PRODUCT MANUAL

FCC PM05C_ENG
Date: February 2005
Supersedes: FCC PM04B_ENG






Chilled Water Fan Coils


CEILING CONCEALED DUCTED


Models: MCC - CW























CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 2/28





INDEX

General Features and Technical Data page 3
Sound Level page 4
Operating Limits and Pressure drops page 5
Outlines and Dimensions page 6
Control Features page 8
- Controls page 8
- Self Diagnosis Table page 8
- Wired Controller SLM3
- Wired Controller Netware2
- Installation of the remote control LCD
page
page
page
9
10
12
Network and System connection page 13
Accessories page 14
Wiring Diagrams page 16
Blower Performance Curves
page 18



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 3/28


GENERAL FEATURES AND TECHNICAL DATA


Available in 8 sizes, MCC line offers a wide range of solutions to air distribution problems applicable on both
new and refurbished buildings.

The robust construction is of corrosion-proof galvanised aluminium. Units feature centrifugal fans, with
forwards curved blades, statically and dynamically balanced with three speeds single-phase motor. The
drain pan is externally insulated to prevent water condensation.

MCC range is completed with a wide range of accessories, such as:
plenum with supply grille discharge adaptor
return bracket adaptor
return grille with filter
Y-joint
insulating aluminium pipes
supply grille

All units feature, as standard, the electronic board [for application with/without valve] and wired control for
wall mount installation.



TECHNICAL DATA


MODEL MCC 010CW 015CW 020CW 025CW 030CW 040CW 050CW 060CW
Nominal Air Flow
(SHigh/High/Medium/Low)
m
3
/h
510/475/
410
730/630/
460
1050/1000
/850
1430/1340
1090
1700/1610
1530/1480
2210/1960
1870/1780
2640/2550
2510/2300
3060/2900
2800/2250
Available External Static
Pressure
Pa 50 50 50 50 150 150 150 150
Total Cooling Capacity
1
kW 2,7 4,8 6,0 7,3 8,8 11,3 14,5 17,5
Total Sensible Capacity
1
kW 2,0 3,5 4,4 5,3 6,5 8,5 10,7 12,8
Heating Capacity2 kW 3,3 5,2 6,4 7,9 9,7 12,8 16,3 19,3
Water Flow Rate l/s 0,126 0,228 0,286 0,345 0,418 0,538 0,692 0,834
Water Pressure Drop -
Cooling
kPa 14 45 86 125 86 79 56 81
Lp (Sound Pressure Level)
3
dB(A) 33/30/26 37/34/29 38/36/24 40/39/36
(49)/46/
42/38
(51)/49/
45/41
(53)/52/
52/47
(55)/53/
50/47
Power Input kW 0,071 0,102 0,148 0,173 0,421 0,550 0,670 0,748
Current Input A 0,30 0,43 0,65 0,74 1,90 2,60 2,90 3,20
Power Supply V/ph/Hz 220-40/1/50
Diameter Condensate Drain inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Water Connections inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Total Volume litres 1,03 1,27 1,55 1,78 2,45 2,81 3,56 4,16
Weight kg 17 21 22 25 39 42 54 62
NOTES
1. At the following nominal conditions: 7/12C inlet/outlet water temperature; 27C db / 19C wb inlet air temperature; high speed
2. At the following nominal conditions: 50C inlet water temperature; 20C inlet air temperature; same water flow as for cooling; high speed
3. At nominal air flow; (super high)/high/medium/low fan speed; 1.4 m below the centre of the unit; 2 m lenght duct at the air discharge outlet and air return inlet (according to
GB/D17758)




CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 4/28


SOUND LEVEL

SOUND PRESSURE LEVEL [Lp]
Power Supply: 240V/1PH/50Hz
MCC - CW: 1,4 m below the unit (according to GB/D17758)

