ALCATEL-LUCENT CONFIDENTIAL: The information contained in this document is
the property of Alcatel-Lucent. Except as expressly authorized in writing by Alcatel-
Lucent, the holder shall keep all information contained herein confidential, shall
disclose the information only to its employees with a need to know, and shall protect
the information from disclosure and dissemination to third parties. Except as expressly
authorized in writing by Alcatel-Lucent, the holder is granted no rights to use the
information contained herein. If you have received this document in error, please notify
the sender and destroy it immediately.
2009 Alcatel-Lucent
All Rights Reserved

P
r
e
l
i
m
i
n
a
r
y
Alcatel-Lucent 9312 Compact Node B
Outdoor Site Specification
Installation Method 06-6273
April 29, 2009
Issue Number: 2.02
0 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 1
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
Table of Contents
1.0 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Reason for Reissue. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.0 Material Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Required Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.0 Precautions and Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.0 Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.1.1 9312 Compact OD Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.1.2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1.3 Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1.3.1 9312 Compact OD Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1.3.2 Details of Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.4 Equipment Packaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1.5 Environmental and Mechanical Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1.6 User Compartment Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1.6.1 User Racks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.1.6.2 User ICO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1.6.3 RETA AISG Optional (Through TRDU AISG only) . . . . . . . . . . . . . . . . . . . . . 20
4.1.6.4 LP PCM Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.1.6.5 IEAM Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.2 9312 Compact OD Power Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.2.1 AC Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.2.2 AC Consumption of 9312 Compact OD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.3 Site Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3.1 Site Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3.1.1 Easy Access Site Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3.1.2 Difficult Access Site Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3.2 Cabinet Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3.2.1 Lifting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.2.2 Horizontal Moving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.3.2.3 Moving a Depopulated Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.3.3 Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3.3.1 Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3.3.2 Floor Flatness. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3.4 Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.4.1 Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.4.2 Cabinet Securing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.5 Wall. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.5.1 Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.5.2 Flatness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.5.3 Cabinet Securing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.6 Site Dimensioning Rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.3.6.1 Cabinet Dimensions and Distance Constraint . . . . . . . . . . . . . . . . . . . . . . . . 30
2 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.3.6.2 Site Layouts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.3.6.3 Cabinets Orientation in Outdoor Site. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.3.6.4 Input Constraint of Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.4 9312 Compact OD Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.4.1 9312 Compact OD Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.4.2 Earth Plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.4.3 Cable Tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.4.3.1 Solution 9312 Compact OD Alone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.5 Site Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.5.1 Cabinet Securing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.5.2 Cabinet Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.5.2.1 9312 Compact OD External Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.5.2.2 Ground Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.5.2.3 BTS AC Supply Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.5.3 External Cables Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.5.4 Distribution Frame for PCM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.5.5 Feeders and Antenna System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.5.6 Lightning Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.5.7 Radio Cables Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.6 Final State of Site Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.0 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.0 Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.1 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.2 Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
End of Document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 3
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
Figures
Figure 1 Cabinet Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 2 UTRAN-UMTS Terrestrial Radio Access Network . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 3 9312 Compact OD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 4 9312 Compact OD Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 5 9312 Compact OD - Outdoor Cabinet Footprint . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 6 Cabinet, Plinth and Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 7 User Compartment View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 8 User Rack Internal Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 9 C-User ICOs Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 10 RETA AISG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 11 LPPCM Module Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 12 IEAM Module layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 13 DC Power Consumption and BBUP Time (Compact) with TRDU 40W . . . . . . . 23
Figure 14 DC Power Consumption Vs TRDU Output Power . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 15 Access Within the Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 16 9312 Compact OD Cabinet Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 17 9312 Compact OD Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 18 Minimum Space Required on Site Layout for 2 Compact OD Side by Side . . . . 32
Figure 19 Minimum Space Required on Site Layout with 2 Compact OD - Back to Back . 32
Figure 20 Floor Solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 21 Wall or Pole Solution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 22 Main Site Circuit Breaker (Single Phase) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 23 Drilling Template. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 24 9312 Compact OD Bulkhead . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 25 Grounding Kits on Feeders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 26 Example of RF Link without UMTS TMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
Tables
Table 1 9312 Compact OD Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 2 Modules and Bare Cabinet Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 3 9312 Compact OD Environmental Requirements. . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 4 User Alarm Connector Pin Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 5 Access Within the Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 6 Cable Quantity for one Cabinet 9312 Compact OD . . . . . . . . . . . . . . . . . . . . . . . 36
Table 7 Type of 9312 Compact OD Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 8 BTS AC Supply Cables: Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 9 BTS AC Supply Cables: Split/Dual Phases (Europe wires) . . . . . . . . . . . . . . . . . 42
Table 10 BTS AC Supply Cables: Split/Dual Phases (US wires). . . . . . . . . . . . . . . . . . . . 43
Table 11 External Cable Section for AC Cable Gland Entry . . . . . . . . . . . . . . . . . . . . . . . 43
Table 12 External Cables Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Table 13 Types of Mini Baluns. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 14 Alcatel-Lucent Jumper RF Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Table 15 Reference Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 5
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
1.0 General Information
1.1 Description
Purpose: This document defines the specifications covering the
selection and preparation of site that must receive the Compact.
The criterion, which allows classifying a site as an easy- or difficult-
access site, is given.
Equipment: This document applies to the deployment of 9312
Compact OD. The cabinet is available on the following electrical
supplying mode:
An Outdoor AC version powered by a power plant.
The internal user space (2U 19" + 2 U 9.5") can be used to connect
user equipment (LPPCM module, IEAM Module optional or CCU of
RETA).
Application: This document is used to define site requirement.
Service Impact: None
Skill Level Requirement: None
1.2 Sequence
This is a stand-alone method.
1.3 Reason for Reissue
Reason for update:
202 Update after internal review
Closes Alert(s): None
Closes CR(s): None
Replaces Method 06-6273 dated: February 27, 2009.

