Abstract In this paper electrical power/energy measurement

algorithms are analyzed considering the effect of steady-state


voltage/current waveform quality, that is, harmonics and
unbalanced conditions in both single-phase and three-phase
power systems.
The performed analysis allows us to identify some fallacies in
different electric power/energy measurement algorithms which
are utilized by most of the digital meters. The effect of using two
of the three sensing elements of the digital meters in three-phase
three-wire systems was also determined. These results were
obtained by testing some of the measuring instruments
commonly used by distribution companies and power marketers.
Additionally, the mistake made when the total three-phase
power is obtained by the sum of the three power readings per
phase is explained. It must be kept in mind that a three-phase
system must be always considered as a whole when analyzing its
operation and performance and that three single-line equivalent
circuits cannot be used when performing three-phase power
calculations.
Finally, a comparative analysis of the values obtained using
four different digital power meters is presented using as a
comparison pattern the values established by the proposed
standard IEEE 1459-2000 Standard Definitions for the
Measurement of Electric Power Quantities Under Sinusoidal, No
sinusoidal, Balanced, or Unbalanced Conditions (Trial-Use).


Palabras Clave Armnicos, desbalance, calidad de energa
elctrica, conexin Aron, factor de potencia, medicin de
potencia elctrica, potencia activa, potencia reactiva, potencia
aparente.
I. INTRODUCCIN
N aspecto fundamental en la utilizacin de la energa
elctrica es su medicin, ya que con base en ella se
realizan las transacciones comerciales entre los clientes y
suministradores de este producto.
Trminos como potencia instantnea, potencia activa,

La entrega del artculo fue el 19 de Agosto de 2005 y su posterior
recepcin y aceptacin tiene fecha del 30 de Septiembre de 2005. Este trabajo
fue desarrollado con el apoyo del Grupo de Investigacin en Sistemas de
Energa Elctrica (GISEL) adscrito a la Escuela de Ingenieras Elctrica,
Electrnica y Telecomunicaciones (E3T) de la Universidad Industrial de
Santander (UIS).
Gabriel Ordez Plata es profesor titular de tiempo completo de la
Universidad Industrial de Santander, Bucaramanga, Colombia; e-mail:
gaby@uis.edu.co.
Csar A. Duarte G. es profesor auxiliar de tiempo completo de la
Universidad Industrial de Santander, Bucaramanga, Colombia; e-mail:
cedagua@uis.edu.co.
potencia reactiva, potencia aparente y factor de potencia han
sido ampliamente empleados en la medicin de potencia y
gran parte del desarrollo de equipos de medicin de energa
elctrica se basa en la estimacin de estos parmetros. La
aparicin de armnicos en las ondas de tensin y corriente, as
como las posibles asimetras de los sistemas de suministro
trifsicos y los desbalances de las cargas elctricas trifsicas
conectadas a estos sistemas inciden en la estimacin de tales
parmetros. Sin embargo, la mayora de los equipos de
medicin de potencia y energa (analgicos o digitales) estn
para funcionar correctamente cuando las condiciones son
senoidales y no se presentan asimetras ni desbalances en
sistemas trifsicos.
En este artculo se establecen las falencias existentes en
algunos de los algoritmos de medicin de potencia y energa
utilizados en medidores digitales, as como el efecto de la
conexin de dos elementos (en lugar de los tres del medidor
digital) utilizada en redes trifsicas trifilares. Para esto se
realizaron simulaciones y pruebas experimentales con algunos
de los equipos de medicin de energa elctrica utilizados por
las empresas de distribucin y comercializacin.
Otro aspecto que se analiza en este artculo es el efecto que
tiene en la medicin de las potencias elctricas de un sistema
trifsico, el hecho de que las potencias totales del sistema se
obtengan como la suma de las potencias de cada una de las
fases del sistema, olvidndose que el sistema trifsico es nico
y tanto en su operacin como en su funcionamiento no puede
ser considerado como tres sistemas monofsicos.
Para abordar estos temas se presentan las definiciones
bsicas de potencia, los efectos de los armnicos y las
asimetras en la estimacin de la misma, analizando los
algoritmos de estimacin utilizados por algunos medidores
digitales para finalmente establecer una comparacin entre las
magnitudes estimadas por estos medidores con relacin a las
estimaciones propuestas por autores como Czarnecki [1], [2] y
Emanuell [3].
II. DEFINICIONES BSICAS DE POTENCIA EN RGIMEN
SENOIDAL
Para analizar el efecto que la forma de las ondas de tensin y
corriente tiene en la estimacin de potencia se debe tener en
cuenta las definiciones bsicas de stas.
A. Potencia instantnea
La tasa instantnea del flujo de energa o potencia
instantnea, p(t), est definida como el producto de la tensin
Mitos y realidades en la medicin de potencia y
energa elctrica
Gabriel Ordez Plata, Miembro, IEEE, y Csar Antonio Duarte Gualdrn.
U
III Simposio Internacional sobre Calidad de la Energa Elctrica SICEL 2005
Bogot D.C., Colombia. Noviembre 16-18 de 2005
SICELIII-42 1