SOUND POWER LEVEL [Lw]
Power Supply: 240V/1PH/50Hz
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
High 33 30 30 29 22 16 10 33
Medium 31 28 28 26 20 13 8 30
Low 28 25 24 22 16 10 7 26
High 39 36 34 32 27 18 11 37
Medium 35 34 32 29 23 14 9 34
Low 32 29 28 25 17 11 8 29
High 42 39 36 34 28 22 17 38
Medium 41 37 34 31 26 20 15 36
Low 40 36 32 29 23 18 13 34
High 42 41 37 34 31 29 23 40
Medium 41 40 36 33 29 28 22 39
Low 36 35 33 31 26 27 21 36
High 50 45 43 42 37 31 26 46
Medium 45 40 40 38 32 26 20 42
Low 42 36 37 33 28 22 15 38
High 54 47 47 45 39 35 29 49
Medium 49 42 43 41 35 31 24 45
Low 45 39 41 37 30 26 18 41
High 54 49 49 48 43 37 35 52
Medium 53 47 46 47 40 35 29 50
Low 51 45 44 44 36 32 26 47
High 55 49 49 50 44 37 33 53
Medium 53 46 47 47 39 34 28 50
Low 51 43 44 43 35 30 24 47
Speed Model
1/1 Octave Sound pressure level (dB,ref 20Pa) Lp
[dB(A)]
MCC010CW
MCC015CW
MCC020CW
MCC025CW
MCC030CW
MCC040CW
MCC050CW
MCC060CW
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
High 57 54 52 52 51 46 44 57
Medium 54 51 50 49 48 43 39 54
Low 51 48 47 46 44 39 35 51
High 60 58 57 56 54 48 44 61
Medium 56 55 54 53 50 44 40 58
Low 52 50 49 48 44 37 34 52
High 63 62 61 61 59 55 51 65
Medium 61 61 59 60 58 53 49 64
Low 57 56 56 56 53 48 44 60
High 63 52 61 62 59 56 53 66
Medium 61 60 59 60 57 53 50 64
Low 58 57 56 57 54 49 47 61
High 65 66 68 69 65 63 60 73
Medium 61 62 64 65 61 58 55 69
Low 56 58 60 61 57 53 49 64
High 65 8 70 72 68 66 65 76
Medium 65 65 67 68 64 62 59 72
Low 59 61 63 64 60 57 54 68
High 67 69 71 72 69 66 64 76
Medium 6 66 69 69 66 63 61 73
Low 63 64 66 67 62 60 57 70
High 69 70 72 74 71 69 68 78
Medium 69 68 70 71 67 65 63 75
Low 64 65 67 67 63 61 59 71
Speed
1/1 Octave Sound pressure level (dB,ref 20Pa) Lw
[dB(A)]
Model
MCC010CW
MCC015CW
MCC020CW
MCC025CW
MCC030CW
MCC040CW
MCC050CW
MCC060CW



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 5/28



OPERATING LIMITS AND PRESSURE DROPS


OPERATING LIMITS MCC - CW
Water Circuit
Maximum water-side pressure
Minimum entering water temperature
Maximum entering water temperature

16.4 kg/cm
2
3C (cooling)
70C (heating)
Room air
Minimum temperature
Maximum temperature

16C (cooling), 10C (heating)
36C (cooling), 30C (heating)
Power supply
Nominal single-phase voltage
Operating voltage limits

230 V / 50 Hz
10%Volt / 2 Hz





PRESSURE DROPS


MCC 010 - 025 CW MCC 030 - 060 CW











*The pressure drop is for the coil only and excludes water connections and valves.