6 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
2.0 Material Requirements
2.1 Required Documents
Regional Installation Safety Manuals (ISM)
Installation Method can be find at:
https://wcdma-ll.app.alcatel-lucent.com/livelink/
livelink.exe?func=ll&objId=36528788&objAction=browse&sort=nam
e&viewType=1
45-9003 Alcatel-Lucent 9312 Compact Product Safety Install
Requirements
No other materials are required to perform this method.
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 7
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
3.0 Precautions and Preparations
3.1 Precautions
Observe the general safety precautions against personal injury and
equipment damage outlined in the regional Installation Safety Manual at
all times.
Please refer to the 45-9003 Alcatel-Lucent 9312 Compact Product
Safety Install Requirements
External alarm protection: The external alarms protection are
mandatory when external alarms are used. They must be protected by
the optional IEAM module (for primary and secondary protection
module).
8 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.0 Specification
4.1 Overview
4.1.1 9312 Compact OD Characteristics
In a UMTS network, the 9312 Compact OD provides the interface
between the RNC and the User Equipment.
The 9312 Compact OD platform is part of the UTRAN architecture and
acts as a NodeB radio part.
Figure 1
TRDU 1
TRDU 2
TRDU 3
IEAM
LPPCM
xCEMu 1
xCEMu 2
xCEMu 3
xCEMu 4
xCCMu
CDAC
Batteries
cUSER ICO
Space
Supply
Unit
Cabinet Overview
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 9
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
Figure 2 UTRAN-UMTS Terrestrial Radio Access Network
- A 9312 Compact OD cabinet overview is given in Figure 3
Figure 3 9312 Compact OD
10 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.1.2 Specifications
All mechanical sub racks and mechanical support systems required
for the installation, transport and operation of the 9312 Compact OD
wireless equipment to be housed within
An optional User Interconnection module (C-USER ICO)
An optional IEAM (external alarm)
Manufacturing Commissioning Alarm module (MCA)
RF ICOr
An interconnection box including AC power distribution
Distribution Unit (CPSU)
A universal cooling unit with AC heaters
4.1.3 Dimensions and Weight
4.1.3.1 9312 Compact OD Dimensions
Table 1 9312 Compact OD Dimensions
9312 Compact OD

Height
1200 mm (47.24 in)
Height with plinth 1370mm (53.93 in)
Depth 700 mm (27.55 in)
Width 580 mm (22.83 in)
Figure 4 below shows the 9312 Compact OD dimensions and Figure 5
display the cabinet footprint.
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 11
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
Figure 4
Below View
Front
Right side
Behind
Left side
Front View
Top View
9312 Compact OD Dimensions
12 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
Figure 5 9312 Compact OD - Outdoor Cabinet Footprint
1
2
8
0

