Description of items Qty Unit
1
1.1
Supply, install, test and commission Intelligent
Addressable Fire Alarm Control Panel (MCP) as per the
technical specification and not limited to having Visual
Display Unit (VDU) preferably 640 character LCD display
with battery back up for 24 hours for normal operation and
another 1 hours on alarm condition. The control panel,
battery charger etc, shall be UL Listed and FM approved.
The panel shall work in a flash scan protocol and shall be
capable of networking with other compatible panels and
Central Station. The panel shall have 1 Loop Capacity and
shall be expandable up to 2 Loops.
2 Set
1.2
Supply, install, test and commission Double Action Manual
Pull Station having an integrally mounted addressable
module that monitors and reports contact status.
82 Nos.
1.3
Supply, install, test and commission Loop Addressable
Sounder, as per specification.
76 Nos.
1.4
Supply, install, test and commission Intelligent
Addressable Input/Monitor Module, as per specification
for interface with Fire Sprinkler Annunciating System.
42 Nos.
1.5
Supply, install, test and commission Intelligent
Addressable Fault Isolator Module capable of monitoring
shorted loop circuit and automatically restore
communications when shorted conditions are corrected.
12 Nos.
1.6
Supply, install, test and commission 24V, 2.5Amps DC
Power Supply Unit for the above sounders.
20 Nos.
1.7
Supply, install, test and commission 2 core x 1.5 mm2
FRLS Cable confirming to IS: 1554 and as per specification.
(Approx. Quantity)
6000 Mtr.
1.8
Supply, install, test and commission 25mm. approved
make PVC Conduits conforming to IS and specification on
walls / ceiling / floor etc complete with all accessories like
junction boxes, collars, bends etc.(Approx. Quantity)
1500 Mtr.
SCHEDULE OF QUANTITIES
INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM
TOTAL FOR INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM
2
2.1
Supply, install, test and commission 25-Zone Public
Addressing Control Desk, approved make, CRCA Powder
Coated, with all call/call back facility, power supply unit
etc, complete, as per specification.
2 Set
2.2
Supply, install, test and commission Solid State Amplifier,
480 W RMS Out Put in rack, including necessary control
wires, jacks etc, as per specification.
4 Set
2.3
Supply, install, test and commission Solid State Mixing
Amplifier, 60 W RMS Out Put in rack, including necessary
control wires, jacks etc, as per specification.
4 Set
2.4
Supply, installation, testing and commissioning of 15 Watt
Wall/Ceiling Mounted Type Speakers with talk back
facility, in CRCA sheet fabricated housing, as per
specification.
76 Set
2.5
Supply, installation, testing and commissioning of
Gooseneck Microphone, as per specifications.
2 Set
2.6
Supply, installation, testing and commissioning of Tone
Generator, as per specification.
2 Mtr.
2.7
Supply, install, test and commission 2 core x 1.0 mm2
Cable confirming to IS: 1554 and as per specification.
(Approx. Quantity)
3000 Mtr.
2.8
Supply, install, test and commission 25mm. approved
make PVC Conduits conforming to IS and specification on
walls / ceiling / floor etc complete with all accessories like
junction boxes, collars, bends etc.(Approx. Quantity)
1500 Mtr.
3 FIRE HOSE REEL AND HYDRANT SYSTEMS
3.1
Supply, installation, testing and commissioning of Manual
Swing Type Fire Hose Reel complete with heavy duty reel,
19mm. dia.x30Mtr. long 2-ply polyester yarn braided
/rubber braided pressure hose bearing IS:444 Type II mark,
6 mm bore Red Coloured, heavy duty nylon on/off jet/spray
nozzle conforming to IS:884, 22mm. isolating valve and all
other necessary fixing accessories.
50 Set
PUBLIC ADDRESSING SYSTEM
TOTAL FOR PUBLIC ADDRESSING SYSTEM
3.2
Supply, installation, testing and commissioning of Fire
Hydrant Valve, bearing to ISI:5290 Type-A mark, Stainless
Steel-304 body with 63mm. oblique instantaneous single
outlet, 75mm. N.B. flanged inlet, Stainless Steel -304
spindle, complete with PVC blank cap, G.I. chain,flange OD
200 mm, PCD 160 mm, four 19 mm dia holes etc.
52 No.
3.3
Supply, installation, testing and commissioning of Fire
Hose, RRL hose jacketed with circular woven synthetic fibre.
conforming to IS: 636:88, with Working Pressure 14
Kg/Cm2, Proof Pressure 22 Kg/Cm2 and Burst Pressure 38
Kg/Cm2. The Fire Hose shall be with IS: 636 Type-A
marking and 63mm.dia.x15Mtr.long x 2 Nos. with 2 pair of
63mm. male and female instantaneous couplings, Stainless
steel-304, having IS: 903 mark and duly S. S. wire
wounded. The hose shall be rolled and hung to suitable M.