0
20
40
60
80
100
120
140
160
0,050 0,100 0,150 0,200 0,250 0,300 0,350 0,400
Water Flow* [l/s]
P
r
e
s
s
u
r
e

d
r
o
p
*

[
k
P
a
]
0
20
40
60
80
100
120
140
0
,
0
5
0
0
,
1
5
0
0
,
2
5
0
0
,
3
5
0
0
,
4
5
0
0
,
5
5
0
0
,
6
5
0
0
,
7
5
0
0
,
8
5
0
0
,
9
5
0
Water Flow* [l/s]
P
r
e
s
s
u
r
e

D
r
o
p
*

[
k
P
a
]
010
015
020
025
030
050
060
040



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 6/28



OUTLINES AND DIMENSIONS


MODELS MCC 010 CW
A mm 765
B mm 741
C mm 702
D mm 261
E mm 411
F mm 351
G mm 171
H mm 118


MODELS MCC 015 CW MCC 020 CW MCC 025 CW
A mm 905 1005 1200
B mm 881 1041 1176
C mm 841 1002 1137
D mm 261 261 261
E mm 411 411 411
F mm 349 349 349
G mm 171 174 171
H mm 118 128 118



B
F
E
A
H
G
C
D
Electronic board
NIM (Optional)
B
G
F
E
D
A
C
H
Scheda elettronica
NIM (Opzionale)
D
Electronic board
NIM (Optional)



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 7/28



MODELS MCC 030 CW MCC 040 CW MCC 050 CW MCC 060 CW
A mm 999 1115 1369 1564
B mm 956 1072 1326 1526
C mm 917 1033 1287 1487
D mm 378 378 378 378
E mm 541 541 541 541
F mm 462 462 462 462
G mm 187 187 187 187
H mm 142 142 134 134








B
C
F
E
A
H
G
Electronic board
NIM (Optional)
D



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 8/28


CONTROL FEATURES


A. CONTROLLI


MODELS STANDARD OPTIONAL
WIRED CONTROL WIRED CONTROL + REMOTE CONTROL
MCC 010 060 CW
SLM3
NETWARE2
or
(SLM3) + AC5300





NETWARE2 SLM3 AC5300





SELF DIAGNOSIS TABLE

WIRED
7 SEGMENT DISPLAY)
OPERATION / FAULTY INDICATION
E1 blinking blinks 4 times
E2 blinking blinks 4 times
E4 blinking blinks 1 times
E6 blinking blinks 2 times




CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 9/28



SLM3 WIRED CONTROL

SLM3 AC5300 (REMOTE CONTROL)
(OPTIONAL)

1. ON/OFF switch
Press to start the air conditioner unit.
Press again to stop the unit.
2. Temperature setting
Set the desired room temperature.
Press button to increase or decrease the set temperature. Setting range are between 16oC to 30oC (60oF to
80oF).
3. Operation Modes
Press the mode button for select the type of operating mode.
- Cooling Only :
COOL, FAN, DRY
- Heat Pump :
COOL, FAN, DRY, HEAT
4. Fan Speed selection.
Press the button until the desired fan speed is achieved.
5. Timer.
Press the set button to select the switch timer of the air conditioner unit (the setting range is between 1 to
15 hours).
6. Sleep mode
Press button to activate the sleep function. This function can only be activated under cool or heating
mode operation. When it is activated under cool mode operation, the set temperature will increase 0.5oC
after 30 minutes, 1oC after 1 hour and 2oC after 2 hours. If it is activated under HEAT mode operation, the
set temperature will be decreased 0.5 C after 30 minutes, 1 C after 1 hour and 2 C after 2 hours.
7. Air Swing
Press button to activate the automatic air swing function.
8. Sensor
Infra red sensor to receive signals from wireless controller.
9. LED display
To display the set temperature (in C) and timer delay setting (in hours).
10. Transmission source
To transmit signals to the air conditioner.



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 10/28



NETWARE2 WIRED CONTROL

DISPLAY
A : Fan Speed Display
Displays the fan speed setting
(Auto/High/Medium/Low)
B : Operation Mode Display
Displays the current mode of operation.
C : Sleep Display
Display the sleep / energy saving status.
D : Error Display
E : Swing Display
Display the aur swing status.
F : Key Lock Display
Display indicates when key lock function is activated.
G : C or F Display
Display the temperature in C or F.
H : Current Time Start / Stop Time Display
Display the current time as well as the start and stop time programmed.
I : On / Off Status Lamp Display
J : Set Temperature or Room Temperature Display
Display the set or room temperature.