instantnea v(t) y la corriente instantnea i(t). La potencia
instantnea cumple con el principio de conservacin de la
energa. En [4] se propone otra forma de definir la potencia
instantnea teniendo en cuenta los efectos de la circulacin de
la corriente en los elementos pasivos: efecto Joule en los
elementos resistivos y creacin de campos magnticos o
elctricos en los elementos almacenadores de energa
elctrica. Independientemente de la forma como se defina la
potencia instantnea, el promedio de la potencia instantnea,
es decir la potencia activa, es igual en ambos casos; as como
la magnitud mxima de la potencia circulante en el sistema
entre elementos almacenadores de energa y las fuentes de
suministro de la misma, denominada potencia reactiva.
A continuacin se muestra el comportamiento de la
potencia instantnea p(t) considerando que la tensin de
suministro es senoidal y que la carga es la combinacin de una
resistencia con una inductancia.
Si la tensin instantnea es:
( ) ) cos( 2 t V t v = (1)
y la carga lineal se caracteriza por: :
( ) ( ). cos jYsen Y G Y jB G Y = = = = (2)
Siendo G la conductancia y B la susceptancia.
Se tiene que debido a la linealidad de la carga, la
caracterstica de la onda de corriente tambin es senoidal pero
escalada y desfasada en grados con respecto a la onda de
tensin.
Para esta carga, la corriente i(t) ser igual a
( ) ( ) ( ) ( ). cos 2 t i t i t I t i
r a
+ = = (3)
Donde:
i
a
(t): Es la componente de la corriente instantnea i(t) en
fase con la onda de tensin y por ende est asociada al efecto
Joule en la resistencia.
( ) ( ) ( ) ( ). * cos 2 cos cos 2 t v G t I t I t i
a a
= = =
(4)
i
r
(t): Es la componente de la corriente instantnea i(t) que
est en cuadratura con la onda de tensin y la origina el
desfase que introduce la carga. sta es responsable del flujo
cclico de energa, por ello no produce trabajo.
( ) ( ) ( )
( )
dt
t dv
B t sen I t sen Isen t i
r r 1
2 2 = = =
(5)
Finalmente, la potencia instantnea se obtiene sumando los
dos efectos, es decir:
( ) ( ) ( ) ( ) ( ) [ ] ( ) ( ) t p t p t i t i t u t i t u t p
r a r a
+ = + = = ) ( (6)
{ }
). 2 ( * *
) 2 cos( 1 * cos * ) (
t sen sen VrmsIrms
t VrmsIrms t p

+ + =
(7)
B. Potencia Activa
Es la potencia asociada al trabajo til que se realiza en los
circuitos elctricos, es decir, es aquella potencia que se
transforma en otro tipo de energa no elctrica. Esta
demanda de potencia est dada por el consumo en una
resistencia debido al efecto Joule.
Matemticamente, la potencia activa corresponde al valor
medio de la potencia instantnea y su expresin para el caso
de seales senoidales es:
( ). cos ) (
1
0
0
VI dt t p
T
P
T t
t
=

+
(8)
La componente p
a
(t) de la potencia instantnea tiene un
valor promedio igual a la potencia activa P y est fluctuando
entre 0 y 2P.
C. Potencia reactiva
Est determinada por la componente de la potencia
instantnea que no se transforma en trabajo til. Esta potencia
representa a una energa que es recuperable elctricamente
hablando. Su origen est en la capacidad que tienen las
inductancias y las capacitancias de almacenar energa
mediante campos magnticos, para la inductancia y campos
elctricos, para la capacitancia. En situaciones senoidales, la
potencia reactiva corresponde al valor pico de la componente
p
r
(t) de la potencia instantnea y est definida de la siguiente
forma:
( ) VIsen Q
r
= (9)
Una forma de medir la potencia reactiva
*
con un
instrumento de activa (promedio) es retardando la tensin 90
grados elctricos y evaluando el promedio de la potencia
instantnea, es decir:
( )

VIsen
VI dt t i
T
t v
T
Q
o
T t
t
=
=

+
) 90 cos( ) ( )
4
(
1
0
0
(10)
Finalmente la potencia instantnea podra expresarse en
funcin de la potencia activa y reactiva como:
( ) ( ) t sen Q t P t p
r
2 2 cos 1 ) ( + + =
(11).
D. Potencia aparente o de dimensionamiento
La potencia aparente S es igual al producto del valor
eficaz de la onda de tensin (dimensionamiento del
aislamiento del sistema) y el valor eficaz de la onda de
corriente (dimensionamiento de la capacidad de transporte del
sistema). Por lo tanto, indica el dimensionamiento que debe
tener un sistema. Por ser slo una cuanta, no define la
direccin del flujo de energa.
Para el caso de un sistema a tensin constante y con seales
de tensin y de corriente senoidales, la expresin que
corresponde a esta potencia es la siguiente:
2 2 2 2
r r a
Q P I I U VI S + = + = = (12)
Como se observa, se debe dimensionar el sistema para
transportar tanto la potencia activa como la reactiva; en
consecuencia, si es posible compensar la reactiva de forma
local en las cargas, se podr liberar capacidad de transporte
1
.
La potencia instantnea se puede expresar en trminos de
estas tres potencias como:

+ =

P
Q
t S P t p
1
tan 2 (cos ) (
(13)

*
Slo cuando el rgimen es senoidal puro.
1
Adicionalmente, se reducira el valor eficaz de la corriente demandada
por la carga y se reducirn las prdidas por transporte de energa.
III Simposio Internacional sobre Calidad de la Energa Elctrica SICEL 2005
SICELIII-42 2

