P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc
Hindustan Petroleum Corporation Ltd Visakha Dispatch Station VR-ATP Area, Naval Base Post Visakhapatnam - 530 014 Andhra Pradesh Mott MacDonald Consultants (India) Pvt. Ltd. Kothari House, CTS No. 185 Off Andheri - Kurla Road Andheri (East) Mumbai 400 059
SPECIFICATION FOR ELECTRICAL INSTALLATION TENDER VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 3 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc
List of Contents Pages
1.0 Introduction ........................................................................................................................... 4 2.0 Location and Environmental Conditions............................................................................... 4 2.1 Plant Location........................................................................................................................ 4 2.2 Environmental Conditions..................................................................................................... 4 2.3 Electrical System Data .......................................................................................................... 4 3.0 Scope of Supply..................................................................................................................... 5 4.0 Codes and Standards ............................................................................................................. 6 5.0 Design requirements.............................................................................................................. 7 6.0 Inspection and testing............................................................................................................ 9 7.0 Vendor documentation ........................................................................................................ 10 8.0 Spares and special tools....................................................................................................... 11 8.1 Spares .................................................................................................................................. 11 8.2 Special tools ........................................................................................................................ 11 9.0 Installation and commissioning........................................................................................... 11 10.0 Packing and transportation.................................................................................................. 11 11.0 Statutory Approval .............................................................................................................. 11 12.0 Guarantee............................................................................................................................. 12 Appendix-A: Table of Compliance................................................................................................. 13 Appendix-B: Codes & Standards .................................................................................................. 15 Appendix-C: Requisition for Engineering Documents ................................................................. 17 Appendix-D: Technical Data Sheet & Guaranteed Technical Particulars ..................................... 19 [Refer Doc. No. 254625-300-DS-ELE-008 (Pages 1 to 17)] .......................................................... 19 Appendix-E: Specification for Electrical Equipment to be supplied by Contractor ....................... 20 Appendix-F: Specification for Installation, Testing & Commissioning of Electrical Equipment .. 21 Appendix-G: Schedule of Quantity................................................................................................. 22 Appendix H : Recommended List of vendors ........................................................................... 23 Appendix-I: List of Enclosed Drawings.......................................................................................... 25
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 4 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc
1.0 Introduction
1.1 This specification covers the minimum requirements for the Design, Engineering, preparation of detailed drawings & documents, Obtaining necessary approvals, Material procurement, Fabrication, Assembly, Painting, Inspection at Vendors works, Delivery to site, Erection, Testing and Commissioning, Approval from Local statutory authorities for installation etc. for Electrical Equipment Installation for Black Oil Terminal Project of M/s. HPCL, located at Visakhapatnam, A.P., India.
Following are the definitions:
Owner / Purchaser Hindustan Petroleum Corporation Ltd. Consultant Mott MacDonald Consultants (India) Pvt. Ltd.[MMCI] Vendor/ Contractor Electrical Contractor APSEB Andhra Pradesh State Electricity Board. Shall This is to be understood as mandatory in relation to the requirements of this document. Should This is to be understood as a strong recommendation to comply with the requirements of this document. Equipment This is to be understood as vendor supplied equipment with all accessories.
1.2 The Vendor shall ensure that the design complies with the requirements of this specification and its referenced specifications and standards. The data sheets, Appendix D, which forms part of this specification, shall be completed by the Vendor. The Vendor shall highlight any non-compliance at the offer stage in the Table of Compliance, Appendix A. The Table of Compliance and filled in data sheets shall form a part of the offer. Not providing completed compliance table and data sheets can cause rejection of the offer. Failure to clearly identify specific deviations shall be assumed by the Purchaser to be total compliance with the specification.
1.3 This specification does not relieve the Vendor from final guarantee as to materials, apparatus, workmanship and performance of the equipment supplied.
2.0 Location and Environmental Conditions
2.1 Plant Location
Black Oil Terminal Project is located at Visakhapatnam, A.P., India. Electrical Equipment Installation shall be done within plant complex.
2.2 Environmental Conditions
Refer Doc No.: 254625-300-SP-GEN-001 for details.
2.3 Electrical System Data
Refer Doc No.: 254625-300-DS-ELE-001 for details. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 5 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc
3.0 Scope of Supply
The Electrical Equipment shall be supplied & Installed in accordance with this specification, standards stated herein & enclosed appendices.
3.1 Contactor scope Scope of Supply includes, but not necessarily be limited to, the following : Design, supply, manufacturing, inspection / testing, packing and forwarding, delivery at site, installation, supervision, commissioning, statutory certification and guarantee. Supply & Installation of electrical equipment as specified in Appendix-E, F & G and Unloading, handling, erection, testing and commissioning of free issue material / equipment supplied by the Owner as specified in Appendix-F & G. The entire scope of work shall comply with the requirements of latest statutory regulations in force but not limited to the Indian Electricity Rules & Acts, Relevant IS Specifications, Local Statutory Regulations and Specifications of this Tender. Electrical Design, Engineering, Preparation of Detail Design Documents, obtaining Approval from Statutory Authorities / Client / Consultant. All consumables required for the work such as welding rods, insulation tape etc., conforming to relevant IS, shall be arranged by the contractor at his own cost. Tools & tackles required for the work shall be arranged by the contractor and shall be kept at his own custody. Engineering Services (Ref.Cl.no.3.2 for details). Statutory Approvals. Performance testing of Electrical Equipment. Any Items instruments required for testing shall be arranged by contactor during the contract period. For Supply Equipment: Start-up spares and commissioning spares. For Supply Equipment: Spares for two years normal operation. List of special tools required (Vendor to provide list with the offer). Inspection and Testing as specified. Submission of documents as specified. Painting as specified. Installation/Erection and commissioning. Any other items, required to make system complete. 3.2 Engineering Services The Vendor shall provide engineering services, which shall include, but not necessarily be limited to, the following: VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 6 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc Providing/co-ordinating detailed design of all equipment and components within the scope of supply. Resolving engineering queries related to the equipment and components within the scope of supply. Performing and co-ordinating all aspects of design. Performing all relevant calculations pertaining to the package design. Providing progress reports etc. Providing expediting services for all sub-vendors. Providing quality assurance, including all sub-vendors with respect to ISO 9000 or equivalent. Quality Assurance. Training of clients personnel at site / Vendors shop.
3.3 Following documents attached as Appendices shall be referred Appendix-E : Specification for Electrical Equipment to be supplied by Contractor [Doc. No. 254625-300-SP-ELE-008] Appendix-F : Specification for Installation, Testing & Commissioning of Electrical Equipment [Doc. No. 254625-300-SP-ELE-009] Appendix-G: Schedule of Quantity [Doc. No. 254625-300-SC-ELE-008(Part A) & 254625-300- SC-ELE-009 (Part B&C]. Appendix-H : Recommended List of Vendors Appendix-I : Drawings attached
4.0 Codes and Standards
4.1 General
All Electrical Equipment & Installation shall meet the requirements of this specification and latest edition of applicable standards listed in enclosed Appendix-B.
4.2 Conflicting Requirements
In case of conflict between documents relating to the enquiry or purchase order, the following priority of documents shall apply.
First priority : Purchase order and variations thereto Second priority : Data/requisition sheets and drawings Third priority : This engineering specification. Fourth priority : International standards.
Note: Should any conflict arise either before or after order placement the Vendor shall immediately inform the Purchaser for technical resolution of the conflict.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 7 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc 5.0 Design requirements 5.1 General 5.1.1 It is not the intent of this specification to completely specify all the details of design and construction. Nevertheless, the equipment to be supplied by the Vendor shall also conform to the high standards of engineering, design, workmanship, etc. in all respects.
5.1.2 Any part of equipment or component not specifically mentioned in this specification that required for making the Installation complete, safe and reliable should be provided by the Vendor at no extra cost.
5.1.3 The Vendor shall make all possible efforts to comply strictly with the requirements of this specification and other specifications as mentioned in this specification. In case, any deviations are considered essential by the vendor after making all possible efforts, these shall be separately listed in the offer under List of deviations to specifications for purchasers considerations. The deviations / exceptions shall be listed separately for each specification / document with cross references and proper reasons for the deviations. In case of any deviation not listed under the List of deviations to the specifications, although it is appearing in other part of the offer, shall not be considered / applicable. Hence all the requirements shall be binding on the vendor without any cost and schedule implications to the Purchaser.
5.1.4 Compliance to this specification shall not relieve the vendor of the responsibility of supplying the equipment and auxiliaries of proper design, material and workmanship to meet the operating requirements specified. In case of requirements of additional instruments, controls, safety devices and any other auxiliaries for safe, smooth and trouble free operation of the equipment, the Vendor shall include the same in his scope of supply.
5.1.5 The offered equipment or its accessories shall be sourced from a reputed and established manufacturer and having requisite design, engineering, manufacturing and testing facility.
5.1.6 The offered model shall be from the regular manufacturing range of the supplier and the design shall have had a minimum of two years successful field operation with the same model having the same design and materials of constructions. Relevant information of the offered equipment like catalogues, references, users certificate etc. shall be furnished along with the offer.
5.1.7 All equipment shall be designed to operate satisfactorily under the ambient, environmental and power supply conditions indicated in of this specification.
5.1.8 Any and all other works not indicated explicitly, but required to complete the job including obtaining statutory clearances are included in the Vendors scope.
5.1.9 Vendor shall take vendor drawing approval from Owner/Consultant for all equipment/systems, which is included in the Vendors scope.
5.1.10 Necessary approval of any other Govt. agencies as required will have to be obtained by the vendor. 5.2 Services by Purchaser 5.2.1 Graded Site. 5.2.2 Approach to site.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 8 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc 5.3 Electrical Equipment / Panels / Materials:
5.3.1 The quantities mentioned in the Schedule of Quantity are tentative. However these shall be used for the purpose of estimation only. 5.3.2 The actual quantities of the materials required & its delivery schedule shall be discussed by contractor with Engineer-in-Charge. Contractor shall adhere to the decisions made by the Engineer-in-Charge. 5.3.3 Excess material supplied by the contractor if any which are not consumed in the work shall be returned to the contractor by the Owner. 5.3.4 The material rates quoted by the Contractor are inclusive of all duties, taxes and F.O.R. site basis and no additional charges shall be paid. 5.3.5 Materials / Equipment / Panels which are in the scope of Owner's supply shall be issued to the contractor from their stores or anywhere inside the Plant premises. 5.3.6 All materials received by the contractor at site shall be stored in an appropriate manner at a location as directed by the Engineer-in-Charge. 5.3.7 Material reconciliation shall be carried out by the contractor and relevant documents shall be produced by him before final bill & got approved by the Engineer-in-Charge. 5.3.8 Balance material as per the reconciliation statement if any shall be returned to stores by the Contractor. 5.3.9 Suitable recovery shall be made from the contractor's bills for the materials not returned by him. 5.4 Instructions to Vendor 5.4.1 All necessary co-ordination with regard to sub-contracted equipment shall be carried out by the Vendor. 5.4.2 Prices quoted for the equipment in the price Schedule shall be exclusive of type test charges. 5.4.3 All unit prices quoted shall be valid until the date of successful commissioning of all Electrical Equipment. 5.4.4 Owner/Consultant has full authority for deletion of items which are not required from the scope of supply. Rate for deletion will be considered as per the unit rate prices quoted. 5.4.5 Vendor may note that the Owner reserves the right to split the order in any manner. 5.4.6 This being a lumpsum all inclusive contract all expenses for commissioning including transportation, lodging and boarding of vendors personnel shall be suitably included by contractor. 5.4.7 As & when the need arises, the vendor shall depute his representative / engineer for discussions with the Owner/consultant till the completion of the project to finalise outstanding issues. 5.4.8 Makes of all equipment including bought out items & consumables shall be as per `Recommended list of vendors attached in tender document. Equipment of only accepted makes shall be supplied by vendor without any commercial implications. 5.4.9 Vendor shall submit bar chart indicating schedules of drawing submission, manufacture, delivery etc. immediately on placement of LOI / PO (whichever is earlier) to enable Owner to monitor work progress. 5.4.10 Being the Electrical contractor, for the supply & Installation of specified equipment, the overall responsibility for the timely supply of electrical equipment lies with the vendor.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 9 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc 6.0 Inspection and testing 6.1 The responsibility for inspection, certification, etc. of all materials, parts lies with the Vendor.
The Vendor shall specify all of the inspection and testing requirements in the quality plan which shall identify the activities requiring the Owners approval, review, witnessing etc.
Inspection and testing requirements shall be in accordance with this specification, other applicable standards as listed in this specification and the data sheets.
All Equipment shall be inspected for compliances with: Requirement of Owners specification & correspondence therefore. Applicable codes, standards and specifications, which shall also include sub-referenced standards therein. Test and Inspection Plans produced by the equipment manufacturer.
Inspectors have the right to request additional inspections or tests to ensure that the equipment complies with the specification and all relevant codes & standards.
6.2 Vendor shall furnish valid Type Test Certificates of similar models along with the offer. Fresh type tests for the equipment are not needed, provided the Vendor can submit certificates that the equipment complies with all type tests as prescribed by IEC/IS Standard specifying the test requirements for that equipment.
6.3 Routine tests on all the equipment shall be carried out as per the relevant IEC/IS. Equipment offered for final inspection shall be complete and ready for shipment, with the possible exception of the final paint finish.
6.4 Vendor to furnish required copies (as per RED form) of test certificates, Ref Documents, Drawings, and Instruction Manuals before equipment are dispatched.
6.5 Factory acceptance test (FAT) is required to be done at no extra cost to the purchaser. The purchaser or his representative shall be advised of the tentative date for FAT at least 3 weeks in advance prior to the test date.
6.6 Access to the manufacturing shop of Vendor / Sub-Vendor, at all reasonable times shall be made available to representative of Purchaser / Consultants / Third Party Inspection Agency for Inspection & Testing of electrical equipment.
6.7 Any defects found by the TPI or the Owners appointed Inspector shall be rectified in his presence. Where this is not possible or practical, check lists shall be prepared and signed by the Third Party Inspector stating all pending items. Copies of these lists shall be sent to the Owner to enable their subsequent checking. The equipment shall not leave the Vendor factory before all defects have been rectified and without the written permission of the Owner.
6.8 All spare parts shall be subjected to the same inspection standards and full material certification as the main order.
6.9 The equipment shall not leave the Vendor / Sub-Vendors factory before all discovered defects have been rectified and without the written permission of the Owner/Purchaser.
6.10 Any acceptance or release of equipment following an inspection or test activity shall in no way relieve the Vendor of his contractual responsibility to provide guarantees as to the suitability of VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 10 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc the materials, workmanship and performance of the equipment in accordance with this Specification.
6.11 Owner/Consultant reserves the right to waive the inspection at any stage. Inspection shall be carried out only on receipt of Vendor's internal test report of the equipment offered and scrutiny of the same. In the event, on receipt of inspection call, the Owner/Consultants representative reaches the Vendor's works and finds the material not ready for inspection/incomplete/has short supply, the inspector will return to his base station and all expenses incurred by the inspector including to and from travelling expenses from his base station to place of inspection, boarding and lodging etc shall be reimbursed by Vendor.
6.12 The tests to be carried out by vendor on completion of installation are broadly listed in Specification for Installation, Testing & Commissioning of Electrical Equipment in Appendix-F. Vendor shall mobilise all the testing equipment to carry out these tests & for which no extra cost shall be borne by Owner. 7.0 Vendor documentation 7.1 All information listed here is to be furnished along with the offer as a minimum. a. Clause wise comments / deviations on specification in `Table of Compliance [enclosed Appendix A]. If not furnished, compliance to all requirements in specifications will be binding on the Vendor. b. A detailed scope of supply that fully describes the package offered. c. Duly filled up guaranteed technical particulars [enclosed Appendix-D]. d. List of all equipment supplied in package with Makes. e. For Supply Items List of recommended spares of each equipment for two years normal operation with itemised rates. Type test certificates of each equipment. Technical Catalogues and brochures of major Components. f. List of clientele for similar installations in last 5 years. g. Complete list of special tools (if required) h. Documents as per RED.
7.2 The Vendor shall furnish the drawings and documents as per enclosed Requisition for Engineering Documents - RED Form [Appendix-C].
7.3 Any other drawing required for approval from APSEB/statutory authority, for installation shall be included by vendor.
7.4 The Owner/Consultant will review drawings submitted by Vendor & return to the Vendor one copy of drawings with comments to carry out necessary changes, if any, during the engineering / manufacturing stage.
7.5 Drawings submitted by Vendor shall clearly indicate schematics, B.O.M., GA, foundation drawings, terminal diagrams etc. The schematic drawings shall clearly indicate cross reference catalogue numbers, component relays of each scheme along with range & variable steps of each component / scheme & the recommended settings. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 11 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc 7.6 The documents required by the Third Party Inspection Agency are not covered under this specification. The Vendor shall provide all the drawings and documents required by the Third Party Inspection agency in compliance with the applicable codes and standards. 8.0 Spares and special tools 8.1 Spares
The Vendor shall furnish list of spares and supply all necessary spares for testing, pre- commissioning, commissioning. Any of the spares if used during testing/commissioning must be replenished at no extra cost to the purchaser.
The Vendor shall also supply all consumables during erection up to commissioning.
In addition to above, Vendor to supply spares for two years operation.
8.2 Special tools
The Vendor shall supply a set of any special tools, which are required for the installation, commissioning, operation and maintenance of the equipment being supplied. A list of special tools shall be furnished along with the offer. 9.0 Installation and commissioning Installation & commissioning shall be included in vendor scope. Vendor shall despatch Installation and Commissioning instructions for supply equipment at least 2 weeks before the arrival of the equipment.
Vendor shall provide qualified personnel to supervise the installation and carryout site testing and commissioning of all equipment supplied under this package contract.
Prices for these services shall be included by vendor. 10.0 Packing and transportation Packing, Shipping and delivery at site, unloading etc. of equipment shall be in Vendors scope.
Packing, shipping and delivery of equipment at site and unloading requirements shall be as per agreed Terms & Conditions of HPCL.
Preparation of the equipment for shipment is a crucial step in the completion of this contract. The Vendor must take into consideration that all equipment shall be prepared for proper transportation. 11.0 Statutory Approval Electrical equipment supplied & complete installation shall be acceptable to local Statutory authorities viz. Electrical Inspectorate, APSEB etc. and changes required, if any, shall be carried out by the vendor without any extra cost. All necessary documents shall be completely filled by contractor, with all necessary attachments & then submitted to HPCL for the signature.
