0 valutazioniIl 0% ha trovato utile questo documento (0 voti)
214 visualizzazioni40 pagine
This document is a specification for piping fabrication and erection for the Foroozan Offshore Complex Renovation and Reconstruction Project. It provides requirements for materials, fabrication, installation, inspection, testing, cleaning and painting of piping systems. The specification references applicable codes and standards and establishes procedures for shop and field fabrication including welding, bending, tolerances and supports. It also outlines requirements for pressure testing, flushing, cleaning and documentation.
Descrizione originale:
Spec
Titolo originale
F500-0000-PI-SP-5003-D2-Specification For Piping Fabrication And Erection.pdf
This document is a specification for piping fabrication and erection for the Foroozan Offshore Complex Renovation and Reconstruction Project. It provides requirements for materials, fabrication, installation, inspection, testing, cleaning and painting of piping systems. The specification references applicable codes and standards and establishes procedures for shop and field fabrication including welding, bending, tolerances and supports. It also outlines requirements for pressure testing, flushing, cleaning and documentation.
This document is a specification for piping fabrication and erection for the Foroozan Offshore Complex Renovation and Reconstruction Project. It provides requirements for materials, fabrication, installation, inspection, testing, cleaning and painting of piping systems. The specification references applicable codes and standards and establishes procedures for shop and field fabrication including welding, bending, tolerances and supports. It also outlines requirements for pressure testing, flushing, cleaning and documentation.
Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 1 of 40
SPECIFICATION FOR PIPING FABRICATION AND ERECTION D2 31-Jul-10 Approved For Construction A.A. J.Afkar H.Dadgar A.Jahani H.Aramideh S.Azkat D1 18-Aug-09 Issued For Approval S.S J.Afkar H.Dadgar A.Jahani H.Aramideh S.Azkat D0 23-May-09 Issued For Comments S.S J.Afkar H.Dadgar A.Jahani H.Aramideh S.Azkat Rev. Date Purpose of Issue Prep. Check. Approv. Approv. Approv. ISI IOEC/NARDIS COMPANY
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 2 of 40
TABULATION OF REVISED PAGES Sheet Revisions Sheet Revisions D0 D1 D2 D0 D1 D2 1 X X X 36 X X X
2 X X X 37 X X X
3 X X X 38 X X X
4 X X X 39 X X X
5 X X X 40 X X X
6 X X X 41
7 X X X 42
8 X X X 43 9 X X X 44 10 X X X 45 11 X X X 46 12 X X X 47 13 X X X 48 14 X X X 49 15 X X X 50 16 X X X 51 17 X X X 52 18 X X X 53 19 X X X 54 20 X X X 55 21 X X X 56 22 X X X 57 23 X X X 58 24 X X X 59 25 X X X 60 26 X X X 61 27 X X X 62 28 X X X 63 29 X X X 64 30 X X X 65 31 X X X 66 32 X X X 67 33 X X X 68 34 X X X 69 35 X X X 70
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 3 of 40
TABLE OF CONTENT 1 INTRODUCTION ............................................................................................................................................. 5 1.1 General Description of the Project ............................................................................................................. 5 1.2 Definition ..................................................................................................................................................... 5 2 OBJECTIVE ..................................................................................................................................................... 6 3 REFERENCE DOCUMENTS .......................................................................................................................... 6 3.1 Codes and Standards ................................................................................................................................. 6 3.2 Specifications / Drawings, etc. .................................................................................................................... 6 3.3 Order of Preference .................................................................................................................................... 7 4 DESIGN ........................................................................................................................................................... 7 5 MATERIALS .................................................................................................................................................... 8 5.1 Storage / Handling of Materials .................................................................................................................. 8 5.2 Material Identification .................................................................................................................................. 9 6 FABRICATION .............................................................................................................................................. 10 6.1 Shop Fabrication ...................................................................................................................................... 10 6.2 Location of Field Welds ............................................................................................................................ 11 6.3 Field Fabrication ....................................................................................................................................... 11 6.4 Verification of Field Dimensions (New and retro-fit system) .................................................................... 11 6.5 Make-up Length ........................................................................................................................................ 12 6.6 Tolerances ................................................................................................................................................ 12 6.7 Minimum Distance between Welds .......................................................................................................... 13 6.8 Branch Connections ................................................................................................................................. 13 6.9 Galvanized Piping ..................................................................................................................................... 14 6.10 End Preparation ........................................................................................................................................ 15 6.11 Welding ..................................................................................................................................................... 16 6.12 Bending ..................................................................................................................................................... 16 7 INSTALLATION............................................................................................................................................. 17 7.1 Flange Assembly ...................................................................................................................................... 18 7.2 Threaded Connections ............................................................................................................................. 29
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 4 of 40
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 5 of 40
1 INTRODUCTION 1.1 General Description of the Project
The project concerns the reconstruction and renovation of an existing oilfield in Persian Gulf. Foroozan field is located approximately 100km southwest of Kharg Island export terminal. The field was initially developed in the early 1970s with the first production commencing towards the end of 1975. Peak production of about 180,000 was briefly obtained in late 1978 but in more recent years production has experienced a continuous decline associated with increased water production. The oil and gas produced in Foroozan field are processed at 2 main offshore production complexes, FX and
FZ.
1.2 Definition
Wherever the word "shall" has been used, its meaning is to be understood as mandatory. Wherever the word "should" has been used, its meaning is to be understood as strongly recommended or advised. Wherever the wording "may be" has been used, its meaning is to be understood as a freedom of choice. The following words and expressions shall have the meanings hereby assigned to them except where the context of this document otherwise requires: "Company" mean Iranian Offshore Oil (COMPANY) Company. "EPC Contractor" mean Company mentioned in the Contract as party of the "other part" and includes its successors and permitted assignees. (IOEC/Nardis) " Consultant" mean the company which provided engineering design of project. The name of this company is "Intelligent Solution Incorporation" and abbreviation is "ISI". " Basic Consultant" mean the company which provided basic engineering design of project. The name of this company is "Ranhill Worley Parson" and abbreviation is "RWP". " Vendor" means anyone who provides goods or services to a company. A vendor often manufactures and/or sells their products to a customer. "NIOC" mean National Iranian Oil Company, a company incorporated under the laws of Iran, whose Head Office is situated in Tehran, Iran.
Whenever terms appear in this document as capitalized terms, they shall have the meaning ascribed to them here above.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 6 of 40
2 OBJECTIVE
This specification covers the minimum requirements for fabrication and installation of steel piping, including pipe supports. Fabrication and installation of tubing, lined pipe and nonmetallic piping are excluded from the scope of this specification and shall be executed in accordance with ASME B31.3/ASME B31.8 and manufacturer's requirements and recommendations.
