15. RAT 23151NCO-11 CO-11 TD=5.000 CTR=800/5Pickup=3.A Noinst. TP@5=1.3192s 16 16. RAT 23150P CO-11 INST TD=1.000 CTR=800/5Pickup=7.A Noinst. TP@5=0.048s 17 17. HUE 142 FUSE S&C Link65T Total clear. 18 18. RAT 231 FUSE S&C Link100T Total clear. 19 19. RAT 231 51P CO-11 CO-11 TD=1.800 CTR=800/5Pickup=6.A Noinst. TP@5=0.4533s A A. Conductordamagecurve. k=0.08620A=133100.0cmils ConductorACSR AWGSize2/0 MIDLINE C390FEDFROMRAT 231- MINIMUMCONDUCTOR TOPROTECT B B. Conductordamagecurve. k=0.06710A=556000.0cmils ConductorAAC MIDLINE C390FEDFROMHUE 142- MINIMUMCONDUCTOR TOPROTECT 44 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. DEVICES: CTI (Sec.) Relay Fuse Total Clear 0.2 Relay Series Trip Recloser 0.4 Relay Relayed Line Recloser 0.3 Lo Side Xfmr Relay Feeder Relay 0.4 Hi Side Xfmr Relay Feeder Relay 0.4 Xfmr Fuse Min Melt Feeder Relay 0.4 Coordinating Time Intervals 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8kV IDR FEEDER 251 By J DH For Idaho RdFeeder 251inIdaho RdPHASE 12007base.olr No. Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008 TRANSFORMER PROTECTION STATIONVCB 251PROTECTION MAXIMUM FEEDER FUSE HI-SIDE CT'S LO-SIDE CT'S MINIMUM FAULT TO DETECT: 3LG=2460A, SLG=1833A, L-L=2130A 1 1. IDR A-77751P 351 SEL-VI TD=1.200 CTR=600/5Pickup=2.A No inst. TP@5=0.3096s H=8.33 2 2. IDR A-77751G 351 SEL-VI TD=1.000 CTR=600/5Pickup=1.A No inst. TP@5=0.258s H=8.33 3 3. IDR A-77751N 351 SEL-EI TD=5.700 CTR=1200/5Pickup=3.A No inst. TP@5=1.5473s 4 4. IDR A-77751Q 351 SEL-EI TD=4.200 CTR=600/5Pickup=1.3A No inst. TP@5=1.1401s H=8.33 5 5. IDR A-77751Q 587W2 SEL-EI TD=4.300 CTR=1200/5Pickup=5.4A No inst. TP@5=1.1672s 6 6. IDR 25150P 351S INST TD=1.000 CTR=800/5Pickup=7.A No inst. TP@5=0.048s 7 7. IDR 25151P 351S SEL-EI TD=1.500 CTR=800/5Pickup=6.A No inst. TP@5=0.4072s 8 8. IDR 25150G 351S INST TD=1.000 CTR=800/5Pickup=3.A No inst. TP@5=0.048s 9 9. IDR 25151G 351S SEL-EI TD=3.900 CTR=800/5Pickup=3.A No inst. TP@5=1.0587s 10 10. IDR 25151Q 351S SEL-EI TD=3.500 CTR=800/5Pickup=5.2A No inst. TP@5=0.9501s 11 11. 251140T FUSE stn S&C Link140T Total clear. A A. Conductor damage curve. k=0.08620A=133100.0cmils Conductor ACSR AWG Size 2/0 FEEDER 251SMALLEST CONDUCTOR TO PROTECT B B. Transf. damage curve. 12.00MVA. Category 3 Base I=502.00A. Z= 8.2percent. IDAHO RD12/16/20MVA XFMR 45 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. DEVICES: CTI (Sec.) Relay Fuse Total Clear 0.2 Relay Series Trip Recloser 0.4 Relay Relayed Line Recloser 0.3 Lo Side Xfmr Relay Feeder Relay 0.4 Hi Side Xfmr Relay Feeder Relay 0.4 Xfmr Fuse Min Melt Feeder Relay 0.4 Coordinating Time Intervals 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @ Voltage 13.8KV By For No. Comment Date TRANSFORMER PROTECTION FEEDER VCB PROTECTION MAXIMUM FEEDER FUSE 1 1. SMD-2B 65E VERY SLOW 176-19-065 Minimummelt. H=8.33 2 2. LAT42150P CO-9 INST TD=1.000 CTR=600/5Pickup=4.6A No inst. TP@5=0.048s 3 3. LAT42151P CO-9 CO-9 TD=1.900 CTR=600/5Pickup=4.A No inst. TP@5=0.4618s 4 4. LAT42150N CO-9 INST TD=1.000 CTR=600/5Pickup=3.A No inst. TP@5=0.048s 5 5. LAT42151N CO-9 CO-9 TD=3.000 CTR=600/5Pickup=3.A No inst. TP@5=0.7228s 6 6. LAT421FUSE S&C Link100T Total clear. A A. Transf. damagecurve. 