OPERATION
K : Operating Lamp
L : On / Off
Starting operation :
When the unit is off, press the ON/OFF button. The
operation LED lights and the unit will be turned on.
Stopping operation :
When the unit is on, press the ON/OFF button. The
operation LED is extinguished and controls are
turned off.
M : Set Temperature
Press this button to set the temperature. By
pressing up or down once, temperature changes by 1C
(or 1F).
The temperature range is16C to 30C (60F to 85F).
In FAN mode, temperature can not be set.
Pressing up and down buttons simultaneously will toggle the temperature unit between C and F.
When set temperature button is pressed, the set temperature will be displayed for 5 seconds. After
that, room temperature will be displayed.
N : Mode
Press MODE button to select operation mode from Cool, Heat, Dry and Fan. The display will show
the selected mode.
O : Fan
Press FAN button to select Auto, High, Medium or Low fan speed.
P : Swing
Press SWING button to activate the air sweep function.
Q : Sleep
Press SLEEP button to activate the sleep or energy saving mode.



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 11/28



R : Timer Hold / Resume Display
S : Current Time Display
T : Operating Lamp
U : Key Lock
This feature protects the controls from being
tampered with by children or unauthorized
persons.
To activate, press the MINUTE button three
times consecutively. KEY LOCK symbol will
appear on
the LCD display.
During this time, ON/OFF button and FAN
button can be used.
To cancel this feature, press the MINUTE button again three times consecutively.
V : Minute
When the control is in set clock or set timer mode, pressing the HOUR button will change the set
hour.
W : Hour
When the control is in set clock or set timer mode, pressing the HOUR button will change the set
hour.
X : Day
When the control is in set clock or set timer mode, pressing the DAY button will change the set day.
Y : Clock
Press button once to set the clock mode.
Press button again to disable the clock mode.
When the clock mode is activated, the time and date can be set or changed by pressing the DAY,
HOUR or MINUTE buttons.
Z : Timer Hold / Resume
If 7-days timer is set, the word TIMER ACTIVE is displayed.
To clear the timer setting, press and hold the HOLD button for 2 to 3 seconds until the word TIMER
ACTIVE is no longer displayed.
To resume the timer setting after the timer has been placed on hold, press and hold the HOLD
button again for 2 to 3 seconds until the word TIMER ACTIVE is displayed.

Other functions
- Last state memory using battery back up.
For 7-days programmable time option, battery back up is used to retain the last state data.
Units without battery back up will depend on the EEPROM on the main board.
- Error Indicator
Error code will be shown for any abnormal condition detected.
Refer to main board error codes for detail.





CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 12/28


INSTALLATION OF LCD REMOTE CONTROLLER


Guide

1. First, open up the casing of the LCD remote controller into its top and bottom case using a
screwdriver.To do this, insert the screwdriver into the lower slot and slide it in the outward direction.

2. Fix the bottom case onto the wall with the 2 wooden screws provided. Then, insert the 4 connecting
wires (from the main board) through the slot on the lower center of the case as shown below.

3. Connect one end in each of the 3 wires to the terminal block behind the top case as illustrated.

4. To select cooling only model or heatpump model, some adjustment required in the dip switch setting.

5. Fasten back the top and bottom case into place. Hook the two upper claws into their respective slots and
snap the lower part shut.



DIP-SWICH SETTING FOR MODEL SELECTION


PIN FUNCTION REMARKS
JH &JD RESERVE JH-OFF,JD-OFF
COOL, DRY, FAN JH-OFF,JD-ON
COOL, DRY, FAN, HEAT JH-ON,JD-OFF
RTC NO REAL TIME CLOCK RCT-OFF
REAL TIME CLOCK RCT-ON
NO DRY WITHOUT DRY FUNCTION NO DRY-ON
DRY FUNCTION NO DRY -OFF






CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 13/28


NETWORK AND SYSTEM CONNECTION

It allows to set up a network of up to 16 Fan Coils in a Master & Slave configuration.