3 REFERENCE DOCUMENTS 3.1 Codes and Standards
ASME B31.3 Process Piping. ASME B31.8 Gas Transmission and Distribution Piping Systems. ASME B16.25 Butt-welding Ends. API RP 686 Machinery Installation and Installation Design
3.2 Specifications / Drawings, etc.
F500F500-0000-PI-SP-5001 Specification for Piping Materials. F500F500-0000-PI-DB-5000 Piping Design Basis F500F500-0000-PI-SP-5010 Piping Standard Drawings F500F500-0000-ME-SP-4001 Surface Preparation and Painting, Coating and Corrosion Protection F500F500-0000-PI-SP-5005 Pressure Testing, Flushing and Reinstatement of Piping Systems. F500F500-0000-PI-SP-5009 Specification for Welding of Piping F500F500-0000-PI-SP-5002 Specification for Pipe, Fittings & Flanges F500F500-0000-PI-SP-5004 Specification for Valves
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 7 of 40
3.3 Order of Preference
In case of conflict between regulations, codes and standards listed shall be applied in the following priority order:
Purchase Order Material Requisition Data Sheets Project Specifications and Standard Drawings International Codes and standards National Codes and Standards Supplier Specifications.
Latest editions of all Codes and Standards as valid on date of Contract shall be applicable. Deviations from applicable rules, codes and standards shall be subject to Purchasers/Owners written approval.
4 DESIGN
The Fabricator Contractor / Sub-Contractor will furnish piping detail drawings of plan and isometric. The detail drawing will contain all the relevant dimensions for fabrication, together with a bill of materials. The dimensions on the drawings will be true dimensions without any allowance for weld gaps.
Piping designed by Fabricator Contractor/Sub-Contractor shall meet the requirements of ASME B31.3 and where applicable, ASME B31.4/ASME B31.8.
Fabricator Contractor/Sub-Contractor shall be fully responsible for conformity between his detailed sketches and the latest revision of drawings supplied by Design Consultant/Contractor.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 8 of 40
5 MATERIALS
All piping materials shall conform to the requirements of the applicable general specifications or to requirements on the drawings, inquiry and/or purchase order.
All materials included in the finished piping systems (free-issued materials and material purchased by Fabricator Contractor/Subcontractor) shall be undamaged and fully in accordance with the piping material class and pipe support drawings indicated on the piping drawing and/or P&ID. For piping material classes, see specification F500F500-0000-PI-SP-5003: Specification for Piping Materials". Material substitutions or deviations from the piping material classes shall not be made without prior written approval of Owners/ Authorized representative. Fabricator Contractor shall submit a written justification for each proposed substitute materials.
Fabricator Contractor/Subcontractor shall provide a copy of the mill certificates including chemical and physical properties for all materials.
Fabricator Contractor/Subcontractor shall be responsible for any loss or damage to free issued materials.
Fabrication of plastic and plastic lined steel piping shall be in accordance ASME B31.3 and the manufacturers latest recommendation.
5.1 Storage / Handling of Materials
Piping shall be stored in a clean, dry or well-drained area on elevated dunnage and protected against contact with salts or salty water.
Stainless-steel piping shall be stored on wooden blocks, separately from carbon, and galvanized carbon steel.
Stainless-steel materials shall not be loaded, unloaded or handled with hoisting devices (e.g. steel ropes and forklift trucks) containing zinc or other harmful materials.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 9 of 40
Storage and control procedures shall be prepared by the Fabricator Contractor/Subcontractor to be submitted for review/approval by Owner/Authorized representatives.
Pre-fabricated pipe work shall be properly stored on level grand with 50 mm thick supports to avoid contact with moisture.
5.2 Material Identification Materials issued to Fabricator Contractor/Subcontractor shall be properly marked in accordance with the requirements of the applicable material specifications and requirements of the purchase order requisitions and/or local codes and regulations.
In an areas wherein material identification symbols are located near or along the proximity of the weld or on a piece of material to be cut off; material shall be re-stamped prior to welding or cutting to avoid loss of traceability.
The governing principle shall be that in the installed piping systems, all components can be identified and traced to their origin and complete specifications.
Marking and re-marking by Fabricator Contractor/Subcontractor's representatives shall be performed or executed by hard dye stamping or engraving, whichever is applicable.
All hard stamping shall be done by means of low stress stamps on pressure-bearing parts. Low stress stamped shall have a round nose with a radius of 0.25 mm minimum.
Hard dye stamping or engraving is not allowed for galvanized piping.
For ferrous materials with a thickness of equal to or less than 5 mm ( 5mm) and austenitic steel with a thickness of equal to or less than 10 mm ( 10mm), marking shall be performed by engraving.
When similar materials (e.g. carbon - low-temperature carbon steel or 304-316 stainless steel) are used for the same project, materials will be supplied with additional color coding to be able to make a quick visual identification of different types of material.
Note: Color coding need not be transferred prior to welding or cutting.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 10 of 40
6 FABRICATION Pipe work shall be fabricated by welding, screwing, and/or flanging as specified on the design drawing and specifications. Fabricated metal piping shall meet local authority requirements for all piping requiring inspection and approval by local authorities such as HSE requirement , wind or humidity. All other fabricated metal piping shall meet the requirements of ASME B31.3 and where applicable, ASME B31.4/ ASME B31.8. In order to prevent corrosion of stainless steel, fabrication of carbon steel and galvanized carbon steel shall be done in a separate area. Area means different shops or two (2) areas in one (1) shop separated by suitable (temporary) walls. For the same reason as above, tools used for fabrication of carbon steel and galvanized steel may not be used for fabrication of stainless steel. Only tools made of stainless steel are allowed for grinding, brushing, clamping, etc. These requirements apply to shop and field fabrication. 6.1 Shop Fabrication Shop fabricated piping is define as piping components or fired heater tube assemblies (if applicable) which are performed or welded together, in a pipe fabricating shop located offsite, to form integral pieces ready for assembly and erection. This may include bending, forming, threading, bevelling, welding or other operations necessary for such work and external welded attachments where specified. Shop fabrication under this specification shall include all the components of the pipeline or parts thereof entering into fabricated assemblies (spools), but shall exclude all piping specialties other than those with welding end constructions such as bolting, gaskets, flanged valves and fittings, blind flanges, orifice plates and similar items. Fabricator Contractor/Subcontractor will be responsible for selection of piping to be shop fabricated on site or off site. For some piping systems Fabricator Contractor/Subcontractor may have opt for preferential preference for shop fabrication to a maximum extent possible, e.g.: Lined piping.