m
m

7
0
0
7
0
0

1
1
4
5

Top View
100
4.1.3.2 Details of Weight
The table hereafter gives the weight of all modules and bare cabinet:
Table 2 Modules and Bare Cabinet Weights
Compo-
nent
Weight Qty Weight With
options
Weight Without
options
lbs Kg
Pre cabled
cabinet
264.55 120 1 120 kg (264.55 lbs) 120 kg (264.55 lbs)
TRDU 2100
MHz
23.15 10.5 3 31.5 kg (69.45 lbs) 31.5 kg (69.45 lbs)
xCEMu 2.65 1.2 4 4.8 kg (10.60 lbs) 4.8 kg (10.60 lbs)
xCCMu 3.53 1.6 1 1.6 kg (3.53 lbs) 1.6 kg (3.53 lbs)
CPSU with
one rectifier
15.65 7.1 1 7.1 kg (15.65 lbs) 7.1 kg (15.65 lbs)
Rectifier 6.5 2.95 1 5.9 kg (13 lbs) 5.9 kg (13 lbs)
MCA 1.1 0.5 1 0.5 kg (1.1 lbs) 0.5 kg (1.1 lbs)
Batteries 33.07 15 4 60 kg (132.28 lbs) 60 kg (132.28 lbs)
User Space
(up to)*
8.8 4 3 12 kg (26.40 lbs) 0
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 13
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
* Not add in the subtotal
CCU Mod-
ule RETA
(optional)
2,42 1,1 1 1,1 kg (2,42 lbs) 0
LPPCM
(optional)
2.2 1 1 1 kg (2.2 lbs) 0
IEAM
(optional)
2.2 1 1 1 kg (2.2 lbs) 0
c-USER-
ICO
(optional)
2.2 1 1 1 kg (2.2 lbs) 0
Configura-
tion cabling
(estimated)
13,22 6 1 6 kg (13,22 lbs) 6 kg (13,22 lbs)
Plinth 24.25 11 1 11kg (24.25 lbs) 11kg (24.25 lbs)
Subtotal 251.5 kg (554.46
lbs)
247.4 kg (545.42
lbs)
Pallet (esti-
mated)
10 kg (22.04 lbs) 10 kg (22.04 lbs)
Total 261.5kg (576.5 lbs) 257.4 kg (567.47
lbs)
Table 2 Modules and Bare Cabinet Weights
14 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.1.4 Equipment Packaging
The cabinet is fully assembled in conventional delivery conditions,
shipped on its wooden pallet.
Note: A plinth is delivery with the cabinet.
The wooden pallet weight around 16 kg (35,27 lb) TBC
Until the cabinet is disassembled from its wooden pallet, the packaging
increases the cabinets weight and dimensions during installation phase
(moving).
For sites with difficult access, the 9312 Compact OD cabinet is ordered
fully equipped, and can be depopulated in warehouse for delivering on
site. The modules that have to be inserted in the cabinet on site are
delivered in specific protective packaging.
Figure 6 Cabinet, Plinth and Pallet
Plinth
9312 Compact OD
Wooden pallet
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 15
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.1.5 Environmental and Mechanical Conditions
The 9312 Compact OD is designed to be installed in outdoor
environment with the following requirement
Table 3 9312 Compact OD Environmental Requirements
Requirement 9312 Compact OD
Manufacturing
The 9312 Compact OD is manufactured according to the WEEE
(Waste of Electrical and Electronic Equipment) and RoHS
(Restriction of Hazardous Substances) recommendations.
Environmental
Shall be compliant with R9 Reference Documents on page 51 class
4.1E except for: low temperature and high temperature, relative
humidity levels (between 5% and 95%) condensing and high
absolute humidity (36g/m3)
Ingress Protection
Weather resistant to prevent ingress of rain, snow, dust and other
solid foreign objects to a minimum level of IP55 as specified by R2
Reference Documents on page 51
Acoustic noise
level
for protected area
The acoustic noise level shall comply with outdoor environment
class 4.1E of R7 Reference Documents on page 51
LwAd < 56 dB when t<= 25C
LwAd < 67 dB up to +55C
Temperature Con-
ditions
Designed to operate at full specification with external temperature
range from -40C to +55C, Start up to -25
Solar Radiation
Shall operate at full specification with a solar radiation of 1120W/m
within the external temperature range
Win Speed
Shall withstand the over-turning force exerted by a wind speed of 200 km/
h as defined by R10 Reference Documents on page 51, when installed
on floor, mast and wall.
Biological
Support deployment in locations with biological conditions as defined in
class 4B1 of R3 Reference Documents on page 51
Chemical Active
Substance
Support deployment in locations where the maximum levels of chemical
contaminants are those defined by R3 Reference Documents on page 51
class 4C2
Mechanical active
substance
Support deployment at locations where the maximum level of sand and
dust are those defined by reference R3 Reference Documents on page 51
class 4S2
Electrolytic Cor-
rosion
The difference in potential between dissimilar materials in contact shall
not exceed: 0,5 Volt for parts not normally exposed to the external
ambient environment
0,25 Volt for parts normally exposed to the external ambient
environment.
16 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
Impact on the Surrounding
When fitted with its cooling system, the cabinet shall not amplify
mechanically transmitted noise within the audible frequency range
(20Hz - 20KHz)
Note: The noise may be higher than the one previously indicated on the
table above due to the real configuration of the site (proximity of
walls or any reflective surfaces). In this case, specific protections
against noise can be added to comply with the local
recommendations.
Electromagnetic Compatibility
The 9312 Compact OD shall comply with different requirement in terms
of EMC.
For European market, 9312 Compact OD shall comply with the
requirements stated in R12 and R15 Reference Documents on page 51
In addition, the 9312 Compact OD Outdoor is compliant with the 3GPP
specification.
Earthquake
Vibration and
Shock
Once installed, the 9312 Compact OD shall meet the Zone 4 earthquake
requirement as specified in R11 Reference Documents on page 51
Impact on the sur-
rounding
See below
Storage and
Transport
9312 Compact OD shall comply with R5 and R6 Reference Documents
on page 51
Table 3 9312 Compact OD Environmental Requirements
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 17
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.1.6 User Compartment Characteristics
User equipment rack is proposed in all 9312 Compact OD cabinet.
A standard user ico with up to 3 outputs -48V power supply and up to 4
alarms is proposed on 9312 Compact OD, with maximal capacity:
2x 1U 19" slot at the Side of the cabinet, which can be used for:
2 x 1U for User Equipment (option, CCU RETA for example)
2x 1/2U 9.5" at the side of the 2 x 1U which can be used for:
1/2 U for IEAM-16 external alarms kit, optional.
1/2 U for LPPCM (Lightning Protection PCM), optional.
The optional C-User ICO provides connectivity for 4 DC -48V power
supplies with associated fuses.
C-User Ico is not part of the 2 1/2 U
The power budget is 350W for the user equipment shelf.
Figure 7 User Compartment View
2X1U USER
RACK 19"
Li-ion Internal
Battery (option)
PCM Lightning
Protection (option)
IEAM External
Alarm Kit (option)
C-User ICO
(option)
18 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.1.6.1 User Racks
Figure 8 User Rack Internal Space
OEM modules nominal front panel dimensions shall be:
Rack 19" (A on Figure 8):
- Height available for OEM equipment: 2U (U = 44.45mm)
- Width available for OEM equipment: Standard 19 inch (482.6mm)
- Depth available for OEM equipment: 400mm
Rack 1/2 19" (B on Figure 8):
- Height available for OEM equipment: 2U (U = 44.45mm)
- Width available for OEM equipment: around 1/2 19 inch (230mm)
- Depth available for OEM equipment: 340 mm
The fixing points shall be compatible with a standard 19 inch rack or
1/2 19", and the mounting screws shall be in accordance with the
metric standard (M6 x 15). The material of all the screws shall be
Stainless Steel.
The total weight of all the OEM modules in a 9312 Compact OD
cabinet user space shall not exceed 12 kg
The OEM modules and cables shall function at full performance,
when the local air temperature at the intake to the external surface of
the OEM module, is within the range -5C to +50C.
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 19
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.1.6.2 User ICO
Figure 9 C-User ICOs Views
PWR IN
J3
J4
J2
PWR USER1
PWR USER2
PWR USER3
J5
J6
ALARM
USE ALARM
The optional C-User ICO (USERICO) panels provides 3 x -48V DC
power ports with associated fuses. The maximum -48V DC power is
350W supplied by the cabinet. A maximum of 3 power connections are
available on 3 connectors MateN Lock female 3 contacts (-48V, 0V,
GND). A alarm connector may provide 4 alarms on one SUB-D9 pin
female connector.
The OEM module shall generate a dry loop
Note: If the alarm pin is connected to the ground (mechanical ground),
there is no alarm. If the alarm pin is open, there is an alarm.
Table 4 User Alarm Connector Pin Out
PINS SIGNAL
1 Unused
2 Unused
3 Alarm 4
4 Alarm 3
5 Alarm 2
6 Alarm 1
7 GND
8 GND
9 GND
20 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.1.6.3 RETA AISG Optional (Through TRDU AISG only)
The RETA permits the remote variable electrical tilting of cabinet
antennae for operating and optimizing the UMTS network. It is
composed of one CCU (Central Control Unit) located inside the cabinet
and other devices located outside the cabinet, one or several RCU
(Remote Control Unit),
The CCU controls one or several RCU. It provides the power for the
connected devices (RCU) and handles alarming.
The RCU or RCU Slim is a remote controlled motor. It is mounted on
the antenna and adjusts the electrical downtilt angle.
The RCU can be connected to daisy chain, no need to use a splitter.
The CCU managed the entire AISG network. It is installed in 9312
Compact OD user rack. It is connected to node B system to the xCCMu
module (in Compact) via Ethernet 10base T link (Site LAN).
The CCU is powered by DC -48V through USER ICO. It provides 3
RS485 AISG outputs to AISG antenna network via TRDU AISG and
control cables.
Some alarms coming from the CCU are transmitted to the node B via C-
USER ICO (User alarms).
The RET solution proposed only in case of co-localization of 9312
Compact OD.
Other kits constituting the global RET system (TMA AISG, RCU) are
ordering in ship loose.
TMA AISG should be used for the RETA solution (+24V)
The CCU characteristic:
Power DC -48V, Current max 1.5A
Figure 10 RETA AISG
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 21
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.1.6.4 LP PCM Module
The LPPCM module is proposed to provide the connection of 8 E1 PCM
and their protection against electrical perturbations that could occur
between the 9312 Compact OD and the customer equipment.
LPPCM has a function that protects devices from excessive voltage &
current caused by power induction, lightning, etc.
The LPPCM Module consists of one module located on the 1/2 user
space with one line connection through the PCM input and one
equipment connection through the xCCM-u board.
Figure 11 LPPCM Module Layout
22 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.1.6.5 IEAM Module
The External Alarm Module Kit is proposed to provide the connection
of 16 external alarms and 6 remote controls and their protection against
electrical perturbations that could occur between the 9312 Compact OD
and the customer equipment.
The External Alarm Module Kit consists of one module and two digital
cables and one ground cable.
The External Alarm Module Kit is located in the left hand side of Digital
Modules when viewed from the front of the cabinet.
Figure 12 IEAM Module layout
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 23
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.2 9312 Compact OD Power Requirements
This chapter describe the power characteristics and requirements for
9312 Compact OD, currently this 9312 Compact OD is proposed only
in one variant AC.
4.2.1 AC Voltage Range
The 9312 Compact OD outdoor AC only cabinet is powered from one
of the following power supply networks:
230VAC, single phase, Two wires (Phase, Neutral) and protective
earth (180/264VAC 22%/+15%)
120/240VAC, Split phase US, Three wires (Phase 1, Phase 2, Neutral)
and protective earth (180/264VAC 22%/+15%)
The AC power networks shall be TT or TN-S. However, the cabinet
shall suffer no irreversible damage when it is wrongfully connected to
an IT or TN-C power network.
The cabinet operate at full performances across the voltage range
[180V; 264V] and the frequency range [45Hz; 65Hz].
4.2.2 AC Consumption of 9312 Compact OD
Below some examples of power consumptions and battery backup time
in function of some configurations (xCEM-u, xCCM-u and TRDU 40W
2100Mhz)
Figure 13 DC Power Consumption and BBUP Time (Compact) with TRDU 40W
Note: Typical Power consumptions provided assume external
temperature at 25C, maximum assume in all the temperature
range
24 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
In case batteries are charging, the max DC power consumption is
1600W with one rectifier or 2000W when the configuration is equipped
with 2 rectifiers, thanks to the input current limitation.
In case heaters are on (during the cold start up or when temperature is
lower than 0C and equipment power consumption is lower than 800W),
the Max DC power consumption is 800W (cf Environmental cooling
system chapter).
The power supply consumption, based on the TRDU output power and
some measurements, is the following (Figures have to be confirmed
with the serial production):
Figure 14 DC Power Consumption Vs TRDU Output Power

Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 25
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.3 Site Requirements
4.3.1 Site Access
Once a site has been selected, access conditions should be evaluated to
determine whether the cabinet should be delivered populated (easy-
access site) or depopulated (difficult-access site).
The access conditions must comply with cabinet dimensions and the
available moving equipment.
The packaging can be removed to get over an obstacle (door or
staircase...) but keep some protection of the 9312 Compact OD
(Antistatic bag or vapor barrier or blanket...)
4.3.1.1 Easy Access Site Characteristics
The site access conditions allow the mechanical handling of a
populated cabinet throughout the distance separating the delivery
point from the mounting location without manual carrying.
The mechanical means used to carry and/or hoist the fully populated
cabinet (e.g. dolly system, elevator, etc) must be qualified to bear the
fully populated cabinet weight in compliance with standard security
requirements.
4.3.1.2 Difficult Access Site Characteristics
For this type of site, mechanical means cannot cover the entire
delivery to mounting location distance; part of the way (as small as it
might be) requires manual carrying. As a consequence, the cabinet
can be depopulated to reduce its weight.
Even though the cabinet can be carried manually, the maximum use
of mechanical means is encouraged to enhance the safety and security
of both staff and equipment.
4.3.2 Cabinet Handling
The 9312 Compact OD cabinets are delivered upright with a corrugated
cardboard sleeve on a wooden pallet in case of road transport. They are
delivered lying in plywood crates in case of air and sea transports. In all
cases, the specific packing allows their handling by means of a fork-lift
truck.
The equipment should be unpacked as close as possible to their precise
mounting location.
The path from the delivery point to the mounting location should be
clear of any obstacles.
26 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
Note: The Handle Extractor is now classified as a separate tool, and will
not delivered with the node B (3JR08430AA)
4.3.2.1 Lifting
The populated cabinet must be handled with mechanical devices (the
cabinet may only be guided manually during lift-off or during final
positioning, provided that basic safety rules are observed by the
personnel).
The cabinets are hoisted with 4 lifting eyes M12 type associated with a
spacer, by a lifting vehicle suited to the cabinet weight and to the site
characteristics (height, jib).
Note: This equipment should be lifted using 4 (four) lifting ring sets.
Four sets but these are NOT delivered with the Node B. (A lifting
ring set comprises 1 (one) lifting ring 1AD011980007 + 1 (one)
spacer 1AD003950005).
Since the hoisting operation with a lifting vehicle is designed to position
the cabinet directly on its mounting support, the access conditions of the
lifting vehicle are extremely important and obviously, the mounting
support, if needed, should be installed before hand.
In case of outdoor hoisting with a jib crane, the parameters to take into
account are:
Floor mechanical resistance.
Height of the building.
Width of the building.
Width of the street.
Width of pavements / sidewalks.
Natural obstacles.
Safety requirements for the hoisting operation.
All other handling methods must be specified and validated if required
by the project.
A specific manual moving by 4 installers (mover profile) or a specific
mechanical moving by 2 installers means is needed to install this 9312
Compact OD.
The empty cabinet can be carried by 2 installers (mover profile).
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 27
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.3.2.2 Horizontal Moving
A standard forklift/dolly is used to move the cabinet, secured to its
wooden pallet.
The path should be clear of obstacles (gravel, cable way, conduits...).
In case of flat roof, the driving path must be prepared to avoid damage
to original supporting surfaces, in terms of terrace floor mechanical
resistance and waterproofing.
4.3.2.3 Moving a Depopulated Cabinet
The access to reach the building entrance from the truck should respect
the following minimum dimensions given in the Table 5 below.:
Table 5 Access Within the Building
N Layout Height Width Comment
A Doors 1.80 m (5.9 ft.) 0.90 m (2.95 ft.)
B Corridor 1.80 m (5.9 ft.) 1.00 mm (3.3 ft.) Case of way in straight line.
C Corridor 1.80 m (5.9 ft.) 1.00 mm (3.3 ft.) Case of way with right angle
turn.
D Staircase 1.80 m (5.9 ft.) 1.40 mm (4.6 ft.)
E Staircase 1.80 m (5.9 ft.) 1.40 mm (4.6 ft.) Half floor (to turn).
Spiral
staircase
1.80 m (5.9 ft.) 1.40 m (4.6 ft.) Minimal interior diameter 2.80
m (9.2 ft.)
Note: Lift elevator capacity: Weight of cabinet + Handling means
weight + People weight. Check that the lift/elevator max. load is
sufficient to lift the cabinet, its means of handling and personnel
simultaneously.
Figure 15 Access Within the Building
28 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.3.3 Floor
The 9312 Compact OD cabinet can be installed either on a concrete
floor or on a raised floor.
The floor covering must be antistatic (about 1MOhms) or the technician
must use an antistatic bracelet.
4.3.3.1 Resistance
In accordance to cabinet weight and door opening, the minimum floor
resistance should be, AC fully configured: 220 kg/m