SMART MANAGER

When part of a hydronic system, all FCUs' operations can be managed through Smart Manager. Acting as
central controller, Smart Manager allows the user to visualize the status, set operating modes and parameter
values for up to 50 Chillers and 256 Fan Coils, by individual unit, by group or by system.




CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 14/28


ACCESSORIES








1.Delivery Plenum
assembly
2.Adaptor

3.Return adaptor with
bracket

4.Return grille with
adaptor and filter



5.Y joint

6.Insulated alluminium
tube
7.Anemostat






























7
2
1
5
3
6
4
7
2
1
5
3
6
4



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 15/28



VALVE KITS

MCC - CW

The kit includes:

- 3-way/4-port regulating valve; diameter
- thermoelectric actuator 230 vca
- copper pipes 18 with welded connections GAS, Niples type
- fittings

















*measures in mm
100.9
86.8
28.3
186.7
58.0
86.8
100.9
86.8
28.3
186.7
58.0
86.8



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 16/28


WIRING DIAGRAMS


MODELS MCC 010 / 015 / 020 / 025 CW
SLM3 / NETWARE2 WIRED CONTROL














N2
N
1
Y
E
L
L
O
W

(
F
M
)
B
L
U
E

(
F
H
)
B
R
O
W
N

(
F
L
)
FAN MOTOR
B
L
A
C
K
TO CHILLER UNIT
SOLENOID VALVE
E 50Hz
N 1 PHASE
L 240 VAC
LOW
CN6
ROOM
COMP
TRANSFORMER
MED
T FULL
L
I
V
E
V
A
L
V
E
H
I
G
H
V
A
L
V
E
L
W
H
I
T
E
R
E
D
B
L
A
C
K
N
CN4
O
D
I
D
H
E
A
T
THERMISTOR
C
O
I
L

S
E
N
S
O
R
VALVE
HEAT
SOLENOID VALVE : OPTIONAL
- - - : FIELD SUPPLY WIRING
- WITH JUMPER FOR HEAT PUMP
- WITHOUT JUMPER FOR VALVELESS APPLICATION
- WITH JUMPER FOR VALVE APPLICATION
- WITHOUT JUMPER FOR COOLING ONLY



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 17/28



MODELS MCC 028 / 030 / 038 / 040 / 050 / 060 CW
SLM3 / NETWARE2 WIRED CONTROL











SOLENOID VALVE
TO CHILLER UNIT
Y
E
L
L
O
W

(
F
L
)
W
H
I
T
E

(
F
H
)
B
L
U
E

(
F
M
)
N
1
N2
B
L
A
C
K
BLOWER
MOTOR
N
B
L
A
C
K
R
E
D
W
H
I
T
E
L
V
A
L
V
E
H
I
G
H
V
A
L
V
E
L
I
V
E
T FULL
MED
TRANSFORMER
COMP
ROOM
CN6
LOW
L 240 VAC
N 1 PHASE
E 50Hz
C
O
I
L

S
E
N
S
O
R
THERMISTOR
H
E
A
T
I
D
O
D
CN4
RED BLACK
- WITHOUT JUMPER FOR COOLING ONLY
- WITH JUMPER FOR HEAT PUMP
- - - : FIELD SUPPLY WIRING
SOLENOID VALVE : OPTIONAL
HEAT
VALVE
- WITHOUT JUMPER FOR VALVELESS APPLICATION
- WITH JUMPER FOR VALVE APPLICATION



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 18/28


BLOWER PERFORMANCE CURVES


MCC 010CW



PRESSIONE
INTERN
Portata Aria
Pr
es
si
o
n
e
St
ati
ca
T
ot
al
PRESSIONE
INTERN
Portata Aria
Pr
es
si
o
n
e
St
ati
ca
T
ot
al
CFM
Portata
T
o
t
a
l

S
t
a
t
i
c

P
r
e
s
s
u
r
e

[
m
m

w
a
t
e
r
]