The fabricator contractor shall keep on file the records and reports specified herein available for examination by OWNER or its representative for at least eighteen (18) months after date of shipment.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 11 of 40
6.2 Location of Field Welds The size of spools and location of field welds shall be determined by the Fabricator Contractor/ Subcontractor. Field welds shall be located so that the spools shall be as large as possible and consistent with shipping limitations. Field weld locations shall be governed by the following: Lengths of spools shall not be limited by "match lines" that appear on drawings. A line and its branches which appear on more than one (1) drawing is not intended to mean that a field weld is desired at the continuation point from one drawing to another. Where piping is shown passing through a wall or floor, the first weld point on either side of the wall or floor shall be made a field weld, provided it is located at least 150 mm away from the end of the pipe sleeve. Erection conditions shall be considered in determining the size of spools. 6.3 Field Fabrication All piping or fired heater tube assemblies (if applicable) which are fabricated on site, including bending, forming, threading, bevelling, welding, assembly of shop fabricated piping, or other operations necessary for the erection and installation of a piping system. Field fabrication under this specification covers, but is not necessary limited to, the following operations: Erection of shop-fabricated piping. Fabrication and erection of all field-fabricated piping. Design, routing, fabrication and erection of all field-fabricated piping for which no isometric piping or piping plan drawings are available. Fabrication and erection of all pipe supports and auxiliary steel as detailed in the pipe support drawings. Design, fabrication and erection of all pipe supports for small bore piping, which shall form part and to be executed in line with the available drawings for supports. 6.4 Verification of Field Dimensions (New and retro-fit system) Fabrication of piping and pipe supports shall be in accordance with the supplied design drawings. However, due to equipment location and fabrication tolerances, field verification of overall dimensions shall be made by Fabricator Contractor/Subcontractor prior to erection, to ensure a proper fit-up at all connections to equipment and other piping.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 12 of 40
Fabricator Contractor/Subcontractor is required to conduct a systematic form of field measurement including elevation and dimension of existing facilities and new related tie-in and new piping works. The requirements of engaging third party contractor for the laser scanning works(i.e. usage of a laser survey) to verify elevation/dimension of all tie-in works, new piping and equipment to be installed on the existing platforms is strongly advise and recommended. 6.5 Make-up Length Fabricator Contractor/Subcontractor shall apply 150 mm make-up lengths in order to make adjustments, necessary due to construction deviations. The required material shall be taken from the construction allowances/contingencies. 6.6 Tolerances
6.6.1 Overall Dimensions The dimensional tolerances of all fabricated lines shall not exceed the values given below: Less 1.5 m Length than 1.5 m and longer
Center to center } Center to flange face } 1.5 mm 3 mm Flange face to flange face } The angular dimensions of bends shall be within degree. Manufacturers tolerance shall govern where forged fittings are welded and join together.
6.6.2 Thinning of Wall Thickness and Ovality in Bends The maximum decrease of wall thickness shall not exceed 10% of the nominal wall thickness. For tolerances on the maximum flattening, refer to ASME B31.3 and where applicable, ASME B31.4/B31.8
6.6.3 Flange Face Alignment For flange joints in rigid systems (free unrestrained straight length less then 10D at one or both sides of the flange) flange faces shall be aligned to the design plane within 2.5 mm/m. For all other flange joints flange faces shall be aligned to the design plane within 5 mm/m. Heating of pipework to achieve alignment of flanges at equipment shall not be permitted.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 13 of 40
6.6.4 Position of Bolt Holes for Flanged Piping Flange bolt holes shall be aligned within 3 mm maximum offset. Unless otherwise detailed on the drawings, flange bolt holes shall straddle the north-south centerline when the flange face is in the horizontal position and shall straddle the vertical flange centerline when the flange is in the vertical position. 6.7 Minimum Distance between Welds The minimum distance between weld edges shall be as per requirements of specification, Specification for Welding of Piping, document no. F500F500-0000-PI-SP-5009. The minimum distance between welded joints, including longitudinal welds, and openings, branch welds, reinforcements, attachment devices, supports, etc. shall be as per requirements of Para 12.9 of Specification for Welding of Piping Fabricator Contractor/Subcontractor shall provide and or specify additional requirements (such as radiography, ultrasonic inspection or postweld heat treatment) in case of deviations. The longitudinal welds of two (2) adjacent rings or tubes shall be staggered approximately 90. Longitudinal welds shall not be situated at the bottom of the pipe. In cases where staggering is not possible, e.g. fitting to fitting connections. The weld joint shall be subjected to non-destructive testing.
6.8 Branch Connections
The requirements for branch reinforcements for piping shall conform to the applicable codes. Any branch reinforcements requirements for fired heater tube assemblies will be furnished with the heater tube assembly drawings and specifications. Branch connection type shall be in accordance with the piping drawing or the piping material class, when no drawing is supplied.Branch connection could be set on or set in. Where openings for branches are cut in run of pipe, all materials which may drop inside the pipe shall be completely removed before the branch line is welded into place. Branch connection cut-outs shall be properly Bevelled and to accurately matched to form a suitable groove for welding. To enable and permit complete penetration of the welds at all points, resulting in a quality comparable with girth welds, in the same piping system.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 14 of 40
Weld details for branch welds shall be included in the welding procedure specification. Reference is made to the relevant section of ASME B31.3/ASME B31.4/ASME B31.8. The centerline of the branch connections shall intersect the centerline of the header, unless otherwise specified on the piping drawing. Nozzle joints shall be of the "set-on" type, made so that the branch connection abuts the outside surface of the run wall. Threaded couplings shall subsequently be checked with a thread gauge to ensure against thread damage or distortion. Requirements of a 6 mm diameter vent hole in the reinforcing pad or saddle, to reveal leakage in the weld between the branch and main run and to provide venting during welding and heat treating operations, shall be provided. If the reinforcement pad consists of more than one piece, each piece shall have a vent hole. 6.9 Galvanized Piping Galvanized piping up to and including 2" (DN 50) nominal size shall in general be assembled from threaded galvanized components. Piping larger than 2" (DN 50) nominal size shall be pre-fabricated in accordance with this specification and subsequently hot-dipped galvanized in accordance with ASTM A153. Fabricator Contractor/Subcontractor shall take into account that after the spools have been galvanized no welding will be allowed. This implies that field break shall be located at flanged connections or connections using threaded couplings and that welded-on pipe supports shall be welded to the spools before galvanizing. Welding of galvanized steel to austenitic steel pressure parts is prohibited. Subcontractor shall consider maximum dimensions of the galvanizing facilities he intends to use, when determining spool dimensions and locations of field breaks. Visual and dimensional inspections by Owners Authorized representative, nondestructive weld examinations if applicable and hydrostatic testing shall be executed before spools are hot-dip galvanized. Threaded connections shall be reworked to clean thread depth. Repair of galvanized piping shall be as per ASTM A780, as referenced in ASTM A153.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 15 of 40
6.10 End Preparation
6.10.1 Cutting Cutting pipes may be done either by mechanical means (preferred) or by flame cutting or plasma cutting when the following is taken into account:
For carbon steel, flame (or arc) cutting and bevelling is acceptable only if the cut is reasonably smooth and all oxides are removed from the surface by grinding to bright metal.