The Vendor shall provide liaison services, which shall include, but not necessarily be limited to, the following: The contractor shall have valid licence to execute Electrical Installation works as given under the scope of works. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 12 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc It shall be total responsibility of vendor to obtain approval for Installation of all electrical Equipment from statutory authorities at no extra cost. Necessary co-ordination with statutory authorities for Procedures, for supply & installation of Electrical equipment will be the total responsibility of vendor. 12.0 Guarantee Equipment & installation shall be guaranteed to meet the specified performance at specified conditions in terms of power, air flow, thermal performance, design conditions etc.
Equipment and its components & Installation shall be guaranteed against faulty design, defective / improper materials poor workmanship or failure from normal use during the guarantee period.
Vendor shall make all necessary and desirable alterations, repairs and replacement free of charge in the event of mal performance or defects occurring in the equipment during guarantee period.
Also refer to guarantee clause as per General Terms & Conditions Clause No. 5-n.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 13 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc Appendix-A: Table of Compliance
The Vendor shall confirm that clauses of the specification have been complied with/accepted or further clarifications are desired, or Vendor has taken a deviation with reason thereto.
CLIENT : HPCL : BLACK OIL TERMINAL VENDOR REF. Spec. Clause No. Conforms Yes/No Alternative Yes/No Clarification 1
2
2.1
2.2
2.3
3
3.1
3.2
3.3
4
4.1
4.2
5
5.1
5.2
5.3
5.4
6
7
8
9
10
11
12
Appendix A:
Appendix B:
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 14 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc CLIENT : HPCL : BLACK OIL TERMINAL VENDOR REF. Spec. Clause No. Conforms Yes/No Alternative Yes/No Clarification Appendix C:
Appendix D:
Appendix E:
Appendix F:
Appendix G:
Appendix H:
Appendix I:
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 15 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc Appendix-B: Codes & Standards IS 1248 :Part I :2003 : Direct Acting Indicating Analogue Electrical Measuring Instruments and their Accessories IS-6875 (Part 1 to 3) :1992 : Recommendations for the colour of Local Control Station IS 12063 :2004 : Classification of degrees of protection provided by enclosures of electrical equipment. IS-4794 (Part 1 & 2) :2002 : Push Button Switches General Requirements and Tests. IS : 8623 :Part I: 1998 : Factory built assemblies of switchgear and Controlgear. IS : 8623 :Part III: 1998 : Specification for Low-Voltage Switchgear and Controlgear Assemblies - Part 3 : Particular Requirements for Equipment Where Unskilled Persons have Access for Their Use IS : 13703: Part I : 2002 : Low voltage fuses. IS : 10118 :Part -1:2006 : Code of practice for selection of switchgear and Controlgear. IS: 1255: 2001 : Code of practice for installation and maintenance of power cables upto and including 33 KV rating. IS: 10810(Part 43):2006
: Method of Test for cables; Part 43 Insulation resistance. (Part 43) IS: 10810(Part45):2006
: Method of Test for cables; Part 45 High voltage test. (Part45) IS-7816 : 2002 : Guide for testing Insulation resistance of rotating machines IS : 13947 :2004 : General requirement for switchgear and control gear for voltage not exceeding 1100 V IS:2309 :2005 : Protection of buildings and allied structures against lightning. IS:3043 :2006 : Code of practice for earthing IS:7689 : 2005 : Guide for control of undesirable static electricity IS-732 : 2005 : Code of practice for electrical installation IS-2148 : 2004 : Specification for Flameproof Enclosures of Electrical Apparatus IS-5571 : 2006 : Guide for selection of Electrical Equipment in hazardous areas. IS-5572 :1999 : Classification of hazardous areas (other than Mines) having flammable gases & vapours for electrical installation. IS-6381: 2004 : Construction & Testing of electrical apparatus with type of protection e IS-8289 :2001 : Electrical equipment with type of protection n IS-8224 :2003 : Electrical Lighting fittings for division 2 areas IS-13346 :2004 : General requirements of electrical apparatus for explosive gas atmosphere. IS-13408(Part-I) :2003 : Code of practice for the selection and maintenance of electrical apparatus for use in potentially explosive atmospheres.(other than mining applications or explosive processing and manufacture). IS-10028 (Part-2) : Code of practice for selection, installation and maintenance of transformer : Part 2 - Installation VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 16 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc IS-10028 (Part-3) : Code of practice for selection, installation and maintenance of switchgear and control gear : Part 3 - Installation SP-30(BIS) :2005 : National Electrical Code. OISD-RP-137 : Inspection of electrical equipment OISD 147 : Inspection and safe practices during electrical installations OISD-RP-149 : Design aspects for safety in electrical systems OISD-GDN-180 : Lightning Protection OISD 110 : Recommended practices on static electricity SP-30(BIS) :2005 : National Electrical Code. Indian Electricity Act and Rules. :1956 Indian Factories Act :1948 Indian Explosives Act : 1848 Insurance Regulations of development Authority (IRDA) Rules : 2002 Regulation of local authorities such as Electrical Inspectorate. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 17 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc Appendix-C: Requisition for Engineering Documents RED Form Owner/Purchasers Office Distribution Office M/s. Hindustan Petroleum Corporation Ltd. Viskaha Dispatch Station VR-ATP Area, Naval Base Post Visakhapatnam 530 014 Mott MacDonald Consultants(I) Pvt. Ltd Kothari House, CTS No. 185 Off Andheri Kurla Road Andheri ( East), Mumbai 400059, India SPECIAL INSTRUCTIONS Prints Documents shall be sent to: Production Schedule 5 The Purchasing Office via courier service Manufacturing, inspection & testing sequence plan 5 The Purchasing Office via courier service DRAWINGS Required number for TIMING FOR SUBMITTAL OFFER APPROVAL FINAL - for approval 2 weeks after order date Approval drawings / Final drawings to be submitted under cover of an ADS form / FDS form respectively Prints Prints Disk Prints - final issue 2 weeks after approval date Documents shall be submitted to: Submission of Following not limited to: Guaranteed Technical Particulars 2 5 2 5 All Equipment Vendor Drawings for Contractor Supply items: General Arrangement Drawing including Plan, Front elevation, Rear elevation, Side Elevation, & relevant cross sectional View, weights, main dimensions, etc. of supplied Electrical equipment. Schematic diagram indicating terminal nos. for external connection with BOM Rating & Diagram plate, Name Plate Drawing for each equipment Dimensional drawing of clamps and connectors 5 2 5
Installation Drawings: Earthing & Lightning Protection Cabling, Trenches, Conduits, Trays, Bends, Tees Etc. Lighting Control Panel drawings indicating floor/wall/pedestal fixing arrangements, pad locking arrangements, Cable entry openings, etc. Any other detailed Installation drawings 5 2 5 Cable Schedule & Interconnection Schedule (Refer Note 2) * 5 2 5 List of accessories for testing & maintenance of each electrical equipment 2 5 2 5
Bill of Material for Electrical equipment 2 5 2 5 List of Make for Electrical Equipment 2 5 2 5 Type Test Certificates of Electrical Equipment 2 5 2 5
Routine Test Certificates of Electrical Equipment 5 2 5 Spares List for two Years Operation 2 5 2 5 Technical Catalogues of Electrical equipment. 2 5 2 5 As Built Drawings 2 5 SPARE PARTS DOCUMENTS 2 5 TEST AND INSPECTION DOCUMENTS Prints Documents to be submitted under transmittal Manufacturing report 2 5 Documents shall be submitted to: VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 18 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc Test Report / Data Curves foe switch yard equipment 2 5 Calibration Certificates for testing Instruments. 2 5 Bought out Equipment Certificates. 2 5 Purchasing Office via courier service within 4 weeks OPERATING DOCUMENTS Purchasing Office via courier service not later than time of Installation manual 2 5 Dispatch of equipment. Operational manual 2 5 Combine into one manual Maintenance instructions 2 5
Notes: 1. Referenced standards / codes shall be the latest issue unless otherwise stated. 2. * Cable Schedule shall be prepared by Contractor based on actual cable routing. Interconnection schedule shall be prepared by Contractor based on Equipment vendor drawings which will be furnished in the event of order. REMARKS Invoice must certify that the drawings and engineering documents specified above have been dispatched to all parties concerned. Any deviation from the timing for submittal of documents shall be notified to the Approval / Distribution Offices by fax or E mail. Shop fabrication shall not be started before the required approval drawings have been released for construction by the party concerned, unless otherwise stated on the "Approval Drawing Specification". Each document shall bear the item / tag and order reference number and be dispatched by air mail, unless other instructions are stated on the RED. Units / dimensions to be used on Engineering documents shall be SI. The documents shall be in English. Description on drawings and similar documents may be in other languages provided English translations are also given. Drawings and documents shall comply with accepted national or international standards for the preparation of technical drawings. Only the following standard drawing sizes should be used: A4, A3, A2, and A1. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 19 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc
Appendix-D: Technical Data Sheet & Guaranteed Technical Particulars [Refer Doc. No. 254625-300-DS-ELE-008 (Pages 1 to 17)]
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 1 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc TECHNICAL DATA SHEET & GUARANTEED TECHNICAL PARTICULARS NOTE : 1) If Specific Deviations are not taken against Specification Clauses, it will be assumed that Vendor has accepted the Specification Clause. A] Cables Sr. No. Description Vendor Data / Confirmation A Supplier B Manufacturer 1.0 General Requirements 1.1 Operating Voltage 1.2 Maximum Voltage 1.3 Frequency 1.4 Ambient Temperature 1.5 Standards 1.6 Marking and Identification 1.7 Applicable Cable catalogues / Cable data 1.8 Maximum possible cable drums length offered 1.9 Tolerance on drum length in % 1.10 Weight of Cable in Kg/Km 2.0 Inspection And Testing 2.1 List of Offered Test 3.0 Cable Specification 3.1 Voltage Grade 3.2 Short Circuit Withstand Capacity for 1 sec. in kA
For Conductor For Insulation screen For Armour For combined Screen/Armour 3.3 Conductor Material VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 2 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Max conductor temperature (on load) Max conductor temperature (on fault) 3.4 Shape of conductor 3.5 Insulation Material Colour Coding 3.6 Armour 3.7 Outer Sheath Material Colour coding 3.8 Diameter in mm Overall diameter of cable Diameter of cable over armour Diameter of cable over inner sheath 3.9 Tabulated current carrying capacity in ground and air with installation conditions
3.10 Tabulated Resistance & Reactance Note: Vendor to furnish technical data pertaining to the calculation of derating factors such as ground temperature, soil resistivity, and depth of laying and grouping of cables for various types of installations. B] Cable Trays SR. NO. DESCRIPTION VENDOR CONFIRMATION 1 Make & Manufacturers Name
2 Type of Cable Trays
3 Material of Cable Trays 4 Material of coating & its thickness
5 Size of Horizontal supports
6 Interval of Clamping the Cable Trays in mm 7 Interval to Support adjacent Cable Trays in mm 8 Cover Sheet a) Material VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 3 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc SR. NO. DESCRIPTION VENDOR CONFIRMATION b) Standard length 9 List of Deviations, if any.
C] Terminations for HT & LT Cables SR. NO. DESCRIPTION VENDOR CONFIRMATION 1 Make
2 Name of Manufacturer
3 Catalogues Attached?
4 Voltage Grade of HT & LT Cable Terminations
5 Type of Outdoor cable Glands
6 Type of Indoor cable Glands
7 List of Deviations, if any
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 4 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc D] MLDP, ELDP, YLDP, PDP, PDP FOR MOV, LDB, SELDB, PDB & Outdoor MOV PDB Note: Vendor shall submit guaranteed technical particulars separately for MLDP, ELDP, YLDP, PDP, PDP FOR MOV, LDB, SELDB, PDB & outdoor MOV PDB Sr. No Description To be filled in by Vendor A) GENERAL 1) Manufacturer 2) Country of Manufacture
3) Applicable codes & standards
4) Type test certificate furnished 5) List of Routine test offered
B) CONSTRUCTION 1) Enclosure material 2) Type 3) Thickness of sheet metal mm 4) Degree of Protection 5) Paint Shade 6) Cable entry (Incoming & Outgoing) 7) Material & thickness of gland plates mm
8) Overall Dimension of DB ( L x B x H) mm
C) BUSBARS 1) Rated continuous current kA 2) Short circuit rating [1 sec] kA 3) Main Busbar location 4) Busbar material 5) Clearances Ph/Ph, Ph/n & Ph/earth mm 6) Ground Bus Size mm
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 5 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Sr. No Description To be filled in by Vendor D) MCCB/MCB/ELCB
1) Make 2) Type & Service 3) Voltage, frequency & poles 4) Rated current A 5) Short circuit rating kA 6) Sym. interrupting capacity kA 7) Total interrupting time ms 8) Making current (Peak) kA 9) Operating mechanism
E) SWITCHES 1) Make 2) Type 3) Duty 4) Rating A 5) Interlocking with Door + Defect Interlocking facility
6) Shrouding of Incoming Terminal 7) Rotary / Link Type 8) Single Break / Double Break
F) FUSES 1) Make 2) Type 3) Rupturing Capacity 4) Rating A VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 6 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Sr. No Description To be filled in by Vendor 5) Control Fuse Make G) CURRENT TRANSFORMER 1) Make 2) Type & services 3) Voltage & frequency 4) Ratio 5) Rated VA burden 6) Accuracy class 7) Short circuit current rating for 1 sec. 8) Class of Insulation 9) Terminals type
H) INDICATING INSTRUMENTS 1) Make 2) Size 3) Type 4) Range for Incoming & Outgoing
I) WIRING 1) Size 2) Insulation 3) Voltage class
J) EARTHING 1) Earth Bus Size 2) Material 3) Location VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 7 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Sr. No Description To be filled in by Vendor 4) Provision for Connection to Grid K) LIGHTING TRANSFORMER 1) Manufacturer 4) Rating (at nominal, maximum & minimum tap)
5) Cooling Method 6) Transformation Ratio (at principal tap) 7) Vector Group 8) Voltage rating of windings 9) Impedance Voltage (at 75C and continuous max. rating)
10) Efficiency (at rated power and 0.8 pf) 11) Regulation (at rated power and 0.8 pf) 12) Tap changer a) Tap Details b) On HV or LV winding c) No. of steps (including principal tap) d) Range e) Size of each tap %
E] LT Capacitor & APFC Panel Note: Vendor shall submit guaranteed technical particulars separately for each APFC Panel. Sr No Description To be filled in by Vendor A) GENERAL 1) Manufacturer 2) Country of Manufacture VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 8 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Sr No Description To be filled in by Vendor 3) Applicable codes & standards 4) Type test certificate furnished 5) List of Routine test offered 6) Documents as per Cl-7 of Doc. No.254625-300-RQ-ELE-003 furnished?
B) ENCLOSURE
1) Enclosure material
2) Type & Execution 3) Thickness of sheet metal mm 4) Degree of Protection 5) Paint Shade Inside Outside
7) Cable entry (Incoming & Outgoing) 8) Material & thickness of gland plates mm
9) Mounting height of components Minimum Maximum mm
10) Overall dimension of APFC Panel ( L x B x H) mm 13) Panel Heat Load for HVAC Watts
C) BUSBARS 1) Rated continuous current kA 2) Short circuit rating [1 sec] kA 3) Main Busbar location VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 9 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Sr No Description To be filled in by Vendor 4) Busbar material 5) Clearances Ph/Ph, Ph/n & Ph/earth 6) Ground Bus Size mm
D) CAPACITORS 1) Make and type 2) Reference standard 3) Inrush current 4) Voltage rating 5) Over voltage limit 6) Over Current limit 7) Capacitance tolerance 8) Insulation Level. 9) Dielectric material 10) Impregnation 11) Dielectric losses 12) Degree of protection 13) Service life 14) Safety features provided 15) Discharge resistors 16) Maximum permissible transient peak current
17) Dissipation factor tan at 20 C 18) Time constant at 20 C , relative humidity 65 % (minimum value)
19) Cooling 20) Mounting position 21) Type of terminal used VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 10 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Sr No Description To be filled in by Vendor
E) APFC RELAY 1) Make 2) Type 3) Control voltage V 4) Location 5) Power Factor Setting Range 6) Auto/Manual Selector Switch Provided? Yes/No 7) Push Button Provided? Yes/No 8) Time Delay 9) List of Controller Features as per Specification
F) AIR CIRCUIT BREAKER 1) Make 2) Type 3) Voltage, frequency & poles 4) Rated current A 5) Short circuit rating kA 6) Sym. interrupting capacity kA 7) Total interrupting time ms 8) Making current (Peak) kA 9) Power Frequency Withstand Voltage kV 10) Lightning Impulse Withstand Voltage kV 11) Anti pumping feature provided 12) Trip-free feature VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 11 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Sr No Description To be filled in by Vendor 13) Provision for pad locking facility in the OFF position
14) No. of auxiliary contacts for owners use 15) Spring charging motor rating at 110V DC VA 16) Time required to charge spring from fully discharged condition ms 17) Control Supply voltage V 18) Maximum tripping coil consumption /ACB VA 19) Maximum closing coil consumption /ACB VA
G) MCCB 1) Make 2) Voltage, frequency & poles 3) Rated current A 4) Short circuit rating kA 5) Sym. interrupting capacity kA 6) Total interrupting time ms 7) Making current (Peak) kA 8) Operating mechanism 9) Trip - free feature 10) Provision for pad locking facility in the OFF position
11) No. of auxiliary contacts for owners use
H) CONTACTORS 1) Make 2) Type 3) Service 4) Rating A VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 12 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Sr No Description To be filled in by Vendor 5) Duty
I) CURRENT TRANSFORMER 1) Make 2) Type & services 3) Voltage & frequency 4) Ratio 5) Rated burden VA 6) Accuracy class 7) Short circuit current rating kA 8) Class of Insulation 9) Shorting link for secondary 8) Class of Insulation
J) INDICATING INSTRUMENTS [To be filled for each type of instruments] 1) Make 2) Size 3) Type 4) Range for Incoming & Outgoing 5) Burden VA
K) WIRING 1) Insulation 2) Voltage class V 3) Size & Colour code Power Circuits Control circuits
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 13 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc Sr No Description To be filled in by Vendor
L) EARTHING 1) Earth Bus Size 2) Material 3) Location 4) Provision for Connection to Grid
F] Local Control Station Note: Vendor shall submit guaranteed technical particulars separately for Flame proof Type Local Control Station
SR. NO. DESCRIPTION VENDOR CONFIRMATION A MANUFACTURER
B CONSTRUCTION
1 Type of Enclosure
2 Enclosure Material
3 Degree of Protection
4 Canopy Provided
5 Paint Shade
6 Provision of Local / Remote Switch 7 Provision of Ammeter & Size
C WIRING
1 Size of Wire used
2 Voltage Class
3 Insulation Type
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 14 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc
G] Light Fittings Note: Vendor shall submit guaranteed technical particulars separately for Flame proof Type Light Fittings SR. NO. DESCRIPTION VENDOR CONFIRMATION 1 Make & Manufacturers Name 2 Catalogues attached? 3 Light Fixtures
a) Type as per Schedule of Quantity? (yes/No)
b) Body Material c) Degree of Protection provided d) Gaskets Material e) Earthing Terminal f) No. of cable Entry g) Paint Finish h) Power factor 4 Features Provided for Lamp, Starter, Ballasts, Lamp/Starter Holder as per specified in 254625-300-SP- ELE-008/009
5 Reflectors a) Material
b) Thickness
c) Provision for improving the performance
6 List of Deviations, if any 7 List of test to be performed
8 List of Spares, if any
9 G.A.Drawing for all type of Light fittings with Dimensions
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 15 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc SR. NO. DESCRIPTION VENDOR CONFIRMATION 2 Name of Manufacturer
3 Applicable Technical Standards for Switch & Socket
4 Catalogues Attached?
5 Degree o Protection
6 Type of Switch
7 Type of Receptacles
8 List of Deviations, if any
9 List of Spares, if any
I] Junction Box SR. NO. DESCRIPTION VENDOR CONFIRMATION 1 Make
2 Name of Manufacturer
3 Catalogues Attached?
4 Degree of Protection
5 Material of Enclosure
6 Canopy Provided
7 No. of Earthing Terminals
8 Weight Kgs
9 Overall Dimensions (H x L x W)mm
10 20% Spare Terminals provided?