7.50MVA. Category 3 Base I=313.78A. Z= 6.9percent. LatahJ ct 13.8kV - LATAHJ CT115 115.kV T B B. Conductor damage curve. k=0.08620A=105500.0cmils Conductor ACSR AWG Size 1/0 46 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. DEVICES: CTI (Sec.) Relay Fuse Total Clear 0.2 Relay Series Trip Recloser 0.4 Relay Relayed Line Recloser 0.3 Lo Side Xfmr Relay Feeder Relay 0.4 Hi Side Xfmr Relay Feeder Relay 0.4 Xfmr Fuse Min Melt Feeder Relay 0.4 Coordinating Time Intervals 47 Coordinating Time Intervals 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @Voltage13.8kV By DLH For M15A-172CS withfdr 515withKearney140T Fuse No. Comment ThreePhaseFault Date 12/12/05 1 1. Moscow515Kear 140T Kearney140T Minimummelt. I=5158.1A T= 0.10s 2 2. M15-515PhaseTime CO-11 TD=1.500 CTR=160Pickup=6.A Noinst. TP@5=0.3766s I=5158.1A (32.2 sec A) T= 0.33s 3 3. M15A-172Phase CO- 9 TD=1.500 CTR=120Pickup=2.A Inst=1200A TP@5=0.3605s I= 619.0A (5.2 sec A) T= 1.03s H=8.33 FAULT DESCRIPTION: Close-InFaulton: 0MoscowCity#213.8kV - 0BUS1TAP 13.8kV 1L 3LG 3LG Fault Coordination Example: Top Ckt Swr w/ Phase E-M relay ----- 0.4 sec. ------ Middle - E-M Phase relay for a 500 Amp Feeder ----- 0.2 sec. ------ Bottom 140T Feeder Fuse (Total Clear) 48 Coordinating Time Intervals 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @Voltage13.8kV By DLH For MoscowCS withfdr 515with140T fuses No. Comment SingleLinetoGroundFault Date 12/12/05 1 1. Moscow515 Kear140T Kearney140T Minimummelt. I=5346.4A T= 0.09s 2 2. M15515GND TIME CO-11 TD=4.000 CTR=160Pickup=3.A Noinst. TP@5=1.0192s I=5346.5A (33.4 sec A) T= 0.29s 3 3. M15-515PhaseTime CO-11 TD=1.500 CTR=160Pickup=6.A Noinst. TP@5=0.3766s I=5346.4A (33.4 sec A) T= 0.31s 4 4. M15A-172GND TIME CO-11 TD=4.000 CTR=240Pickup=4.A Noinst. TP@5=1.0192s I=5346.5A (22.3 sec A) T= 0.83s FAULT DESCRIPTION: Close-InFaulton: 0MoscowCity#213.8kV - 0BUS1TAP 13.8kV 1L 1LG Type=A SLG Fault Coordination Example: Top Ckt Swr w/ E-M Phase relay ----- 0.4 sec. ------ Middle - E-M relays (Phase & Ground) for a 500 Amp Feeder ----- 0.2 sec. ------ Bottom 140T Feeder Fuse (Total Clear) 49 Coordinating Time Intervals 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @Voltage13.8kV By DLH For MoscowCS A-172withfdr 515with140T Fuse No. Comment LinetoLineFault Date 1 1. Moscow515Kear 140T Kearney140T Minimummelt. I=4467.0A T= 0.12s 2 2. M15-515PhaseTime CO-11 TD=1.500 CTR=160Pickup=6.A Noinst. TP@5=0.3766s I=4467.0A (27.9 sec A) T= 0.43s 3 3. M15A-172Phase CO- 9 TD=1.500 CTR=120Pickup=2.A Inst=1200A TP@5=0.3605s I= 619.0A (5.2 sec A) T= 1.03s H=8.33 FAULT DESCRIPTION: Close-InFaulton: 0MoscowCity#213.8kV - 0BUS1TAP 13.8kV 1L LL Type=B-C L-L Fault Coordination Example: Top Ckt Swr w/ E-M relay ----- 0.4 sec. ------ Middle - E-M (Phase) relay for a 500 Amp Feeder ----- 0.2 sec. ------ Bottom 140T Feeder Fuse (Total Clear) 50 The Final Product 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 CURRENT (A) S E C O N D S 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 2 3 4 5 7 10 20 30 40 50 70 100 200 300 400 500 700 1000 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 .01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1 TIME-CURRENT CURVES @Voltage13.8kV INT 12F2&MID 466R By J DH For IndianTrail feeder 12F2and12F2Midline466R inINT 2007base.olr No. Comment AT SUB:3LG=5719A,LL=4951A,SLG=5880A Date 1-29-08 TRANSFORMER PROTECTION STATION VCB12F2PROTECTION EAST BRANCH - FEEDER MAXIMUMFUSE FAULT DUTY