Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
6ihpUuv
rr
ruqyt
hhyr
rrx
ryvt
vvyhv
vu
phvhy
hytvu
syhv
8rry
ur
puhpuvrhrrrrq
Dqr Ur
IrhyIrxQrTrUhvrThivyv6hyv
I. INTRODUCTION
M.C.G. Silveira is a PhD. student at UNESP Ilha Solteira, SP, Brazil (e-mail:
carmo@feis.unesp.br).
A. D. P. Lotufo is with UNESP Ilha Solteira, SP, Brasil, and Ph.D. student at
UNESP Ilha Solteira, SP, Brazil (e-mail: annadiva@dee.feis.unesp.br).
C. R. Minussi is with UNESP Ilha Solteira, SP, Brazil (e-mail:
minussi@dee.feis.unesp.br).
L1
L 1
(2)
L 1
where:
= + V;
0
V
synchronous speed of the rotor
= I ;
+
= inertia constant (s);
= nominal frequency of system (Hz);
I
=
0 ;
v
L1
(1)
3 ( ) = 3P 3H ( 0 3&2$ ) / 07
(5)
0 3 ( )
(4)
where:
LS 3 ( ) G
v
(6)
v
if 0
M1
ART b
M1
07
QV
M1
Srr
Ihyvhv
i
ab
i
!
HhpuUhpxvt
Hh
Avryq
hi
ART a
Srr
hi
(3)
Ihyvhv
h
where:
(FULW = total critical energy of the system;
= total energy of the system evaluated on the instant
(H
of the fault elimination (WH).
= choice parameter;
= learning rate parameter.
= = (D)/|D|
where:
D = input vector;
= = [= = = ] (normalized);
| | = norm function.
!
[= = ]
= [= = =
p
= ]
p
(7)
where:
= = 1=.
p
= (P
|,| =
=
=
=)
v
= P.
7 = | , Z | / ( + | Z |),
w
(8)
L =
(10)
(11)
) + ( ) Z
yq
yq
(13)
(9)
=(,Z
r
E
=
=
=
=
=
(14)
\ = I(D, )
where:
\
I (D)
60,
N = 6
)X]]\ $570$3
60,
)X]]\ $570$36
\6
60,
(15)
where:
= set of codified information.
)X]]\ $570$3
Preprocessing Information
(16)
$ ,QSXW 6WLPXOXV
The proposed neural structure seeks to analyze EPS
transient stability, that corresponds to determine the security
margin, considering three-phase short-circuit faults with
outage of a transmission line. The neural network input
pattern vectors are defined as:
D
[3 4]
(17)
where:
D
3
4
3
4
Q
v
v
=
=
=
=
=
=
% 2XWSXW 6WLPXOXV
The output stimulus to be applied on the ARTb module of
the ARTMAP neural network are the security margins
corresponding to the input pattern vectors (ARTa module).
The strategy used in this work, is the using of security margin
intervals where are the contingencies. For example, a
contingency having the security margin equal to 0.5 can be
arbitrated as pertaining to the interval (0.4 0.6). This permits
that the contingencies can be expressed as a binary code and
reduce the number of classes on the ARTb module, which is a
more adequate form to work with ARTMAP network,
= ( 0 ) ( 0 )
6
(18)
where:
,0
7
x
(19)
where:
06,
11
12
13
14
15
Fault
Fault
Number
1
2
3
4
5
Short-circuit
Bus
15
18
18
29
39
Circuit open
Initial Bus
14
16
18
29
39
Final Bus
15
18
44
30
40
TABLE III
SPECIFICATION OF NEURAL NETWORK PARAMETERS
Item
Value
0.99
0.97
0.90
1
0.1
h
i
hi
Learning rate parameter
Choice parameter
Vigilance parameters:
TABLE IV
COMPARATIVE ANALYSIS OF THE TRANSIENT STABILITY RESULTS
Fault
Number
!
"
#
$
: 0.10 s.