11 Paint Finish
12 List of Test to be performed
13 List of Spares, if any.
14 Identification of wires
J] Lighting Poles SR. NO. DESCRIPTION VENDOR CONFIRMATION 1.0 Manufacturers Name
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 16 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc SR. NO. DESCRIPTION VENDOR CONFIRMATION 2.0 Make
3.0 Applicable standards
4.0 Material of Construction
5.0 Paint Shade
6.0 Wind Velocity
7.0 No. of Earthing Terminals
8.0 Weight Kgs
K] MISCELLANEOUS EQUIPMENT
SR. NO. DESCRIPTION VENDOR CONFIRMATION 1 Protective Rubber Mat a) Size mm b) Voltage Grade kV c) Qty. Mtr. 2 Danger Boards a) Size mm b) Material & Painted with c) Qty. Nos.
3 Hand Gloves a) Material b) Voltage Grade kV c) Qty. Nos. 4 Gravels a) Size of gravels mm b) Area Covered with Gravels 5 Shock Treatment Chart a) Size mm b) Material & Painted with c) Qty. Nos. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-DS-ELE-008 Rev: B Page 17 of 17
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-DS-ELE-008.doc SR. NO. DESCRIPTION VENDOR CONFIRMATION 6 Cable Markers a) Engravation on top of Cable Markers b) Material c) Size mm 7 Exhaust Fans a) Size mm b) Qty. Nos. 8 Fire Extinguisher a) Type b) Capacity Kg c) Working Pressure Kg/Cm 2
d) Qty. Nos. 9 Canopy a) Material b) Qty. Nos. 10 List of Additional Equipment
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 20 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc
Appendix-E: Specification for Electrical Equipment to be supplied by Contractor
[Refer Doc. No. 254625-300-SP-ELE-008 (Pages 1 to 26)]
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 1 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
SPECIFICATION FOR ELECTRICAL EQUIPMENT TO BE SUPPLIED BY CONTRACTOR
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 2 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
List of Content Page No 1 Scope 4 2 Equipment Specification 4 2.1 H.V. & L.V. Cables & Accessories 4 2.1.1 General Construction 4 2.1.2 Cable Accessories 6 2.1.3 Cable Glands 6 2.1.4 Cable Lugs 6 2.2 Busduct 6 2.2.1 Construction 6 2.2.2 Busbars 7 2.2.3 Busbar Supports 7 2.2.4 Space Heater 8 2.2.5 Earth Bus 8 2.2.6 Termination at the ends of Busduct 8 2.2.7 Special Chambers 8 2.2.8 Marking for Reassembly 8 2.3 L.T. Capacitor & APFC Panel 8 2.3.1 Constructional Features 8 2.3.2 Components 11 2.4 Power Distribution Panel & Lighting Distribution Panel with Energy Saver Feature 14 2.4.1 Constructional Features 14 2.4.2 Components 15 2.5 Energy Saver Feature in Lighting Distribution Board 16 2.6 Power Distribution Panel for MOVs 17 2.6.1 Constructional Features 17 2.6.2 Components 17 2.7 Outdoor MOV Power Distribution Board 17 2.8 Cable Trays 18 2.9 Flameproof & Industrial type Control Stations 18 2.9.1 Construction 18 2.9.2 Component Specification 19 2.10 Flameproof & Industrial Lighting and Power Panels 19 2.10.1 Construction 19 2.10.2 Component Specification 20 2.11 Flameproof and Industrial Light Fixtures & Junction Boxes 20 2.11.1 Construction 20 2.11.2 Lighting Fixtures 21 2.11.3 Control Gear Box (Integral Light Fitting) 21 2.11.4 Junction Boxes 22 2.11.5 Lighting Poles 22 VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 3 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
2.12 Earthing 22 2.13 Flameproof & Industrial type plugs & Sockets 23 2.13.1 Construction 23 2.13.2 Component Specification 24 3 Makes of Components 24 4 Nameplate 24 5 Inspection, Testing and Acceptance 25 6 Packing and Despatch 25 6.1 Packing and Despatch of cable drums 25
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 4 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
1 Scope 1.1 This specification covers the requirements of design, manufacture, painting, inspection & testing at manufacturers works and delivery to site inclusive of packing and transportation and commissioning at site of all electrical equipments covered in clause 2.0 Equipment Specification. 1.2 This specification shall be read in conjunction with Specification for Electrical Installation Tender (Doc. No. 254625-300-RQ-ELE-003). 1.3 The equipment offered shall be complete in all respects. Any material or accessories, which may not have been specifically mentioned in the specifications but which are usually necessary for satisfactory, safe, trouble free, operation shall be provided without any extra charges. 1.4 It is not the intent to specify completely herein, all details of design and construction of the equipment. However the equipment shall conform in all respects to high standards of engineering, design and workmanship and shall be capable of performing in continuous operation in a manner acceptable to the Owner/Consultant who will interpret the meaning of drawings and specifications and shall have the power to reject any work or materials which, as per his judgment are not in full accordance with requirement. 1.5 Vendor shall ensure the quality of workmanship for manufacture of equipment. The equipment shall be supplied as per the latest applicable standards and as stipulated in this specification. 1.6 Quantity shall be worked out by vendor based on attached drawings. The vendor shall make his own estimate of quantities for all items, such as equipment, power & control cabling system, lighting system, earthing system, auxiliary power distribution, civil works, etc.
2 Equipment Specification 2.1 H.V. & L.V. Cables & Accessories 2.1.1 General Construction The cables shall be suitable for laying in trays, trenches, ducts, pipe sleeves and conduits and for underground-buried installation with uncontrolled backfill and possibility of flooding by water and chemicals. Outer sheath of all PVC and XLPE cables shall be black in colour and the minimum value of oxygen index shall be 29 at 27 + 2 C. In addition suitable chemicals shall be added into the PVC compound of the outer sheath to protect the cable against rodent and termite attack. All cables covered in this specification shall be flame retardant low smoke (FRLS). Sequential marking of the length of the cable in metres shall be provided on the outer sheath at every one metre. The embossing /engraving shall be legible and indelible. The overall diameter of the cables shall be strictly as per the values declared by the manufacturer in the technical information subject to a maximum tolerance of 2 mm up to overall diameter of 60mm and 3mm for beyond 60mm.
2.1.1.1 PVC Control Cables All control cables for use on low voltage systems shall be 650/1100 V grade with copper conductor, PVC insulated with extruded PVC inner sheathed and extruded FRLS PVC outer sheathed as per IS-1554 (Part-I) unless specified otherwise. The core insulation shall be with PVC compound applied over the conductor by extrusion and shall conform to the requirements of type 'A' compound as per IS: 5831. The thickness of insulation and the tolerance on thickness of insulation shall be as per Table 2 of IS: 1554 (Part- 1). Control cables having 6 cores and above shall be identified with prominent and indelible VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 5 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
numerals on the outer surface of the insulation. Colour of the numbers shall contrast with the colour of insulation with a spacing of maximum 50 mm between two consecutive numbers. Colour coding for cables up to 5 cores shall be as per Indian standard. The inner sheath shall be applied over the laid-up cores by extrusion and shall be of PVC conforming to the requirements of Type ST-1 PVC compound as per IS: 5831. The minimum thickness of inner sheath shall be as per IS: 1554 (Part-1). Single core cables shall have no inner sheath. The outer sheath for the cables shall be applied by extrusion and shall be of PVC compound conforming to the requirements of type ST-1 compound as per IS: 5831. The minimum and average thickness of outer sheath for unarmoured cables and minimum thickness of outer sheath for armoured cables shall be as per IS: 1554 (Part -1).
2.1.1.2 XLPE Power Cables 33 kV Power Cables : 33kV (E) grade, Stranded Aluminium conductor, Screened, XLPE insulated, Galvanised steel strip Armoured, Extruded FRLS PVC outer sheathed generally confirming to IS 7098 Part-2 1985. L.V. Power Cables : 1.1kV grade, XLPE insulated, multi stranded conductor, single/multi core, steel strip/wire armoured, Extruded PVC inner sheathed & Extruded FRLS PVC outer sheathed confirming to IS 7098 (Part-1). The conductors shall be stranded and compacted circular for all cables. All 33 kV cables shall be provided with both conductor screening and insulation screening. The conductors shall be provided with non-metallic extruded semi conducting screen. The core insulation shall be with cross linked polyethylene insulating compound dry cured, applied by extrusion. It shall be free from voids and shall withstand all mechanical and thermal stresses under steady state and transient operating conditions. It shall conform to the properties given in Table-1 of IS: 7098 (Part -2). The insulation screen shall consist of non-metallic extruded semi-conducting compound in combination with a non-magnetic metallic copper screen. Unless specified otherwise, the copper screen for all the three cores together shall be capable of carrying the single line to ground fault current value and the duration specified in the data sheet. The conductor screen, XLPE insulation and insulation screen shall all be extruded in one operation by 'Triple Extrusion' process to ensure perfect bonding between the layers. The core identification shall be by coloured strips or by printed numerals. The inner sheath shall be applied over the laid up cores by extrusion and shall conform to the requirements of type ST 2 compound of IS: 5831. The extruded inner sheath shall be of uniform thickness. In case of single core cables, there shall be extruded inner sheath between insulation metallic screen and armouring. For multicore cables, the armouring shall be by galvanized steel strips as per method (b) of IS- 7098 (Part-2). If armouring is specified for single core cables in the data sheet, the same shall be with H4 grade hard drawn aluminium round wire of 2.5 mm diameter. The outer sheath of the cables shall be applied by extrusion over the armouring and shall be of PVC compound conforming to the requirements of Type ST 2 compound of IS: 5831. The minimum and average thickness of outer sheath for unarmoured cables and minimum thickness of outer sheath for armoured cables shall be as per IS: 7098 (Part-2) The thickness of the insulation, inner sheath shall be governed by values given in IS: 7098 (Part -2).
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 6 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
2.1.2 Cable Accessories The termination and straight through jointing kits for use on the systems shall be suitable for the type of cables offered as per this specification. The accessories shall be supplied in kit form. Each component of the kit shall carry the manufacturer's mark of origin. The kit shall include all stress grading, insulating and sealing materials apart from conductor fittings and consumable items .An installation instruction sheet shall also be included in each kit. The contents of the accessories kit including all consumable shall be suitable for storage without deterioration at a temperature of 45 C, with shelf life extending to more than 5 years.
2.1.2.1 Terminating kits Heat shrinkable terminating kits shall be suitable for termination of H.V. cables to an indoor switchgear or to a cable box of an outdoor mounted transformer. For outdoor terminations, weather shields / sealing ends and any other accessories required shall also form part of the kit. The terminating kits shall be from one of the approved makes.
2.1.2.2 Jointing kits The straight through jointing kits shall be suitable for installation on overhead trays, trays in cable cellar, concrete lined trenches, and ducts and for underground burial with uncontrolled backfill and possibility of flooding by water and chemicals. These shall have protection against any mechanical damage and suitably designed to be protected against rodent and termite attack. The inner sheath similar to that provided for cables shall be provided as part of straight through joint. The jointing kits shall be from one of the approved makes.
2.1.3 Cable Glands Double compression type nickel plated brass cable glands shall be used. Rubber components used in cable gland shall be of neoprene. Cable glands shall be of weatherproof or flameproof as per area classification.
2.1.4 Cable Lugs Cable lugs shall be of tinned copper for copper cable and aluminium lugs for aluminium cable, crimping type & of reputed make.
2.2 Busduct 2.2.1 Construction The Busduct shall be of box frame construction of Sheet Steel enclosure suitably braced to withstand the maximum mechanical and electrodynamics forces. The Busduct enclosure shall be fabricated from 2 mm thick Sheet Steel. Eddy current heating, if applicable, shall be taken into account. The section of the Busduct shall be rectangle & non-phase segregated. The degree of protection shall be IP-55.The Busduct shall have fire barriers inside. The Busduct enclosure shall be suitable for indoor/outdoor installation as specified. The outdoor portion of Busduct shall be suitable for outdoor installation without any additional protection from owners end. However, rain hood shall be provided as an additional protection for outdoor installation. Canopy and proper fixing arrangements shall be provided for the same.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 7 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
The Busduct shall be provided with removable top covers fitted with gaskets secured by sufficient number of nuts, bolts to ensure that these covers are dustproof. All joints and covers shall be provided with non-deteriorating type gaskets of neoprene between joints. These covers shall be of suitable length for ease of removal and shall be arranged to give complete accessibility to the busbars, joints, bends and supports, etc. The entire busduct shall be dust and vermin proof. Louvers shall not be provided. The design of Busduct enclosure shall be such that it will withstand the operating conditions arising out of the following : a. Normal operating conditions b. Momentary short circuit currents c. Rigours of adverse weather conditions, and d. Combinations of above. The busduct shall be provided with flanged ends to connect the busduct to transformer at one end and switchgear at other end. These flanges shall match with corresponding flanges in the equipment to which these are connected. Vendor shall provide suitable flexible termination arrangement at 415V switchgear and transformer ends. The busduct shall be supplied complete with all the hardware necessary for making the terminations. Proper wall sealing arrangements shall be provided at the wall where bus duct enters the substation building. Busduct with wall mounting flange will be acceptable for the sealing arrangement. The enclosure shall be provided with suitable mounting lugs at suitable interval. The mounting lugs shall be suitable for hanger type supports. Vendor shall design and indicate the supporting arrangement for busduct. Under Normal operating conditions, the surface temperature of the enclosure shall not exceed 70C.
2.2.2 Busbars The busbars shall be of electrical grade Aluminium flats adequately sized to carry maximum specified continuous current & short circuit current for 1sec, at maximum site temperature specified. The final temperature of busbars and connectors at joints between connector and busbar should not exceed 75C when carrying rated currents. Also the final busbar temperature shall not exceed 250C when specified short circuit current for 1sec duration flows through. Current density of Busbars shall be 0.8 Amp/mm2 max. All busbars shall be insulated with heat shrinkable PVC sleeves. All busbars shall be colour coded such that on removal of any inspection cover the phases shall be identifiable. Wherever required for long run of busduct, expansion joints with flexible strips shall be provided to allow for expansion and contraction due to temperature variations arising out of normal continuous current flow and short circuit current flow for specified duration. Minimum one expansion joint shall be provided for each 3000 mm long straight length of busduct. In case this is not provided, Vendor shall substantiate the same with Calculations.
2.2.3 Busbar Supports The busbars shall be supported by non-deteriorating type (non-hygroscopic, non-carbonising, Corrosion resistance) Solid core resin cast epoxy insulators of requisite electrical / mechanical strength. The insulators shall be 1.1 KV grade for 415V system. The mechanical strength shall VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 8 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
be sufficient to withstand forces arising out of peak short circuit current. Each shipping section shall meet this requirement separately. Adequate Creepage distance shall be available on insulator to operate under high humid conditions and effects of condensed moisture due to variations in temperature within busduct due to different conditions of loading. Minimum number of skirts shall be 3 on each insulator. The spacing of the insulating supports shall be decided on the basis of the fault withstand capacity.
2.2.4 Space Heater Busduct shall be provided with anti-condensation space heaters with controlling thermostats of adequate capacity to maintain internal temperature above dew point to prevent moisture condensation in busduct. Space heaters shall be rated for 240V, single phase, 50 Hz AC supply. Space heater shall be provided on both sides of the fire barrier.
2.2.5 Earth Bus Two earth bus of 50 mm x 8 mm aluminium shall run on the external side of the busduct through the whole length of the busduct and shall be positively connected to the body of the busduct enclosure. At both ends of the earth bus provision shall be made to connect it to main earthing system.
2.2.6 Termination at the ends of Busduct The busduct shall be provided with flexible at both ends for connecting it with transformer at one end and 415V switchgear at other end. The Flexibles shall be made of thin copper strips. The ends of the flexible shall be clamped by copper plate. The ends of flexible shall be tin plated.
2.2.7 Special Chambers To match the phase sequence of the two equipments connected by busduct, a suitable phase cross over chamber shall be provided; if required, at suitable location. This chamber shall generally be located in transformer yard.
2.2.8 Marking for Reassembly All busduct parts like enclosure, adaptor box, rain hoods, enclosure covers, supports, busbar and busbar fish plates shall be identified distinctly by clear numbers. These shall be indicated in drawing.
