6
circuit-breakers
Rated voltages
Rated currents
Rated breaking currents
Installation
72.5 - 800 kV
4000 A
up to 63 kA
Outdoor
................................................................................................................
.............................................................................................................................
.................................................................................................
..................................................................................................................................
Main features and advantages
Testing
Design
Restrike-free interruption of capacitive current
The circuit-breakers have passed type tests in
accordance with IEC standards.
Mechanical endurance tests to 10 000 opera-
The breaker pole constitutes a sealed unit ,
which includes one or two breaking unit(s),
support and operating insulators, and pole
linkage housing. To the latter the opening
spring is attached.
To ensure the quality of the gas, each
breaker is provided with a filter for moisture
absorbtion.
The breaker poles are filled with gas to a
pressure of 0.7 MPa (abs. + 20C) for opera-
tion down to - 30C.
The breaker is designed and tested for
operations in ambient temperatures down
to -50C.
due to optimized contact design and movement.
Low overvoltages when switching inductive currents as
a result of optimum quenching at current zero.
High dielectric strength even at atmospheric
pressure, due to optimized contact gap.
High security against gas leakage due to double X-
rings in all dynamic seals and double O-rings in static
seals, verified during more than 30 years of field opera-
tion under various climatic conditions. ( gas loss
much less than 1 percent / year.)
Long maintenance intervals due to separate current
paths for continuous and arcing currents, respectively.
Reliable components due to all parts optimized, aided
by advanced computer technology, for electrical and
mechanical stresses.
High seismic withstand capability due to optimized pole
and structure.
Low noise level due to low mechanical energy required
for operation.
Easy installation and commisioning. Each
circuit-breaker is pre-tested and shipped to
installation site in the form of a few pre-
assembled units.
Optional synchronised switching due to
synchronising relay type Switchsync.
Optional supervisory control due to condition
monitoring.
The HPL is a puffer type SF
6
circuit-breaker
designed for system voltages 72.5 - 800 kV and for
rated short-circuit currents up to 63 kA. The design
incorporates an improved puffer interrupter based on
experience from previous interrupter designs.
Circuit-breakers with one breaking unit per pole
can be operated with one operating mechanism per
breaker. All single pole operated circuit-breakers are
equipped with one operating mechanism per pole.
The HPL circuit-breaker complies with the IEC and
ANSI international standards.
The HPL circuit-breaker family satisfies the highest
demands. It is based on the latest developments
SF
6
Circuit-breakers for outdoor installation
SF
6
SF
6
in dielectric dimensioning and arc physics research.
Following are the main advantages:
tions have been performed.
Before delivery each circuit-breaker must pass
routine tests in accordance with IEC and ANSI.
For each circuit-breaker a routine test report is
issued showing actual test results.
The breaking unit insulator encloses the
breaking chamber with stationary and
moving arcing contacts. The current paths
are connected to the end flanges for
terminal connection.
The support insulator encloses the operating
insulator which connects the operating
mechanism to the breaking unit.
SF
6
SF
6
Number of breaks per pole
Rated voltage
Power frequency withstand voltage:
To earth
Across open pole
Lightning impulse withstand voltage (LIWL):
To earth
Across open pole
Switching impulse withstand voltage (SIWL):
To earth
Across open pole
Minimum creepage distance
Rated normal current
Rated breaking current
First pole to clear factor
Making current / peak
Duration of short circuit
Closing time
Opening time
Total break timne
Dead time
Rated opening sequence
Technical Data
Values complying with IEC (50 Hz), other values on request.