(only for the 9312


Compact OD)
If needed, a load-spreading structure should be studied in compliance
with the maximum floor resistance allowed by the supporting surface
and the type of mounting interface chosen to install the cabinets (I-
Beams, customer frame...).
4.3.3.2 Floor Flatness
The 9312 Compact OD must be installed on a level floor surface. The
maximum tolerance for floor flatness is 5 mm over 2 m (~ 0.2 over
78).
In other words, the vertical tolerance shall not exceed 5 mm over a 2 m
horizontal length.
If the floor does not respect this maximum tolerance, the cabinet once
installed may be twisted and the cabinet door might be impossible to
open. In this case, cabinet watertightness along the front doors shall not
be guaranteed.
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 29
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.3.4 Pole
4.3.4.1 Resistance
The pole with the bracket should support more 300 Kg of load.
The bracket should be fixed on a pole of diameter 200 mm (8 in) to 600
mm (24 in). The bracket are fixed by threaded pin and clamps.
The 9312 Compact OD should be installed at a height of 170 mm (6.69
in) minimum from the floor. But at a height of 500 mm (19.70 in) is
recommended for a comfortable work
4.3.4.2 Cabinet Securing
The cabinet are secured on the bracket by 4 screws/bolts. The optional
plinth could be used but is not mandatory.
4.3.5 Wall
4.3.5.1 Resistance
The wall with the bracket should be to support more 300 Kg of load.
4.3.5.2 Flatness
The supporting wall must be flat and more or less vertical (maximum tilt
of 5 per cent).
The cabinet can be installed on different types of wall:
solid wall
solid wood
The cabinet should be installed to 170 mm (6.69 in) minimum of height
of the floor. But at a height of 500 mm (19.70 in) is recommended for a
comfortable work (man height)
Depending of wall type, all elements for fixed the bracket on the wall
should be designed by the customer. (Pegs, screws etc..)
4.3.5.3 Cabinet Securing
The cabinet are secured on the bracket by 4 screws/bolts. The optional
plinth could be used but is not mandatory.
30 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.3.6 Site Dimensioning Rules
The criteria governing the size of the site are:
the cabinet dimensions and the distance constraint,
the relative positions of cabinets (Site layout),
cabinets orientation in outdoor site, with respect to exposure to winds/
sun and possible nuisance caused to the neighbourhood (noise).
the input constraint of cables.
If the site contains more than one cabinet, the dimensions and
constraint must be adapted
4.3.6.1 Cabinet Dimensions and Distance Constraint
The clearances considers the clean surface which is the minimum
surface required to install the cabinets on site. Cabling access bulkheads
are available on the front side of the cabinet.
The following figures display the minimum surface for a cabinet on site
installation.
Figure 16 9312 Compact OD Cabinet Installation
700
580
1280
100
For be able to open the door with 120 angle and with 100mm in front
of it, refer to next Figure 17 which give the associated dimensions
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 31
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
Figure 17 9312 Compact OD Cabinet
580 mm
1236 mm
700 mm
Note: If the installers have to move around the cabinet, and for customer
purpose in terms of installation or maintenance, these dimensions
could be modified.
Example:
50 mm from the left side for the door lock
100 mm of space on the sides and on the back of the cabinet,
600 mm of space on the front of the cabinets when the door is opened.
4.3.6.2 Site Layouts
Different types of layouts are defined in order to have up to more than
one cabinet on the site.
For multi-cabinets sites, the roof mechanical resistance of building will
impact on the layout selection.
Other site configurations may be chosen as long as they respect the
equipment requirements (clearances, cable paths, max. inter-cabinet
distance...).
32 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
Figure 18 Minimum Space Required on Site Layout for 2 Compact OD Side by Side
50 mm

Figure 19 Minimum Space Required on Site Layout with 2 Compact OD - Back to Back
580 mm
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 33
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.3.6.3 Cabinets Orientation in Outdoor Site
The cabinet must be placed so that following rules are respected (if
possible):
heat dissipation is optimized by placing the cabinet back facing south
for northern-hemisphere countries (the cabinet back should face north
for southern-hemisphere countries).
rainfall effects are limited by placing the cabinet parallel to the
direction of dominant winds.
in case of a high-wind area (typhoon...), the cabinet should be placed
in a protected zone.
The local weather conditions must be taken into account to determine
the priority between the rules above.
Possible nuisance caused to the neighborhood must also be taken into
account (noise...).
4.3.6.4 Input Constraint of Cables
The positioning of the cabinet must take into account the arrival of the
cables to the cabinet.
34 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.4 9312 Compact OD Site Preparation
This section describes the preparatory work which should be carried out
on site prior to the 9312 Compact OD outdoor variant installation.
4.4.1 9312 Compact OD Support
The 9312 Compact OD outdoor can be installed on the types of sites
below:
Ground level or terraces of buildings
The cabinet(s) can be installed on a concrete pad (with its plinth) or on
an I-beam structure. In any case, the structure should be able to support
the cabinet(s) weight(s) and respect the securing holes positioning.
Figure 20 Floor Solution
pole or wall mounting with frame support
A pole or wall mounting bracket can be used by the customer and to be
made with the following constraints:
- The fixing points of the cabinet
- The cabinets dimensions (weight and size)
- Interface and environmental conditions of the cabinet.
The pole and wall support the maximum cabinet weight and
environmental constraints (Snow, wind, ice...).
It is preferable to install the pole/wall mounting to have the cabinet at
the man height for operation purpose.
The 9312 Compact OD can be fixed on pole from 8"(200 mm) to 24"
(600 mm).
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 35
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
Figure 21 Wall or Pole Solution
Wall
Pole
Pole
The floor, wall, pole mounting kit are provided in an optional ancillaries
kit. All external mounting kits should be approved for outdoor use. If the
mounting kit are not ordered, their characteristics should comply with
the ancillaries definitions, Alcatel-Lucent 9312 Compact OD IRM Kits
Definition. (Plinth is not mandatory of this two case)
Note: Only for the wall solution the pegs and screws for fixing the
mounting bracket should be designed by the customer, depending
from the wall type.
4.4.2 Earth Plate
The earth plate is installed systematically on each site, all the site
grounding circuits are connected to it:
Cabinet grounding via a 25 mm