2.3 L.T. Capacitor & APFC Panel 2.3.1 Constructional Features The APFC Panels shall be totally enclosed, dust and vermin proof, free standing of uniform height, cubicle multi-tier compartmentalised floor mounting type. The construction shall be such that extension on the either side shall be possible. The busbars, incoming and outgoing feeders compartment and capacitor storage space shall be fabricated from cold rolled sheet steel panel of 2mm thickness. Removable type undrilled gland plates shall be provided at bottom of the panel. Stiffeners shall be provided wherever necessary. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 9 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
APFC Panels shall be provided with integral baseframe which shall be bolted/welded on the cross members provided by owner. Amply dimensioned oblong holes shall be provided on the base frame. The baseframe shall be of standard sections, re-rolled sections will not be acceptable. Vendor shall give baseframe details in foundation drawing. Cross members or foundation on which baseframe is mounted is excluded from Vendors Scope of supply. The APFC Panels shall be properly ventilated by louvers and covered inside with wire mesh.All cable entries shall be from the Bottom for both incoming and outgoing cables. Terminals shall be located sufficiently away from gland plate to facilitate easy connection. The construction of APFC Panel shall conform to a degree of protection to IP-42. All doors, removable covers, gland plates and joints between adjacent sections shall be gasketed all round with neoprene gaskets. Lifting facility shall be provided for each shipping section. The live side of isolating switches must be fully insulated or shrouded. All main isolating devices shall have provision for padlocking in the "OFF" position only and shall be interlocked with door. Each outgoing feeder shall be fixed type with the power switchgear & capacitors in the front side. Rear access is not possible. The capacitor units shall be integral with the control panel unit complete with internal wiring. Each capacitor feeder shall be provided with quick-make, quick- break capacitor duty MCCB & contactor, "ON" and OFF indicating lamps, ammeter + ASS and terminal blocks. Each compartment door shall be interlocked with switch. The feeder compartment doors & cable alley doors shall be of lift-off type with hinges on one side and turn lock on other side, which will ensure tight closing of the doors, making the compartment effectively dust-proof. Care shall be taken while providing gaskets at hinged points. The size and layout of feeder compartments, busbars and cable alleys shall be such as to enable easy maintenance of the equipment mounted inside. The mounting height of all components on panel door shall be between 300 to 1800 mm from floor. The Vendor shall ensure that temperature within the cubicle is within acceptable limits and that the heat from Capacitor Bank does not get transferred to the Switchgear Assembly. The Vendor may consider using ventilation fans for effective heat removal. Space heater for each cubicle / vertical panel shall be located at the bottom of the panel and shall be controlled through a thermostat with an adjustable setting and a manually operated switch. Panels shall have fluorescent light fittings for internal illumination with door switch.
2.3.1.1 Busbars The busbar shall be made out of high conductivity electrolytic grade aluminium with adequate cross section to carry continuous current. The busbars shall be insulated with colour coded heat shrinkable PVC sleeves and supported by non-hygroscopic material insulators with anti-tracking arrangements. Liberal clearance and Creepage distances shall be provided for the busbar system to minimize the possibility of faults. The busbar system shall be designed for fault level & maximum operating temp mentioned in Electrical System Data. The horizontal and vertical busbar compartment in Panel shall be totally segregated from rest of the compartments and rendered totally inaccessible under normal circumstances. No equipment shall be mounted on busbar chambers. All busbar compartments shall be provided with bolted type gasketed covers. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 10 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
Inter Panel Metal barriers of full height and width shall be provided between the bus compartment and the out-going cable compartment.
2.3.1.2 Earthing Horizontal earth bus bar located at the bottom shall be provided from end-to-end of the assembly. Earth bus joints shall be solidly bolted. The earth bus shall be connected to the plant- grounding grid at each end of APFC panel. Two numbers external earth terminal shall be provided to adopt system earth conductor All non-current carrying metal parts of APFC panel shall be effectively connected to the earth bus bar. All metal doors and removable barriers shall be bonded to the rigid part of structure by stranded insulated copper wires of 2.5 sq. mm minimum through earthing stabs. The earth bus shall be connected at each end of APFC panel by accessible removable link.
2.3.1.3 Wiring & Terminations Internal Power wiring shall be means of tinned copper strips with colour code at regular intervals. All internal control wiring shall be with stranded conductor insulated copper wires of 2.5 sq. mm, 600 V / 1 kV grade & PVC insulated. Stranded conductors shall be terminated by means of tinned copper lugs. Conductor shall run without splices from terminal to terminal. Sufficient space and supports shall be provided in the enclosure for field cable routing to the terminals. Incoming & Outgoing power terminals shall be bolted type. They shall be a minimum 50 mm wide to provide proper bolt and washer application. Size of hole shall match size of cable lugs. The power and control devices shall be furnished with finger-safe terminals. Terminals shall be rated for 600 V A.C. Control terminals shall be screw compression type. Each wire shall be marked with the wire number & All terminal blocks shall be furnished with white marking strips marked with terminal numbers in accordance with the wiring diagrams. The terminal blocks shall be furnished with minimum 20% spare control terminals. Colour Coding for internal panel wiring shall be as follows: Power Wires : Red, Yellow, Blue for Phases. AC Control Circuits : Red DC Control circuits Positive : Blue Negative : Blue with white strip Neutral Wires : Black. Ground Wires : Yellow & Green Interlock control circuits wired from an external power source : Yellow
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 11 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
2.3.2 Components 2.3.2.1 Power Factor Correction Capacitors: Heavy-duty Film + Foil dielectric capacitors shall be used for the power factor correction. The capacitors shall be designed to handle over voltages and over currents without reducing capacitor life. The Capacitors shall be dry type, hermetically sealed, constructed of All polypropylene two layer film + foil dielectric with self-healing metallised electrodes. The capacitor cells shall be impregnated with biodegradable, non-PCB impregnant. Each capacitor shall be equipped with a Pressure Sensitive Interrupter, for protecting the capacitor cell from rupturing. The individual capacitor element shall have current limiting fuses 600 Volts, with wire internal and blown fuse indicator shall be provided in each phase of each capacitor bank/ step. The fuses shall provide protection against short circuit currents. The capacitor units shall be provided with discharge resistors to reduce the residual voltage to 50V or less within 60 seconds of switching- off. The capacitor shall be rated at 415V. The capacitor shall be suitable for + 10% over voltage. The container of the capacitor shall be of high quality sheet steel with minimum joints and suitable for mounting on a base channel. All mating surfaces shall be provided with neoprene gaskets to render the enclosure dust / vermin proof. Each 3 phase Capacitor unit shall be formed from basic units of 25/50 kVAr, by connecting suitable nos. in series or parallel. The Capacitor Bank shall be robust in construction, maintain rated output for at least 7 - 8 years and shall have tropicalised design. The container of the capacitor shall be of high quality sheet steel with minimum joints and suitable for mounting on a base channel. The capacitor banks formed from individual units shall have sheet steel cable box complete with copper links suitable to receive PVC insulated PVC sheathed, copper conductor, un-armoured cables. Each Capacitor Bank shall be provided with 2 nos. external earth terminals each complete with 2 plain and 1 spring washers. This Earthing bolt shall be connected to body earth. The connection from active elements of the capacitor to the terminal box shall be through studs fixed to cover properly sealed to make the capacitor unit hermetically sealed. The active elements shall be mixed dielectric type or All Polypropylene. Each Capacitor Bank shall be fitted with Perspex nameplate.
2.3.2.2 Automatic power factor controller relay The controller shall be microprocessor based (with adjustable control), having auto / manual control selection mounted on the front of the panel with indication having minimum 16 steps. The control circuit shall sense the power factor, KVAR of the connected power system and based on the desired power factor selected from the front of the panel, it shall close / open the output relay contacts with a definite time lag to switch ON & OFF the required capacitor banks. The controller shall tap the reference voltage from the incoming voltage 3 phase, 4- wire supply. Reference current signal shall be sensed from current transformer with 5A secondary connected in middle phase mounted in the Low Voltage Switchgear (supplied by others). The controller shall have a setting range for target power factor from 0.80 inductive to unity. To avoid 'hunting', minimum set KVAR selection shall be available on the front of the panel. An auto/manual selector switch shall be provided on the controller for control of capacitor banks VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 12 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
with the set ranges of target power factor and % KVAR, in auto mode and without these ranges in manual mode. Push buttons shall be provided on the controller to switch ON & OFF the capacitor banks in manual mode. The Controller shall be programmed for setting the timing sequence to take care of the discharge time of the capacitor. The switching sequence shall be such, as to permit utilization of all the capacitor banks, thereby increasing the operational life of the capacitors. The power factor controller relay unit shall comply with the following standard features: - a. Digital display of operating conditions viz., capacitor step sizes, number of switching operations per step, defective capacitor step, etc., b. Digital display of system parameters viz., active, reactive, and apparent power, power factor, voltage, current, thermal current load, harmonics, load flow direction etc., c. The controller shall have protection against over voltage and current path reversed connection. d. Manual/Automatic selector switch for selecting the controller mode of operation. e. Variable switching programmes viz., fully automatic, conventional and manual operation. f. Monitoring of out of limit conditions with visual alarm viz., over and under compensation, power loss of capacitors, current overload, harmonic overload etc., g. Adjustable switching ON or OFF time delay from 10 to 60 seconds. h. Fault output relay for signalling of target power factor is not reached. i. Automatic rotational switching program to ensure that the steps are used equally. j. A voltage transformer (control transformer) shall be provided within APFC enclosure for control power. k. RS485 Interface port for data transmission l. Fault signaling contact for control alarm.
2.3.2.3 Air circuit breaker Incomers of the APFC Panel shall be provided with ACB for incomer rating 2000Amp. Air circuit breakers shall confirm to the following requirements:- Short Circuit breaking capacity (Ics) shall be minimum 50 kA RMS Symmetrical at 415 Volts. Also, the Short Circuit Withstand capacity shall be 50 kA minimum, for 1 sec at 415 Volts. The air circuit breaker shall be manually and electrically operated, fixed type equipped with motor wound spring charged closing & trip mechanism. The spring charging motor shall be suitable for 110 V, DC supply. Means shall be provided for slow closing and opening of the breaker for maintenance purpose and for manual charging and closing of electrically operated breakers during emergencies. Following safety features and accessories shall be provided in the breaker:- It shall not be possible to open the compartment door when the circuit breaker is ON. Heavy duty self-aligning earth contact. Anti pumping circuit shall be provided such that the breaker shall not reclose after tripping even though a close signal may be continuously present. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 13 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
Position (TRIP-NEUTRAL-CLOSE) Selector Switch with spring return from Trip/Close to Neutral. The CB shall be provided with microprocessor based direct acting protection releases for overload, short circuit, earth fault & Under-voltage. The releases shall be adjustable type. The Circuit Breaker shall be provided with mechanical ON/OFF, TRIP and SPRING CHARGED, DISCHARGED indication, T/N/C control switch, mechanical trip push button, mechanical close' push button, and padlocking facility.
2.3.2.4 Moulded Case Circuit Breaker (MCCB) All the outgoing feeders shall be equipped with MCCBs. MCCB shall be equipped with adjustable instantaneous magnetic trip element. The Short Circuit Breaking capacity (Ics) shall be minimum 50 kA RMS Symmetrical at 415Volts. Also, the Short Circuit Withstand capacity shall be 50 kA minimum, for 1 sec at 415 Volts. MCCB shall be designed for application in individual Capacitor bank circuit. They shall operate on the magnetic principle with a current sensing element in each pole to provide short circuit protection. MCCB shall be triple pole manually operated with handle. A padlocking facility shall be provided to lock the unit MCCB operating handle in the OFF position. MCCB operating mechanism shall be quick-make, quick-break and trip-free. Trip free mechanism shall be independent of manual operation.
2.3.2.5 Power contactors All contactors shall be 3 pole air - break, magnetic, capacitor duty type. The rating of contactor shall be suitably assigned. The individual capacitor bank/step shall be switched using NEMA rating magnetic contactors suitable for switching capacitive currents. The minimum life expectancy of the contactor shall be one million switching operations. Each Power contactor shall have 2 NO and 2 NC auxiliary contacts wired upto terminal block for Purchaser's use.
2.3.2.6 Indicating & Measuring Instruments Indicating lamps shall be LED type. Voltage rating of the bulb shall match control circuit voltage. A suitable range of analog ammeter with selector switch and analog voltmeter with selector switch shall be provided for the incoming feeder.
2.3.2.7 Current transformer CT shall be epoxy moulded cast resin. Manufacturer shall check the saturation factor, ratio, and burden and accuracy class of CT before mounting them. Name plates shall be provided on each CT The terminals of CT shall be stud type. Loose leads of CT are not acceptable. The CTs shall withstand thermal and dynamic stresses due to max. short circuit current as specified. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 14 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
2.4 Power Distribution Panel & Lighting Distribution Panel with Energy Saver Feature 2.4.1 Constructional Features The general construction details of the board shall be subject to purchaser's approval and shall be in line with IS-8321 for Factory's Build Assemblies. The Power & Lighting Distribution Panels shall be fabricated from CRCA sheet steel of minimum thickness 2 mm. The load bearing members and the doors with large instruments shall be fabricated from suitably thicker sheets. Stiffeners shall be provided, wherever required. The individual panels of the distribution board shall be identical in depth and height and when bolted together shall give appearance of one continuous panel. The Panels shall be complete with the base frame of min. height of 75 mm.The cable entry of distribution boards shall be from bottom with removable undrilled gland plate. The Panels shall have totally segregated busbar chamber, cable alley and feeder compartment. Each feeder in the board shall be mounted in separate compartments. The compartment shall be totally segregated so that, in case of a fault in any feeder, the damage is restricted to that compartment only. The barriers shall be used to achieve compartmentalisation. The compartment doors shall be provided with concealed hinges and thumb screws with retaining washer. The spacing of thumb screws shall ensure proper compression of gasket. The compartment doors shall be interlocked with the switch of the feeder such that the door can be opened only when the switch is off. The cable alley shall be provided with hinged doors & shall be provided with arrangement for fixing cable clamps. The distribution board shall be suitable for extension on either side. The Distribution Board shall be single front & shall have front access only, both for maintenance and operation. The boards shall be suitable for placing against the wall. Gaskets shall be provided between all joints, beneath the door and gland plates to ensure effective dust and vermin proofing. The hardware used shall be high tensile strength steel with zinc passivation or chromium plated. A separate vertical section shall be provided for the main incoming power feeder. Adequate lifting lugs / hooks shall be provided for each shipping section. The horizontal and vertical busbar compartment in PDP & LDP shall be totally segregated from rest of the compartments and rendered totally inaccessible under normal circumstances. The busbar chamber shall be adequately sized and totally enclosed and at the same time maintaining the temperature rise of busbars within the permissible values as per relevant standards. Temperature rise of offered busbars shall be specifically stated in the offer by VENDOR. The busbar chamber shall be complete with bolted cover. No equipment shall be mounted on Busbar chamber. The Degree of Protection of LDP & PDP shall be IP-42 or better LDP shall be provided with lighting transformer to reduce fault level.
2.4.1.1 Wiring & Terminations All the equipments covered in this specification shall be supplied completely wired internally to components and terminal blocks and ready for purchasers external cable connections. The Incomer Terminals shall be suitable for termination of Aluminium armoured cables as indicated in SLD. If Incoming MCCB/MCB terminals are not adequate to receive the incoming cable size additional terminal shall be provided. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 15 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
The Terminal Block provided for connecting Outgoing Cables shall have terminals suitable for terminating the Aluminium armoured cables. The connection between feeders and the busbars shall be with links of adequate size in case of feeders above 63 amperes and with 650 V grade PVC insulated copper / aluminium conductor in case of feeders of rating below 63 ampere. Terminal blocks shall be rated 600 V. Terminals shall be permanently marked with white marking strips in accordance with the Wiring Diagram. The terminal blocks shall be furnished with minimum 10% spare terminals All cable terminations shall be via lugs. Tin-plated copper lugs suitable for aluminium conductors shall be provided for the main incoming power feeder. Fork type tin plated copper lugs shall be provided in the incoming line section for connecting the main grounding conductor.
2.4.1.2 Earthing The Distribution Board shall be provided with continuous earth busbar complete with 2 terminals for connecting the earth busbar to the system earthing grid. Separate earth A1.busbar shall be provided throughout inside the panel & shall be brought out at ends.
2.4.2 Components 2.4.2.1 Switches The switches shall be heavy duty, load break quick break complete with shrouding for incoming and outgoing terminals. The switches shall be complete with door interlocking mechanism wherever required in order to provide interlocking with the compartment door such that the door can be opened only when the switch is off. The switch handle shall have clear indication for the ON and OFF position of the switch.
2.4.2.2 Fuses The fuse shall be HRC type and shall conform to relevant Indian Standards. The fuses shall be link / diazed type. The fuse shall be provided with mechanism to indicate fuse blow off.
2.4.2.3 MCCB/ MCB/ ELCB MCCB / MCB shall be suitable for the fault level as achieved by Lighting Transformer. The MCCB's shall be complete with over-current and short circuit tripping types. MCCB shall be triple pole manually operated with handle. A padlocking facility shall be provided to lock the MCCB unit-operating handle in the OFF position. MCCB operating mechanism shall be quick-make, quick-break and trip-free. Trip free mechanism shall be independent of manual operation. ELCB shall be of reputed make.
2.4.2.4 Power contactors All contactors shall be air break, magnetic conforming to AC3 category of duty. All power contactors shall have a minimum of 2 NO + 2 NC auxiliary contacts. The auxiliary contractors shall have 4 No + 4 NC contacts. The spare contacts shall be wired up to the terminal block. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 16 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
2.4.2.5 Indicating & Measuring Instruments The indicating and measuring instrument such as voltmeter, ammeter, MFM meter shall be flush mounting type. The instruments shall be mounted on the compartment door and the mounting height shall be above 300 mm but below 1800 mm from the base of the switch board. The indicating lamps wherever provided shall be filament type complete with series resistance.
2.4.2.6 Current transformer CT shall be cast resin. They shall be mounted on a stationary part of switchgear. Manufacturer shall check the saturation factor, ratio, burden and accuracy class of CT before mounting them. Name plates shall be provided on each CT The terminals of CT shall be stud type. Loose leads of CT are not acceptable. The CTs shall withstand thermal and dynamic stresses due to max. short circuit current as specified.
2.4.2.7 Lighting Transformer The plant lighting system shall be fed by the lighting transformer. The lighting transformer shall be 415 / 415 V, three phase delta-star connected, dry type with OCTC, located inside the respective lighting distribution board. Lighting transformer shall be sized to take care of the total lighting load of the plant with a provision for 10% extra capacity and suitable impedance to reduce the short circuit withstand capacity. (Refer Single Line diagram for MLDP, EMLDP & Yard Lighting DP). Manufacturer shall submit lighting transformer calculation for approval.
