PCS 7 V7.1 SP3 / CEMAT V7.1 SP1 How to incorporate the SINAMICS Module
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 43-62
6 How to install Siemens SINAMICS object into your project
6.1 PLC part
6.1.1 Preparations
If not already available, install the appropriate typefile for the SIEMENS SINAMICS Series frequency converters by using the Hardware configuration ->Options ->Install New GSD.
On your subcontrol CD you will find the following GSD typefiles :
- SI018105.GSG for SINAMICS G130/G150 - SI018116.GSG for SINAMICS G120, CU240S DP V2.10 - SI028116.GSG for SINAMICS G120, CU240S DP V3.0 - SI038116.GSG for SINAMICS G120, CU240S DP V3.2 - SI0280E5.GSG for SINAMICS S
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 44-62
6.1.2 Hardware configuration
The SINAMICS G130 frequency converter is representative for the different SINAMICS frequency converter types that support the message frame 352 with 6 words PCD read / write. Select the SINAMICS G130/G150 object out of the catalogue folder SINAMICS, connect it to the designated DP-Master system and assign an available DP-Slave address.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 45-62
Select the SIEMENS Telegram type 352 and drop it to I/O area. The I/O addresses will be automatically predefined. If the predefined addresses are not suitable for your project reassign them manually.
Compile and download the changes. Make sure that the parameters on Siemens SINAMICS frequency converter matches your adjustment (Telegram type, slave address).
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 46-62
6.1.3 Hardware configuration when the tool STARTER is used
The Siemens drive configuration tool STARTER provides the possibility to configure frequency converters and other drive controllers via the DP interface of the S7 CPU from your engineering station. In order to grant access to the converters you have to use a different STEP 7 hardware configuration.
Select the object SINAMICS G130 directly out of the folder SINAMICS ->SINAMICS G130 and connect it to your DP mastersystem :
After connecting the SINAMICS object to your DP mastersystem the following configuration dialogs will appear. If not so, you have presumably selected the DP slave from the wrong object folder (The embedding of the GSD type files as well as the configuration tool STARTER creates a folder named SINAMICS in the hardware catalogue). If the frequency converter should be configured via STARTER, it is essential to use the correct object out of the hardware catalogue.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 47-62
The first configuration dialog requires the selection of the correct device version of the used frequency converter :
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 48-62
Next, select the SIEMENS message frame 352, PZD 6/6 for the converter :
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 49-62
The I/O addresses will be assigned automatically, but you may change them according to your project requirements. Therefore use the tab Details of the object property window.
After compiling and downloading the hardware configuration and adjusting the settings of the SINAMICS the PROFIBUS connection between the S7-PLC and the SINAMICS should work.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 50-62
The component view of the SIMATIC MANAGER will show a converter object for each SINAMICS connected to your PLC. Double click on the converter object in order to start the drive configuration tool STARTER :
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 51-62
6.1.4 Software configuration
Open the library C_SINA out of the folder S7_lib of the CD and open it additionally to your project. Copy the function block C_SINA (FB 1082) in the component view into the block folder of the designated PLC in your project and the block container of the project library. Rename the function block if FB 1082 is already used in your project. Open the plant view of your project and insert a new CFC in the designated folder. Assign a proper name for that new CFC and open it. Insert the SINAMICS function block (C_SINA) under Options ->block types from the Offline block folder into the chart folder.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 52-62
After pressing F5 (View update) the SINAMICS function block should appear in the library SUBC. Drag and drop the C_SINA function block from the catalog into the CFC plan and assign the block name and comment under block properties according to your tag defaults.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 53-62
PCS7 is able to generate a symbol in the process pictures for each Siemens SINAMICS - Object used in CFC. In order to activate this automatic function you have to name the wanted blocksymbol.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 54-62
Then open the alarm dialog.
The alarm dialog is used to configure the alarms of the block. You have to define the additional text for each of the 16 alarms, according to the CEMAT Engeering rules use the block comment.
Now close the alarm dialog and the property window. Within the Process Object View this work (copy the block comment) could be easily done in one step for all 16 messages.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 55-62
Since Cemat V7.1 SP1 the block C_SINA doesn't need the adapter block C_APADT any more. As usual in Cemat, the block C_SINA could connected via GR_LINK1, GR_LINK2 or MUX_LINK to his groups and routes from the CEMAT library.