De acuerdo con esta expresin, la potencia instantnea
oscilar entre un valor mximo igual a P+S y un valor
mnimo igual a P-S.
E. Factor de potencia
En 1920 Lyon [4] propuso la siguiente definicin de factor
de potencia: Es la razn entre la potencia consumida por una
carga sobre la potencia ms grande que podra absorber
cualquier carga con iguales valores eficaces de tensin y
corriente. Es decir que el factor de potencia corresponde a la
razn entre la potencia que se transforma en trabajo til
(potencia activa) y la potencia para la cual se dimensiona el
sistema (potencia aparente) e indica el grado de eficiencia con
el que se explota un sistema de energa elctrica. Est dado
por:
I
Ia
S
P
fp = =
(14)
Slo en el caso que las seales de tensin y corriente sean
senoidales, el factor de potencia se puede expresar como el
coseno del ngulo entre la tensin y la corriente.
III. DEFINICIONES DE POTENCIAS EN SISTEMAS ELCTRICOS
CONSIDERANDO REGMENES PERIDICOS NO SENOIDALES
La aparicin de cargas no lineales y/o variantes con el
tiempo ha hecho que las ondas de tensin y corriente de los
sistemas de energa elctrica estn conformadas por
componentes de frecuencias armnicamente relacionadas de
tal forma que se pueden expresar como:

=
+ + =
1
0 0
) cos( 2 ) (
k
k k
t k A A t f (15)
Donde, cada componente armnica est caracterizada por
la amplitud (A
k
), el ngulo de fase (
k
) y la frecuencia (k
0
).
Por otro lado, un ndice de medida de la deformacin de la
onda correspondiente (tensin y/o corriente) es la razn entre
el valor eficaz de las componentes armnicas distintas a la
fundamental con respecto al valor eficaz de la componente
fundamental [3], [6]. Este ndice se conoce como distorsin
armnica total y est dado para la tensin y la corriente por las
siguientes expresiones:
1
1
2
1
1
2
I
I
DAT THD
V
V
DAT THD
n
n
I I
n
n
V V

= =
= =
(16)
cuenta las definiciones bsicas de stas.
A. Definiciones de potencia en sistemas monofsicos
Los armnicos, tanto de la seal de tensin como de la
seal de corriente incrementan la potencia aparente (potencia
de dimensionamiento) del sistema.
Por consiguiente, la expresin de la potencia aparente toma
la siguiente expresin [6]:
2 2
1 1
2 2
2
2
1
2 2
2
1
2
1 1
... ...
I V
n n RMS RMS
DAT DAT I V S
I I I V V V I V S
+ + =
+ + + + + + = =
(17)
En (17) se observa que en situaciones no senoidales la
potencia de dimensionamiento del sistema se incrementa con
respecto al caso senoidal en un factor k que depende de la
distorsin armnica total de la tensin y la corriente:
1 1 1
kS I kU S = = (18)
En consecuencia, para transportar la misma potencia activa
fundamental (potencia de dimensionamiento S
1
), la aparicin
de los armnicos hace que se requiera una potencia de
dimensionamiento k veces mayor a la que se tendra si las
seales fuesen senoidales de una nica frecuencia.
Las componentes armnicas de las seales de tensin y de
corriente establecen una potencia aparente que se puede
descomponer de diferentes formas. Es as como en [3] y [7]
esta potencia se expresa como:
( ) ( ) ( ) ( )
2 2
1
2
1
2
1 1
2 2
1
2
1
2
H H H H
H H RMS RMS
I V I V I V I V S
I I V V I V S
+ + + =
= + + = =
(19)
En esta descomposicin, la potencia aparente se puede
dividir en las siguientes componentes:
2 2 2 2
1
2 2
1
2
H V I N
S D D S S S S + + + = + =
(20)
Donde S
N
corresponde a la potencia aparente debida a la
aparicin de componentes armnicas en las ondas de tensin y
corriente. Esta potencia se puede expresar en funcin de tres
trminos: D
I
, potencia aparente de distorsin de corriente, D
V
,
potencia aparente de distorsin de tensin y S
H
, potencia
aparente armnica. Estas tres potencias se pueden expresar en
trminos de la potencia aparente de la componente
fundamental (S
1
) como:
( ) ( )
( ) ( )
( )( ) ( )( )
I V I V H H H
V V H V
I I H I
DAT DAT S DAT DAT I V I V S
DAT S DAT I V I V D
DAT S DAT I V I V D
1 1 1
1 1 1 1
1 1 1 1
= = =
= = =
= = =
(21)
La representacin matemtica de la potencia aparente dada
en (21) permite establecer el efecto de las componentes
armnicas en el dimensionamiento del sistema.
En cuanto a la potencia activa, la obtencin del valor
promedio de la potencia instantnea en sistemas monofsicos
con ondas de tensin y corriente con componentes armnicas
hace que la expresin dada en (8) se convierta en:
( )

=
+
= =
N
k
k k k
T t
t
I V dt t p
T
P
1
cos ) (
1
0
0

(22)
Por consiguiente, la potencia activa del sistema corresponde
a la suma de las potencias activas correspondientes a cada una
de las componentes armnicas de las seales de tensin y
corriente. La estimacin adecuada de esta potencia requiere
que el instrumento utilizado (analgico o digital) tenga un
adecuado ancho de banda. De hecho, en estudios realizados en
medidores de energa analgicos [9] se ha encontrado que la
respuesta en frecuencia de estos equipos no es la adecuada,
con lo cual los errores en la estimacin de potencia activa
cuando aparecen componentes armnicas en las seales de
tensin y corriente en varios casos puede sobrepasar los
mximos establecidos por la clase del medidor.
La obtencin de la potencia no activa (reactiva o ficticia) en
sistemas con componentes armnicas en las ondas de tensin
III Simposio Internacional sobre Calidad de la Energa Elctrica SICEL 2005
SICELIII-42 3

y corriente es la mayor falencia que se encuentra en equipos
de medida de energa elctrica. Ya que la aparicin de
armnicos en los sistemas incrementa la potencia de
dimensionamiento, la medicin de la potencia no activa debe
tener en cuenta todos los efectos que hacen que se presente
este incremento. Por consiguiente para efectos de medicin de
potencia o energa, la potencia reactiva debe estimarse como:
2 2
P S Q = (23)
La obtencin de esta potencia en medidores analgicos es
un procedimiento complejo, pero en medidores digitales esta
evaluacin es sencilla.
Sin embargo, en la revisin de los algoritmos de estimacin
de potencia reactiva de medidores digitales se ha encontrado
que la forma de estimar esta potencia se basa en la estimacin
propuesta por Budeanu para sistemas con componentes
armnicas:
( )