2.4.2.8 Busbars The busbar shall be of high conductivity electrolytic grade aluminium with adequate cross section to carry continuous current with temperature rise limited to value specified in Indian Standard. The busbars shall be insulated with colour coded heat shrinkable PVC sleeves and supported by non-hygroscopic material insulators with anti-tracking arrangements. Liberal clearance and Creepage distances shall be provided for the busbar system to minimize the possibility of faults. The joints between busbar as well as between busbars and the links for outgoing connections shall be complete with spring washers. 2.5 Energy Saver Feature in Lighting Distribution Board Energy saver feature in LDP shall be with PLC based controller with software interface via RS- 232 and Ethernet, circuit breaker for short circuit & overload protection. The password protected software shall communicate with the controller to display current schedule and update or add any new programmes. Energy saver panel shall have LCD display with backlight, it shall display time/date and current preset level, power & energy used. It shall also have fully programmable daily/monthly/yearly calendar with holiday scheduler for controlling each outgoing circuit. It shall have auto start/shutdown facility with 0-30 minute ignition cycle. The facility operator shall be able to access locally or remotely by using the software & manage any of the elements listed below: Schedule or manually implement automatic energy reduction levels and on/off switching Participate in peak shaving/load shedding/utility energy requirements without disruption of work View power usage and energy consumption of each circuit VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 17 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
The size and layout of feeder compartments, busbars and cable alleys shall be such as to enable easy maintenance of the equipment mounted inside. Space heater for each cubicle / vertical panel shall be located at the bottom of the panel and shall be controlled through a thermostat with an adjustable setting and a manually operated switch. Panels shall have fluorescent light fittings for internal illumination with door switch. 2.6 Power Distribution Panel for MOVs 2.6.1 Constructional Features The Power Distribution Panel for MOVs shall be metal enclosed, compartmentalised, floor mounted, free standing, non-drawout type suitable for indoor installation with degree of protection IP-42. The panel shall be fabricated from CRCA sheet steel of minimum thickness 2 mm. The doors and covers shall be made of minimum 1.6 mm cold rolled sheet steel. All doors and covers shall be provided with neoprene gaskets. The panel shall be complete with the base frame of min. height of 75 mm. The cable entry of panel shall be from bottom with removable undrilled gland plate. The Panel shall be suitable for extension on either side. The panel shall be single front & shall have front access only, both for maintenance and operation. Adequate lifting lugs/ hooks shall be provided. The maximum height of the operating handle/ switches shall not exceed 1800 mm and the minimum height shall not be below 300 mm. All hardware shall be corrosion resistant. All joints and connections of panel members shall be made by cadmium plated high quality steel bolts, nuts and washers secured against loosening. 2.6.2 Components The two nos. of Incomer feeders shall be Four Pole MCCB of 200A rating. The incomer feeder shall have voltmeter with selector switch, ammeter with selector switch and 3 nos. pilot lamps for supply indication and Multi Function Meter. Mechanical interlock between the two nos. Incomers shall be provided such that any one feeder can be closed at any time. Necessary adequate Incoming terminals shall be provided to connect suitable size cable as recommended or as shown in SLD. Each outgoing circuit shall comprise of Triple pole MCCB of 63A rating with neutral isolating type bus-bar arrangement . All MCCBs shall be with time delayed O/C, S/C & E/F releases. The panel shall have 20% spare feeders, which will include minimum of one spare feeder of each rating. The panel shall be designed to ensure maximum safety during operation, inspection and maintenance. Necessary adequate out going terminals shall be provided to connect suitable size cable as recommended or as shown in SLD. The panel shall be provided with continuous earth busbar complete with 2 terminals for connecting the earth busbar to the system earthing grid.
2.7 Outdoor MOV Power Distribution Board The Outdoor MOV Power Distribution Board shall be metal enclosed, non-compartmentalised, floor mounted, free standing, non-drawout type suitable for outdoor installation with degree of protection IP-55.
The Incomer feeder shall be Triple Pole Neutral (TPN) MCCB of 63A rating with neutral isolating type bus-bar arrangement. The incomer feeder shall have voltmeter with selector switch, ammeter with selector switch and 3 nos. pilot lamps for supply indication. Each outgoing feeder shall comprise of 10A MCB with thermal overcurrent & magnetic short circuit releases & shall be of Motor Duty type. The MOV PDB shall be located in the field at strategic locations as VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 18 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
indicated in the Drawing attached in Appendix-I. The location indicated in the drawing is tentative only, the exact location shall be decided by vendor as per the site conditions.
2.8 Cable Trays 2.8.1 Cable trays shall be ladder type prefabricated hot dip galvanised sheet steel of thickness 2.5mm trays. 2.8.2 GI Coating thickness shall be of 75 micron. 2.8.3 Dimension details of cable trays shall be provided as per attached Drawing No. 254625-300- ELE-4801 in Appendix-I. 2.8.4 Outer most tier of all vertical cable trays shall be covered with GI sheet for protection against physical damage to cables. 2.8.5 Cable trays shall be covered by removable top covers on upper most tier allowing adequate ventilation in following cases where: Mechanical damage of cables is likely to occur during maintenance in the plant. Oil or spillage of chemicals can be expected. Protection from exposure to sun is required. 2.8.6 The cable trays shall be supplied in standard lengths of 3000 mm and clear width of trays shall be 150 (for perforated type trays), 300, 500, 700, 900 mm (for ladder type trays). 2.8.7 GI cover sheet shall allow adequate ventilation to the cables and shall be in standard length of 3000 mm, flanged on both sides for fixing on cable tray. Covers shall be complete with required GI hardware. 2.8.8 The adjacent cable trays shall be supported at every 2 to 2.5mtr depending on tray width. 2.8.9 Clamping arrangement shall be done on the length of cable trays at every interval of 1000 mm for horizontal trays & 300/500 mm for vertical trays.
2.9 Flameproof & Industrial type Control Stations 2.9.1 Construction Flameproof control station shall be made of cast light metal alloy and shall be free from frictional sparking hazard. The magnesium content in the alloy shall be as per IS-13346. Flameproof enclosure shall be suitable for zone 1 & 2, gas group IIA / IIB & temperature class T-3. The enclosures of the industrial control station shall be made of CRCA sheet steel (2 mm), dust & vermin proof and accessories suitable for installation in Industrial outdoor areas and shall have enclosure protection as per IP-55. The control stations shall be suitable for use in outdoor open locations and shall have IP-55 degree of protection. They shall preferably be provided with integral canopy. However, where the enclosure has been certified without integral canopy, a separate canopy can be accepted. The separate canopy shall be made of at least 14 SWG (2mm) galvanised sheet steel or FRP. The canopy shall be suitable for providing protection against rain from top and two sides. Unless otherwise specified all control stations shall be suitable for 240 V AC control supply. The control stations shall be provided with gaskets made of non-inflammable and self- extinguishing material. The enclosures shall be treated and prepared for painting with two coats of epoxy paint with final colour shade (both internal and external) as Silver grey No. 628 (IS-5) All accessories like nuts, bolts, washers etc. shall be made of stainless steel SS-304. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 19 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
The control stations shall be provided with two earthing studs with lugs on the external surface of the enclosures suitable for termination of 8 SWG GI wire. Each control station shall be provided with 2 nos. bottom cable entries and 1 no. flameproof nickel plated brass sealing plug. The control stations shall have external fixing lugs for mounting on wall or column. The holes provided on these lugs shall be of oblong type.
2.9.2 Component Specification Push buttons for START and STOP shall be of GREEN and RED colour respectively. Unless otherwise specified, each push button shall have one normally open and one normally closed contact. The STOP push button shall be mushroom type with stay put feature and lockable in pressed position. Selector switches shall have three/ four positions (Local, Off & Remote) for Local Control Station. Unless otherwise specified, all selector switches shall have minimum two poles for each position. Each position shall be indelibly marked on the control station. All ammeters shall be of moving iron type having an accuracy class of 3 and suitable for 1 Ampere CT secondary. Unless otherwise specified, min. size of ammeter shall either be 50 mm x 50 mm. 80% of the scale length shall cover 100% of the CT primary current uniformly and the balance 20% of the scale shall cover 100-600% of the CT primary. A red mark corresponding to the full load current of the motor shall be provided on the ammeter dial. The ammeter front glass shall be toughened (Type 'A' glass). All push button and control switch contacts shall be rated for min. 5 Amps at 240 V AC-15. Indicating lamp(s) wherever provided shall be clustered LED type (with minimum 3 nos. LEDs, preferably connected in parallel), mounted inside an enclosure of minimum diameter of 15mm.
2.10 Flameproof & Industrial Lighting and Power Panels 2.10.1 Construction The enclosures of the flameproof lighting and power panels shall be made of cast light metal alloy and shall be free from frictional sparking hazard. The magnesium content in the alloy shall be as per IS-13346. Flameproof enclosure shall be suitable for zone 1 & 2, gas group IIA / IIB & temperature class T-3. The enclosures of the industrial lighting & power panels shall be made of 2mm thick sheet steel and shall be dust & vermin proof. All metal surfaces shall be cleaned free of rust. The enclosures shall be sized to facilitate easy maintenance and heat dissipation. Panels shall be indoor / outdoor type as specified. Indoor type panels shall have IP-42 degree of protection and panels located in outdoor open locations shall have IP-55 degree of protection. The panels shall be suitable for surface or flush mounting on wall surface as specified. They shall preferably be provided with integral canopy. However, where the enclosure has been certified without integral canopy, a separate canopy can be accepted. The separate canopy shall be made of at least 2mm galvanised sheet steel or FRP. The canopy shall be suitable for providing protection against rain from top and two sides. The lighting and power panels shall be provided with gaskets made of non-inflammable and self- extinguishing material. The enclosures shall be treated and prepared for painting with two coats of epoxy paint with final colour shade (both internal and external) as Silver grey shade 628 (IS-5) All accessories like nuts, bolts, washers etc. shall be made of stainless steel SS-304. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 20 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
All the non-current carrying metallic parts of the panel shall be inherently bonded together. Each lighting and power panel shall be provided with two earthing studs with lugs on the exterior of the panel enclosure suitable for termination of 10 mm dia GI wire rope. Each outgoing feeder shall be provided with distinct terminals for phase, neutral and earth. The terminal block enclosures shall be adequately sized to properly terminate the cables by taking into account the required bending radii of cable cores and shall have the following minimum gland to terminal distances:
Conductor Size Up to 2.5 mm 2
Above 2.5 mm & Up to 10 mm 2
Above 10 mm 2 & Up to 35 mm 2
Above 35 mm & Up to 70 mm 2
Gland to terminal distance 40 mm 100 mm 150 mm 300 mm The panels shall be provided with suitably sized cable entries at the bottom/ sides, for incoming and outgoing cables. Flameproof nickel plated brass sealing plugs shall be supplied, for plugging the unused cable entries. The quantity of sealing plugs shall be equal to 20% of the total number of outgoing cable entries. The panels shall have external fixing lugs for mounting on wall or column. The holes provided on these lugs shall be of oblong type.
2.10.2 Component Specification Busbars in the lighting and power panels shall be made of high conductivity copper, and shall be supported by non-hygroscopic insulators. Busbars shall be colour coded for identification of phases and neutral. Unless otherwise specified, the incomer shall have one no. TP MCB with neutral link, 3 nos. fuses for maintenance and 3 nos. 30mA single phase ELCB for each circuit. Unless otherwise specified, the outgoing feeders shall be provided with double pole 10A MCBs having overload and short-circuit releases. Unless otherwise specified, all MCBs shall be with 16kA (M9 category) interrupting capacity. The ELCB shall be hand reset type. One no. door mounted reset push button shall be provided. The operating knobs (ON/ OFF/ RESET) shall be provided with a suitable rack and pinion arrangement for operating them smoothly from outside. Wherever the size of incoming cable to lighting, power panels is more than 35 sq.mm a suitable cable adapter box shall be provided and attached to the panel. The incoming cable leads shall be connected to terminal block (bolted type terminals) of required size. This terminal block shall be connected to TPN incomer unit through separate PVC insulated copper conductor wires/bus bars. Sufficient space shall be provided (minimum 300mm) between gland plate and the bottom of terminal block for easy termination.
2.11 Flameproof and Industrial Light Fixtures & Junction Boxes 2.11.1 Construction The enclosures of the flameproof lighting fixtures, control gear box and junction boxes shall be of cast light metal alloy and shall be free from frictional sparking hazard. The magnesium content in the alloy shall be as per IS-13346. Flameproof enclosure shall be suitable for zone 1 & 2, gas group IIA / IIB & temperature class T-3. The enclosure of the industrial lighting fixtures, control gear box and junction boxes shall be of CRCA sheet steel, dust & vermin proof. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 21 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
All equipment shall be suitable for use in outdoor open locations and shall have IP-55 degree of protection. The enclosures shall be provided with gaskets made of non-inflammable and self-extinguishing material. The enclosures shall be treated and prepared for painting with two coats of epoxy paint with final colour shade (both internal and external) as Silver grey shade 628 (IS-5) All accessories like nuts, bolts, washers etc. shall be made of stainless steel SS-304. All equipments on single phase supply shall be provided with an independent earth terminal with lug inside the enclosure for terminating the third (earth) core of the cable and shall have facility for looping.
2.11.2 Lighting Fixtures Glass used for lighting fixture shall be clear and suitable for use under conditions involving exceptional risk of mechanical damage. Well glass lighting fixture for Zone-2 classified area shall meet requirement of IS-8224. Mechanical strength of well glass shall satisfy requirement of IS-2206 (for type A glass) for flame proof lighting fixtures, and IS-6381 for Div. 2 lighting fixtures. All well glass fixtures shall be provided with a protective wire cage using minimum 5 mm welded steel construction and having mesh dimensions not exceeding 50mm x 70mm.The material of the cage shall be galvanised steel or epoxy powder coated mild steel. The fixing parts of the enclosure, which are to be opened for replacement of bulb, shall be so fastened that they can be unfastened only with special tools. The lighting fixtures in Zone-2/ Zone-1 area, shall have approved type enclosed break lamp holder and complete enclosure certified as having restricted breathing type construction. In case of lighting fixtures, the holder shall additionally have a spring-loaded lock to hold the lamp in position and to prevent the lamp coming off loose in the holder. Lamp holder shall be Edison screw type. All lighting fixtures shall be provided with 2 no. threaded entry and 1 no. double compression nickel plated brass cable gland. The glands shall be suitable for the specified cable size. All the fixtures having double cable entry shall be supplied with 1 no. nickel plated brass plug for sealing the unused entry. The top of all well glass lighting fixtures shall be identically drilled/ threaded to facilitate installation on pole/ column or ceiling. The flood lighting fixtures shall be supplied with adjustable mounting arrangement both in horizontal and vertical plane. All lighting fixtures shall be provided with suitable mirror-polished aluminium internal reflector of suitable thickness to ensure adequate mechanical strength.
2.11.3 Control Gear Box (Integral Light Fitting) Lighting fixtures suitable for discharge lamps shall be provided with power factor correction capacitor, choke starter etc., housed in separate compartment. The choke shall be copper wound. The complete control gear shall have power factor not less than 0.9. The control gear boxes shall be provided with 3 nos. entries and 3 nos. double compression nickel plated brass cable glands. The glands shall be suitable for the specified cable size. 20% of the control gear boxes shall be supplied with 1 no. nickel plated brass plug for sealing the unused entry. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 22 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
Control gear box for flame proof fixtures shall be flameproof type unless specified otherwise.
2.11.4 Junction Boxes Unless otherwise specified, the junction boxes shall be of flameproof construction suitable for zone 1 & 2, gas group IIA/IIB, temperature class T-3. Each junction box shall be complete with requisite number of cable entries and double compression flameproof nickel plated brass cable glands to suit the specified cable size and flameproof sealing plugs.
2.11.5 Lighting Poles Lighting poles shall be fabricated from MS steel tubular/ octangular pipes with joints, swaged together when hot and bevelled on outside edges. Lighting poles shall be hot dip galvanised with thickness of coating 70m. Poles shall be coated with bituminous preservative solution on the ground portion of the outside surface. Remainder of the outside surface shall be given two coats of red oxide primer and finished with two coats of aluminium paint. The pole shall have a marshalling box/Junction Box near the bottom to contain HRC fuses, a neutral link, an earth stud and terminal block. Each pole shall have two distinct earthing points for connecting to the plant earth grid.
2.12 Earthing Earthing system shall comply with the requirements of IS- 3043 and IEEE-80. All materials and hardware to be supplied by the contractor shall be new, unused and of best quality and shall conform to the specifications given here under and to latest specifications of Bureau of Indian Standards. Contractor shall bring material samples to site and get it approved by Engineer-in-charge before installation. The following conductor materials are proposed for the earthing system : i) Conductor above ground level, cable trenches and along cable trays GI Earth strip ii) Conductors buried in earth and concrete GI Earth strip iii) Outdoor structure, Plant, Earth pits A set of three copper-bonded steel earth rods of 2m each arranged in a triangular fashion & separated from each other by a flat copper conductor (copper strip). iv) TRF Neutral Earth pits & DG Neutral Copper Plate electrodes of size 600 x 600 x 10mm with 2 Nos.50 x 6mm G.I.Earth strips as per IS 3043. v) Lightning protection air terminations and down conductors for building A set of three copper-bonded steel earth rods of 2m each arranged in a triangular fashion & separated from each other by a flat copper conductor (copper strip). The galvanizing of the earthing material shall be done as per IS 2629-1985. Earth Electrodes shall have disconnecting facility. The rate shall be inclusive of excavation, Earth Electrodes fixing, backfilling, construction of earth pit chamber and earth pit cover, etc. Earthing conductors in the plant shall be laid in the form of a grid. Earthing leads of transformer & D.G.Sets neutral shall be directly connected to two separate G.I. earth plate electrodes VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 23 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
whereas, in the plant, outdoor structure, towers, tanks, building columns, loading racks, pipe racks, vessel & heat exchanger etc shall have two distinct earth connections. All interconnections of the earthing grid conductors shall have welded type joints except at electrodes with disconnecting facility and at equipment with bolted connections. All indoor earthing grids shall be suitably interconnected to the external earthing grid. Steel strips/conduits, cable trays etc shall not be used as earth continuity conductors. Earth pit marker showing details as indicated in Installation drawings 254625-300-ELE-4804- Sh-1 attached in Appendix-I shall be provided.