S. support in the Fire Station.
52 Set
3.4
Supply, installation, testing and commissioning of Branch
Pipe, Stainless Steel-304, short type, with 63mm. male
instantaneous inlet, male threaded outlet, fitted with 16mm.
bore nozzle, having IS: 903 mark.
52 Set
3.5
Supply, installation, testing and commissioning of Air
Release Valve Gunmetal, conforming to IS 903:1993,
having rubber ball with sealing seat and with 25mm. BSP
threaded male inlet, including necessary accessories and
connections.
6 Set
3.6
Supply, installation, testing and commissioning of 25mm.
Ball Valve,PN-20gunmetal/cast alloy, conforming to IS:
13095, including necessary accessories and connections.
6 Set
3.7
Supply, installation, testing and commissioning of 4" dia.
Pressure Gauge. ISI Marked from Approved
Manufacturers.
6 No.
3.8
Supply, installation, testing and commissioning of Butterfly
Valve, slim seal, standard lever operated type confirming to
BS:5155 with IS: 13095 Mark, slim seal standard lever
operated type confirming with required flanges, nuts, bolts
etc. complete.
3.8.a 150mm. PN-20 RO No.
3.8.b 150mm. PN-16 12 No.
3.8c 100mm. PN-16 2 No.
3.8d 80mm. PN-16 6 No.
3.8e 50mm. PN-16 2 No
3.9
Supply, installation, testing and commissioning of Pressure
Reducing Station complete with Pressure Reducing Valve,
conforming to AFNOR NF 43-006 and BS6765, including all
necessary accessories, 25 Bar Rating, (3.5 to 8 Bar) as
detailed in the Technical Specifications and with Pressure
Gauges with siphon connections on upstream and down
stream etc. This Station shall be for reducing pressure in
Fire Hydrant System in lower floors.
3.9a 150mm. 2 No.
3.10
Supply, installation, testing and commissioning of Non
Return Valve, Wafer Swing Check type, PN-20,
conforming to IS: 13095 type confirming with companion
flanges, nuts, bolts etc. complete. 150mm.
4 No.
3.11
Supply, installation, testing and commission Y-Strainer with
Cast Iron Body with ANSI Flanges, 1/8" heavy gauge
perforated. S. S. Screen, etc. confirming with suitable fixing
flanges, nuts, bolts etc. complete. 150mm.
2 Set
3.12
Supply, installation, pressure testing and commissioning of
Above Ground Fire Hydrant Pipe Work with Heavy Duty
(Class-C) Mild Steel Pipes, confirming to IS :1239 Part - I,
with Heavy Duty Fittings, confirming to IS:1239 Part - II,
(Forged Steel Screwed Fittings for Pipes up to 50mm. dia.
and But Welded Fittings, for pipes above 50mm. dia), such
as tees, elbows, check nuts, unions, flanges, nipples etc.
including cutting, threading, welding, jointing, fixing in
ducts, on walls, ceiling by using suitable supports, providing
higher sizes of Sleeves/Opening, wherever required, and
protecting with approved wash primer and top coat (two
coats) painting system as per specification.
3.12a 150mm. dia 308 Mtr.
3.12b 100mm. dia 60 Mtr.
3.12c 80mm. dia. 16 Mtr.
3.12d 25mm. dia. 12 Mtr.
3.13
Fire Station Shutter, fabricated out of 16 swg. M.S. Sheet.
Door shall be 1000 x 1600 mm. min. & fixed with 4 mm
thick Wired Glass, Rubber Beading and Locking
arrangement. Quoted rate shall be includes all fasteners etc,
and complete shutter shall be powder coated of approved
colour both inside and out side. (OPTIONAL)
50 Set
4
4.1
Supply, installation, testing and commissioning of Standard
Response Upright Type Automatic Fire Sprinkler, 68/79
degree, K- Factor: 5.6 or equal with necessary accessories
and fittings.
564 Nos.
4.2
Supply, installation, testing and commissioning of Standard
Response Pendant Type Automatic Fire Sprinkler, 68/79
degree, K- factor: 5.6 or equal with necessary accessories
and fittings.
284 Nos.
4.3
Supply, installation, testing and commissioning of Standard
Response Side Wall Type Automatic Fire Sprinkler, 68
degree, K- factor: 5.6 or equal with necessary accessories
and fittings.