=
=
N
k
k k k
sen I V Q
1

(24)
Esta forma de estimar la potencia reactiva ha sido
ampliamente discutida ([1], [2]) y se ha establecido la
inconsistencia de la misma. Dado que la potencia reactiva por
armnico corresponde al valor mximo de una oscilacin de
potencia con diferente frecuencia para cada uno de los
armnicos, las potencias reactivas de los diferentes armnicos
son ortogonales entre si y no estn en fase como se considera
en (24).
Con relacin a la definicin del factor de potencia es claro que
no puede seguirse empleando la definicin del coseno de la
diferencia de ngulo de fase entre la tensin y la corriente, ya
que cada para cada una de las frecuencias que tenga la seal se
tendr un ngulo de fase distinto. Por esta razn la definicin
de factor de potencia establecida en (14) es la adecuada.
B. Definiciones de potencia en sistemas trifsicos
Las definiciones de potencia en sistemas trifsicos se han
derivado de las definiciones propuestas para sistemas
monofsicos; es decir, que se considera que la potencia total
del sistema es la suma de las potencias obtenidas en cada una
de las fases. Este enfoque tiene validez en la definicin de la
potencia activa, independientemente de las caractersticas del
sistema trifsico, ya que al ser sta el valor medio de la
potencia instantnea, la suma de los promedios de las
potencias instantneas por fase corresponde a la potencia
activa total del sistema trifsico.
Sin embargo, para las dems potencias (aparente y
reactiva), la suma de las potencias por fase no siempre
corresponder a la potencia total del sistema, ya que efectos
como los armnicos y los desbalances del sistema hacen que
la suma de las potencias por fase no corresponda a la potencia
total del sistema. De hecho se definen dos potencias aparentes
(dimensionamiento): la aritmtica y la vectorial.
La deficiencia de este enfoque est en considerar el sistema
trifsico como tres sistemas monofsicos, cuando en realidad
la generacin, la transmisin, la distribucin, y en general el
diseo y operacin de los sistemas trifsicos se hace
considerndolo como un sistema nico. Este es uno de los
mitos que an se mantiene en la medicin de potencias y
energas en sistemas trifsicos y se incub al considerar que
todas las potencias del sistema se podan estimar de igual
forma que la potencia activa, lo cual es cierto slo cuando las
condiciones del sistema trifsico son las ideales: tensin de
suministro simtrica, carga balanceada y sistema sin
armnicos.
En [1] se realiza una comparacin de las definiciones de
potencia y se presenta una propuesta para estimar las
potencias en sistemas trifsicos (en [2] se realiza un anlisis
detallado del modelo propuesto). Adems de Czarnecki,
varios autores han planteado diferentes modelos para la
definicin de potencia en sistema trifsicos, siendo el ms
novedoso el propuesto por el comit de instrumentacin y
medidas en sistemas de potencia de la sociedad Power
Engineering del IEEE en enero del 2000.
Esta propuesta denominada: IEEE Std 1459-2000: IEEE
Trial-Use Standard Definitions for the Measurement of
Electric Power Quantities Under Sinusoidal, No sinusoidal,
Balanced, or Unbalanced Conditions ha sido ampliamente
discutida por diferentes investigadores del mundo como se
puede comprobar en la participacin de alrededor 30
miembros del Working Group on No sinusoidal Situations y
de las ms de 40 publicaciones que al respecto se han
realizado en el IEEE desde el ao 2000
Entre los aspectos a resaltar del modelo de potencias
propuesto en el IEEE Std 1459-2000 se tienen los siguientes:
1) Para la estimacin de las potencias solamente se requiere
de la evaluacin del valor eficaz de las seales de tensin y
corriente, y de las componentes fundamentales de estas
seales.
2) La estimacin propuesta permite discriminar las potencias
causadas tanto por la componente fundamental como por
las componentes armnicas.
3) Establece un ndice basado en las potencias aparentes del
sistema que permite valorar el efecto de los armnicos en
el sistema.
4) El factor de potencia es una medida del grado de
utilizacin del sistema (eficiencia del mismo).
5) En sistemas trifsicos define una potencia aparente
efectiva que se evala proponiendo un sistema trifsico
equivalente simtrico y balanceado que se obtiene
considerando que las prdidas en el transporte de potencia
son las mismas que en el sistema trifsico original.
6) La potencia aparente efectiva es nica, con lo cual
desaparece la ambigedad del modelo basado en la
propuesta de Budeanu de dos potencias aparentes (la
aritmtica y la vectorial). Debido a esto se define un nico
factor de potencia en sistemas trifsicos.
7) Establece un ndice basado en las potencias aparentes de la
componente fundamental para valorar el desbalance de la
carga trifsica.
8) La evaluacin de la potencia no activa (reactiva) se obtiene
a partir de la potencia aparente efectiva y la potencia activa
total.
III Simposio Internacional sobre Calidad de la Energa Elctrica SICEL 2005
SICELIII-42 4