2.13 Flameproof & Industrial type plugs & Sockets 2.13.1 Construction The enclosures of the flameproof plugs, sockets & transformers shall be made of cast light metal alloy and shall be free from frictional sparking hazard. The magnesium content in the alloy shall be as per IS-13346. Flameproof enclosure shall be suitable for zone 1 & 2, gas group IIA / IIB & temperature class T-3. The enclosures of the industrial plugs, sockets & transformers shall be made of CRCA sheet steel, dust & vermin proof. The enclosures shall be sized to facilitate easy maintenance and heat dissipation. The equipment shall be suitable for use in outdoor open locations and shall have IP-55 degree of protection. The sockets for fixed installation, i.e. 415 V three phase sockets and 240 V single phase sockets, shall be provided with integral canopy. However, where the enclosure has been certified without integral canopy, a separate canopy can be accepted. The separate canopy shall be made of at least 2mm galvanised sheet steel or FRP. The canopy shall be suitable for providing protection against rain from top and two sides. The enclosures shall be provided with gaskets made of non inflammable and self extinguishing material. The enclosures shall be treated and prepared for painting with two coats of epoxy paint with final colour shade (both internal and external) Silver grey No. 628 (IS-5) All accessories like nuts, bolts, washers etc. shall be made of stainless steel SS-304. All the non current carrying metallic parts of the equipment shall be inherently bonded together. The TPN sockets shall be provided with two earthing studs, with lugs on the exterior of the enclosure, suitable for termination of 10 mm dia GI wire rope. Internal earth terminal shall be provided in each enclosure for all single plugs and sockets for connecting the earth core of the cables. The terminal block enclosures shall be adequately sized to properly terminate the cables by taking into account the required bending radii of cable cores and shall have the following minimum gland to terminal distances:
Conductor Size Up to 2.5 mm 2 Above 2.5 mm & Up to 10 mm 2
Above 10 mm 2 & Up to 35 mm 2
Above 35 mm & Up to 70 mm 2
Gland to terminal distance 40 mm 100 mm 150 mm 300 mm The sockets shall be provided with 2 nos. suitably sized cable entries at the bottom for specified cable sizes. The plugs shall be supplied with 1 no. suitably sized cable entry for specified cable size. Each socket shall be supplied with 1 no. flameproof nickel plated brass sealing plug, for plugging the unused cable entry. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 24 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
The sockets shall have external fixing lugs for mounting on wall or column. The holes provided on these lugs shall be of oblong type.
2.13.2 Component Specification The sockets shall be provided with a switch and a mechanical interlock so as to break the electrical circuit before the plug is completely withdrawn and make the circuit after the plug is fully inserted. In order to prevent accidental removal of plug from socket, the engagement and disengagement shall be by two separate and distinct movement and positions. Unless otherwise specified, 415V, 63A three phase flameproof plug and socket meant for welding receptacle/ any other three phase auxiliary load, shall be provided with 5 pins (3P+N+E). 5 pin socket shall be provided with 63A, four pole (TPN) heavy duty switch. The sockets shall be provided with either a spring loaded hinged cover, or with a cap connected through metallic chain, to close the same when not in service. Scraping earth connection shall be provided between the plug and socket. Earth pin of plug shall first engage with earth pin of switch socket. The plug assembly shall be mechanically rugged, light and shall not unduly stress the socket or its own pins when fitted on to the socket. The diameter of the earth pin of the plug and socket shall be at least 1.1 times the diameter of the phase pins.
3 Makes of Components Makes of components shall be as per Re-commended list of vendors attached in tender document.
4 Nameplate Permanent non-corrosive nameplate with engraved white letters on black background indicating the switchgear designation shall be fixed at the top of the central panel. Name plates shall contain the following information: First line : Equipment Item No. Second line : Equipment Description Third line : Equipment Rating. Fourth Line : System voltage. The following information shall be inscribed on a non-destructive, corrosion-resistant, indelible name/rating plate attached to the inner side of the unit enclosure door: Purchaser's order number. Year of manufacture. Name of Manufacturer. Type and serial number of unit. Purchasers Equipment Number. Nominal input current and voltage (incl. nature of current & number of phases). Rated nominal output current and voltage. Nominal DC / battery voltage. Ingress protection degree. All terminals of equipment and components shall be identifiable by alphanumerical markings in accordance with the Manufacturer's drawings. Terminals of input and output supply cables shall VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 25 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
be clearly and uniquely marked to indicate their purpose and the phase/polarity of the supply. All wires shall be marked according to the electrical diagrams with closed loop markers (ferrules) or stamped. Danger labels shall have black letters on a yellow background.
5 Inspection, Testing and Acceptance During fabrication, the equipment shall be subjected to inspection by Owner or by an agency authorised by the owner, if specified/ agreed in Inspection Test Plan. Manufacturer shall furnish all necessary information concerning the supply to Owner's inspector. All routine/ acceptance tests shall be carried out at manufacturer's works under his care & expense. Type test certificates from CMRI or equivalent test house, applicable CCE/ DGFASLI/ DGMS approval certificates, BIS license and original drawings referred in type test certificates shall be shown to the inspection agency on demand during inspection. The certificates and BIS license must be valid at the time of despatch. Test certificates of bought out components shall be shown to the inspection agency on demand during inspection. All equipments shall be subjected to various acceptance tests as per standards but not limited to the following: General visual inspection Dimensional inspection Verification of mechanical and electrical operations Dielectric tests Routine pressure test Any other routine and acceptance test as per applicable standards.
6 Packing and Despatch All the equipment shall be divided into several sections for protection and ease of handling during transportation. The equipment shall be properly packed for the selected mode of transportation, i.e. by ship/ rail or trailer, and shall be wrapped in polythene sheets before being placed in crates/ cases to prevent damage to finish. The crates/ cases shall have skid bottom for handling. Special notations such as 'Fragile', 'This side up', 'Center of gravity', 'Weight', 'Owner's particulars', TO no.' etc., shall be clearly marked on the packages together with other details as per purchase order. The equipment may be stored in a covered shed for long periods before installation. The packing should be suitable for such storage.
6.1 Packing and Despatch of cable drums Cables shall be despatched in non-returnable wooden or steel drums of suitable barrel diameter, securely battened, with the take-offend fully protected against mechanical damage. The wood used for construction of the drum shall be properly seasoned, sound and free from defects. Wood preservatives shall be applied to the entire drum. Ferrous parts used shall be treated with a suitable rust preventive finish or coating to avoid rusting during transit or storage. On the flange of the drum, necessary information such as project title, manufacturer's name, type size, voltage grade of cable, length of cable in metres, drum no., cable code, BIS certification mark, gross weight etc. shall be printed. An arrow shall be printed on the drum with suitable instructions to show the direction of rotation of the drum. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-008 Rev: B Page 26 of 26
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-008.doc
PVC / Rubber end caps shall be supplied free of cost for each drum with a minimum of eight per thousand metre length. In addition, ends of the cables shall be properly sealed with caps to avoid ingress of water during transportation and storage.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 21 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc
Appendix-F: Specification for Installation, Testing & Commissioning of Electrical Equipment [Refer Doc. No. 254625-300-SP-ELE-009 (Pages 1 to 36)]
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 1 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
SPECIFICATION FOR INSTALLATION, TESTING & COMMISSIONING OF ELECTRICAL EQUIPMENTS
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 2 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
List of Content Page No 1 Scope 3 2 General 3 3 Installation of Equipment 8 3.1 Switchboards and Bus Ducts 8 3.2 Transformers 11 3.3 LV Motors 14 3.4 Batteries/ Battery charger 15 3.5 Welding Receptacles 16 3.6 Push Button/Control Stations 16 3.7 APSEB Overhead Line Conversion 16 3.8 Four Pole Structure (Technical Specifications) 16 3.9 Cables 20 3.10 Earthing 25 3.11 Lighting Installation 29 4 Field Inspection, Testing and Commissioning 32 5 Contractor shall provide the following items in substation, as per Indian Electricity Rules: 35 6 Miscellaneous equipment 35 7 List of Construction Equipment 35 7.1 Equipment: 35 7.2 Test Instruments 36 8 Clearance and Safety 36
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 3 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
1 Scope This specification defines the requirements for the installation, field inspection, testing and commissioning assistance of free issue electrical items and supply , installation, testing and commissioning of bulk electrical items, forming part of electrical power distribution and utilisation system.
2 General 2.1 Responsibility of Contractor 2.1.1 In all matters relating to the supply and installation of electrical equipment, the electrical installation contractor is responsible for the quality and correctness of workmanship and for the quality and suitability of materials of his supply, in accordance with the relevant contract documents / drawings, specifications, standards, bills of material, etc. and must be prepared to re-make any section of the work or replace any materials, including re- installation thereof, to the satisfaction of Owner/MMCI in accordance with the conditions of the contract. 2.1.2 All ancillary / minor supply and installation including hardware / accessories are deemed to be included whether specially stated or not. 2.2 Deviation and Clarification If the contractor finds it necessary to deviate from the specifications of any items of work, as described in the schedule or wish to clarify any point particularly with regard to exclusions / inclusion in the scope of work, he shall list these points in consolidated list at the time of tendering. 2.3 Completion Programme 2.3.1 The contractor shall draw a detailed programme for the supply of materials and installation work to fit into the overall project programme of the owner, based on the availability of plant and free-issue equipment provided by the owner. The contractor shall obtain owners / MMCI representatives acceptance of the programme. The contractor shall work to this and shall provide sufficient labour and tools / tackles / materials to meet the programme dates. 2.3.2 The contractor shall estimate the percentage of work completed on each section of the works each week and shall pass this information to the Site Engineer. Site Engineer will decide whether such percentages are a true record of the actual work carried out. The Site Engineer, if required, may instruct the contractor in writing to increase the labour force tools and tackles at site. The contractor shall immediately take action and shall ensure that progress of the works is brought in line with the progress curves and to the satisfaction of the site engineer. No idle time claims shall be applicable under this contract. 2.3.3 The contractor shall arrange for his Resident Engineer to be available for a weekly site meeting to cover general progress. 2.3.4 The delivery of materials, which are to be provided by the contractor, shall be in accordance with the predetermined programme agreed between the owner / MMCI representative and the contractor. 2.4 Site Supervision The contractor shall provide adequate number of competent and qualified full time supervisors at site. OWNER/ MMCI site engineer shall monitor the work / inspect the materials supplied by the contractor and issue necessary instructions to the contractor as and when required.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 4 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
2.5 Co-Ordination 2.5.1 The contractor shall arrange through OWNER / MMCI site engineer for the co-ordination of his works with those of other trades and shall arrange his works to avoid interference with or interruption to the general programme. 2.5.2 The contractor will be required to carry out the installation work side by side with other installation work being executed by other contractors. The contractor shall extend all co- operation as may be required to other contractors in carrying out their work. 2.6 Drawings 2.6.1 The contractor shall be supplied with general arrangement, schematic wiring drawings and layout drawings showing the routing of cables and earthing, location of motors, switchgears, control panels, push buttons stations, socket outlets, lighting fittings, etc. 2.6.2 The contractor shall prepare where required detailed working drawings and obtain OWNER / MMCI site engineer's approval prior to starting the installation. 2.6.3 All field corrections shall be marked up on the copy of relevant drawings and such As- Built drawings shall be submitted to the site engineer on the completion of the work in a particular section. Two sets of the drawings shall be handed over to the contractor to mark As-built corrections. 2.7 Measurements 2.7.1 The contractor shall inform the site engineer when various sections of the contract works are completed. 2.7.2 Contractor's representative on site shall maintain records and measurement sheets as the work progress. The summarised measured quantities of each cable size, type of equipment, etc. will be entered on the sheets and initialled by both, contractor's representative and the site engineer weekly. The contractor shall then submit a copy of the summarised sheets to substantiate his claim for payment. 2.7.3 The site engineer's signature on the measurement sheet at the completion of each interim measurement does not commit the owner to payment for the work described. The signature shall mean that the site engineer and the contractor agree with the measured work. The liability of the owner to pay the contractor for the measured work shall be defined by the terms of the contract. 2.7.4 Contractor shall ensure that the measurement of quantities in case of underground activities will be certified by MMCI engineer before backfilling. 2.7.5 Contractor shall raise only one running bill per month for supply & installation. 2.7.6 Measurement Procedure a) Cables Measurement shall be from lug to lug. b) Cable Tray / Cable Cable Tray / Duct along Duct with bends, T section, shall be measured along the centre line. c) Excavation Average width and depth shall be considered. Length will be measured along the centre line. d) Sand Item shall be measured on the basis of stack measurement. e) Rock Cutting Item shall be measured as per civil standard of collecting the rocks and giving void allowance.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 5 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
2.8 Corrective Work 2.8.1 Corrective work when caused by error of the contractor shall be carried out by him free of cost to the owner. 2.8.2 Corrective work which has been called for by the owner / MMCI representative shall be cost as follows : a) The removal of any section of the contract work shall be cost on the day-work basis according to the daily rates for the type of labour involved. b) Remedial work will be cost according to the schedule of rates or at rates agreed upon in the case of lumpsum contract. c) Re-erection of any section of the contract works shall be cost according to the Schedule of Work / Rates. 2.9 Extra Items In the event of any item of work which needs to be carried out for the completion of the work and which is not covered by this specification, such an item of works shall be termed an extra item. The contractor shall first notify with provisional rate and get a written agreement from the site engineer before commissioning the work. In order to facilitate the finalisation of the rate for items not covered in the schedule of rates, but which are similar in nature to the items already covered therein, the rates for these items shall be arrived at by extending the rates for similar extra item as applicable. In case, it is not possible to derive rates for extra items as mentioned earlier, contractor shall submit detailed rate analysis with supporting vouchers to substantiate the rate for approval to site engineer. 2.10 Approval of Authorities The contractor shall co-ordinate the inspection / approval by the authorities of the work carried out by him for the purpose of compliance with the necessary regulations issued by them. The owner shall pay any statutory fees required to be to the authorities for obtaining their approval of the installation work carried out by the contractor. 2.11 Guarantee 2.11.1 Installation of free-issue items The contractor shall guarantee the installation of all free issue items against faulty workmanship for a period of 12 months from the date of handing over. 2.12 Consumables 2.12.1 The contractor shall supply all the consumable materials and installation materials required for complete erection like lubricating oil, kerosene solvents sealing compound, insulating tapes, asbestos sheets, tapes and cords, connectors, burning / soldering / plumbing materials, numbering ferrules, numbering tags, saddles, cleats, markers, hardwares, etc. All hardwares used shall be hot dip galvanised only. 2.12.2 The consumable material such as lubricating oil / grease, etc. required for testing and commissioning of the equipment such as motors and driven equipment will be arranged by Owner. 2.13 Painting 2.13.1 The contractor shall paint all fabricated structural item (structures, M.S. Canopy supports and trays, etc.) erected by contractor with approved anti-corrosive paints as specified. All welded joints and insulated parts will be thoroughly cleaned with wire brush before painting. Paint will be applied uniformly on the surface. Painting should be with 2 coats of red oxide primer followed by 2 coats of finished paint of shade to be informed by MMCI / Owners site engineer. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 6 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
2.13.2 The contractor shall make all numbering and lettering on the equipment/ panels/ light fittings, etc. with approved paint, supplied by him, wherever required. 2.14 Civil Engineering Work 2.14.1 MMCI, under separate contract will arrange for all major civil engineering works such as foundation for plant and equipment, built-up cable trenches / ducts, as shown on the relevant drawings, etc. Necessary openings in the foundations for fixing of foundation bolts and anchor plates etc. will be provided by MMCI as shown on the relevant drawings. The contractors scope of work shall include any minor civil work directly connected with his work and in making good all breakages / damages caused in the execution of his work at no extra cost to the owner. The contractor shall be responsible for the true and proper setting out of the work in relation to original points, lines and levels of reference and for the correctness of levels, dimensions and alignment of all part of the work and for the provision of all necessary instruments appliances and labour in connection therewith. The contractor shall layout one or more permanent bench marks in some central place before starting the work. 2.14.2 The contractor shall check and inform in writing to MMCI Engineer if any discrepancy is noticed by him in civil work. The site engineer then shall arrange for necessary rectification, if necessary. 2.14.3 Other openings, sleeves, etc. required to be provided in the brickwork / concrete for electrical work shall be carried out by the contractor and shall be made good to the satisfaction of MMCI at no extra cost. 2.14.4 All damages caused to the foundation due to negligence of the contractor shall be rectified by him at his own cost as directed by the Site Engineer. 2.14.5 Excavation of trench for direct burial of underground cables, including supply and spreading of sand, supply and laying of concrete slab / brick top cover, G.I. / concrete pipes, brick separator wherever required and backfilling with good earth shall be included in the scope of the contractors work. Definition of IS for soil will be applicable in deciding nature of the soil. Contractor shall consider as blasting is prohibited for rock cutting. However, blasting for rock cutting may be allowed in certain cases depending on the site location as considered by site engineer. 2.14.6 The contractor shall also at the end of each day's work, ensure that all the trenches within the plant buildings are properly covered by means of protection covers, wooden planks, steel plates, etc. as temporary measures or cordoned off by a bamboo barricade. 2.14.7 For the preformed trenches, the contractor shall supply and install the necessary supporting steel work, if called for. 2.15 Storage 2.15.1 The contractor shall provide and maintain at no extra cost to the owner suitable temporary storage facilities and site office within the area allocated to him by the owner free-of-cost. 2.15.2 The contractor shall provide the necessary security services to safeguard the materials which shall be his responsibility under the terms of the contract. 2.15.3 When the contractor is established on site, he shall off-load, sort out, store or stack and record to owner's satisfaction all materials, which have been fabricated or ordered by the contractor. 2.15.4 At the end of the contract, the contractor shall completely remove and dispose of all temporary works erected on site allocated to him to the satisfaction of the MMCI / Owners representative. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 7 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
2.16 Clean-up of Work Site The Contractor's Scope shall include cleaning up of the work site and carting away all unnecessary materials from the work site from time to time at no extra cost. 2.17 Statutory Licence / Certificate of Competency All the supervisors / electricians employed to carry out the installation work at site shall hold the statutory certificates of competency for the nature of work entrusted and shall fully meet the requirements of the local Electrical Inspectorate prior to commencement of the work. Also, contractor shall have valid electrical contractors license to work in a state. 2.18 Receipt and Reconciliation of Material 2.18.1 Free-issue items 2.18.1.1 The Owner shall supply major electrical equipment as free-issue items at a given point within the plant premises. 2.18.1.2 The contractors scope of work includes taking delivery of these equipment / materials packed or unpacked, from Owners store, transporting to place of installation, testing and commissioning. 2.18.1.3 All costs arising from the transporting of free-issue materials from the owners stores to the final destination of installation shall be included by contractor in installation rate. 2.18.1.4 All necessary tools, tackles and facilities required for transporting of free-issue items shall be made available by the contractor at no extra cost. 2.18.1.5 The contractor shall visually inspect all free-issue materials for any defects of workmanship or damage. The contractor shall accept the liability for all the items issued to him till the same are installed, commissioned and handed over to the owner. 2.18.1.6 The contractor shall inform the owner of the free-issue items that he wishes to requisition from the owner three days in advance. 2.18.2 Scrap & Excess Material 2.18.2.1 On completion of the work, the contractor shall submit Material Reconciliation Statements for all material issued by Owner, in the proforma prescribed by site engineer. 2.18.2.2 The following wastage and scrap allowances are permissible : Nol-Salvageable Unaccountable a) Structural Steel (Length less than 1 Mtr) 3% 0.5% b) Pipes (Length less than 0.5M) 2% 0.5% c) Cables (Length less than 5M) 2% 0.5% d) Cable tray 0.5% -- 2.18.2.3 All excess materials and scrap shall be returned after duly accounting for, to the storage points, in good condition, without which contract will be deemed to be incomplete. 2.18.2.4 If the contractor fails to return the surplus material aforesaid, the owner will charge the contractor for such un-returned materials at rates prevailing in the market.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 8 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
3 Installation of Equipment Prior to start of installation of the electrical equipment, Contractor shall verify that equipment and complete materials have been received. Handling, shifting to required site location, installation, testing and commissioning of all electrical equipment shall be done by contractor with utmost care. Manufacturer's instructions and the requirements given in their technical manuals shall be strictly adhered. The substation/switchgear room wherein the equipment shall be installed shall be kept clean, dry and free from all debris. Panel floor cutouts not in immediate use shall be suitably covered to avoid any mishap. When handling the switchboard panels, care shall be taken to observe the correct lifting arrangements and to make sure that slings are attached to the manufacturer's designated lifting points. No parts shall be subjected to undue strains or sudden stresses which could cause damage to the equipment.