For stainless steel, flame cutting is prohibited, but plasma cutting may be applied.
Preheating during thermal cutting shall be the same as applied during welding (see specification "Specification for Welding of Piping document no. F500F500-0000-PI-SP-5009.
6.10.2 Bevelling End profiles of pipes and fittings to be butt welded shall be in accordance with ASME B16.25. Bevelling is not required when a make-up length is provided.
6.10.3 Tapering Weld alignment shall be in accordance with ASME B31.3 or ASME B31.4/ ASME B31.8.
6.10.4 Threading The threading of pipe shall be in accordance with the applicable standard. The type of thread is indicated on the piping drawing or in the applicable pipe class.
6.10.5 Plain Ends Pipes for sizes 1 shall be cut square or will be specified by schudle .
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 16 of 40
6.11 Welding The following activities shall be executed in accordance with the requirements as described in specification Specification for Welding of Piping, document no. F500F500-0000-PI-SP-5009.
Alignment.
Preheating.
Tack welding.
Welding.
Repair welding.
Postweld heat treatment.
Backing ring and consumable inserts shall be prohibited unless approved in advance by OWNER. Fields welds shall normally be butt-welded type rather than stub-in or miter type, unless otherwise approved in writing by OWNER.
6.12 Bending
6.12.1 General Pipe bending may be considered as an alternate to welded fabrication. This consideration shall be made prior to piping fabrication to take advantage of possible economics. If bending is specified, the fabricators bending procedures shall be in strict accordance with ASME B31.3/ASME B31.8 and shall be subject to prior approval by Owner/Purchasers representative. Bending of pipes shall only be done where indicated on the isometric drawings or when allowed by the applicable pipe class, otherwise welding elbows shall be used.
If the pipe contains a longitudinal weld, this weld shall be located in the neutral zone. At site, cold pipe bending is not allowed.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 17 of 40
Hot bending at site is not allowed, but shall be executed by Fabricator Contractor/ Subcontractors with induction pipe-bending machines in accordance with the requirements of a bending procedure approved by Owner. Pipe bending shall be carried out in pipe bending machines or presses using formers. Tolerances for thinning, flattening and wrinkling are specified in section 6.6.
6.12.2 Additional Requirements for Ferritic Steels For feritic steels, with the exception of the quenched and tempered grades, a normalizing heat treatment shall be applied when the hardness increase in Vickers or Brinell is more than 100, unless local regulations are more stringent.
For quenched and tempered feritic steels an appropriate stress-relieving heat treatment shall be applied when the hardness increase in Vickers or Brinell is more than 100, unless local regulations are more stringent. Stress relieving shall be at least 10C below the tempering temperature. The use of water for cooling is not permitted.
7 INSTALLATION Fabricator Contractor/Subcontractor shall be responsible for installation of all piping spools including pipe supports, all piping components, such as bolting, gaskets, flanged valves and fittings, blind flanges, etc., and all other items, such as flow meters, control valves, orifice plates and similar items necessary to complete final piping erection with all lines cleaned, supported, pressure tested and ready for plant operation. Alignment of piping to equipment (machinery, vessels, exchangers, etc.) shall permit fit-up without bending or springing the pipe under any circumstances. Alignment shall be checked and approved by Owner/Authorized representative prior to bolt-up. API RP 686 provide proper guide lines for installation sequence and bolting up of piping connected to machinery. Where a discrepancy between drawing dimensions and field dimensions exists, sufficient modifications shall be made to eliminate unintended cold springing and cold forcing. Deviations from the arrangement shown on drawings shall only be made after approval of Owners representative. Fabricator Contractor/ Subcontractor shall submit alternative routing for review and approval by Owner representative.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 18 of 40
Alternative routing shall keep clear all access ways and equipment openings and shall maintain accessibility of valves and instruments. Cutting, welding and making attachments to structural members, vessels, exchangers and other equipment, not detailed in the piping and piping support drawings, shall not be permitted without prior approval of Owner representative. Stainless steel shall be suitably protected during installation or modification of carbon-steel, and galvanized carbon-steel piping at site. All stainless steel pipe potentially exposed to zinc dust contamination shall be protected with polythene sheeting. This requirements will apply also to piping under or close to at the same level, as galvanized steel (grating/structural members/etc.). The sheeting shall be securely wrapped against tearing by wind and shall be removed upon completion of the works. Scaffolding, which is galvanized pipe, shall be kept at a distance of at least of 200 mm from stainless steel pipe in order to prevent the possibility of surface contamination. Pulling of pipe along piperacks is forbidden unless rollers are used. Vents, drains, condensate drip legs, pressure instrument and other connections shall be installed where indicated on the isometric drawings, in accordance with piping standards included in specification "Piping Standard Drawings", doc. no. F500F500-0000-PI-SP-5008. Protective devices on pipe ends, flanges and equipment openings shall remain in place until the piping connection is ready to be made. 7.1 Flange Assembly 7.1.1 Tools Usage of adjustable wrenches (Bahco) or wrench hammers is prohibited. For application of correct tool related to flange size and rating, see table I. The calibration of torque wrenches and tensioners shall be checked against manufacturer's specifications upon receipt. Any tools that are out of calibration shall be rejected. Requirement of verification and rechecking of the calibration shall be made as per tool manufacturer standard. Any tool found to be out of calibration shall immediately be withdrawn or taken out of service for repair. All flanged joints secured with tools found to be defective shall be re-checked with a properly functioning tool.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 19 of 40
7.1.2 Flange Identification Flanges subject to hydraulic bolt tensioning shall be numbered on the isometric or on the general arrangement drawing by the subcontractor. Starting with the flow direction of each line number within one (1) unit, the flange sets shall be identified as F1, F2, F3, etc., followed by the line number, e.g. F1-P30006. The numbering system for flanged joints at equipment not part of a piping system, e.g. manholes, etc., shall be such that each equipment flange set is identified with the nozzle number as shown on the equipment drawing, followed by the equipment number, e.g. M1-R1101. The above described numbering system shall be used to relate each "assembly record" as described in section 7.1.8 and section 12.1 to the relating flange set. 7.1.3 Torque Values In case torque wrenches (manual or hydraulic) are used, bolts shall be tightened until torque values, as indicated in table II, are reached. In case tensioning equipment is used, bolts shall be tightened until bolt force values, as indicated in table II are reached. Listed values are NOT APPLICABLE for designed flanges over 60 inches. For these flanges the equipment manufacturer shall indicate on his drawings the bolt torque value used in the calculation made for the design of the flange. For bolt material not listed in table II contact EPC1 Contractor to obtain correct torque and bolt force values. a. Listed values are based on the empiric bolt force in flanges according to ASME Section VIII, Div. 1, Appendix S. b. Torque moments are based on the pitch of the thread, the friction resistance between the thread surfaces and the bearing surfaces of the nut on the flanges. c. Friction coefficient f = 0.1
7.1.4 Installation Inspection of Material Inspect the gasket material for possible damage or defects such as bends or creases. Inspect the mating flange facings for dirt, parallelism, flatness, surface roughness, mechanical damage and corrosion. Use a suitable solvent to clean the surfaces.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 20 of 40
The contact area of the flanges shall be free of excessive pitting, radial tool marks and scratches. Flange facings which are found to be damaged during construction, shall be re-machined at subcontractor's expense. Inspect the studs and nuts. They should be free of dirt and corrosion and well lubricated. The studs shall be straight and the threads free of nicks, burrs and chips. The Subcontractor shall ensure that the correct gasket material and thickness as specified in the Piping Material Classes and on the piping drawings will be used.