AT 140T- WHEN FED FROMNORTH (N.O.PT) 12F2MIDLINE466R PROTECTION WEST OR NORTH BRANCH - FEEDER MAXIMUMFUSE FAULT DUTY AT 150E;3LG=2318, LL=2008, SLG=1684 3LG=1932, LL=1673, SLG=1388 FAULT DUTY AT 140T- WHEN FED FROMWEST MID 466R 3LG=2093, LL=1813, SLG=1520 9& 15 11 &4 1 1.INT A-74251P 351 SEL-VI TD=1.200 CTR=600/5Pickup=2.ANo inst.TP@5=0.3096s H=8.33 2 2.INT A-74251G 351 SEL-VI TD=1.000 CTR=600/5Pickup=1.ANo inst.TP@5=0.258s H=8.33 3 3.INT A-74251N 351 SEL-EI TD=5.600 CTR=1200/5Pickup=3.ANo inst.TP@5=1.5201s 4 4.INT A-74251Q 351 SEL-EI TD=4.200 CTR=600/5Pickup=1.3ANo inst.TP@5=1.1401s H=8.33 5 5.INT F2150EFUSE SMU-20_150E Totalclear. 6 6.INT 12F250P 351S INST TD=1.000 CTR=800/5Pickup=7.ANo inst.TP@5=0.048s 7 7.INT 12F251P 351S SEL-EI TD=1.500 CTR=800/5Pickup=6.ANo inst.TP@5=0.4072s 8 8.INT 12F250G 351S INST TD=1.000 CTR=800/5Pickup=3.ANo inst.TP@5=0.048s 9 9.INT 12F251G 351S SEL-EI TD=3.900 CTR=800/5Pickup=3.ANo inst.TP@5=1.0587s 10 10.INT 12F251Q 351S SEL-EI TD=3.500 CTR=800/5Pickup=5.2ANo inst.TP@5=0.9501s 11 11.INT A-74251Q 587W2 SEL-EI TD=4.300 CTR=1200/5Pickup=5.4ANo inst.TP@5=1.1672s 12 12.F2MID 466R 50P 351R INST TD=1.000 CTR=500/1Pickup=1.68ANo inst.TP@5=0.048s 13 13.F2MID 466R 51P 351R SEL-EI TD=2.300 CTR=500/1Pickup=1.44ANo inst.TP@5=0.6243s 14 14.F2MID 466R 50G 351R INST TD=1.000 CTR=500/1Pickup=0.89ANo inst.TP@5=0.048s 15 15.F2MID 466R 51G 351R SEL-EI TD=4.200 CTR=500/1Pickup=0.89ANo inst.TP@5=1.1401s 16 16.F2MID 466R 51Q 351R SEL-EI TD=3.800 CTR=500/1Pickup=1.54ANo inst.TP@5=1.0315s 17 17.INT F2140TFUSEstn S&C Link140T Total clear. A A.Transf.damagecurve. 12.00MVA.Category 3 BaseI=502.00A. Z=8.4percent. INDIAN TRAIL 12/16/20MVAXFMR B B.Conductor damagecurve. k=0.14040A=52630.0cmils Conductor Copper (bare) AWG Size2 NORTH BRANCH SMALLEST TRUNKCONDUCTOR C C.Conductor damagecurve. k=0.04704A=350000.0cmils CableXLPE90C/250C EAST BRANCH SMALLEST TRUNKCONDUCTOR - 350CN15 D D.Conductor damagecurve. k=0.08620A=105500.0cmils Conductor ACSR AWG Size2/0 WEST BRANCH SMALLESTTRUNKCONDUCTOR An example of a completed 13.8kV Feeder Coordination Study with 20 Time-Current Curves representing: Instantaneous & Time-Delay Curves for the: - Transformer high side protection, - Transformer low side protection, - Station feeder breaker protection, - Midline feeder breaker protection. Two Fuses Transformer Damage Curve Three Conductor Damage Curves 51 2 Time delay relay. 27 Undervoltage relay. 43 Manual transfer or selective device. We use these for cutting in and out instantaneous overcurrent relays, reclosing relays etc. 50 (or 50P) Instantaneous overcurrent phase relay. 50N (or 50G) Instantaneous overcurrent ground (or neutral) relay. 50Q Instantaneous Negative Sequence overcurrent relay. 51 (or 51P) Time delay overcurrent phase relay. 51N (or 51G) Time delay overcurrent ground (or neutral) relay. 51Q Time delay Negative Sequence overcurrent relay. 52 AC circuit breaker. IEEE Device Designations commonly used in Distribution Protection Avista sometimes adds letters to these such as F for feeders, T for transformers, B for bus and BF for breaker failure. 52/a Circuit breaker auxiliary switch closed when the breaker is closed. 52/b Circuit breaker auxiliary switch closed when the breaker is open. 59 Overvoltage relay. 62 Time Delay relay 63 Sudden pressure relay. 79 AC Reclosing relay. 