The lifting position mark indicated on packing casing shall be adhered to strictly, for keeping it in required vertical position.
Contractor shall check and report to the Engineer-in-charge about any damaged item and / or missing component for getting the same replaced as per specifications. During installation, all accessories and loose items shall also be inspected by the contractor before their assembly/mounting.
3.1 Switchboards and Bus Ducts 3.1.1 The term switchboard here includes all HV/LV switchboard panels, motor control centers, power and lighting distribution boards, UPS panels, ACDB, Battery charger panels, DCDB etc.
The switchboard panels shall be handled with care, avoiding any impact to the equipment. Dragging of the panels directly on floor shall be avoided. Roller bars may be used for shifting of panels. Use of a crane and trailer shall be made for handling of equipment. The switchboard panels shall be properly supported on the truck or trailer by means of ropes to avoid any chance of tilting. The switchboards shall be lifted after ensuring that panel supports, nuts and bolts are all intact and tightened. While lifting the panels in packed conditions, utmost care shall be taken to avoid any damage to insulators, bushings, metering and protective equipment.
The panels shall be preferably kept inside the packing cases till foundations are ready. Proper rain/sun/dust protection shall be ensured till switchboards are installed.
3.1.2 The switchboard panels shall be installed on prepared foundations or floor cutouts. Steel base channels shall be welded to inserts provided in floor slab. Cross members shall be provided at the junctions of each shipping section and other places as required.. It shall be ensured that the base plate level of HV switchboard shall match with the finished floor level.
The foundation pockets and the grouted bolts shall be cured for a minimum period of 48 hours. Proper level of base frames shall be maintained throughout and shall be checked with water level/spirit level. Steel Shims shall be provided below base frame wherever required.
3.1.3 The switchboard panels shall be taken out from the packed cases and shifted one by one to its proper place. All the panels shall be assembled, aligned and leveled. Alignment of VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 9 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
panels shall be checked in both longitudinal and lateral directions. It shall be ensured that panel to panel coupling bolts, bus bar links etc. fit properly without any strain on any part. No new holes for jointing of the panels other than those recommended by the vendor shall be drilled. No gaps shall be left between the panels. Gap if any found between panels shall be suitably sealed using sealing compound or T-profile. The lifting, racking in and out operation of the breaker and all other motions shall be free from any obstruction.
The panels shall be checked for correct vertical position using Plumb line and spirit levels. The switchboard panels shall be tack welded at suitable intervals at base channel. After erection of switchboard panels, all uncovered portions of floor cutouts shall be covered with 6 mm thick removable chequered plates finished with floor level. The design of the chequered plates shall be such that the maximum allowable deflection is L/200 (where L is the span of the chequered plates in meters) for a live load of 500 kg./sq. meters.
Additional stiffer shall be provided at the bottom if required. Suitable lifting arrangements shall be provided for chequered plates. The chequered plates shall be painted with a coat of red oxide zinc chromate primer after proper surface preparation as per specifications. Where specified, panels' cutouts provided for future use shall be filled with lean concrete.
3.1.4 After completion of Installation of switchboards, all the cubicles, switchboard components such as switches, starters, CT and PT chambers, bus bar chamber shall be cleaned and checked for tightness of all the components. Vacuum circuit breakers shall be checked for integrity of bottle seals. All loosely supplied items shall be fitted up. Bus bar sections or links shall be inserted and where specified, of high voltage equipment shall be insulated. Interconnection wiring between shipping sections shall be made by contractor.
All the wiring connections shall also be checked. Contact resistance of all bus bar joints and contactors shall be checked. Insulator shall be checked for any damage. All the starters, switches, contacts shall be cleaned with CTC where required.
All the moving parts shall be checked for easy and free movement. Hinges of panel doors shall be lubricated to give free and noise free movement. All openings shall be kept completely closed to avoid ingress of any foreign particles inside the panel.
Functional scheme verification of individual feeder shall be carried out and minor wiring modifications in the panel wiring, if required shall be done as per the directions of Engineer-in-charge. Special attention shall be paid to CT circuits' polarity, wiring continuity and correctness in the protection as well as measurement circuits. Auto transfer scheme shall be simulated and verified. During the course of scheme verification tests, defective components if any shall be taken out, after bringing to the notice of Engineer-in- charge. The same shall be replaced by component supplied by owner.
3.1.5 Where switchboard is damp or having a low IR value due to damaged insulators/ bushings/any other insulated parts, or any other reason, the entire switchboard shall be dried-up according to the instruction of the Engineer-in-charge for the IR value to improve to a safe level for commissioning. Care shall be taken to protect the surrounding insulation from direct local heating during the drying up process.
3.1.6 All moving parts, of closing/tripping mechanism, racking in and racking out mechanism, spouts and shutter closing mechanism shall be checked for proper operation. All the auxiliary contacts of breaker shall be checked-up, cleaned and contact pressure measured.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 10 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
3.1.7 All the control wiring, PTs, bushings, bus bars, other live parts of switchgear, incoming and outgoing cables shall be meggered.
3.1.8 Electrical simulation tests shall be carried out for all the protective, alarm and annunciation relays and external interfaces to ascertain proper functioning.
3.1.9 Safety insulation mats of approved make and of required voltage grade shall be provided in the sub-station.
3.1.10 Pre-Commissioning Check List Before commissioning any switchboard, following points shall be checked and ensured for safe energising of the switchboard: i. That the installation of equipment to be commissioned is complete in all respects with its auxiliaries and all other mounting including earthing. Openings in floor within and outside panels have been sealed off. All cover and door gaskets are intact to make the enclosure vermin proof.
ii. That all the metering instruments have been checked and found in working order. Indicating lamps are healthy and are in correct position. All power and control fuses are of proper rating.
iii. That the high voltage tests of incoming and outgoing cables have been conducted and results are satisfactory. iv. That IR Value has been recorded for bus bars, circuit breaker, incoming and outgoing cables, control wiring and potential transformers. Where required joint resistance of bus bars have been recorded and found to be satisfactory. All the surroundings and panels have been cleaned and temporary earth leads have been removed.
v. Following tests shall be ensured for all bus bars - Tightness of all nuts/bolts using Torque wrench - IR value - Contact resistance using 100A DC Kit - Cleaning of bus bar chamber using vacuum cleaner - Conducting jelly shall be applied on AL/CU joints as per manufacturer's recommendations - HV test in case of HV switchboard
vi. Following tests/Checks shall also be performed on the switchboards - Functional verification of individual feeders including all spare feeders - Simulation test for under voltage tripping of related feeders such as motor feeder, capacitor feeders etc - Verification of control supply schemes - Checks for all panel illuminations, indicating lamps, sockets - All upstream and down stream interlocks
3.1.11 Bus Ducts The bus ducts as per issued drawings will be supplied in parts and all the parts shall be assembled and the bus bar connections shall be made at site. The insulators in bus ducts shall be inspected for any possible damage during transit and the defective ones shall be replaced. The insulators shall be cleaned. Contact surface of bus bars, bus bar bolts and nuts shall be thoroughly cleaned. Petroleum jelly shall then be applied and bolted connection made. The bus duct enclosure shall be checked for earth continuity and then earthed at two VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 11 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
places. The bus duct shall be properly supported between switchgear and transformer. The opening in the wall where the bus duct enters the switchgear room shall be completely sealed to avoid rain water entry. Expansion joints, flexible connections etc. shall be properly connected. The bus duct levelling shall be checked with spirit level and pendulum weight.
Pre-commissioning check list
Before commissioning any bus duct, following points shall be checked and ensured for safe energising of the bus ducts - All joints are tightened using torque trench - Cleaning of bus duct chamber with vacuums cleaner - Silica gel breather shall be connected if supplied. If required, silica gel shall be - reactivated as per the instruction of engineer in charge. - Space heater circuit shall be checked and tripping through thermostat shall be ensured - Contact resistance shall be measured for all phases/neutral using 100A DC kit - High voltage test in case of HV bus ducts
3.2 Transformers Transformers on receipt at site shall be unloaded by means of crane or lifting devices of adequate capacity. All lifting lugs shall be used to avoid unbalanced lifting and undue stresses on lugs. Lifting lugs if any provided for partial lifting (e.g. for active part, conservator) etc. shall not be used for lifting complete transformer. Parts other than those identified for lifting of the transformer shall not be used for lifting. While slinging, care shall be taken to avoid slings touching other parts.
3.2.1 Before lifting transformer, it shall be ensured that all cover bolts are tightened fully. In case when it is necessary to use jacks for lifting, projections provided for the purposes of jacking shall be used . Lifting jacks shall not be used under the valves or radiator tubes. For transporting transformers from stores to site, the transformers shall be loaded on a suitable capacity truck or trailer. The transformers shall be properly supported by steel ropes and stoppers on the trailer to avoid tilting of the transformers in transit due to jerks and vibrations. At no instance the transformer shall be kept on bare ground. Where it is not possible to unload the transformer directly on a foundation, it shall be unloaded on a properly built wooden sleeper platform. A transformer shall never be left without putting stoppers to the wheels.
3.2.2 Transformers shall be examined, for any sign of damage in transit. Particular attention shall be given to the following in this regard. i. Dents on tank wall or cooling tubes, radiators ii. Damage to protruding parts like valves, sight glass etc. iii. Loosening of bolts due to vibration in transit. iv. Cracked or broken bushings. v. Oil leakage particularly along welds.
If any thing adverse is noted the same shall be brought to the notice of Engineer- in- charge.
3.2.3 Contractor shall examine the transformer base, oil pit, fire walls and foundations laid by the civil contractor. It shall be ensured that oil spills can not propagate along cable trenches. Any discrepancy noted will be brought to the notice of Engineer- in- charge. Transformers shall be placed on channels or rails over concrete foundations. The transformers shall be levelled, aligned and checked for free movement on the channels or rails. Stoppers shall be VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 12 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
provided to the transformers immediately to prevent any movement. All the accessories like radiators, cooling fans, valves, conservator tanks, explosion vent pipe, bushings and other devices which are supplied in different packages shall be checked for any transit damage and cleaned thoroughly before fixing on the transformer. All loosely supplied parts shall be assembled as per manufacturer's instruction manuals/ drawings and documents. All the connections for CTs bushings and other wiring shall be checked for tightness and correctness before replacing the lid or tightening all the bolts. Gravels shall be filled in the transformer bay, soak pit as per requirement.
3.2.4 Topping of transformer with oil Before topping up with oil, transformer shall be fitted with all accessories such as valves, gauges, thermometers etc. Oil samples shall be taken from each drum and tested for determination of dielectric strength. Any sign of leakage of the barrel or of its having been opened shall be recorded and reported. It is necessary to filter the oil before the transformers are filled. It shall be ensured in oil filling operation that no air pockets are left in the tank and that no dust or moisture enters the oil. All air vents shall be opened. Oil shall be filled through a streamline oil filter using metal hose. To prevent aeration of the oil, the transformer tank shall be filled through the bottom drain valve. In a transformer with conservator tank, the rate of oil flow shall be reduced when the level is almost upto the bottom of the main cover to prevent internal pressure from rupturing the pressure relief- pipe diaphragm. Sufficient time shall be allowed for the oil to permeate the transformers and also for the locked -up air bubbles to escape. Any air accumulation in the buchholz relay shall be released.
3.2.5 Transformer Oil i. Sample of oil from the transformer shall be taken from the bottom of the tank.
ii. Testing of Oil For dielectric test, the oil shall be tested as described in IS: 335. The oil shall also be tested for acidity in accordance with the methods prescribed.
3.2.6 Drying out of the transformers, if required, shall be carried out and record maintained in accordance with IS: 10028. Normally a streamline filter shall be used for drying-up. IR value versus time of both windings along with OTI/WTI and filtrations machine temperature curve for IR value Vs time shall also be plotted and recorded during the drying-up process.
Precautions when drying i. The maximum sustained temperature to which transformer oil may be subjected shall be limited to 80 C. ii. The transformer shall be carefully monitored throughout the drying out process and all observations shall be carefully recorded. iii. Drying out shall be continued so that the insulation resistance as prescribed in the standard code of practice is attained and the value remains constant for more than 12 hours. However, a minimum number of cycles shall be done for each transformer as found necessary by the Engineer-in-charge. Generally a Megger reading of 2 megohms / kV at 60 C temperature, with a 5 kV Megger may be a rough indication for stopping the dehydration.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 13 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
3.2.7 The following work on transformers shall be performed by the contractor if specifically called for: i. Before finally commissioning the transformer it may sometimes be desired to run it for a few hours on short-circuit, applying a low voltage, approximately equal to the impedance voltage of the transformer. During this process, regular readings of the insulation resistance of the winding to earth and winding to winding and temperature against time shall be recorded. ii. Testing of radiator tubes for any leakage and rectifying these by welding / brazing.
3.2.8 Pre-commissioning Check List: Before commissioning of any transformer, the following points shall be checked for safe energisation of the transformer: i. All the accessories have been fixed properly and transformer body and neutral are properly earthed. The transformer dehydration is over and results are satisfactory and approved by the Engineer-in-charge. In case transformers are idle for more than one month after dehydration, transformer oil has been given at least two circulations. ii. Oil level, in the transformer conservator tank and all the bushings is upto the marked point and the oil has been tested for dielectric strength and acidity. Oil filtration (if required) shall be carried out. iii. Silicagel is in reactivated condition. The breather pipe is clear from any blocking and contains oil upto the proper level. iv. The explosion vent diaphragm does not have any dents. Accumulation of any oil and air had been released. v. The tap setting on which the off load tap switch is locked shall be recorded. Generally the off-load tap switch shall be kept on nominal tap. vi. Buchholz relay has been tested and checked up for any friction in the movement, and floats are free. All the other protective relays, alarm and annunciation relays have been tested. vii. Metering equipment has been tested and polarity test of PT's and transformer winding is satisfactory. Phase sequence and connections have been checked for proper vector group. viii. Ratio test and winding resistance on all the tap positions is satisfactory. ix. Gaps of arcing horns for the bushings where provided are in order and earth connections for the surge diverters have been checked. x. Winding and oil temperature thermometer pockets contain oil and the winding and oil temperature settings on dial gauges are in order. xi. Simulation tests for all external interface connection alarm, annunciation and trip circuits have been checked and are in order. xii. Insulation resistance of all the control circuits and IR value of the transformer windings and all the incoming and outgoing cables have been checked. xiii. Valves in the cooling system and valve between the buchholz relay and the conservator tank are in open position. xiv. Setting of all the protective relays is at the desired value and DC Trip supply is healthy. xv. Magnetic, current and magnetic balance test have been conducted VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 14 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
xvi. Simulation test for WTI,OTI,PRV,OSR xvii. Settings of WTI/OTI as per the instruction of the manufacturer xviii. Earthing resistance value for the neutral earthing
3.2.9 Observations after Commissioning After switching on the transformer the following points shall be observed and recorded. i. The inrush magnetizing current and no-load current. ii. Alarm, if any, or if any relay flag has operated. iii. Voltage and current on all the three phases. iv. Transformer hum or abnormal noise. v. Circulation of oil and leakages. vi. Record current, voltage, cooling air temperature, winding temperature and oil temperature readings, hourly for 24 hours. vii. Cable end boxes for any over-heating.
3.3 LV Motors 3.3.1 All the motors generally would be erected by the mechanical contractor.
3.3.2 Electrical contractor shall keep the motor space heater energised as per the directions of Engineer-in-charge. Electrical contractor shall measure the insulation resistance of motor windings. Insulation resistance of the motors shall be measured between the winding of the machine and its frame by means of a 500 / 1000 V Meggar in case of 415 V motors. A minimum value of 1 megohm for 415 V motors shall be considered a safe value. In case of lower I.R. Value, the insulation value shall be improved by any of the following methods as directed by the Engineer-in-charge. i. Blowing hot air from external source. ii. Putting the motor in oven. iii. Placing heaters or lamps around and inside after making suitable guarding and covering arrangements so as to conserve the heat.