(4 AWG) ground copper cable,


Antenna feeder grounding kits,
Metallic conduits or cable trays
Grounding cable from AC box distribution or others.
This earth plate is installed close to the cable entry of the BTS base
cabinets:
on the terrace,
in the cable trench.
It is continuously linked to the earth electrode of site.
36 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
The maximum impedance of the earth electrode measured from the
earth plate must be less than 10 Ohms.
4.4.3 Cable Tray
The cable tray is dimensioned according to the site configuration (refer
to Table 6) and must be grounded. It allows:
The cable routing (AC power, ground cables, feeders...),
The cable protection (for example to avoid damage possibly caused
by ice blocks falling from the top of the mast),
The rules of separation between light and heavy current cables.
Table 6 Cable Quantity for one Cabinet 9312 Compact OD
Items Quantity Type of Signal
AC Power cable 1 AC Voltage
PCM Cable Up to 2 PCM
Ground cable 1 Ground
RF Cable Up to 6 Radio
Alarm Cable Up to 2 Alarm
The connection of all the external cables is done in front lower side of
the 9312 Compact OD. There are 4 paths (each side of plinth) to route
the external cables (Floor solution only is mandatory)
In case the 9312 Compact OD is installed on a pole or wall mounting
support, the cables must come from below.
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 37
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.4.3.1 Solution 9312 Compact OD Alone
Customer AC Box
The 9312 Compact OD cabinet AC Model is not provided with main
disconnect device. Therefore, appropriate disconnect device should be
provided as part of the building installation by the customer.
For a site with several cabinets whatever the cabinet type, one
disconnect device is required for each equipment installed on the site.
The customer AC box is not provided by Alcatel-Lucent. The location
of the customer AC box must take into account the length of the cables
connected to the cabinet (<20 m for the cables provided with the
ancillary kit).
The customer AC box must contain an appropriate disconnect device,
easily accessible by the service personnel and marked as the disconnect
device of the equipment.
The breaker which protects the cabinet must be a C-curve for European
site and in accordance with Canadian Electrical Code C22.1 / National
Electrical Code ANSI/NPPA 70 (branch-circuit protection) for North
America.
The customer AC box must be dimensioned according to the connected
system characteristics.
The insulated earth conductor for the product must be green/yellow.
The customer AC box feeding BTS cabinets must be dimensioned to
feed fully equipped BTS cabinets in operational conditions and worst
case configurations (all RM broadcasting, ac input voltage variation).
Note: A differential device is not mandatory for our cabinets. If the site
breaker has such a differential device, it has to be rated at 500 mA
minimum, delayed type (type S).
The power distribution system must be of TT or TN-S type. Refer
to national installation grounding requirement for details.
The Main site circuit breaker must be dimensioned in compliance with
all the existing equipment of the site whatever the cabinet type.
38 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
Figure 22
Main site breaker
bipolar, D curve
BTS dedicated 40A breaker
bipolar, C curve
S8000 1st cabinet
subscription line
line available for other purpose
Mains
S8000 2nd cabinet
BTS dedicated 40A breaker
bipolar, C curve
BTS dedicated breaker,
bipolar, C curve
BTS dedicated breaker,
bipolar, C curve
9312 Compact OD
Second Cabinet
Main Site Circuit Breaker (Single Phase)
The global current requirement in operational conditions and worst case
configurations for the 9312 Compact OD AC, on a power network
single phase 220-240 Vac or split phases 208-240 Vac, will not exceed
11 A in steady state (heaters).
The closest standard circuit breaker dimension is 16A, bipolar, C
curve.
The AC cable should be connected on the ground via the metallically
hardware of customer breaker or other.
For installation in site of one BTS, a existing kit with AC cable of 25 m
could be re-used:
NTQG48 BF: Ens Inst Street AC Sing Cord 25m ROHS version
NTQG48FF: Ens Inst Street Cord Bi 25m Rohs version
For installation in site of more BTS a Roll solution could be used:
3BK25561AAAA AC Power Cable 3x2.5 mm Roll 100m
No roll for Bi phase cable (type US)
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 39
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.5 Site Installation
4.5.1 Cabinet Securing
A specific anchor kit is defined. The cabinets are secured with four M10
bolts.
The securing hole diameters of the cabinets are 20 mm (0.79 in).
If the cabinets are installed on a concrete pad, holes are drilled in the
concrete pad using the drilling template given below (see Figure 23),
then the cabinets are positioned in the final location and secured to the
concrete pad.
Figure 23
52 mm (2.05 in)
1
2
3
m
m
(
4
.
8
4

i
n
)
330 mm
(12.99 in)
Dia 20 mm
(0.79 in)
476 mm
(18.74 in)
Drilling Template
A specific anchor kit is an option of the cabinet
This anchor kit requires drilling into the concrete floor to a depth of 100
mm (3.9 in).
40 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.5.2 Cabinet Wiring
4.5.2.1 9312 Compact OD External Cables
These cables are available next to the cabinet, are mechanically
protected inside metallic tubes or in metallic cables trays. In both cases
the metallic cable protection must be grounded to the earth plate
interface.
On outdoor site, all external cables on-site must be approved for outdoor
use (in terms of resistance to humidity, heat, UV rays...), and must be
flexible.
The connections are done at the bottom of the 9312 Compact OD front
on the bulkhead. Refer to Figure 24.
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 41
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
Figure 24 9312 Compact OD Bulkhead
Above View