7.1.5 Assembly of Flange Connection The Fabricator Contractor/Subcontractor shall ensure that all bolting materials and types used are in accordance with the service requirements specified on individual material specifications (piping material classes) and detailed on the piping isometrics. All flanges bolting shall be checked for correct grade and to ensure that they are free from damage to the bolt/nut and any coating prior to fitting. The Fabricator Contractor/Subcontractor shall ensure that during the installation of galvanised or PTFE coated bolts, care will be taken that the coating is not damaged when bolt tightening. Any coating that is damaged shall be brought to the attention of the Owner Authorized representatives. Align the flanges properly. For tolerances on flange joints see specification section 6.6. The bolt holes shall match so that the studs can be inserted freely. Install the gasket. Gaskets shall not be lubricated. Use four (4) studs at 0, 90, 180 and 270 degree angle as centering guides for the gasket. In the case of spiral-wound gaskets, ensure that the inner diameter of the centering ring is at all points within the outside diameter of the raised face. Clamp securely in place. Insert the balance of the studs. Apply a suitable lubricant to the threads and the face of the nut that contacts the flange. Hand tightens all studs and nuts. Center studs between nuts so an equal number of threads projects at each end. When hydraulic bolt tensioning is required, a threaded length equal to the bolt diameter should protrude at the end where the bolt tensioner is to be placed. For other sizes, each stud bolt shall be assembled with a projection of no more than one full thread beyond the nut at one end.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 21 of 40
7.1.6 Bolt Torque Standard Wrench a. Tightened bolts crosswise in at least two (2) stages. First stage to approximately 50% if the estimated value based on experience. Second stage to 100% of the estimated value. Bolting shall be tightened in a sequence assuring equal distribution of bolt loading. b. Check all bolts for even distribution of required load. Steel to cast iron flanged joints shall be made up with extreme care. In order to avoid breaking of cast iron equipment flanges, piping flanges shall be brought up flush with gasket and equipment flanges into close parallel and lateral alignment, before uniformly tightening bolts.
Manual or Hydraulic Torque Wrench a. Tighten bolts crosswise in at least three (3) stages: First stage to 40% of recommended value as per table II.
Second stage to 80% of recommended value.
Third stage to 100% of recommended value.
b. Check all bolts at 100% of recommended value.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 22 of 40
7.1.7 Hydraulic Bolt Tensioning The application of bolt-tensioning equipment shall be in strict accordance with supplier's instruction manual and safety procedures. Fabricator Contractor/Subcontractor shall propose a supplier/subcontractor for hydraulic bolt tensioning equipment and/or services, for approval by Owner Authorized representative. The personnel using the equipment shall be adequately trained in the application of such equipment. The tensioning of the bolts is carried out crosswise in a number of cycles, depending on the number of tools that can be applied simultaneously. As a minimum following number of tensioners shall be applied during each cycle:
NUMBER OF BOLTS NUMBER OF TENSIONERS TO USE 32 and less 50% of bolts 36 to 60 1 / 3 of bolts 64 and up of bolts
Bolt tensioning shall be executed in two (2) steps in accordance with the tensioning procedure as supplied by the tensioning subcontractor (see section 12) at the hydraulic pressure as calculated by tensioning subcontractor based on information supplied by Fabricator Contractor/Subcontractor. After completion of bolt tensioning four (4) bolts at 90 degrees angle each shall be checked for the break loose point. Flanges not meeting the required values shall be re-tensioned. After bolt tensioning has been completed, the extended threaded part shall be greased and covered with suitable caps to prevent damage and corrosion during operation of the plant. Upon completion of bolt tensioning each flange shall be provided with a wire seal(s) as indicated below.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 23 of 40
Flange numbers as described in paragraph 7.1.2 shall be low stress dye stamped on the rim of one of the flanges.
7.1.8 Leaking Flange Assemblies Flange assemblies found to be leaking during hydro-testing shall be tightened as listed below: a. Flanges assembled with standard wrenches shall be tightened with manual torque wrenches using procedure as described in subsection 7.1.6. b. Flanges assembled with manual torque wrenches shall be tightened with hydraulic torque wrenches using procedure as described in subsection 7.1.6. Flange assemblies tightened with hydraulic torque wrenches or hydraulic bolt tensioning equipment and found to be leaking during hydro-testing shall be dis-assembled, inspected and re-assembled in accordance with the requirements of this specification. Flange assemblies still leaking after tightening as described in subsection 7.1.5 shall also be dis- assembled, inspected and re-assembled in accordance with the requirements of this specification. Re-assembly shall be done with tools as described in subsection 7.1.6a and 7.1.6b. In case of re- assembly a new gasket is recommended.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 24 of 40
Subcontractor shall prepare an assembly record for all flanges which are dis-assembled and re- assembled because of leakage problems. The bolt tensioning subcontractor shall prepare design calculations for all applicable flange sizes, in order to determine the required bolt loads and, consequently, the required pressures in the hydraulic bolt tensioning equipment. Calculations shall take into account the following design factors: Minimum and maximum gasket seating stress. Allowable bolt stress. Flange material. Design pressure. Hydrostatic test pressure. External loadings
The bolt tensioning fabricator contractor/sub-contractor shall issue a hydraulic bolt tensioning procedure for approval by the Owner or Authorized representative. The procedure shall show all required information such as Type of bolt tensioning equipment. Operation manual. Record preparation instructions. Establishment of the "break loose" pressure, based on minimum four (4) tensioners. Any precautions to be taken.
