OT18-60A

OUTDOOR THERMOSTAT
INSTALLATION INSTRUCTIONS
Goodman Manufacturing Company, L.P. 2003-2006
2550 North Loop West, Suite 400, Houston, TX 77092
www.goodmanmfg.com -or- www.amana-hac.com
P/N: IO-510D Date: March 2006
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This
includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention
to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is
more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to
instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific
good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices.
However, if there is a direct conflict between existing practices and the content of this manual, the
precautions listed here take precedence.
DESCRIPTION
This single pole double throw thermostat device with adjust-
able 0 to 45 temperature range is employed in conjunction
with the room thermostat to control the electric heaters that
have been added to Goodman and Amana

cooling and heat


pump product. This kit includes an Outdoor Thermostat, three
wires, mounting bracket, (3) wire caps, and (2) self-drilling
screws.
Note: If the outdoor ambient temperature is below 0 F (-18
C) with 50% or higher Relative Humidity, an Outdoor Thermo-
stat must be installed and set at (0 F) on the dial. Failure to
comply wth this requirement may result in damage to the prod-
uct which may not be covered by the manufacturers warranty.
See Figures 12 and 15 for wiring connections.
The schematic and the terminal view of this device is showed
in Figure 2:
When used as an outdoor thermostat to control increments of
electric heat, connections will be made to terminals 2 and 1.
As temperature rises above the set point contacts 2 to 1 will
open thus preventing the controlled increment of supplemental
heat from operating. As outdoor temperature falls below the
set point contacts 2 to 1 will close allowing the controlled in-
crement of heat to operate. See Figures 10, 11, 13, and 14 for
wiring connections.
Use the wires supplied for Outdoor Thermostat connections. If
the installation is with an All Fuel kit, refer to the Installation
Instructions supplied with the AFE18 All Fuel kit for wiring con-
nections.
2
INSTALLATION
The outdoor thermostat is designed to be installed in the space
allocated in the control box of the Amana

and Goodman cool-


ing and heat pump units.
Set Point
Adjustment
Screw
Set Point
Indicator
Mark
(Shown @ O F)
Thermostat
Dial
DEAD
DIAL
315
45
COLD (Turn Clockwise)
WARM (Turn Counterclockwise)
OT18-60
THERMOSTAT CAM
Figure 1

Normally Open
Contacts 2-1
Close On
Temperature Fall
Normally Closed
Contacts 2-3
Open On
Temperature Fall
RANCO THERMOSTAT - RANCO PART # A22-1260-00
GOODMAN PART # B13708-67
Figure 2
WARNING
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK,
DISCONNECT ELECTRICAL POWER BEFORE INSTALLING THE OUTDOOR
THERMOSTAT.
1. Remove the sheet metal screws securing the unit control
box cover.
2. Install the OT18-60A Outside Thermostat using the sup-
plied bracket and self-drilling screws (see Figures 3 through
9.). NOTE: Early Amana

and Goodman split, packaged


cooling and heat pump units, refer to Figures 3 through 6.
AS*, GS* and SS* split cooling and heat pump units, re-
fer to Figures 7 and 8. GP* packaged cooling and heat
pump units, refer to Figure 9.)
3. Wire the thermostat per Figures 10, 11, 12, 13, 14, and
15.
4. Route the capillary away from live terminals to prevent
electrical shorts.
NOTE: Outdoor Thermostat copper capillary will remain
inside of the control box on early Amana and Goodman
models. On AS*,GS*, GP* and SS* models, the capillary
will extend outside the control box.
5. Set installed thermostat(s) to the proper outdoor temper-
ature. Insert a screwdriver in slot of thermostat dial (Fig-
ure 1). Turn set point indicator as shown in figure to de-
sired temperature setting on label (counterclockwise for
WARM, clockwise for COLD).
6. Reinstall the control box cover.
GOODMAN
SPLIT SYSTEM HEAT PUMP
Figure 3
GOODMAN
PACKAGE SYSTEM COOLING
AND HEAT PUMP
Figure 4
AMANA