Table 7 Type of 9312 Compact OD Connections
Terminal Number Type of connector (cabinet side)
Equipotentiality point 2 (on each side of plinth) M6 (1/4) Stud
GND 1 1 x M6 (1/4) Stud
AC Power 1 IP 66 cable gland for an AC cable
from 15 to 18 mm (0,55 to 0,7 in)
PCM Cable Up to 2
RF Connectors 6 7/16 connector type
4.5.2.2 Ground Cable
The grounding cable from the cabinet to the site earth plate must be as
short as possible, with a section of at least 25 mm (AWG 4).
The inter-cabinet ground cables if any routed between 9312 Compact
42 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
OD and others cabinet colocalised on the same site (for equipotentiality)
must be as short as possible, with a section of at least 16 mm (AWG 6).
For installation in site of one BTS, a existing Ground cable kit of 25 m
could be re-used:
NTQG48DF: Ens Inst Str/Mono Cord GND 25m ROHS version
For installation in site of more BTS, a roll solution could be used:
3BK08957BA: Cable 1x16 mm Y/G Roll 100m
4.5.2.3 BTS AC Supply Cables
The mains AC supply cable comes directly from the customer AC box
and is connected directly to the cabinet AC inputs.
The cables used for powering each BTS cabinet must be able to hold at
least 11.5A for single, split phases configurations,
They are dimensioned according to the distance between the cabinet and
the customer AC box. The voltage drop due to cable resistance must be
so that the voltage at the cabinet level is in the window 180-264 Vac for
all AC mains.
Each power supply cable is composed of conductors (three for single
phase, four for split phases) of the same section as described below.
Table 8 BTS AC Supply Cables: Single Phase
Cable type Cable color
For example
Section (mm) Max. length (m)
4 25
4 25
4 25
Phase Brown
Neutral Blue
PE (Protective Earth) Yellow/Green
Table 9 BTS AC Supply Cables: Split/Dual Phases (Europe wires)
Cable type Cable color
For example
Section (AWG) Max. length (m)
L1 Brown 4 25
L2 Black 4 25
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 43
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
The cable must be flexible and screened, and each conductor must be of
multi-thread type (to facilitate lug crimping).
The cables must be waterproofed and must have a section compatible
with the AC cable gland entry in order to guarantee the IP55 of the
cabinet.
Table 11 External Cable Section for AC Cable Gland Entry
Mono/Split Phase
4.5.3 External Cables Marking
Table 12 External Cables Marking
Function Labeling
Cabinet k DC Standard -48V or 0V Cab k DC -48V or 0V
Cabinet k AC single/split phase L, N, PE / L1, L2, N, PE
Cabinet k Protective Ground Cab k GND
Neutral (grounded conductor) Blue 4 25
Electric ground (grounding
conductor)
Yellow/Green 4 25
Table 10 BTS AC Supply Cables: Split/Dual Phases (US wires)
Cable type Cable color
For example
Section (AWG) Max. length (m)
4 25
4 25
4 25
4 25
L1 Black
L2 Red
Neutral (grounded conductor) White
Electric ground (grounding
conductor)
Yellow/Green
External diameter up to 23 mm TBC
44 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.5.4 Distribution Frame for PCM
The 9312 Compact OD is not connected directly to the
telecommunication network, but by means of a DF. This DF is a
connection point between the PCM cables from the BTS and the
transmission network.
There are two major cases for the connection to the PCM link:
Or the telecommunication network is 120 E1; in that case the only
equipment necessary to ensure the PCM connection between the DF
and the BTS is one or two PCM cable.
Or the telecommunication network is E1 75 ; in that case, as the
BTS works in 120, it is necessary to ensure an adaptation from the
BTSs 120 to the customer networks 75 . As a consequence, the
PCM cable should be equipped with Mini-Baluns male, and the DF
should be able to receive it.
There are 4 types of mini Balun connectors described in Table 13
Types of Mini Baluns.
Table 13 Types of Mini Baluns
KIT Reference
75 ohms BNC NTQG41GF
75 ohms 1.6-5.6 NTUM98LF
75 ohms SMZ Type 43 NTUM98YF
Conn BNC To RJ45
Balun. 75 Ohms
N0111189
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 45
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.5.5 Feeders and Antenna System
The customer must foresee and install the antennae system and the
feeders. The antennae are installed in compliance with the radio
engineering studies by trained staff.
Feeders are used to establish the RF link between the BTS and the
antennae or TMAs. The feeders are in cable tray, near the radio cabinet,
ready to be connected. A female 7/16 connector equips each feeder end.
The feeder interconnections shall comply with outdoor constraints
(waterproofing...).
On the BTS side, the feeders should arrive as close as possible to the
cabinet mounting location (the number of feeders depends on the
configuration type) in order:
To allow an easier installation: depends on the size of feeder used, it
might be very difficult to position correctly the feeder in front of the
RF connector on BTS side.
To avoid excessive efforts on the RF connector on the BTS side: risk
of damage to the connectors.
To allow easier maintenance operation.
The Cable used for feeder should have a maximum attenuation of
6.99dB/100m at 2300Mhz. Couple connector losses = 0.2dBmax.
46 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.5.6 Lightning Protection
All the site must be protected against direct lightning strikes. The site
must be equipped with a lightning conductor on top. For lightening
protection it is important that the radio lines from the antenna to the
cabinet are regularly grounded with grounding kit (see Figure 25).
The antenna ports of the cabinet can be protected with a gas tube surge
arrestor (optional).
Note: In case TMA is employed, the site should be equipped with
specific surge arrestor as gaz tub in order to avoid short circuit
between the inner and outer connector of feeder (the TMA is
supplied in DC voltage thanks to its RF cables).
The cabinet also includes a surge arrestor for induced current surge on
the AC Main power supply.
Figure 25 Grounding Kits on Feeders
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 47
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
4.5.7 Radio Cables Types
RF Jumpers
The antenna feeders arrive as close as possible to the BTS cabinet
mounting location; the interconnection between the feeders and jumpers
is done outside.
The number of feeders depends on the combiner type and on the number
of sectors.
The feeder interconnections shall comply with outdoor constraints
(waterproofing...).
The radio feeders are coming from the antenna mast. They must be
protected at the ground level by a metallic cable tray (to avoid damage
possibly caused by ice blocks falling from the top of the mast).
Peculiarities of RF Links
The RF jumpers are optional. The BTS should be connected to the
feeders via RF jumpers, the minimum bending radius should comply
with the space available below the cabinet, in plinth space.
The jumper connector should be straight, Male, DIN 7/16 for a key 32
mm (hexagonal head).
Table 14 Alcatel-Lucent Jumper RF Code
Order code Description
3BK05360CAAA JUMPER 7/16MM LG=2M The Jumper length is site dependent.
W/o specification, provide 2 meters
length.
With TMA provide 4 jumpers per sec-
tor on the Antenna side and 2 jumpers
per sector on the Node B side (see fig
14)
W/o TMA provide 2 jumpers per sector
on the Antenna side and 2 jumpers per
sector on the Node B side (see fig 14)
3BK05360DAAA JUMPER 7/16MM LG=3M
Standard 2 m max. long jumpers are used to connect the feeders to the
BTS.
For each sector, several antennae can be available (for Main and
Diversity reception), the number depending on configuration.
48 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
Connection to the Aerial RF Part
The use of jumpers on each side of the feeder (BTS/feeder and Feeder/
antenna or TMA) is recommended when using LDF or FSJ type of
feeder. Example of RF Link with UMTS TMA