VII. CONCLUSION
It is developed in this work a proceeding for a multimachine electric power system transient stability analysis, by a
fuzzy ARTMAP neural network. With this architecture, it
could be idealized a proceeding for electric power system
transient stability analysis. The neural network input stimulus
are constituted by the active and reactive nodal power vectors
(analog data). The outputs correspond to the system security
margins represented by the intervals between the maximum
and the minimum values. This way, it is possible to represent
the outputs in binary code (binary outputs). The obtained
results can be considered satisfactory, i.e., they attained the
proposed objectives. The ARTMAP neural network gives good
and fast solutions (around 1 second using a Pentium III, 500
MHz microcomputer, considering the execution of the voting
strategy with 5 training repetition). The quality of the solutions
is adequate. Nevertheless, some imprecision is observed, which
come from a training set not enough complete, and not from
the neural network. It is emphasized that the precision of the
results is dependent of the volume of the data training and also
of the quantity of output segments (60,).
1
2
3
4
5
!
"
#
$
1
2
3
4
5
!
"
#
$
1
2
3
4
5
!
"
#
$
1
2
3
4
5
Seed
123
289
73
190
391
381
73
1
355
999
24
257
191
309
60
71
137
19
244
60
200
28
163
131
2
100
389
275
380
77
121
320
11
220
55
Neural Network
15
7
9
15
13
14
9
12
15
12
12
7
8
15
8
12
5
5
15
8
12
5
5
12
6
11
5
5
15
6
11
4
5
15
7
11
4
5
14
7
VIII. REFERENCES
[1]
[2]
[3]
[4]
[5]
[6]
IX. BIOGRAPHIES
graduated
in Physical Science from UNESP, Rio Claro, SP,
Brazil, in 1987. Received her M.Sc. degree from
UNESP, Ilha Solteira, SP, Brazil, in 1994. She is
presently a Ph.D. student at UNESP-Ilha Solteira,
doing research in the area of electric power
system transient stability and neural Network.
E_mail: carmo@feis.unesp.br .
Hhvh q 8h Br qh Tvyrvh
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
9 Q Gs graduated
in electrical
engineering from UFSM, Santa Maria, RS,
Brazil in 1978 and M.Sc. from UFSC,
Florianpolis, SC, Brazil, in 1982. She is
currently an Assistant Professor at UNESP Ilha
Solteira, SP, Brazil and Ph.D. student at UNESP,
doing research in the area of transient and
preventive control of electrical power system. Email: annadiva@dee.feis.unesp.br .
6h
230 kV
(71)
(72)
43
(68)
(69)
(67)
S. Santiago
33
(51)
(39)
10
36
25
230
(58)
(42)
Itaba
(65)
(10)
(11)
V. Aires
37
(62)
(63)
(64)
(49)
31
40
(35)
(37)
(38)
13
(9)
45
(59)
(60)
(61)
(34)
Rancho
Queimado 24
230
J. Lacerda
230
230
Siderpolis
(7)
Ceci
(12)
230
(13)
6
(54)
(8)
(53)
34
Forquilinha
13.8 13.8
(57)
230
(47)
22
23
(46)
230
(14)
525 kV 230 kV
(66)
39
Farroupilha
13.8
13.8 230kV
1
1
14
(18)
(32)
(33)
525
(6)
(15)
15
28
13.8
29
Passo
Fundo
(48)
525
Blumenau
230
Barraco
(19)
16
32
Joinvile
(45)
20
525
(17)
(28)
230
(26)
(20)
(16)
(29)
(30)
21
(36)
Xanxer
Pinheiro
230
(31)
S. Mateus
(27)
19
Pato 230
Branco
230
525
26
17
(50)
Curitiba
(44)
(40)
(43)
13.8
(21)
(41)
(52)
10
(23)
13.8
525
(3)
525
18
(22)
11
(4)
Segredo
230 kV
230
27
Ivaipor
(2)
Apucarana
(24)
525
12 (1)
(5)
Areia
41
(70)
Salto
Osrio
525
42
44
(25)
Curitiba-Norte
230
230 kV
(73)
Londrina
Maring
Campo Mouro
S Hvv
graduated in electrical
engineering from UFSM, Santa Maria, RS,
Brazil in 1978, M.Sc. and Ph.D. from UFSC,
Florianpolis, SC, Brazil, in 1981, and 1990,
respectively. He is currently an Associate
Professor at UNESP Ilha Solteira, SP, Brazil.
His main interests are in analysis, control of
power systems, and neural networks. E-mail:
minussi@dee.feis.unesp.br .
8hy
35
(55)
30
13.8
38 230
525
Gravata
(56)
13.8