Es de resaltar que esta propuesta elimina los mitos que
hasta ahora existen en la medicin de potencias y energas
elctrica, ya que la obtencin de las potencias reactiva y
aparente rompe con todas las definiciones que hasta ahora se
han utilizado, las cuales presentan dificultades para estimar
adecuadamente la potencia en diferentes situaciones que se
pueden presentar en el funcionamiento de los sistemas
elctricos. Adicionalmente, los algoritmos utilizados para la
estimacin de las potencias son de fcil implementacin en
sistemas de medicin.
Las expresiones para obtener las potencias en sistemas
trifsicos de tres hilos se describen a continuacin.
Las corrientes efectivas del sistema trifsico (total, de la
componente fundamental y de las componentes diferentes a la
fundamental) se obtienen como:
2
1
2 2 2 2
2
1
2
1
2
1 1
2 2 2
3
3
3
e e cH bH aH eH
c b a e
c b a e
I I I I I I
I I I I
I I I I
= + + =
+ + =
+ + =
(25)
Las corrientes I
a
, I
b
e I
c
corresponden a las corrientes de las
fases a, b y c respectivamente del sistema trifsico.
De forma similar, las tensiones efectivas del sistema
trifsico (total, de la componente fundamental y de las
componentes diferentes a la fundamental) son iguales a:
2
1
2 2 2 2
2
1
2
1
2
1 1
2 2 2
9
9
9
e e caH bcH abH eH
ca bc ab e
ca bc ab e
V V V V V V
V V V V
V V V V
= + + =
+ + =
+ + =
(26)
Las tensiones V
ab
, V
bc
e V
ca
corresponden a las tensiones de
lnea del sistema trifsico.
A partir de (25) y (26) se obtienen las potencias efectivas
totales del sistema, de la componente fundamental y de las
componentes diferentes a la fundamental como:
2 2 2 2
1
2
1 1 1
3
3
eH eV eI e e eN
e e e
e e e
S D D S S S
I V S
I V S
+ + = =
=
=
(27)
Las potencias aparentes de distorsin de corriente, de
distorsin de tensin y armnica son iguales a:
eH eH eH
e eH eV
eH e eI
I V S
I V D
I V D
3
3
3
1
1
=
=
=
(28)
La potencia activa total trifsica se evala como:
( )

+
+ + = + + =
T t
t
c c b b a a c b a
dt i v i v i v
T
P P P P
0
0
1
(29)
La potencia reactiva total trifsica es igual a:
2 2
P S Q
e
= (30)
Finalmente, el factor de potencia total trifsico es igual a:
e
S P FP= (31)
Los valores de potencia activa, potencia reactiva y factor de
potencia tambin se pueden evaluar para la componente
fundamental. Las expresiones a utilizar son similares a las
descritas en (29) a (31), slo que en este caso se utiliza la
componente fundamental de tensin y corriente para evaluar
la potencia activa trifsica de la componente fundamental y en
lugar de la potencia aparente efectiva total (S
e
) se utilizan en
las expresiones la potencia aparente efectiva de la componente
fundamental (S
e1
).
Para sistemas trifsicos de cuatro hilos se utilizan las
expresiones presentadas para obtener las potencias teniendo
en cuenta que cambian las expresiones para calcular la
corriente efectiva y la tensin efectiva.
La obtencin de la corriente efectiva tiene en cuenta la
corriente del neutro (I
n
). Es decir:
2
1
2 2 2 2 2
2
1
2
1
2
1
2
1 1
2 2 2 2
3
3
3
e e nH cH bH aH eH
n c b a e
n c b a e
I I I I I I I
I I I I I
I I I I I
= + + + =
+ + + =
+ + + =
(32)
De forma similar la obtencin de la tensin efectiva tiene en
cuenta las tensiones de fase y de lnea del sistema, la ecuacin
correspondiente es la siguiente:
( ) [ ]
( ) [ ]
( ) [ ]
2
1
2 2 2 2 2 2 2
2
1
2
1
2
1
2
1
2
1
2
1 1
2 2 2 2 2 2
18 3
18 3
18 3
e e caH bcH abH cH bH aH eH
ca bc ab c b a e
ca bc ab c b a e
V V V V V V V V V
V V V V V V V
V V V V V V V
= + + + + + =
+ + + + + =
+ + + + + =
(33)
IV. MEDICIN DE LA ENERGA ELCTRICA CON MEDIDORES
DIGITALES
Con el auge de los equipos de medicin digital, la medicin
de energa elctrica est siendo revisada para establecer
metodologas de medicin con una adecuada exactitud que
generen confianza tanto en los suministradores como en los
usuarios del servicio. La medicin de la energa activa es
realizada de forma semejante por todos los medidores
digitales y bsicamente se realiza de la misma forma que con
los medidores electromecnicos; es decir, acumulando el
producto de las seales de tensin y corriente. Sin embargo,
an no hay uniformidad en los criterios de estimacin de las
energas aparente y reactiva como se describe en [10].
Para establecer como estiman la energa elctrica algunos
medidores digitales, se realiz una revisin de cuatro
diferentes medidores digitales de energa elctrica [8] (los ms
utilizados en los clientes no regulados de la Empresa
Electrificadora de Santander S.A. E.S.P.) y se encontr que la
estimacin de las potencias elctricas por fase se realiza con
algoritmos que difieren especficamente en la forma como
evalan las potencias y energas reactiva y aparente.
Todos los medidores obtienen las potencias trifsicas
sumando las potencias estimadas por cada fase; es decir, que
en esencia se considera que las potencias del sistema trifsico
corresponden a la suma de las potencias de tres sistemas
monofsicos.
La estimacin de la potencia activa monofsica de todos los
medidores se realiza promediando la potencia instantnea, que
para la fase a es:
[ ] [ ]