Fabricator Contractor/Subcontractor shall prepare an assembly record for each flange joint which needs to be tensioned. These records shall be issued as part of the turn-over packages. Information to be shown on the assembly record shall be at least: Identification: Unit. Line number. Pipe class. Flange set number. Flange size/rating. Company representative's name and signature.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 25 of 40
Inspection of the flange facing: Roughness. Damage: Dents, tool marks. Cleanliness. Company representative's name and signature.
Flange fit-up: Gasket type. Gasket size. Bolt diameter and length. Number of bolts. Bolt material. Flange alignment. Company representative's name and signature. Bolt tensioning:
Pressure A, (the higher tool pressure, taking into account the maximum bolt stress, that is applied to obtain at least the average bolt stress). Pressure B, (the lower tool pressure, required to obtain the average bolt stress). Tool number. "Break loose" pressure (check B pressure at four (4) bolts at 90% each) or bolt torque value. Company representative's name and signature.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 26 of 40
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 27 of 40
LEGEND
TOOL BOLT SIZE 1. Standard wrench 1 inch 2. Torque wrench 1 inch 3. Hydraulic torque wrench 1 inch (note 1) 4. Bolt tensioning equipment > 1 inch
Note 1: Manual torque wrench with multiplier is an acceptable alternative.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 28 of 40
TABLE II Bolt Torque and Bolt Force Values
BOLT DIA. (INCH) THREADS INCH A193 B7, A193 B16 AND A320 L7, 26 IN. AND LARGER FOR 150 LB & 300 LB ASME B16.47 SERIES A (MSS) A193 B7, A193 B16 AND A320-L7, OTHER SIZES/RATINGS ASME B16.5 TORQUE VALUE IN Nm BOLT FORCE IN N (note 1) TORQUE VALUE IN Nm
BOLT FORCE IN N (note 2) Carbon steel Stainless steel Carbon steel (note 1) Stainless Steel (note 3)
Notes: 1. 65% of empirical values to ASME Section VIII, div. 1, Appendix S 2. 85% of empirical values to ASME Section VIII, div. 1, Appendix S 3. 43% of empirical values to ASME Section VIII, div. 1, Appendix S
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 29 of 40
7.2 Threaded Connections All threaded connections shall be seal welded, except the following: Connections in galvanized piping. Screwed plugs in valved drains and vents. Screwed thermowells and instrument connections. Screwed control valves and safety/relief valves. Screwed plugs in hydrostatic test vents and drains without valves shall be seal welded after completion of testing. Usage of sealing compound or teflon tape for all connections which are not seal welded. Teflon tape is only allowed in utility services, at a design temperature of maximum 200C.
7.3 Pipe Supports 7.3.1 Temporary Supports During erection, piping shall be adequate temporary supported until the final supports are installed. Temporary supports shall rest on structural beams. Piping shall not be temporarily supported from platform grating or from scaffolding. Temporary supports shall consist of wooden blocks and/or steel hoisting ropes. Synthetic ropes or strings are not acceptable as temporary supports. Steel temporary supporting materials for stainless steel materials shall preferably be stainless steel. Usage of galvanized temporary support material is not permitted. The use of adjacent structures or equipment as temporary supporting or lifting attachment shall not be permitted unless authority has been obtained from the Companys Representative in writing. Temporary attachment shall be of the same material as the parent material and shall be performed by qualified welders. Pipework shall not primarily be supported via control or block valves.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 30 of 40
7.3.2 General Fabricator Contractor/Subcontractor shall adjust the pipe support to overcome construction measure deviations. Shims used to achieve full bearing between a pipe and/or a pipe attachment and the main support member must have sufficient area to carry the load. After erection, shims shall be welded to the main steel to prevent slippage when the pipe moves during operation. Shims shall not be welded to the pipe. Shims which are to be welded to pipe shoes shall extend the full length and width of the shoe. Care shall be taken to avoid undue strain being placed on a vessel or item of equipment by unsupported lengths of piping. Flange connections to strain sensitive equipment shall be the last connection made on completion of a line or interconnecting system of lines complete with permanent supports. Alternative supports shall only be installed after approval by Owner/Authorized representative. Pipe supports shall not be located at the weld point of piping welded construction. Pipe support subcontractor shall remove fireproofing locally from steel columns and beams for a proper installation of pipe support according to the pipe support drawings. Fireproofing shall be repaired on the main structure and will not be installed on the additional pipe support, unless otherwise shown. Any fireproofing around directional anchors from pipes which are free to move in the transverse direction shall be kept free minimum 50 mm from the pipe anchor parts. Should there be any expansion bolts to be installed or provided in the concrete members (if any), care shall be taken not to undercut retaining bars in the concrete. Pipe supports shall be adjusted to suit the final location of the expansion bolts. Pipe supports shall not be welded to the pipe line unless specified in the design and piping drawings. Force shall not be used to align pipes to support locations during installations. Permanent pipe supports shall, where possible, be installed before the erection of the associated pipework. The Fabricator Contractor/Subcontractor shall ensure that provision of adequate support for heavy valves and fittings before the pipework is erected or subjected to pressure test. The burning of holes in structural steel work or component parts is strictly forbidden. Supporting steelwork shall be set at the correct elevation, being true and level in all directions.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 31 of 40
Metallic surfaces of supports which will be inaccessible after erection shall be prepared and coated before assembly of the component in accordance with the Painting, Coating and Corrosion Protection Specification document no. F500-0000-ME-SP-4001. Hanger rods shall be adjusted to correctly hanging after tightening of all components parts, surplus threading may be removed. Pipe hanger shall not be used as temporary lifting attachments. The use of adjacent structures or equipment as temporary supporting or lifting attachments shall not be permitted unless with approval of the Fabricator Contractor/Subcontractor in writing.
7.3.3 Variable Spring Supports Installation The spring hanger list included in the pipe support drawings will give, for each spring: a. The operating load. b. The cold set load. c. The amount and direction of travel.
When the spring is delivered, it will have been loaded to the preset load and locked into this position by means of the cold setting stops. Depending upon the manufacturer, the cold setting stops will take the form of a plain rivet through section bar inserted above and below the piston plate inside the load scale slot.