81 Frequency relay. 86 Lock out relay which has several contacts. Avista uses 86T for a transformer lockout, 86B for a bus lockout etc. 87 Differential relay. 94 Auxiliary tripping relay. Mikes Turn 52 53 Criteria (for outdoor bus arrangement, not switchgear) Protect the Transformer from thermal damage - Refer to Damage Curves Backup feeder protection (as much as possible) - Sensitivity is limited because load is higher Coordinate with downstream devices (feeder relays) Carry normal maximum load (phase only) Pick up Cold Load after outages Distribution Transformer Electromechanical Relays 54 Relays: 3 High Side Phase Overcurrent (with time and instantaneous elements) 1 Low Side Ground Overcurrent (with time and instantaneous elements) Sudden Pressure Relay Distribution Transformer Electromechanical Relays - Setting Criteria 55 Phase Overcurrent Settings Current measured on 115kV side P Pickup (time overcurrent) Dont trip for load or cold load pickup (use 2.4 * highest MVA rating) Ends up being higher than the feeder phase element pickup Example: 12/16/20 MVA unit would use 2.4*20*5 =240 amps (1940A low side) 51P Time Lever (time dial) Coordinate with feeder relays for maximum fault (close in feeder fault) CTI is 0.4 seconds Worst coordination case: - on low side (discrepancy due to delta/wye conn.) Multiple feeder load can make the transformer relay operate faster 50P Pickup(instantaneous overcurrent) Must not trip for feeder faults set at 170% of low side bus fault Accounts for DC offset Distribution Transformer Electromechanical Relays - Setting Criteria 56 Ground Overcurrent Settings Current measured on 13.8 kV side N Pickup (time overcurrent) Set to same sensitivity as feeder phase relay (in case the feeder ground relay is failed) This setting is higher than the feeder ground, so we lose some sensitivity for backup 51N Time Lever (time dial) Coordinate with feeder relays for ground faults CTI is 0.4 seconds 50N Pickup(instantaneous overcurrent) DO NOT USE!!!! Distribution Transformer Electromechanical Relays - Setting Criteria 57 Distribution Transformer & Feeder Protection with Microprocessor Relays Advantages: More precise TAP settings More Relay Elements Programmable Logic / Buttons Lower burden to CT Event Reports!!!!!!!!! Communications Coordinate with like elements (faster) More Settings MicroprocessorRelay 58 Distribution Transformer & Feeder Protection with Microprocessor Relays Elements We Set: 51P 50P 50P2 (FTB) 51G 50G (115kV) 51N (13.8kV) 50N1 (FTB) FTB = Fast Trip Block (feeder relays must be Microprocessor) 59 Transformer Phase Overcurrent Settings - Current measured on 115kV Side 51P - Phase Time Overcurrent Pickup Set to 240% of nameplate (same as EM relay) 51P Time Dial Set to coordinate with feeders fastest element for each fault CTI is still 0.4 seconds 50P1 Phase instantaneous #1 Pickup Direct Trip Set to 130% of max 13.8 kV fault (vs. 170% with EM relay) 50P2 Phase instantaneous pickup for Fast Trip Block scheme Set above transformer inrush 4 Cycle time delay Blocked if any feeder overcurrent elements are picked up Distribution Transformer & Feeder Protection with Microprocessor Relays 60 Transformer Ground Overcurrent Settings - Current calculated from 115kV CTs 51G - Ground Time Overcurrent Pickup Set very low (will not see low side ground faults due to transformer connection). Usually 120 Amps. 51GTime Dial Set very low 50G1 Ground Instantaneous #1 Pickup Set very low. Usually 120 Amps. Distribution Transformer & Feeder Protection with Microprocessor Relays Symmetrical Components! 