=
=
1
0
1
N
n
a a a
n i n v
N
P
(34)
La potencia activa trifsica se obtiene sumando las
potencias obtenidas para cada una de las fases del sistema. La
III Simposio Internacional sobre Calidad de la Energa Elctrica SICEL 2005
SICELIII-42 5

energa activa se estima de forma similar, la nica diferencia
es que no se realiza la divisin por N (nmero de muestras de
tensin y corriente). Cuando estos equipos se conectan en
sistemas trifsicos de tres hilos, se hace cero la corriente de
uno de los medidores monofsicos y se estima la potencia del
sistemas conectando los otros dos medidores monofsicos a
las tensiones de lnea que correspondan, dependiendo de las
corrientes que se estn adquiriendo (conexin Aron).
La estimacin de la potencia aparente por fase se efecta
multiplicando los valores eficaces de tensin y corriente, que
para la fase a sera:
RMSa RMSa a
I V S =
(35)
La potencia aparente total trifsica en los medidores
analizados se obtiene como la suma de las potencias aparentes
de cada fase; es decir, se estima la potencia aparente
aritmtica. Sin embargo, la estimacin de la energa aparente
en varios de ellos se obtiene a partir de las estimaciones de las
energas activa y reactiva.
La estimacin de la potencia reactiva por fase en tres de los
medidores analizados se realiza retrasando la seal de tensin
/2 radianes con respecto a la frecuencia del sistema, para
posteriormente evaluar el promedio del producto de esta
tensin con la seal de corriente. En uno de los medidores,
este desplazamiento en el tiempo de la seal de tensin se
realiza integrando la onda. En los otros dos, simplemente se
desplaza la onda de tensin; es decir, que las ondas
modificadas de la seal se obtienen de la siguiente forma:
( ) ( )
( )

=
=

2
t v t v
dt t v t v
Q
Q
(36)
Una vez se modifica la seal de tensin, la potencia reactiva
se evala como:
( ) ( )

=
T
Q
dt t i t v
T
Q
1
(37)
Esta potencia se evala en los medidores digitales como:
[ ] [ ] [ ] [ ]


=

=
= =
1
0
1
0
1 1
N
n
Q
N
n
Q
n i n V
N
n i n V
N
Q (38)
La expresin utilizada para estimar la potencia reactiva por
fase en el otro medidor estudiado es la siguiente:
2 2
P S Q = (39)
De las tres formas de evaluar la potencia reactiva, la ms
adecuada es la propuesta en (39), ya tiene en cuenta para la
estimacin de la potencia reactiva no slo los efectos
relacionados con la magnetizacin (elementos inductivos) o la
carga elctrica (elementos capacitivos) de los materiales sino
tambin los efectos de los armnicos en el sistema.
En todos los casos, la potencia reactiva total se obtiene
sumando las potencias de cada una de las fases.
La estimacin de la energa reactiva calculando la potencia
con (38) slo requiere que no se divida por N. En cambio, si
se utiliza (39) para evaluar la potencia reactiva es necesario
multiplicar las estimaciones de esta potencia por el tiempo
durante el cual se realiza la medicin para obtener la energa
reactiva.
V. CONTRASTACIN DE LAS POTENCIAS EVALUADAS POR LOS
MEDIDORES DIGITALES CON LAS PROPUESTAS EN IEEE 1459
Una vez determinados los algoritmos utilizados por los
equipos de medicin de energa elctrica para evaluar las
diferentes potencias y energas en sistemas trifsicos, se
realiz una contrastacin de los resultados obtenidos por estos
algoritmos con los establecidos en IEEE 1459. Los medidores
se denominaron con las letras A, B, C y D. La diferencia entre
estos medidores radica en las expresiones que utilizan para
evaluar la potencia reactiva y el factor de potencia.
Todos los medidores evalan de igual manera las potencias
activa y aparente. El medidor A evala la potencia reactiva de
acuerdo con (39), los dems medidores utilizan (38). En
cuanto al factor de potencia los medidores A, B y D utilizan la
expresin dada en (14) siendo P y S las potencia totales
trifsicas activa y aparente aritmtica respectivamente.
El factor de potencia del medidor C es obtenido como:
( ) ( ) P Q FP
1
tan cos

= (40)
En este artculo se presenta una simulacin realizada en un
sistema trifsico de tres hilos, considerando una tensin de
suministro simtrica, pero una carga lineal y desbalanceada;
adems se consideran dos formas de conexin: a) utilizando
los tres elementos de medida del instrumento y b) utilizando
slo dos elementos de medida (conexin Aron). En [9] se
muestran los resultados obtenidos bajo otros escenarios de
carga; para efecto de discusin de resultados se presenta este
caso.
Los valores eficaces de la tensin y corriente as como el
ngulo de fase entre ellas se presentan en la tabla I.

Las estimaciones de las potencias obtenidas con cada una
de los medidores utilizando los tres elementos del medidor se
muestran en la tabla II.