884 Nos.
4.4
Supply and installation of 2 piece Chrome Plated friction
fit recessed escutcheon for pendant sprinklers in lobby
and side wall sprinklers in apartments.
1168 Nos.
4.5
Supply only above Upright Type Automatic Fire Sprinkler.
(5% extra.)
RO Nos.
4.6
Supply only above Pendant Type Automatic Fire
Sprinkler. (5% extra.)
RO Nos.
4.7
Supply only above Side Wall Type Automatic Fire
Sprinkler. (5% extra.)
RO Nos.
4.8
Supply, installation, testing and commissioning of Air
Release Valve Gunmetal, conforming to IS 903:1993,
having rubber ball with sealing seat and with 25mm. BSP
threaded male inlet, including necessary accessories and
connections.
6 Set
4.9
Supply, installation, testing and commissioning of 25mm.
Ball Valve, PN-20 gunmetal/cast alloy, conforming
to IS: 13095, including necessary accessories and
connections.
4 Nos.
4.10
Supply, installation, testing and commissioning of Butterfly
Valve, slim seal, standard lever operated type confirming to
BS:5155 with IS: 13095 Mark, slim seal standard lever
operated type confirming with required flanges, nuts, bolts
etc. complete.
4.10a 150mm. PN-20 RO No.
4.10b 150mm. PN-16 10 No.
4.10c 100mm. PN-16 4 No.
4.10d 80mm. PN-16 32 No.
4.10e 65mm. PN-16 2 No.
TOTAL FOR FIRE HOSE REEL AND HYDRANT SYSTEM
AUTOMATIC FIRE SPRINKLER SYSTEM
4.10f 50mm. PN-16 42 No.
4.11
Supply, installation, testing and commissioning of Pressure
Reducing Station complete with Pressure Reducing
Valve, conforming to AFNOR NF 43-006 and BS6765,
including all necessary accessories, 25 Bar Rating, (3.5 to 8
Bar) as detailed in the Technical Specifications and with
Pressure Gauges with siphon connections on upstream and
down stream etc. This Station shall be for reducing pressure
in Fire Sprinkler System in lower floors
4.11a 150mm. dia. 2 No.
OPTIONAL FOR REVISED DESIGN, IF REQUIRED
4.11b 150mm. dia. RO No.
4.11c 100mm. dia. RO No.
4.11d 80mm. dia. RO No.
4.12
Supply, installation, testing and commissioning of 4" dia.
Pressure Gauge. ISI Marked from Approved
Manufacturers.
44 No.
4.13
Supply, installation, testing and commissioning of Flow
Switch, Paddle type, IP 65 Protection with 20 Bar Working
Pressure Protection with all necessary accessories, for
monitoring Fire Sprinkler System. The control cabling from
flow switches to Fire Sprinkler Annunciating Panel shall be
measured separately.
42 Set
4.14
Supply, installation, testing and commissioning of
Hydraulically Operated Fire Sprinkler Alarm Valve (
Installation Control Valve) UL Listed / FM approved,
complete with check valve, trim set, water motor gong,
control valves, pressure switch, pressure gauges etc.
including all necessary flanges and fixing accessories.
4.14a 150mm. dia. 2 No.
4.15
Supply, installation, pressure testing and commissioning of
Above Ground Fire Hydrant Pipe Work with Heavy Duty
(Class-C) Mild Steel Pipes, confirming to IS :1239 Part - I,
with Heavy Duty Fittings, confirming to IS:1239 Part - II,
(Forged Steel Screwed Fittings for Pipes up to 50mm. dia.
and But Welded Fittings, for pipes above 50mm. dia), such
as tees, elbows, check nuts, unions, flanges, nipples etc.
including cutting, threading, welding, jointing, fixing in
ducts, on walls, ceiling by using suitable supports, providing
higher sizes of Sleeves/Opening, wherever required, and
protecting with approved wash primer and top coat (two
coats) painting system as per specification.
4.15a 150mm.dia 218 Mtr.
4.15b 100mm. dia. 148 Mtr.
4.15c 80mm. dia. 406 Mtr.
4.15d 65mm. dia. 768 Mtr.
4.15e 50mm. dia. 1438 Mtr.
4.15f 40mm. dia. 603 Mtr.
4.15g 32mm. dia. 1572 Mtr.
4.15h 25mm. dia. 3468 Mtr.
4.15i 20mm.dia 12 Mtr.
5
Supply, test, commission and install in position following
Portable Fire Extinguisher with Relevant IS Marks.