61 Transformer Neutral Overcurrent Settings - Current measured by neutral CT or calculated from 13.8kV CTs. 51N - Ground Time Overcurrent Pickup Set slightly higher than feeder ground pickup (about 1.3 times) 51NTime Dial Set to coordinate with feeder ground CTI is 0.4 seconds 50N1 Ground Instantaneous for Fast Trip Block Set slightly above the feeder ground instantaneous pickup Time Delay by 4 cycles Blocked if Feeder overcurrent elements are picked up Distribution Transformer & Feeder Protection with Microprocessor Relays 62 Inrush The current seen when energizing a transformer. Need to account for inrush when using instantaneous elements (regular or FTB). Inrush can be approximately 8 times the nameplate of a transformer. Note that the microprocessor relay only responds to the 60 HZ fundamental and that this fundamental portion of inrush current is 60% of the total. So to calculate a setting, we could use the 8 times rule of thumb along with the 60% value. For a 12/16/20 MVA transformer, the expected inrush would be 8*12*5*0.6 =288 amps. We set a little above this number (360 Amps). Distribution Transformer & Feeder Protection with Microprocessor Relays 63 Transformer inrush UNFILTERED current. The peak current is about 1800 amps. Transformer inrush FILTERED current (filtered by digital filters to show basically only 60 HZ). Peak is about 700 amps. Distribution Transformer & Feeder Protection with Microprocessor Relays 64 Distribution Transformer & Feeder Protection with Microprocessor Relays Microprocessor Feeder Relay Overcurrent Reclosing Fast Trip Block Output Breaker Failure Output Elements We Set: 51P 50P 51G 50G 51Q 65 Feeder Phase Overcurrent Settings 51P - Phase Time Overcurrent Pickup Set above load and cold load (960 Amps for 500 Amp feeder) Same as EM pickup 51P Time Dial Same as EM relay (coordinate with downstream protection with CTI) Select a curve 50P Phase instantaneous Pickup Set the same as the 51P pickup (960 Amps) Distribution Transformer & Feeder Protection with Microprocessor Relays 66 Feeder Ground Overcurrent Settings 51G - Phase Time Overcurrent Pickup Same as EM pickup which is 480 Amps 51G Time Dial Same as EM relay (coordinate with downstream protection) Select a curve 50G Phase instantaneous Pickup Set the same as the 51G pickup Distribution Transformer & Feeder Protection with Microprocessor Relays 67 Feeder Negative Sequence Overcurrent Settings 51Q - Negative Sequence Time Overcurrent Pickup Set with equivalent sensitivity as the ground element (not affected by load) Coordinate with downstream protection 51Q Time Dial Same as EM relay (coordinate with downstream protection) Select a curve 50Q Negative Sequence instantaneous Pickup DONT USE!!!!! Contributions from motors during external faults could trip this Distribution Transformer & Feeder Protection with Microprocessor Relays 68 The differential relay is connected to both the high and low side transformer BCTs. EM Differential Relay Since the distribution transformer is connected delta wye the transformer CTs have to be set wye delta to compensate for the