Number of breaks per pole
Rated voltage
Power frequency withstand voltage
To earth
Across open pole
Lightning withstand voltage (LIWL):
To earth
Across open pole
Switching impulse withstand voltage (SIWL):
To earth
Across open pole
Minimum creepage distance
Rated normal current
Rated breaking current
First pole to clear factor
Making current / peak
Duration of short circuit
Closing time
Opening time
Total break time
Dead time
Rated operating sequence
kV
kV
kV
kV
kV
kV
kV
mm/kV
A
kA
kA(peak)
s
ms
ms
ms
ms
IEC
ANSI
1
245
460
460
1050
1050
N/A
N/A
25
4000
50
1.5
125
3
<65
1
300
380
435
1050
1050(+170)
850
850
25
4000
50
1.5
125
3
<65
2
362
450
520
1175
1175(+205)
950
800(+295)
25
4000
50/63
1.3
125/157.5
3
<65
18 or 202
40
300
O - 0.3 sec - CO - 3 min - CO
CO - 15 sec - CO
2
420
520
610
1425
1425(+240)
1050
900(+345)
25
4000
50/63
1.3
125/157.5
3
<65
2
550
620
800
1550
1550(+315)
1175
900(+450)
25
4000
50/63
1.3
125/157.5
3
<65
4
800
830
1150
2100
2100(+455)
1425
1100(+650)
25
4000
50/63
1.3
125/157.5
3
<90
kV
kV
kV
kV
kV
kV
kV
mm/kV
A
kA
kA
s
ms
ms
ms
ms
IEC
ANSI
1
72.5
140
140
325
325
N/A
N/A
25
3150/4000
50/63
1.5
158
3
<75
1
145
275
275
650
650
N/A
N/A
25
3150/4000
50/63
1.5
158
3
<80
1
170
325
325
750
750
N/A
N/A
25
3150/4000
50/63
1.5
158
3
<80
202
40
300
O - 0.3 sec - CO -3 min - CO
CO - 15 sec - CO
2
245
460
460
1050
1050
N/A
N/A
25
3150/4000
50/63
1.5
158
3
<70
2
300
380
435
1050
1050(+170)
850
700(+245)
25
3150/4000
50/63
1.5
158
3
<70
2
362
450
520
1175
1175(+205)
950
800(+295)
25
3150/4000
63
1.3
158
3
<70
HPL 72.5A1 145A1 170A1 245A2 300A2 362A2
HPL 245B1 300 B1 362B2 420B2 550B2 800B4
Dimensions
HPL 72 -170A1
1-pole operation with BLG 1002A
Circuit breaker A B C D E*
Type HPL 72A1 670 1292 3307 4822 1100
Type HPL 145A1 1280 1292 3917 5432 2500
Type HPL 170A1 1520 1292 4157 5672 2500
Circuit breaker F G H K
Type HPL 245A2 2163 1292 3584 6435
Type HPL 300A2 2473 1292 3584 6745
Type HPL 362A2 2860 1292 3584 7145
* Values shown are min. phase spacing (per relevant standards).
Max. permissible phase spacing is 4000.
Dimensions (mm)
HPL 245 - 362A2
1-pole operation with BLG 1002A
HPL 72 - 170A1
3-pole operation with BLG 1002A
Dimensions
HPL 245 - 300B1
3-pole operation with BLG 1002A
HPL 362 - 550 B2
1-pole operation with BLG 1002A
Circuit breaker
Type HPL 245 B1
Type HPL 300 B1
A
1955
2205
B
1914
2124
C
4570
4820
D
6703
7163
E*
3500
3500
Circuit breaker
Type HPL 362 - 420B2
Type HPL 550 B2
F
3105
4135
G
1724
1914
H
4441
4882
J
6541
7571
*Values shown are min. phase spacing (per relevant standards).
HPL 245 - 300B1 HPL 800B4
1-pole operation with BLG 1002A 1-pole operation with BLG 1002A
Dimensions (mm) Dimensions (mm)
Max. permissible spacing is 4000.
ABB Power Technology Products AB / HV Products
SE-771 80 LUDVIKA, Sweden
Tel: +46 240 78 20 00
Fax: +46 240 78 36 50
Internet: www.abb.com
The circuit-breaker is operated by motor charged spring
operating mechanism(s) type BLG 1002A, which is
installed in a splash-proof and corrosion resistant housing,
attached to the structure.
One BLG 1002A is used for three pole operation up to
300 kV
Three BLG 1002As are used for single pole operation.
For further details please see pamphlet SESWG / B2504en..
Operating mechanism Transport and erection
HPL circuit-breaker poles with one breaking unit per phase
are transported as complete units filled with gas to a
slight overpressure. Circuit-breakers with two breaking
units per phase are supplied as breaker head and support
insulator. Each circuit-breaker is routine tested in the
factory.
Erection work at site can be done in less than one day.
No gas treatment is necessary before gas filling. Filling of
SF gas to specified density can be facilitated by using the
following presurizing equipment:
One special control valve, for connection to the gas
bottle, and a gas-filled hose with connectors.
For filling with mixed gas (SF
6
and N
2
SF
6
and CF
4
)
a complementary control valve for connecting to a
separate gas bottle is included.
Using the above equipment, gas filling can be done
without gas being released into the atmosphere.
Grey porcelain
Polymeric insulators
Increased creepage distance (31 mm / kV)
Operational down to -40C, and -50C with mixed gas
Terminal pads for different standards
Rupture Discs
CT brackets and connections for voltages < 170 kV
Special phase distances (3-pole operated circuit-
breaker only)
Pre insertion resistors (2 chamber interrupters only)
Switchsync
40 kg bottles of SF
6
gas for pressurizing
Brown porcelain
Standard creepage: 20 to 25 mm / kV
Operational down to -30C
Aluminum terminals drilled per IEC / ANSI
One (1) support structure per pole
One (1) density monitor per pole
Equipment
Optional Standard
SF
6
SF
6
PLEASE NOTE! ABB Switchgear is working to continuously improve the products.
Therefore we reserve the right to change design, dimensions, and data without prior notice.
Publ. SEHVP/B 2314en
Edition 4, 2001-09
P