En la tabla III se muestran los resultados de potencia
cuando se utiliza la conexin Aron, teniendo en cuenta los tres
TABLA II
POTENCIAS ESTIMADAS POR LOS CUATRO MEDIDORES CONSIDERANDO
QUE SE CONECTAN LOS TRES ELEMENTOS
MEDIDOR P (kW) Q (kVAr) S (kVA) F.P.
A 61,55 16,79 64,25 0,9580
B 61,55 -2,87 64,25 0,9580
C 61,55 -2,87 64,25 0,9989
D 61,55 -2,87 64,25 0,9580
IEEE 1459 61,55 27,18 67,28 0,9148
TABLA I
TENSIONES Y CORRIENTES DEL SISTEMA
Fase Vrms
(V)
V (grados)
Irms (A)
I (grados)
R 120 0 232 -10
S 120 -120 102 -130
T 120 120 201,4 144
III Simposio Internacional sobre Calidad de la Energa Elctrica SICEL 2005
SICELIII-42 6

casos posibles (cambiando la fase de referencia)

Como puede apreciarse en las tablas II y III las
estimaciones de la potencia activa de los cuatro medidores
independientemente de si se utilizan tres o dos elementos es la
misma en todos los casos y coincide con la estimacin dada
por el modelo IEEE 1459.
Por el contrario, la estimacin de la potencia reactiva difiere
en los equipos de medida, especialmente entre el equipo A y
los dems. En el caso de los medidores B a D, el conectar el
dispositivo con tres o dos elementos (independientemente de
la fase que se tome como referencia) no influye en el valor
obtenido de potencia reactiva, an cuando ste tiene un error
apreciable si se considera el valor obtenido con el modelo
IEEE 1459 como referencia, llegando a ser este error en este
ejemplo del orden del 110,56%.
La estimacin de la potencia reactiva del medidor A
depende de la conexin que se realice e influye notablemente
la fase que se tome como referencia cuando se utilizan dos
elementos en sistemas de tres hilos. Los errores obtenidos en
este ejemplo tomando como referencia la estimacin obtenida
con IEEE 1459 varan de 57,21% a 138,63%.
Adicionalmente a la simulacin se muestra una medicin de
potencia realizada en una carga industrial con el medidor C y
se comparan los resultados de potencia con las estimaciones
obtenidas utilizando IEEE 1459. En la figura 1 se muestran las
estimaciones de potencia obtenidas directamente del medidor.

A partir de la informacin de la figura 1 y sabiendo que la
carga industrial de la cual se obtuvo esta informacin es de
tipo lineal se estimaron los valores de tensin y corriente, los
cuales se presentan en la tabla IV.

En la tabla V se presentan los resultados obtenidos del
medidor en la conexin Aron (fase S de referencia) y se
comparan con los que se obtendran si se cambia la fase de
referencia o si se utilizan los tres elementos del medidor.
Tambin se presentan los valores que se estimaran si se
utilizara el modelo IEEE 1459.

Los resultados de la tabla V corroboran lo establecido con
relacin al medidor C y es que independientemente de cmo
se conecten los elementos del medidor, la estimacin de la
potencia reactiva trifsica es similar en todos los casos. Los
cambios de la tensin de referencia influyen en la estimacin
de la potencia aparente; sin embargo, este cambio no afecta la
estimacin del factor de potencia, porque en este medidor la
evaluacin de este ndice se obtiene con (40) y por lo tanto no
interviene la potencia aparente. Para esta carga el error de la
TABLA V
POTENCIAS ESTIMADAS POR EL MEDIDOR C
Tipo de datos P (kW) Q
(kVAr)
S
(kVA)
F.P.
Lectura del medidor 64,257 22,896 77,508 0,942
Lectura del medidor
utilizando los tres
elementos
64,259 22,767 70,318 0,9426
Lectura del medidor
referencia fase R
64,280 22,755 95,598 0,9427
Lectura del medidor
referencia fase T
64,282 22,753 70,465 0,9427
IEEE 1459 64,259 33,953 72,678 0,8842
TABLA IV
TENSIONES Y CORRIENTES DEL SISTEMA
Tensin Vrms
(V)
V (grados)
Irms
(A)
I (grados)
RS 12 720 30 2,056 -30,46
ST 12 736 -90 3,478 -120,63
TR 12 728 149,54 4,035 90
Fig. 1. Visualizacin de lectura del medidor C.
TABLA III
POTENCIAS ESTIMADAS POR LOS CUATRO MEDIDORES CONSIDERANDO
QUE SE CONECTAN DOS ELEMENTOS (CONEXIN ARON)
Medicin en conexin Aron y fase R como referencia (I
R
= 0)
MEDIDOR P (kW) Q (kVAr) S (kVA) F.P.
A 61,54 11,62 63,05 0,9761
B 61,54 -2,87 63,05 0,9761
C 61,54 -2,87 63,05 0,9989
D 61,54 -2,87 63,05 0,9761
Medicin en conexin Aron y fase S como referencia (I
S
= 0)
MEDIDOR P (kW) Q (kVAr) S (kVA) F.P.
A 61,53 64,8466 90,0605 0,6832
B 61,53 -2,8696 90,0605 0,6832
C 61,53 -2,8696 90,0605 0,9989
D 61,53 -2,8696 90,0605 0,6832
Medicin en conexin Aron y fase T como referencia (I
T
= 0)
MEDIDOR P (kW) Q (kVAr) S (kVA) F.P.
A 61,54 30,11 69,40 0,8867
B 61,54 -2,86 69,40 0,8867
C 61,54 -2,86 69,40 0,9989
D 61,54 -2,86 69,40 0,8867
IEEE 1459 61,55 27,18 67,28 0,9148
III Simposio Internacional sobre Calidad de la Energa Elctrica SICEL 2005
SICELIII-42 7