Change the parameters B_ADDR_I and B_ADDR_Q referring to your hardware configuration. Make all necessary connections to the function block according to your project requirements. After compiling and download of the program changes and the necessary adjustments at the Siemens SINAMICS system the communication between the PLC and the Siemens SINAMICS system should work. In order to generate the OS variables please compile the changes of your WinCC project.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 56-62
6.2 HMI part
6.2.1 Copy bitmaps and pdl-files
Use the explorer to copy the files out of the folder WinCC\GraCS of the CD into the GraCS- folder of your project:
Open the pictures C_@PCS7Typicals_CEMV7_SINAMICS and @PCS7Typicals.pdl with the graphics designer. Copy elements out of the picture C_@PCS7Typicals_CEMV7_SINAMICS.pdl and paste them into @PCS7Typicals.pdl.
6.2.3 Position the Siemens SINAMICS control in your process screen
The standard procedure to place a Siemens SINAMICS Object in your process picture is to activate the automatic generation of the symbol in the selected picture out of the CFC. If you want to connect the symbol manually, copy the symbol of C_SINA object into your process picture. Then mark the symbol in your process picture and start the dynamic-wizzard Link a prototype to a structure and select the correct tag.
6.2.4 Configuration files
In order to display the annunciations correctly in the group status an in the alarm window of the Siemens SINAMICS object you have to copy the following files into the folder: D:\CEMAT_CS\Config C_SINA_007.CFG (german) C_SINA_009.CFG (english)
6.2.5 User Archives
To enable the functions of the info window of the Siemens SINAMICS Object and the group instance list two user arcives have to be configured if this has not already been done: SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 57-62
Open the user arcives out of the WinCC explorer and use the function Project ->Import and select the following files out of the folder D:\CEMAT_CS\ua : C_INFO.uap DriveList.uap
Save the user arcives and return to the WinCC explorer.
6.2.6 Helpfiles
Also the helpfiles have to be copied into your CEMAT installation folder D:\CEMAT_CS\DOCU\Reference\Objects:
C_SINA_007.PDF for the german documentation
C_SINA_009.PDF for the english documentation
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 58-62
6.3 Representation Forms of C_SINA
6.3.1 Faceplate of C_SINA
The faceplate provides a detailed view of the Siemens SINAMICS object and is shown by clicking the symbol in the process picture.
Object functions : The buttons Start, Stop and Non Interlocked ON/OFF are only enabled in the single-start mode of the converter and are used to start and stop the converter. If the converter is set to the single-start mode the setpoint of the Siemens SINAMICS may be changed using the input field or the scrollbar. These elements are visible only in the single-start mode.
Invocation buttons for secondary dialog :
Status Status window with status- and commandwords of the Siemens SINAMICS Diagn Diagnosis window with block interfaces and parameters Alarm Alarm window with alarms and operation messages Info Object related informations Help opens this documentation file Close close the faceplate and the secondary dialogs
alarm acknowledge group display print faceplate SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 59-62
In the local operation mode there are two buttons for adjusting the speed setpoint of the frequency converter which act in addition to the local hardware inputs (function block interfaces MORE and LESS) :
Due to security reasons the local hardware buttons have priority to the faceplate buttons.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 60-62
6.3.2 Diagnosiswindow of C_SINA
The diagnosiswindow displays the interfaces, the parameters and the actual values of the Siemens SINAMICS object. If the structured variables for the start interlock, operation interlock and protection interlocks are used, the blue circles appear in the diagnosis window, and the user may use the related buttons to jump to the faceplates of the connected blocks. The operator control elements are used in the same way compared to the faceplate. Additional the parameters may be adjusted and the operating time of the converter may be reset.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 61-62
6.3.3 Statuswindow of C_SINA
The statuswindow displays the status and command words which are sent to or received from the Siemens SINAMICS.
6.3.4 Alarmwindow of C_SINA
The alarmwindow displays the alarms and operation messages of the Siemens SINAMICS object. The operator commands of the message list correspond to the CEMAT standard.
6.3.5 Information dialog of C_SINA
The information dialog is used to display and store object-related informations and notes. These informations are stored in the user archives.
SIEMENS AG Users Manual Subcontrol SINAMICS
Edition: March 2011 I IA AS PA PRM4 Page: 62-62
7 Settings at the SINAMICS frequency converter
7.1 Setting of the DP-slave address
The DP-slave address may be set by using the DIP-switch at the Profibus communication module or by changing the parameter P0918. The address has to be the same that is configured in the STEP7 hardware configuration. Settings of the parameter P0918 do only work when the DIP-switch remains in the default setting, that means the address of the switch is set to 0. A change of the DIP-switch setting will be executed after the return of the power supply of the Profibus communication module and will overwrite the parameter P0918.