Conflicts between criteria and/or local standards shall be brought to the attention of the Contracting Officer for resolution. In such instances, all available information shall be furnished to the Contracting Officer for approval. 7.1.3 INSTALLATION All electrical systems and equipment shall be installed in accordance with the requirements set forth in the documents referenced herein. 7.1.4 TESTING Acceptance test procedures shall be performed on all systems provided. As a minimum the testing procedures shall comply with the requirements of the National Fire Protection Association (NFPA) and the International Electrical Testing Association (NETA). 7.1.5 UNITS Electrical design shall be in the International System of Units (SI). 7.2 PRODUCT CRITERIA a. All electrical material and equipment shall be IEC manufactured and type-tested by an independent testing laboratory. The independent testing laboratory must be certified by the Worldwide System for Conformity Testing and Certification of Electrotechnical Equipment and Components (IECEE). Contractor shall supply testing certification and IECEE certification for all IEC manufactured equipment. Material tested and marked by a Nationally Recognized Testing Laboratory (NRTL), such as Underwriters Laboratories (UL) or Canadian Standards Association (CSA) may be used in lieu of IEC-manufactured, type-tested material as long as the material/equipment is rated for use at the system voltage and frequency. b. Material and equipment installed under this Contract shall be for the appropriate application and installed in accordance with manufacturers recommendations. c. Equipment enclosure types shall be in compliance with the National Electrical Manufacturer's Association (NEMA) or the International Electro-Technical Committee (IEC) standards. d. Major components of equipment shall have the manufacturer's name, address, type or style, voltage and current rating, and catalog number on a non-corrosive and non-heat sensitive plate, securely attached to the equipment. All equipment delivered and placed in storage, prior to installation, shall be protected from the weather, humidity and temperature variation, dirt and dust, and any other contaminants. All equipment shall be in new condition, undamaged and unused. e. All material and equipment shall be a standard product of a manufacturer regularly engaged in the manufacture of the product and shall essentially duplicate items that have been in satisfactory use for at least two (2) years prior to bid opening. 7.3 SYSTEM STANDARDS 7.3.1 ELECTRICAL DISTRIBUTION SYSTEM 7.3.1.1 GENERAL a. Underground distribution systems, shall be in concrete encased schedule 40 PVC duct banks under roadways, parking lots and heavy traffic areas, and direct buried Schedule 80 PVC duct banks in other areas. Underground ducts shall be not less than 100mm diameter and not less than 1220mm below grade. Manholes and handholes shall be provided at changes of direction of more than 40 degrees and elsewhere as required to limit the pulling tension and sidewall pressure on the cables during installation to acceptable levels as defined by the cable manufacturer. Manholes shall be W912DQ-13-R-4034