5.1 CO2 - 4.5 Kg. IS: 2878. 4 Nos.
5.2 Water CO2 - 9 Ltr. IS: 940 54 Nos.
5.3
ABC Dry Chemical - 5 Kg. IS: 2171. (Approx. Vary with no.
of parking.)
50 Nos.
5.4 Fire Bucket. (Approx. Vary with no. of parking.) 54 Nos.
6
Supply and install in position Sign Boards made out of
3mm thick "Opaque" PVC foam board with computer cut,
PVC non-reflective self adhesive vinyl painted foam board,
complete with mirror fasteners.
TOTAL FOR FIRE SPRINKLER SYSTEM
FIRE EXTINGUISHERS
TOTAL FOR FIRE EXTINGUISHERS
SIGNAGE
6.1
Signage Printed "IN CASE OF FIRE, USE STAIRS UNLESS
INSTRUCTED OTHERWISE" of 1.25cm. height letters in red
with white back ground. The size of the board shall be 25 x
25 Cms. and shall be fixed at the height of 2Mts. from
finished floor near Manual Pull Stations.
82 Nos.
6.2
Floor Identification Signage ( ie, GROUND FLOOR etc.) at
each stair enclosure on every floor, indicating the floor
number in words, lettering size shall be 5 Cm. with
contrasting colour from back ground. Size shall be 15cm x
30cm.
90 Nos.
6.3
Supply and install in position the Signage " FIRE ORDER" it
should contain the following matter on 3mm thick "Opaque"
PVC foam board of computerised cut, PVC non-reflective self
adhesive vinyl painted foam board of 2' x 3'.
98 Nos.
A) ALERT THE SECURITY AT SECURITY ROOM BY
ACTUATING MANUAL CALL POINT LOCATED AT
STRATEGIC LOCATIONS.
B) EVACUATE THE OCCUPANTS BY USING FIRE EXITS
AND EMERGENCY EXITS ONLY AND ASSEMBLE AT
VARIOUS ASSEMBLY POINTS.
C) IF POSSIBLE TRY TO EXTINGUISH THE FIRE BY USING
NEAREST / SUITABLE PORTABLE EXTINGUISHER OR
WATER FROM NEAREST WET RISER.
D) BE CALM AND DO NOT GIVE ANY ROOM FROM PANIC,
WALK, DO NOT RUN.
E) IF YOU ENCOUNTER SERIOUS DIFFICULTY IN
EVACUATION, FLAT AND TRY TO ATTRACT ATTENTION OF
RESCUE TEAM.
6.4
ACTION BY SECURITY/RECEPTION UPON RECEIPT OF
INFORMATION THROUGH FIRE ALARM OR FIRE
DETECTORS OR BY USING PUBLIC ADDRESS SYSTEM.
8 Nos.
A) ALERT THE OCCUPANTS BY USING PUBLIC ADDRESS
SYSTEM.
B) INFORM FIRE CONTROL THROUGH ANY ONE OF THE
FOLLOWING PHONE NUMBERS: 101 / ..
C) REFER EVACUATION PLAN FROM EVACUATING
STANDARD PEOPLE.
D) GUIDE THE FIRE FORCE, ON THEIR ARRIVAL TO THE
SEAT OF FIRE.
E) IN CASE OF THE CASUALTIES, CALL AMBULANCE BY
DIALING NUMBER..
FIRE FIGHTING AGENCY -------------------------------
PHONE : -----------------------
FAX : ----------------------------
TOTAL FOR SIGNAGE
1
2
3
4
5
6
FIRE EXTINGUISHERS
SIGNAGE
ABSTRACT
INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM
PUBLIC ADDRESSING SYSTEM
FIRE HOSE REEL AND HYDRANT SYSTEM
FIRE SPRINKLER SYSTEM
GRAND TOTAL
Rate Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
SCHEDULE OF QUANTITIES
INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM
TOTAL FOR INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
PUBLIC ADDRESSING SYSTEM
TOTAL FOR PUBLIC ADDRESSING SYSTEM
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
TOTAL FOR FIRE HOSE REEL AND HYDRANT SYSTEM
AUTOMATIC FIRE SPRINKLER SYSTEM
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
TOTAL FOR FIRE SPRINKLER SYSTEM
FIRE EXTINGUISHERS
TOTAL FOR FIRE EXTINGUISHERS
SIGNAGE
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
FIRE EXTINGUISHERS
SIGNAGE
ABSTRACT
INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM
PUBLIC ADDRESSING SYSTEM
FIRE HOSE REEL AND HYDRANT SYSTEM
FIRE SPRINKLER SYSTEM
0.00 GRAND TOTAL