The cold setting stops must remain undisturbed until the hydrostatic test on the line has been satisfactorily completed, after which the following procedure shall be carried out:
a. At some time between the hydrostatic test and start-up, the cold setting stops shall be removed. Ultimate force must not be used.
b. With the cold setting stops removed, it may be noticed that the line has a tendency to bow up or sag down. This is to be expected as when the line is cold and empty it is obvious that it can be either over supported or under supported since it is designed to be correctly supported at the hot operating condition. Do not readjust the spring load, but contact Owner/Consultant representative when there is doubt.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 32 of 40
7.4 Cold Spring Cold spring or fullness (cold strain) shall not be used accomplished by any case during constrction or fabrication. 7.5 Expansion Joints
Expansion joints shall be installed following thoroughly the instructions of the manufacturer regarding the removal of shipping supports and attachments, adjusting tie-rod nuts, pre-compressing bellows, flow direction, etc. If the joints have welding ends, protection shall be given to the bellows to prevent any injurious effects during welding.
7.6 Final Corrections
7.6.1 Carbon Steel Piping
If corrections are required after fabrication, they may be carried out by a method approved by Owner/Authorized representative. Following correction method is acceptable and recommended:- a) Local heating b) Application of force with local heating
The following restrictions apply to the heating; forcing of piping made from carbon steel, low alloy steel or austenitic stainless steel: i. For carbon steel which does not require a PWHT the maximum temperature during alignment corrections shall be 600 0 C. Temperature-indicating manometer or contact thermometers shall be used to measure the maximum temperature. If temperature-indicating manometer are used, a margin of 50 0 C shall be taken to allow for measurement inaccuracy (i.e. the reading with the manometer shall not exceed 550 0 C. Forcing may be applied if necessary). For carbon steel which requires a PWHT the maximum temperature during alignment corrections shall be the maximum
PWHT temperature. Temperature-indicating manometer or contact thermometers shall be used to measure the maximum temperature. If temperature-indicating crayons are used, a
margin of 500C shall be taken to allow for measurement inaccuracy (i.e. the reading with the crayon shall not e xceed the maximum PWHT temperature minus 50 0 C). Only heating with application of local force shall be used and no quenching shall be used. The area shall either be heated in full compliance with the PWHT procedure or the area which is heated (and corrected) shall be post weld heat treated.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 33 of 40
7.6.2 Austenitic Chromium Nickel Steel Piping
All corrections to the piping should preferably be made in the cold condition. If cold correction is not possible the piping may be heated after w r itten approval by Owner/Authorized representative. The heating shall be applied uniformly and carefully controlled. The temperature shall not exceed 400C.
7.7 Valve
7.7.1 Wherever possible, valves should be kept near grade level. All operating valves installed 1600 mm or more above floor, platform or other point of easy access shall be hammer blow chain wheel operated. Hammer blow chain wheels shall have U-bolt clamps, not J-bolt clamps.
7.7.2 Hand wheels and stems shall be kept out of operating aisles, where practical, otherwise elevated to 1600 mm from grade to bottom of hand wheel.
7.7.3 Valves shall not be installed with stem below a horizontal position (90 degrees reference angle from a vertical plane).
7.7.4 Block valves, when required, shall be installed at nozzles of pressure vessels or in lines connected to nozzles to permit operating valves from grade or a platform. Equipment shall be capable of being isolated if:
Operations can continue without disruption. Depressurising associated facilities will delay maintenance on the equipment.
7.7.5 Gate valves shall be provided with an equalizing globe valve bypass with a minimum size of NPS 1 for the following:
Class ANSI 150 - NPS 12 and larger. Class ANSI 300 and greater - NPS 8 and larger.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 34 of 40
7.7.6 All valves shall have sufficient clearance to facilitate removal of the bonnets, plugs and internals.
7.7.7 Ball valves shall not be used for throttling service.
7.7.8 Valve instruments and other equipments, which may required to be monitored, adjusted or serviced during operation shall be accessible from platform or grade.
7.7.9 Valves shall be oriented in the line as detailed on the piping isometric drawings and shall be readily operable, and removable as required or maintainable, where specified, in-situ. Where no indication exists on isometric or piping GA, gate, butterfly, globe and ball valves in horizontal lines shall be installed with their stems oriented as follows in order of preference: a) Horizontal restriction: Downward Stem 60 O Stem Max Orientation 315 O Stem Max Orientation. b) Vertical restriction: None
7.7.10 Actuated a) Gate, Globe (including 3 way and Y type) shall only be mounted with the stem vertically upwards. b) Rotary valves (butterfly, throttling, ball etc.) shall be mounted with the stem horizontal or vertical. The Contractor shall provide for the checking of gland packings in all valves during hydrostatic testing.
8 INSPECTION AND TESTING 8.1 General Test and measuring equipment used shall be calibrated every six (6) months. All inspection and testing is the responsibility of Fabricator Contractor/Subcontractor. Owner/Authorized representatives shall always have the right to witness inspection. Any defects revealed by any of the examinations performed shall be reworked and retested. All assemblies indicating irremediable defects, excessive repairs, improper fabrication or not being in
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 35 of 40
accordance with the requirements of this specification shall be subject to rejection, even if the conditions are discovered after acceptance at Fabricator Contractor/Subcontractor's shop or revealed during field testing. All costs related to repairs and/or re-fabrication shall be for Fabricator Contractor/Subcontractor's account.
8.2 Positive Material Identification Test Positive material identification (PMI) on alloy materials shall be executed with a Texas Nuclear or equal, as follows: a. Incoming materials in Fabricator Contractor/Subcontractor warehouse will be examined at random by Owner authorized representative to check attached certificates. At random is defined as a random check of materials as per material type (independent of size, rating, wall thickness and type of piping item) up to a maximum of 1% of the total supplied quantity of material. b. Installed material shall be checked for 100% of installed quantity by subcontractor to eliminate possibility of accidental material substitution. c. All installed materials with poor readability of heat numbers or materials where doubt exists concerning the accuracy of the heat numbers if deemed required and upon requested by the Owner or Authorized representative shall be checked by Fabricator Contractor/Subcontractor.
PMI is only required for the following materials:
MATERIAL SERVICE
Stainless Steel All Services Carbon Steel All Services
Fabricator Contractor/Subcontractor will be responsible for execution and documentation of PMI as described under paragraph 8.2b. and paragraph 8.2c.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 36 of 40
8.3 Weld Examination
For weld examination requirements, see specification " Specification for Welding of Piping, document no. F500-0000-PI-SP-5009.