S1 S2 S3
Cabinet
Main
Antenna
Div
Antenna
Feeder 7/8"
(35m)
Jumper
2 m
Jumper
2 m
Jumper
2 m
MAIN PATH DIV PATH
TMA TMA TMA
Hatch
Plate
Minimum single
bending radius
125mm
125mm
250 mm
32mm
50Ohms
TBC
TBC
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 49
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
Figure 26 Example of RF Link without UMTS TMA
S1 S2 S3
UMTS BTS 12020 Version 2
Feeder 7/8"
(35m)
Jumper
2 m
Jumper
2 m
MAIN PATH DIV PATH
Double
UMTS TMA
Double
UMTS TMA
Double
UMTS TMA
Div
Antenna
Main
Antenna
Hatch
Plate
Minimum single
bending radius
125mm
250mm
32mm
50Ohms
Cabinet
TBC
TBC
TBC
50 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
4.6 Final State of Site Preparations
The site access and layout permits the 9312 Compact OD Physical
installation.
If necessary, a mounting support is installed, grounded.
The different external interfaces to the equipment (ground plate,
Customer AC box(es), cable tray, PCM distribution frame...) are
installed.
The following operations have been performed:
A ground plate is connected to the earth sink.
The circuit impedance and the continuity are checked and recorded.
A power supply output is available for each cabinet (breaker off).
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 51
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
5.0 References
Table 15 Reference Documents
Document Number Title
R1 ETS 300 019 -1-4 Environmental Conditions and Environmental
Tests for Telecommunications Equipment; Part
1-4: Classification of Environmental Conditions.
Stationary use at non-weather protected loca-
tions: class 4.1E except for:
Low temperature - 40C
High temperature +55C
Wind: 200 km/h
High absolute humidity 36g/m
3
Mechanical condition: 4M3
R2 IEC 60529 Degree of Protection Provided by Enclosures -
(IP Codes)
R3 IEC 721-3-4 Classification of Environmental Conditions
Partie 3:
Classification of groups of agents
environment and their severities
R4
IEC 721-2-6
Classification of Environmental Conditions.
Part2 : Environmental Conditions Appearing in
Nature-Earthquake Vibration and Shock : Level
3
R5 ETS 300 019-1-1 Classification of Environmental Conditions Stor-
age Class 1.2
R6 ETS 300 019-1-2 Classification of Environmental Conditions
Transportation Class 2.2
R7 ETS 300 753 Acoustic Noise Emitted by Telecommunications
Equipment
R8 ETS 300 019 -2-3 Classification of environmental conditions
R9 ETS 300 019 -1-4 Specification of environmental tests Stationary
use at non-weather protected locations
R10 Bellcore
GR487-CORE
defines Bellcore's requirements for telecom
equipment to be placed in an outdoor environ-
ment
R11
Bellcore
GR 63-CORE
Network Equipment - Building System (NEBS)
requirements. Physical protection.

Document Number Title
R12 EN 301 489-1 and
EN 301 489-23
Electromagnetic Compatibility and Radio spec-
trum matters (ERM); Electromagnetic Compati-
bility (EMC) standard for Radio equipment and
services; Part 1: Common technical require-
ments
R13 CFR 47 Part 15 Class B Radio frequency devices
R14 ICES 03 Digital Apparatus Issue 3, Nov. 22, 1997
R15 3GPP TS 25.113 Technical specification group radio access net-
works. Base Station Electro Magnetic Compati-
bility Ed V3.5.0
R16 PE/DCL/DD/XXXXX BTS compact OD Engineering Rules
R17 IEC 364 Electrical Installation of buildings
R18 IEC 721-3-3 Classification of groups of environmental
parameters and their severity. Stationary use at
weather protected locations: classe3
R19 UL 1950
CSA C22.2 950
IEC 60950
Safety of information technology equipment
including electrical business equipment
52 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification / 53
April 29, 2009 Method 06-6273

P
r
e
l
i
m
i
n
a
r
y
6.0 Appendices
6.1 Abbreviations
A ampere
AC Alternating Current
AWG American Wire Gauge
BTS Base Station Transceiver Subsystem
DC Direct Current
DF Distribution Frame
DDM Dual Duplexer Module
E1 Standard European PCM system
uCECU Universal Compact Environmental Control Unit
EMC Electro-Magnetic Compatibility
EMI Electro-Magnetic Interference
GND GrouND
IP Ingress Protection
RF Radio Frequency
T1 Standard US PCM system
54 / Alcatel-Lucent 9312 Compact Node B Outdoor Site Specification
Method 06-6273 April 29, 2009

P
r
e
l
i
m
i
n
a
r
y
6.2 Terms
Depopulated: Cabinet partially equipped.
Difficult access site: For this type of site, mechanical means cannot cover
the entire delivery truck to mounting location distance. Part of the way (as
small it might be) requires manual carrying.
Easy access site: No manual carrying is required to set the populated cabinet
onto its mounting location.
Optimized operational temperature range: The temperature range
prevailing in most populated areas of the world. Temperature above and
below this range, fall into areas of low non-existent population, or into the
category of one time only recorded extremes.
Populated: Fully equipped cabinet.
Total operational temperature range: The BTS will perform at both
extreme temperatures, however:
at low extremes, the electrical supply requirements of the BTS site
increases.
at high extreme, for more than 5 hours per day and for more than 72
hours per year may result in early failure of temperature dependent
modules and/or components. The sound power by the BTS increases by
0.5 bels per 5C rise above the optimized temperature high extreme.
End of Document