INTERNAL
STATIC
0

100 200

300 400 500 600 700 800

m
3
/h
Flowrate



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 19/28



MCC 015CW





PRESSIONE STATICA
INTERNA
Portata Aria [CFM]
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
PRESSIONE STATICA
INTERNA
Portata Aria [CFM]
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
0 200 400 600 800 1000 1200 1400 1600
CFM
m
3
/h
Portata Aria
T
o
t
a
l

s
t
a
t
i
c

P
r
e
s
s
u
r
e

[
m
m

w
a
t
e
r
]

INTERNAL
STATIC
Flowrate



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 20/28




MCC 020CW






P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
PRESSIONE STATICA
INTERNA
Portata Aria [CFM]
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
PRESSIONE STATICA
INTERNA
Portata Aria [CFM]
CFM
m
3
/h
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Portata Aria
T
o
t
a
l

s
t
a
t
i
c

P
r
e
s
s
u
r
e

[
m
m

w
a
t
e
r
]

INTERNAL
STATIC
Flowrate



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 21/28



MCC 025CW




Portata Aria [CFM]
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
PRESSIONE STATICA
INTERNA
Portata Aria [CFM]
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
PRESSIONE STATICA
INTERNA
CFM
m
3
/h 0 200 400 600 800 1000 1200 1400 1600 1800 2000

Portata Aria
Portata Aria
T
o
t
a
l

S
t
a
t
i
c

P
r
e
s
s
u
r
e

[
m
m

w
a
t
e
r
]

INTERNAL
STATIC
Flowrate



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 22/28




MCC 030CW





Portata Aria [CFM]
PRESSIONE STATICA
INTERNA
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
Portata Aria [CFM]
PRESSIONE STATICA
INTERNA
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
CFM
m
3
/h
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
Portata Aria
T
o
t
a
l
S
t
a
t
i
c
P
r
e
s
s
u
r
e
[
m
m
w
a
t
e
r
]
INTERNAL
STATIC
Flowrate



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 23/28




MCC 040CW





0 300 600 900 1200 1500 1800 2100 2400 2700 3000
Portata Aria
PRESSIONE STATICA
INTERNA
Portata Aria [CFM]
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
PRESSIONE STATICA
INTERNA
Portata Aria [CFM]
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
CFM
m
3
/h
T
o
t
a
l

s
t
a
t
i
c

P
r
e
s
s
u
r
e

[
m
m

w
a
t
e
r
]

INTERNAL
STATIC
Flowrate



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 24/28




MCC 050CW





Portata Aria
PRESSIONE
INTERN
Pr
es
si
o
n
e
St
ati
ca
T
ot
al
PRESSIONE
INTERN
Pr
es
si
o
n
e
St
ati
ca
T
ot
al
CFM

m
3
/h

Portata
T
o
t
a
l

S
t
a
t
i
c

P
r
e
s
s
u
r
e

[
m
m

w
a
t
e
r
]

INTERNAL
STATIC
Flowrate
0 500 1000 1500 2000 2500



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 25/28




MCC 060CW



Portata Aria [CFM]
PRESSIONE STATICA
INTERNA
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
Portata Aria [CFM]
PRESSIONE STATICA
INTERNA
P
r
e
s
s
i
o
n
e

S
t
a
t
i
c
a

T
o
t
a
l
e

[
m
m

a
c
q
u
a
]
CFM
m3/h
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000

Portata aria
T
o
t
a
l

S
t
a
t
i
c

P
r
e
s
s
u
r
e

[
m
m

w
a
t
e
r
]

INTERNAL
STATIC
Flowrate



CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 26/28



We reserve the right to make changes in design and construction at any time without notice.














































CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 27/28






















































CHILLED WATER FAN COILS MCC: McQuay FCC PM05C_ENG page 28/28





















































McQuay Italia S.p.A.
S.S. Nettunense, km 12+300 00040 Cecchina (Roma) Italia
tel. +39 06 937311; fax +39 06 9374014; e-mail mcquay@mcquayitalia.com
www.mcquayeurope.com - info@mcquayeurope.com