8.4 Pressure Testing and Flushing
For pressure testing and flushing of completed piping systems, see Specification for Pressure Testing, Flushing and Reinstatement of Piping Systems", document no. F500-0000-PI-SP-5005. Except when specifically noted on the drawings, spools shall not require shop hydrostatic testing. This shall not, however, relieve subcontractor of the responsibility for any defects in materials and/or fabrication that may be revealed during field hydrostatic testing.
9 CLEANING 9.1 Weld Ends During weld preparation ends of all components shall be freed from any traces of oil, grease, paint, rust, scale, etc., over a distance of 50 mm minimum from the weld edge.
9.2 Piping 9.2.1 Internal During fabrication and installation, Fabricator Contractor/Subcontractor shall prevent foreign materials such as oil, grease, sand, dirt, scale, loose particles from cutting and grinding, etc., from entering the pipe or pipe component. Any foreign materials which may be presence or have entered the pipe or pipe component, they shall immediately be removed before assembly of the parts by a suitable cleaning method, such as blowing through with air or degreasing with suitable cleaning agent or solvent. Cleaning agents and solvents used for degreasing shall not contribute or have any properties that may cause corrosion to the piping.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 37 of 40
9.2.2 External Piping to be painted shall be cleaned in accordance with the requirements of specification "Painting, Coating and Corrosion Protection Specification" document no. F500-0000-ME-SP-4001. Piping system whereby painting requirements is not required, piping shall be properly cleaned by a suitable cleaning method to removed excessive rust, scale or grease only. Cleaning agents and solvents used for degreasing shall not contribute or have any properties that may cause corrosion to the piping. 9.3 Completed Piping Systems Unless otherwise indicated in the pipe class or on the piping drawings or P&ID's, recommended flushing methodology as described in Specification for Pressure Testing, Flushing and Reinstatement of Piping Systems" document no. F500-0000-PI-SP-5005 will be adopted and implemented. 9.4 Degreasing For certain services, lines need to be degreased to prevent operation problem. This requirement will be address in the pipe class or on the piping drawings or P&ID's and will form part of the additional specifications to be supplied by Fabricator Contractor/Subcontractor. Cleaning agents and solvents used for decreasing shall not contribute or have any properties that may cause corrosion of the piping. 10 PAINTING For painting requirements, reference is made to specification "Painting, Coating and Corrosion Protection Specification", document no. F500-0000-ME-SP-4001. 11 DOCUMENTATION Both shop and field fabrication include administration of material certificates, welding operations, destructive and non-destructive examinations and all testing operations as required by the applicable specifications and codes. Fabricator Contractor/Subcontractor shall be responsible for planning and documenting all activities and controls which include, but are not necessarily limited to, the following operations: Material receiving (including administration/filing of certificates). Material traceability
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 38 of 40
Cutting. Bending (at subcontractors for induction bending). Welding. Welders identification Qualification test and records of repairs Heat treatment. Destructive and nondestructive testing. Hydraulic bolt tensioning and/or torquing. Hydrotesting. Flushing. Cleaning. Fabricator Contractor/Subcontractor shall provide Owner/Authorized representative with two (2) copies of material test certificates for all materials purchased by Fabricator Contractor/Subcontractor. Documents relating to assemblies to be shipped shall be submitted to Owner/Authorized representative for review/approval. Documents shall be made available to Owner/Authorized representative at all times. For each piping system (defined as piping items welded together of same material and same design pressure/temperature, e.g. line from a pump to a vessel) Fabricator Contractor/ Subcontractor shall provide a fabrication book containing documents showing all above-listed operations. 12 PREPARATION FOR SHIPMENT Before shop-fabricated assemblies are prepared for shipping, Fabricator Contractor/ Subcontractor's inspector shall check following: Overall dimensions as per piping drawing. Required documentation as per subsections 11. Material identification as per subsection 5.2. After assembly has been released by Fabricator Contractor/Sub-contractor's representative inspector, Fabricator Contractor/Subcontractor shall prepare material for shipping as follows:
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 39 of 40
All assemblies shall be dry and free from water, dirt and loose or foreign materials. Flange faces, machined surfaces and threads in carbon-steel piping shall be coated with a corrosion preventive compound (Rust Ban 324, or equal) before applying the cover, cap or plug. Plastic caps shall be used over all plain, Bevelled or threaded open ends. Wood, metal or plastic covers shall be bolted or strapped to open flanged ends. All protective coverings of piping for shipment and shipping containers shall be of sturdy construction in order to withstand normal shipping abuse. Provisions shall be made to prevent damage to all subassemblies during loading, unloading or shifting of the cargo in transit. Small items shall not be shipped loose, but shall be bagged, boxed or crated. Each container shall be tagged with a description of the contents and destination. Carbon, low-alloy and galvanized carbon steel, stainless steel and duplex stainless steel shall be shipped separately from each other. For stainless-steel and duplex stainless steel spools, subcontractor shall not use steel hoisting devices as described in subsection 5.1 and shall provide suitable transport packing to prevent spools from contacting surfaces containing zinc or other harmful materials during the transportation.
12.1 Spool Piece Marking The appropriate pipe identification, consisting of the line number and spool number, shall be hard dye stamped into the spool. Marking shall be circled with yellow paint. Fabricator Contractor/Subcontractor shall be responsible for ensuring that throughout fabrication all pipe spools are marked and can be identified by the numbers assigned to them by the isometric drawings. The use of die stamping, scratching, etching or bead welding for pipe identification marking shall not be permitted. Pipe spool identification markings shall be clearly written on the pipe using an alkyd, brilliant white colour paint, in two places at diametrically opposite sides and one metal tag secured to the spool piece by multi-strand stainless steel wire or strap. Austenitic stainless steels and Copper Nickel materials shall not be marked with crayons or paint containing sulphur, zinc, lead, aluminium, or compound sulphur.
FOROOZAN OFFSHORE COMPLEX RENOVATION AND RECONSTRUCTION PROJECT Contract No. 3898-86-2FGH SPECIFICATION FOR PIPING FABRICATION AND ERECTION Rev. D2 Proj. Site Disc Doc. Seq. Page F500 0000 PI SP 5003 40 of 40
All post weld heat treated (stress relieved) fabrications shall be clearly marked on both sides WELDING PROHIBITED In addition to the pipe spool identification, the welders identification reference shall be painted adjacent to each weld using an approved paint / crayon. The position chosen shall be transferred to the radiographic records for each respective weld. This transfer shall be carried out to the satisfaction of the Owner and or Authorized Inspectors.
13 ADDITIONAL REQUIREMENTS For additional or deviating requirements concerning fabrication and erection of steel piping, see specifications listed below: F500-0000-ME-SP-4005: Insulation Specification