BRAND
REMOTE HEAT PUMP
Figure 5
3
AMANA

BRAND
REMOTE HEAT PUMP
Figure 6
PO WER
AL ERT
TR IP
C
R
Y
152025
30
35
40
45 0
5
10
TEMP F
OUTDOOR
THERMOSTAT
0140K00041P
GOODMAN MFG. CORP.
KIT NO.: OT18-60A
USE LINE ON CAM TO SELECT TEMPERATURE
O
19 91
DF T W2 Y
D
F
2
A 60
O R
K 2
30
D
F
1
90
TE ST
C
K 1
R C
DEF.
CONTROL
OT18
CAP
COMFORT
ALERT
MODULE
CONTACTOR
ASC*, ASH*, ASX*, ASZ*, GSC*, GSH*,SSX*, SSZ SERIES SMALL
BOX SPLIT SYSTEM COOLING AND HEAT PUMPS
Figure 7
PO WER
AL ERT
TR IP
C
R
Y
1 3
4
2 5
O
19 91
DF T W2 Y
D
F
2
A 60
O R
K 2
30
D
F
1
90
TE ST
C
K 1
R C
COMFORT
ALERT
MODULE
CONTACTOR
DEF.
CONTROL
OT18
CAP
TIME
DELAY
FAN
RELAY
ASX*, ASZ* SERIES LARGE BOX
SPLIT SYSTEM COOLING AND HEAT PUMPS
Figure 8
L2
L1
T
2
T
1