phase shift. Transformer Differential Protection 69 87 R1 87 OP 87 R2 PRI I PRI I SEC I SEC I EXTERNAL FAULT THE SECONDARY CURRENTS FLOW THROUGH BOTH RESTRAINT COILS IN THE SAME DIRECTION AND THEN CIRCULATE BACK THROUGH THE CT'S. THEY DO NOT FLOW THROUGH THE OPERATE COIL CURRENT FLOW THROUGH AN E/M 87 DIFFERENTIAL RELAY FOR AN INTERNAL AND EXTERNAL FAULT BCT'S BCT'S CT POLARITY MARK Transformer Differential Protection External Fault 70 87 R1 87 OP 87 R2 PRI I PRI I INTERNAL FAULT THE SECONDARY CURRENTS FLOW THROUGH BOTH RESTRAINT COILS IN OPPOSITE DIRECTIONS, ADD AND THEN FLOW THROUGH THE OPERATE COIL AND BACK TO THE RESPECTIVE CT'S SEC I SEC I BCT'S BCT'S CT POLARITY MARK Transformer Differential Protection Internal Fault 71 GRAB YOUR HANDOUT! MOSCOW FEEDER 515 PROTECTION EXAMPLE 72 The Scenario A hydraulic midline recloser on a 13.8kV feeder in Moscow, ID is being replaced by a newer relayed recloser. The recloser is P584 on feeder 515. The field engineer would like to replace the recloser in the existing location. Protection engineer must review the feeder protection and report back to the field engineer. NOTE: Avista designs for a fuse saving scheme with one instantaneous trip. The field engineers decide if they want to enable or disable the instantaneous tripping. 73 MOSCOW FEEDER 515 PROTECTION EXAMPLE Where do we start the protection design? 1) Gather Information: Feeder Rating (expected load) Protective devices (Breakers, line reclosers, fuses) Fault Duty (at each protective device) Conductors to be protected Project deadline (tomorrow?) 74 How do we proceed? At each coordination point Loading Coordination What will coordinate with the downstream device Are we above the fuse rating Conductor Protection minimum conductor that can be protected by the feeder settings or fuse Fault Detection Can we detect the fault by our 2:1 margin Fuse Saving for Temporary faults What can a fuse be protected up to? 75 Begin at the END POINT 8: This is a customers load and we are using 3-250 KVA transformers to serve the load. The full load of this size of bank is 31.4 amps. The Avista transformer fusing standard says to use a 65T on this transformer so thats what well choose. 76 FUSE - POINT 6B: What we know: 3 lateral feeding to a 65T at the end #4 ACSR conductor Fuse Selection: Loading Assume the load is all downstream of point 8, so a 65T or higher will still suffice. Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a 100T or smaller fuse Fault Detection - Under the Relay Setting Criteria we want to detect the minimum line end fault with a 2:1 margin. The SLG is 463 so we calculate the max fuse as follows: 463/2 (2:1 margin) = 231 amps. T fuses blow at twice their rating so divide by 2 again, with a result of 115. Fuse must be 100T or less. Coordination From Table 2, we see that we need an 80T or larger to coordinate with the downstream 65T fuse (at fault duties <1400A w/preload) Fuse Saving - From Table 1 we see that an 80T fuse can be protected up to 2,050 amps for temporary faults and the 3 fault is 1,907 amps so we could choose an 80T or higher from that standpoint 77 Point 6B - So what fuse size should we use? 78 POINT 5 Midline Recloser What we know: Conductor to protect: #4 ACSR (can carry 140A load) Max fuse to coordinate with =100T (FUTURE per distribution engineer) Maximum load (per engineer) =84A Settings Considerations: Loading: Cold load would be 84*2 =168 A, but the conductor can carry 140A max. Size for some load growth by setting at 2*conductor rating. 