estimacin de la potencia reactiva con respecto a la estimacin
dada por IEEE 1459 es de 33%. Adems, como el factor de
potencia estimado por el medidor es mayor a 0,9, no se
facturara cobro de reactiva y como se puede ver en la ltima
fila de la tabla V el factor de potencia efectivo es menor de
0,9.
VI. CONCLUSIONES
La medicin de potencia y energa en sistemas elctricos es
fundamental, ya que a partir de ella se establecen la mayora
de las transacciones comerciales entre los diferentes agentes
del sector elctrico. Por esta razn, este proceso debe
realizarse de una manera adecuada para que genere confianza
entre los todos los encargados de la generacin, transmisin
distribucin y comercializacin de la energa elctrica.
Adicionalmente, la reglamentacin relacionada con la
medicin de energa debe considerar la nueva naturaleza de
las cargas conectadas al sistema y a partir de esto determinar
los factores que puedan afectar los procesos de medicin, en
especial los relacionados con las energas reactiva y aparente.
Un mito que debe erradicarse de los procesos de medicin
es el de considerar que las potencias en sistemas trifsicos se
pueden estimar como la suma de las potencias de tres sistemas
monofsicos, lo cual es vlido para la estimacin de la
potencia activa, pero para las dems potencias slo se cumple
en sistemas trifsicos con tensin de suministro simtrica
cargas balanceadas.
Otro aspecto que debe reconsiderarse son los algoritmos de
estimacin de potencia y energa reactiva que utilizan algunos
medidores digitales, ya que se basan en los procesos de
medicin de reactiva utilizados por los medidores de
induccin desaprovechando que una vez se tienen las muestras
de tensin y corriente se pueden utilizar algoritmos que tengan
en cuenta todos los efectos del sistema de suministro y del tipo
de carga, los cuales causan incrementos en la potencia
aparente del sistema.
Revisando los resultados de la simulacin y las medidas
realizadas en una carga industrial se concluye que la conexin
Aron no es la ms adecuada para la estimacin de la potencia
reactiva en sistemas trifsicos que presenten desbalances en la
carga; adicionalmente, el efecto de los armnicos cuando las
cargas no son lineales empeora esta situacin.
Los autores consideran que es conveniente realizar anlisis
del efecto que tienen las medidas inadecuadas de energa
elctrica en la valoracin de las prdidas de energa en
sistemas elctricos. Esto es primordial considerando que se ha
establecido que el factor de potencia debe ser mayor o igual a
0,9 en todos los puntos de frontera del sector elctrico
colombiano, lo cual requiere de una adecuada medicin de las
potencias reactiva y aparente para las diferentes situaciones
que se puedan presentar en el sistema elctrico.
REFERENCIAS
[1] Leszek S. Czarnecki; Comparison of Power Definitions for Circuits
with No sinusoidal Waveform, IEEE , 1990.
[2] Johann F. Petit y Armando J. Ustariz; Anlisis General de Armnicos:
Revisin de las definiciones de potencia, Tesis de grado, Universidad
Industrial de Santander U.I.S. 1997. Director: Gabriel Ordez Plata.
[3] A. E. Emanuel, Summary of IEEE Standard 1459: Definitions for the
Measurement of Electric Power Quantities Under Sinusoidal, No
sinusoidal, Balanced, or Unbalanced Conditions IEEE Transactions On
Industry Application, vol. 40, No 3, pp. 869876, May/June 2004.
[4] Francisco de Len y Jos Cohen, Inconsistencias de las definiciones de
potencia y factor de potencia en circuitos no lineales y/o desbalanceados
Es la nueva norma IEEE1459-2000 la solucin? Reunin de verano
del captulo de potencia del IEEE seccin Mxico, Julio, 2002.
[5] W. V. Lyon, Discussion of Power factor in polyphase circuits, AIEE
Trans., vol. 39, p. 1515-20, 1920.
[6] Johan F Petit, Armando Ustriz, et al; Propuesta de factores de
discriminacin en regmenes no senoidales, Sptimas Jornadas
Hispano-Lusas de Ingeniera Elctrica, 2001.
[7] IEEE Trial-Use Standard Definitions for the Measurement of Electric
Power Quantities Under Sinusoidal, No sinusoidal, Balanced, or
Unbalanced Conditions, IEEE Standard 1459, 2000.
[8] Alexis Castillo, William Carvajal y Gabriel Plata; Comportamiento de
los contadores de energa activa monofsicos tipo induccin en
presencia de ondas de tensin y corriente con componentes armnicas,
5 Simposio regional de mejoramiento empresarial CIDET,
Bucaramanga, 1999.
[9] Oscar Quintero y Edward Gmez; Contadores de estado slido y
digitales: Anlisis de los algoritmos de medicin de energa e ndices de
calidad de onda que se pueden evaluar, proyecto de grado, UIS, 2004.
[10] Handbook for Electricity Metering, 10th Edition, Edison Electric
Institute, 2002.
Gabriel Ordez Plata. Ingeniero Electricista, Doctor Ingeniero Industrial
UPCO, Madrid, Espaa. Profesor Titular de la Escuela de Ingeniera
Elctrica, Electrnica y Telecomunicaciones Universidad Industrial de
Santander (UIS). Director GISEL. reas de trabajo: Tratamiento de seales,
mediciones elctricas, calidad del servicio, gestin tecnolgica y formacin
basada en competencias. E-mail: gaby@uis.edu.co.
Csar Antonio Duarte Gualdrn. Ingeniero Electricista, Magster en
Potencia Elctrica UIS, Bucaramanga, Colombia. Profesor Auxiliar de la
Escuela de Ingeniera Elctrica, Electrnica y Telecomunicaciones
Universidad Industrial de Santander (UIS). Investigador GISEL. reas de
Trabajo: Tratamiento de seales, calidad del servicio de energa elctrica y
formacin basada en competencias. E-mail: cedagua@uis.edu.co.
III Simposio Internacional sobre Calidad de la Energa Elctrica SICEL 2005
SICELIII-42 8