.18
0
XFMR
CONTACTOR
CAP
OT18
GPC*, GPH* SERIES PACKAGED SYSTEM
COOLING AND HEAT PUMPS
Figure 9
4
W2 C O Y R Y
TYPICAL H/P
ROOM THERMOSTAT
OUTDOOR UNIT
(OPTIONAL)
OUTDOOR THERMOSTAT
CLOSE ON TEMPERATURE FALL
R
G
C
W2
RED
GREEN
WHITE
BLUE
INDOOR UNIT
SEE NOTE #2
2 1
R
E
D
Y
E
L
L
O
W
O
R
A
N
G
E
W
H
I
T
E
B
L
U
E
#18 GA. 6 WIRE NEEDED WHEN OT IS USED
O
R
A
N
G
E
Y
E
L
L
O
W
SEE NOTE #2
C BLUE
W2
G
WHITE
GREEN
OUTDOOR UNIT
B
L
U
E
W
H
I
T
E
R
E
D
SEE NOTE 1
#18 GA. 8 WIRE
INDOOR UNIT
R RED
2 1
W3 BROWN
NOTES:
1) "O" AND "E" USED ON HEAT PUMPS ONLY.
2) TERMINAL BLOCK MARKINGS ARE FOR AMANA
AIR HANDLERS
3) "R", "O" AND "W2" CONNECTIONS REQUIRED ON
HEAT PUMPS ONLY.
4) "R" CONNECTION REQUIRED ON AMANA AC UNITS
WITH COMFORT ALERT MODULE.
COLOR CODES
R --RED
Y --YELLOW
BL-BLUE
BR-BROWN
O --ORANGE
W -WHITE
G --GREEN
Figure 10
Figure 11
SEE
NOTE
3
SEE NOTE 4
O C W1 G R E
R
#18 GA 6 WIRE
SEE NOTE 3
O
Y
BL
G
BR
BL
BL
W
BL
W
R R
G
W2 C O Y R Y O R E
TYPICAL H/P
ROOM THERMOSTAT
W2 C W1 G
SEE
NOTE
3
SEE NOTE 4
SPLIT SYSTEM WIRING DIAGRAM - TWO-STAGE ELECTRIC HEAT
ABOVE 10 KW
SEE
NOTE
5
OUTDOOR THERMOSTAT
CLOSE ON TEMPERATURE FALL
O
Y
#18 GA. 6 WIRE
FOR HEAT PUMPS
SEE NOTE 3
R
W
BL
BR
BL
BL
R
W
G
R
BR
G
R
W
BL
5) CONNECT WIRE FROM TERMINAL #2 OF
OUTDOOR THERMOSTAT TO THE WHITE
WIRE ON THE INDOOR UNIT IF A SINGLE
STAGE INDOOR THERMOSTAT IS USED.
R
SPLIT SYSTEM WIRING DIAGRAM - SINGLE STAGE ELECTRIC HEAT
10 KW & BELOW
SEE NOTE 1
#18 GA. 7 WIRE
5
BL R
C W2 O Y R W2 Y O W1 G R C
TYPICAL H/P
ROOM THERMOSTAT
HEAT PUMP
OUTDOOR THERMOSTAT #1
CLOSE ON TEMPERATURE FALL
RED
GREEN
WHITE
BLUE
INDOOR UNIT
#18 GA. 8 WIRE
SEE NOTE #1
R
E
D
Y
E
L
L
O
W
O
R
A
N
G
E
W
H
I
T
E
B
L
U
E
2 1
R
W
BL
BL
3
BR
G
R R
G
BL
W
C
W2
G
R
W3
Figure 12
For outdoor temperatures below 0 F with 50% or higher relative humidity,set outdoor
thermostat at 0 F
.
COLOR CODES
R --RED
Y --YELLOW
BL-BLUE
BR-BROWN
O --ORANGE
W -WHITE
G --GREEN
BROWN
NOTE 1: TERMINAL BLOCK MARKINGS ARE FOR AMANA AIRHANDLERS.
TWO-STAGE ELECTRIC HEAT
NOTE 2: CONNECT OT18 #2 BETWEEN W2 OF THERMOSTAT AND BROWN WIRE ON INDOOR UNIT IF USED.
BR
BR
BA
2 1
BL R
OUTDOOR
THERMOSTAT #2
(IF USED, SEE
NOTE 2)
E
O
Y
W
Y
#18 GA. 5 WIRE
SPLIT SYSTEM WIRING DIAGRAM - HEAT PUMPS ONLY!
ABOVE 10 kW
6
BLUE
WHITE
ORANGE
GREEN
YELLOW
RED
SEE NOTE 1
#18 GAUGE 7 WIRE
OUTDOOR THERMOSTAT
CLOSE ON TEMPERATURE FALL
1 2
Y O C W1 G R E
R
Y
R
G
O
O
G
W BR
BL BL
R
BL
W2 C R Y O W1 G E
1 2
PACKAGE UNITS
BLUE
BROWN
WHITE
ORANGE
GREEN
YELLOW
RED
SEE
NOTE 2
R
Y
G
O O
Y
G
R
BL BL
BR R
W
BR
W
Color Codes
R - Red
Y - Yellow
BL - Blue
BR - Brown
O - Orange
W - White
G - Green
PACKAGE UNIT
Y
Figure 13
OUTDOOR THERMOSTAT
CLOSE ON TEMPERATURE FALL
TYPICAL H/P
ROOM THERMOSTAT
TYPICAL H/P
ROOM THERMOSTAT
SEE NOTE 1
#18 GAUGE 8 WIRE
Figure 14
LOW VOLTAGE
JUNCTION BOX
1) "O" AND "E" USED ON HEAT PUMPS ONLY.
NOTES:
2) IF SINGLE STAGE INDOOR THERMOSTAT IS USED, CONNECT WIRE FROM TERMINAL #1
TO THE WHITE WIRE ON PACKAGE UNITS.
PACKAGE SYSTEM WIRING DIAGRAM - TWO-STAGE ELECTRIC HEAT
ABOVE 10 KW
PACKAGE SYSTEM WIRING DIAGRAM - SINGLE STAGE ELECTRIC HEAT
ABOVE 10 KW
7
R
W2 C R Y O W1 G E
TYPICAL H/P
ROOM THERMOSTAT
1 2
PACKAGE HEAT PUMP
LOW VOLTAGE
JUNCTION BOX
BLUE
BROWN
WHITE
ORANGE
GREEN
YELLOW
RED
#18 GAUGE 8 WIRE
R
Y
G
O O
Y
G
R
BL BL
BR
W
BR
W
3
BL
Y
PACKAGE SYSTEM WIRING DIAGRAM - HEAT PUMPS ONLY!
ABOVE 10 kW
Figure 15
For outdoor temperatures below 0 F with 50% or higher relative humidity,set outdoor
thermostat at 0 F
.
NOTE 1: OT18 #2 CAN BE CONNECTED BETWEEN W2 OF THERMOSTAT AND BROWN WIRE IF DESIRED.
TWO-STAGE ELECTRIC HEAT
COLOR CODES
R --RED
Y --YELLOW
BR-BROWN
O --ORANGE
W -WHITE
G --GREEN
BL-BLUE
OUTDOOR THERMOSTAT #1
CLOSE ON TEMPERATURE FALL
BL
1 2
OUTDOOR THERMOSTAT #2
(IF USED, SEE NOTE 1)
8
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN
ARE SUBJECT TO CHANGE WITHOUT NOTICE
Quality Makes the Difference!
All of our systems are designed and manufactured with the same high quality standards regardless of size or
efficiency. We have designed these units to significantly reduce the most frequent causes of product failure.
They are simple to service and forgiving to operate. We use quality materials and components. Finally, every
unit is run tested before it leaves the factory. Thats why we know. . .Theres No Better Quality.
Visit our website at www.goodmanmfg.com or www.amana-hac.com for information on:
Products
Warranties
Customer Services
Parts
Contractor Programs and Training
Financing Options
2003-2006 Goodman Manufacturing Company, L.P.

Potrebbero piacerti anche