300 Amp phase pickup setting. NOTE: we dont design settings to protect for overload. Conductor Protection: From the table, Avistas 300A feeder settings can protect down to #2 ACSR, so 300A pickup is still acceptable. Review curves to confirm. Fault Detection: detect the minimum fault with a 2:1 margin. Here the min fault is at point 6 1. The - fault at point 6 is 0.866*1907 =1,651 so our margin to detect that fault would be 1651/300 =5.5:1 so no problem with the 300 amps PU from that standpoint (used - because its the minimum multi phase fault) 2. The SLG at point 6 is 1,492 so we could set the ground up to 1492/2 =745 amps and still detect the fault. However, our criteria says to set as low as possible and still coordinate with the largest downstream device and from above were trying to use a 100T. Based on curves, this is 300 amps (same as phase, which is unusual). Coordination: Based on fault study, set the time dial to coordinate with a 100T fuse with 0.2 second CTI. Fuse Saving: The fault duty at the recloser is 3453 3PH and 2762 1LG. An instantaneous trip will protect the 80T fuse if the fault duty is less than 2050 Amps. Some fuse protection is compromised but there is nothing we can do about it. 79 TRUNK FUSE - POINT 3C: What we know: #4 ACSR 3 trunk Load is 84 Amps Downstream protection is the midline recloser Fuse Selection: Loading Assume the load is the same as at the midline recloser. We set that at 300A, and a 200T can carry 295 A continuous. Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a 100T or smaller fuse. Fault Detection - Under the Relay Setting Criteria we want to detect the minimum line end fault with a 2:1 margin. SLG at midline is 2762 so even a 200T would provide enough sensitivity. Coordination PROBLEM! We have coordinated the midline with a 100T, so the upstream fuse must coordinate with that. Fuse Saving: As before, some fuse saving is compromised due to higher fault duty. 80 TRUNK FUSE Point 3C - Solutions? 81 TRUNK FUSE Point 3C - Solutions? Move Recloser Re-conductor 82 FEEDER BREAKER - POINT 1: What we know: This is a 500 amp feeder design. The load is 325 amps and cold load 650 per field engineer. Downstream protection is either the midline recloser or a 140T fuse. Settings Considerations: Loading: A standard 500 amp feeder phase pickup setting of 960 A will carry all normal load and pick up cold load. The ground pickup does not consider load and will be set at 480A. Conductor Protection : The main trunk is 556 ACSR and from Table 7 a 500 amp feeder setting of 960 A can protect 1/0 ACSR or higher. Laterals with smaller conductor must be fused. Fault Detection: The - fault at point 5 is 0.866*3453 =2990 so our margin to detect that fault would be 2990/960 =3.1:1 The SLG at point 5 is 2,762 so our margin to detect that fault is: 2762/480 =5.7:1 Coordination: Use fault study to calculate settings to achieve 0.2 second CTI to fuses and 0.3 second CTI to the recloser. Fuse Saving We have decided that a 140T fuse is the maximum fuse we will use on the feeder even though it cant be saved by an instantaneous trip at the maximum fault duties. 83 Questions?