In case the insulation is low, the following method of drying has to be adopted, after consultation with Engineer-in-charge. During drying the temperature rise of winding shall not exceed the permissible value for the class of insulation used. i. By locking the motor so that it can not rotate and then applying such a low voltage to the stator terminals so as to pass full load current in the stator keeping the stator winding temperature below 90 C . In this case a close watch shall be kept for any possible overheating and I.R. Values vs. temperature shall be plotted and heating continued till I.R. value becomes steady. ii. By blasting hot air from external source, Maximum temperature of winding while drying shall be 70 C to 80 C (thermometer) or 90 C to 95 C by resistance method. Heating shall be done slowly first till steady temperature of winding is reached after 4 to 5 hours, and for large machines after 10 hours. A record has to be kept for drying process, with half an hour readings and, till steady temperature is reached. In case it is essential, the drying process can be supplemented by blower. 3.3.3 It shall be ensured that the motor leads are correctly connected in the terminal box, as indicated in the 'Name Plate'. The covers of all terminal boxes shall be properly fixed, the VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 15 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
gaskets intact. The control circuit shall be tested for proper functioning as per circuit diagram.
3.3.4 In case of synchronous machines, slip rings and brush gear shall be polished and brushes shall be fixed in their holders with clearance and pressure as recommended by the manufacturers.
3.3.5 Before commissioning, the ventilation and cooling system of the motor must be inspected. In case of motor with forced ventilation the air inlet shall be examined to ensure that it is free from moisture and any foreign material. It shall also be ensured that recommended flow and pressure of air is available to produce the required cooling effect.
3.3.6 The motor control gear shall also be carefully examined, the over-load settings may be reduced or time lags bypassed from protective gear to ensure rapid tripping of switchgear in event of faults. The direction of rotation of a new motor specially of large capacity , and phase sequence of supply shall be kept in view while joining and connecting to the motor terminals
3.3.7 Finally the motor shall be started on no-load after decoupling, and shall be allowed to run for a minimum period of 4 hours, or for a time as instructed by Engineer-in-charge. Attention shall be given to the proper running of the bearings, vibration or unusual noises if any. Voltage, starting current, no load current, stator winding and bearing temperature shall be recorded after every 1 hour during this test. Direction of rotation shall be checked and recorded. Normally the motors run in clockwise direction as viewed from the driving end with reference to the phase sequence R, Y, B.
3.3.8 After switching off the motor, the insulation resistance of the motor shall be recorded under hot and cold conditions.
3.3.9 If the no load test run is found satisfactory, the motor shall be allowed to run for 8 hours and all readings shall be recorded.
3.3.10 The following work on motors, may be performed by the contractor if specifically called for. i. The proper level of bearing oil has to be checked. The condition of grease in bearings shall be checked and in case it is necessary, complete replacement of bearing with specified grade of grease after proper cleaning of the bearing shall have to be done. Wherever external greasing facility exists, the condition of grease may be checked by pumping some new grease of specified grade at start. If the grease coming out is deteriorated grease shall be replaced. ii. All the motors, motor exciter set and induction generators directly coupled or coupled through reduction gears shall be checked for abnormal vibration. Any minor defect in a race or roller may give rise to considerable amount of vibration and noise. Contractor shall check and bring to the attention of Engineer-in-charge any defect noticed in this regard. iii. Due care shall be taken to avoid any damage to bearing insulation wherever provided.
3.4 Batteries/ Battery charger Battery (VRLA/ SMF type as specified) shall be erected on stands and insulators supplied by the manufacturer of the batteries. The installation shall be done as per the layout drawings and manufacturer's instructions. Electrolyte if required / as applicable shall be VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 16 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
filled as per manufacturer's instructions. Interrow connections shall be made with the leads supplied by the manufacturer. Functional check shall be done on the battery charger including battery charging and discharging, recharging as per the recommendation of the manufacturer.
3.5 Welding Receptacles The welding receptacles shall be erected on steel/concrete structures as per the drawings. In isolated places a separate support shall be fabricated and installed.
3.6 Push Button/Control Stations The push buttons / control stations shall be installed near to the motors to be controlled. Individual channel supports shall be installed as per installation standard. If control stations for hazardous areas are to be supplied by contractor, these shall be of Ex (d) type, tested by CMRI and approved by CCOE or other applicable certifying authorities. All outdoor push buttons / control stations shall preferably have integral canopies for additional weather protection. The canopy shall be made of 2 mm thick galvanized sheet steel or FRP where these are not integral with the equipment.
3.7 APSEB Overhead Line Conversion Vendor shall supply & install cables and necessary accessories to convert the 33kV overhead line of approx. 60m stretch to underground system. Vendor shall obtain liasioning with APSEB. Exact pole distance shall be provided at site during execution. 3.8 Four Pole Structure (Technical Specifications) 33kV OUTDOOR FP STRUCTURE COMPONENTS
3.8.1.2 Technical Features A) General i. The disconnecting switch shall be Manual operated air break, triple pole, outdoor, gang operated, double break suitable for horizontal, upright mounting on galvanized steel structures, Isolators having contacts moving in horizontal plane are preferred. ii. The disconnect switch shall be capable of interrupting small inductive and capacitive currents such as those while disconnecting lines at no load or transformer no load currents The isolator blades shall be able to carry the rated current continuously without exceeding temperature limits mentioned in design criteria
B) Operating mechanism i. a) The operating mechanism for disconnect switches shall be suitable for local manual operation. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 17 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
ii. b) A signaling device for all poles of the isolator shall be arranged both for closed and open position, to indicate isolator position on remote panel in control room. iii. The manual operation should be easy but not easily accessible. There should be proper locking arrangement for manual operation iv. The operating mechanism shall have positive control of blade movements at all times and under most hazardous conditions. Linkages shall be fitted free from slack and lost motion v. All bearings shall be sealed against dust and moisture heavy-duty type lubricated for life and vi. The manual operating handle shall be mounted on the base supporting structure. Guide bearings shall be provided at a height of 750mm above ground level All brackets, angles, guides, guide bearings & other members necessary for attaching the operating mechanism & operating handles to supporting structure, shall be supplied as an integral part of disconnect switch. The moving blades of isolator shall turn 90 degree after making the contact for ensuring sufficient contact
C) Earth switch The isolator shall be provided with Manual operated earth switch forming integral part The rating of earth switch shall be same as that of isolator with respect to rated peak short circuit current and making current. The earth switch shall be operated by a separate operating mechanism, shall be electrically and mechanically (castle key interlock) interlocked with the isolator, so that, the grounding blade can be closed only, when the isolator is open and the isolator can be closed only when the earth switch is open
D) Additional interlocks The isolator shall be electro-magnetically interlocked with the associated circuit breaker Even manual operation of isolator shall be possible only when the associated breaker is in the open position The interlock shall be so designed that it shall not be possible to operate the isolator even locally when the associated circuit breaker is in the closed position The interlock shall be fool proof in all respects. The interlock relay/solenoid shall be provided in the cabinet for operating mechanism. Necessary auxiliary contacts for interlocks with vacuum circuit breaker shall be provided
E) Auxiliary contacts 3 NO + 3 NC auxiliary contacts shall be provided for the main isolator and 3 NO + 3 NC for earthing switch It shall be possible to convert NO to NC and vice versa at site The auxiliary contacts shall have a continuous current carrying capacity of at least 10 Amps
F) Constructional features i. The switch-blade of main and earth switch shall be copper It shall be of one solid piece construction and shall be assembled that no part of the blade can move relative to the other The thickness and section of the blade shall be such that it retains its form and straightness under all conditions of operation including the flow of system fault current for the period specified. It shall also be capable of withstanding all torsional and bending stresses due to the operation of switches VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 18 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
ii. The isolators shall have high-pressure self-aligning adjustable contacts The contacts shall be well protected all round by a metal cover which provides not only electrostatic screening but also prevents coarse dust from entering between the contacts. The contacts shall be designed such that the contact pressure is released before any movement of blades in the opening direction takes place and is applied after the closing travel is completed There shall be sufficient wiping action of the contacts to make them self-cleaning The contacts shall be made of high grade high conductivity heat resistant material and shall be silver plated. iii. The earthing switch of disconnect switch shall be complete with all parts that are necessary or essential for the efficient operation Such parts shall be deemed to be within the scope iv. Disconnect switch and earth switch including their operating mechanism shall be such that they cannot be dislodged from their open or closed position by gravity, wind pressure. vibrations shocks etc. v. The disconnect switch/earthing switch contacts shall be of silver faced copper vi. All live parts shall be of non-rusting and non-corroding metal Current carrying parts shall be of non-ferrous material such as copper or Aluminum Bolts, screws shall be provided with lock washers, keys or equivalent locking facilities and if provided on current carrying parts shall be made of non-rusting and non-corroding metal such as copper/silicon alloy vii. Base channels and other structural members such as operating pipes, phase coupling rods etc., operating mechanism boxes, bolts, pins etc.. shall be hot dip galvanized. The thickness of galvanizing shall not be less than 100 microns viii. All similar parts shall be interchangeable. ix. The disconnect-switch shall be such that no lubrication of any part is required except at very infrequent intervals x. During the course of normal operation it is likely that the disconnect switch/earth switch may be left in the open/closed position for long periods xi. Disconnect switch shall be such that it is free from visible corona discharge in both closed and opened positions. xii. The clearance between live parts and grounded structures shall not be less than those specified in relevant standards. The inter-phase clearance shall be as per switchyard layout. Inter phase clearance and mounting height shall be more than 1.5m The length of break in open position shall be such that there is absolutely no possibility of arc over from the live parts to the de-energized parts on which any maintenance work may have to be done The speed of opening or closing the switch shall be designed to ensure that the arcing during the operation is reduced to the minimum.
G) Insulators i. Insulators shall be made of high strength porcelain and shall be suitable for the service voltage and BIL specified ii. Porcelain used for the manufacture of insulators shall be homogeneous and free from flaws or imperfections that might affect the mechanical and dielectric quality. They shall be thoroughly vitrified, tough and impervious to moisture. Glazing of porcelain shall be uniformly brown colour, free blisters, burs and VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 19 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
other similar defects. Insulators of the same rating and type shall be interchangeable. iii. iii) The porcelain and metal parts shall be assembled in such a manner that any thermal expansion differential between the metal and porcelain parts through the range of temperature variation shall not loosen the parts or create undue internal stresses which may affect the electrical or mechanical strength and rigidity Each cap and base shall be of high-grade cast steel or malleable steel casting and they shall be machine faced smoothly and galvanized Insulators shall be stack types.
H) Accessories i. Stainless steel nameplate shall be provided on disconnecting switches, earthing switches and operating devices The nameplate shall contain the information set out in IS-9920 & 9921 ii. Suitable locking arrangement with lock shall be provided for the isolator operating mechanism, so that, it can be locked in either fully open or fully closed positions iii. Each pole of the, disconnect switches shall be provided with two grounding pads at opposite ends, brazed to the base channel. Flexible copper ground connectors shall be provided. for connecting operating handles of disconnect switches and earthing switches to the grounding system iv. Suitable adjustable arcing horns made of tinned electrolytic copper shall be provided on disconnecting switches. 3.8.2 Lightning Arresters Lightning Arresters shall be station class non-linear resistor type for protection of switchyard equipment and transformers against lightning and switching surges The lightning arresters shall be self-supporting type in single pole Assembly suitable for outdoor installation
3.8.2.1 Design Criteria Refer Electrical System Detail (Doc. No. 254625-300-DS-ELE-001) & for environmental conditions refer Doc. No. 254625-300-SP-GEN-001.
A) Constructional features i. The arresters shall be suitable for mounting on outdoor structures ii. The arrester shall adequate thermal discharge capacity for switching surges, long duration surges and multiple strokes. The arrester shall be capable of withstanding internal pressures developed due to the above discharges without operation of pressure relief vents. iii. The arrester shall be provided with pressure relief devices, which will prevent shattering of porcelain in case of excessive gas pressure build up. iv. The insulator housing of the arrester shall be of porcelain with high mechanical strength and rigidity suitable for operation under site conditions listed in design criteria v. All metal shall be non-rusting and non-corroding metal. screws etc., shall be provided with lock washers vi. Bolts, VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 20 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
vii. Arresters shall be capable of spark over on frequent switching surges
3.8.3 Four Pole Structure (Construction) Four pole structure with bracing s and cross arms for supporting installing the pin and / or strain insulators shall be designed as per the following specification.
i) Each pole shall be heavy-duty rail (IRS-HSB) having a unit weight of 52 kg/ metre. However it should satisfy APSEB requirements.
ii) The Four Pole structure shall be designed suitable for receiving / terminating 33 kV overhead conductors or Cables of APSEB.
The structure shall designed for mounting one lightning arrester per phase at incoming as well as two outgoing feeders and Two triple pole Air-break disconnecting switches. Further this FP structure shall be provided with extra cross arm(s) arrangement to erect/ install HT XLPE Aluminum cables with outdoor termination It shall facilitate termination of each core of the HT cable directly without any further links The arrangement of all the components on this FPS shall be furnished along with the offer separate double channel (ISMC-100) cross arms shall be provided for installing sets of lighting arresters and two 3 pole Air Break switch with bus.
iii) Earth shall be excavated to make pits size 1M X 1M X 2.5M (depth) for each pole of the Four pole structure. The rail pole shall be placed over a small (50-100 mm thick) padding of concrete in perfectly vertical position and then the entire pit shall be concreted & compacted using a concrete mix of '1 cement: 3 coarse sand: 6. graded stone aggregate" including curing thereafter Compacting the soil around, using boulders / earth shall be carried out if required at no extra cost.
iv) The FP structure shall be complete with bracing's (ISA 50 x 50 6). channels ISMC-100 as cross arms for pin insulators and additionally double channel (ISMC-100) cross arms for tension / strain insulators, bus and connection conductors (DOG) wherever applicable.
v) Each rail pole of the FPS shall be provided with anti-climbing devices
vi) Each FP structure shall be earthed as per the rules of IE 3.9 Cables 3.9.1 Cable Laying Cable installation shall include power, control, lighting cables. These cables shall be laid in directly buried trenches or RCC trenches/ cable trays/ pipe sleeves as detailed in the cable layout drawings. Cable routing given on the cable layout drawings shall be checked in the field so as to avoid interference with the structures, heat sources, drains, piping, air- conditioning duct etc. Any change in routing shall be done to suit the field conditions wherever deemed necessary, after obtaining approval of Engineer-in-charge. H.V., L.V. power and control cables shall be separated from each other by adequate spacing. Details of cable routes and cable spacing not shown in detail on these drawing shall be determined by the contractor and approved by the Engineer-in-charge. When single core cables are laid in flat formation, the individual cable fixing clamps and spacers shall be non-magnetic material. As a general practice, the sheath of single core cables shall be earthed at one point to keep sheath at earth potential unless otherwise stated. Single core cables, when laid in VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 21 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
trefoil formation shall be braced by suitable clamps at a distance, not exceeding 3 meters along the cable routing.
The lengths indicated in the cables schedule are only approximate. The contractor shall ascertain the exact length of cable for a particular feeder by measuring at site. All cable routes shall be carefully measured. Before the start of cable laying, the contractor shall prepare cable drum schedule and get that approved by Engineer-in-charge to minimize/ avoid straight through joints and then the cables cut to the required lengths, leaving sufficient lengths for the terminations of cable at both ends. The various cable lengths cut from the cable reels shall be carefully selected to prevent undue wastage of cables. Extra loop length shall be given for feeder cables where required as per the directions of Engineer-in-charge to meet contingencies.
Overhead trays shall be installed 2700 mm (minimum) above grade level and 300 mm above FGL in case cable trays are installed along with pipe sleepers. At road crossing overhead trays shall be installed at 7000 mm (minimum) above grade level or cables shall be routed cable tray culvert / Electrical road crossings as per layout drawings. Sufficient care shall be taken while laying cables to avoid formation of twist, sharp bend etc. in order to avoid mechanical injuries to cables. Rollers shall be used for pulling of cables. Cable installation shall provide minimum cable bending radii as recommended by cable manufacturer.
Cables shall be neatly arranged in the trenches/ trays in such a manner that criss-crossing is avoided and final take off to the motor / switchgear is facilitated. Cable routing between cable trench and equipment / motors shall be taken through PVC/RCC sleeves of adequate size. Pipe sleeves shall be laid at an angle of maximum 45 to the trench wall. Bending radii of pipe shall not be less than 12D. It is to be ensured that both the ends of PVC/RCC pipe sleeves shall be sealed with approved weather proof sealing plastic compound after cabling. All cables shall be identified close to their termination point by cable tag numbers as per cable schedule. Cable tag numbers shall be punched on aluminium/ lead straps (2mm thick, 20mm wide and of enough length) securely fastened to the cable and wrapped around it. In unpaved areas, cable trenches shall be identified by means of cable markers. These cable markers shall be placed at location of changes in the direction of cables and at intervals of not more than 30m and also at cable straight through joint locations. All temporary ends of cables must be protected against dirt and moisture to prevent damage to the insulation. For this purpose, ends of cables shall be taped with an approved PVC end cap or rubber insulating tape.
Each row of cables shall be laid in place before covering with sand. All wall opening/ pipe sleeves shall be effectively sealed after installation of cables to avoid seepage of water inside building/ lined trench. Every cable shall be given an insulation test in presence of Engineer-in-charge/ Owner before filling the cable trench with sand. Any cable which is found defective shall be replaced. Where cables pass through foundation walls, the necessary openings shall be provided in advance for the same by another agency. However, should it become necessary to cut holes in existing structures for example floor slab etc. the electrical contractor shall determine their location and obtain approval of the Engineer-in- charge before carrying out the same. Cables for road crossings shall be taken through RCC/ Hume pipes as shown in the cable layout drawings. At road crossing and other places where cables enter pipe sleeves, adequate bed of sand shall be given so that the cables do not slack and get damaged by pipe ends.
Cables Laid Direct in Ground Cables shall be laid underground in excavated cable trenches where specified in cable layout drawings. Trenches shall be of sufficient depth and width for accommodation of all VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 22 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
cables. Cables shall be properly placed as per installation standards. Minimum depth of directly buried cable trench shall be 750 mm for L.V. and 900 mm for H.V. cables. The depth & width of the trench shall vary depending upon the number of layers of cables. It is to be ensured by the contractor that the bottom of buried trenches shall be cleared of all rocks, stones and sharp objects before cables are placed. The trench bottom shall be filled with a layer of sand or stone dust. This sand/ stone dust shall be levelled and cables laid over it. These cables shall be covered with 150 mm of sand on top of the largest diameter cable and sand shall be lightly compacted. A flat protective covering of 75 mm thick second class red bricks or concrete tiles shall then be laid and the remainder of the trench shall then be back-filled with soil, rammed and levelled.
Cables Laid in Concrete Trench Minimum depth of RCC cable trench shall be 500 mm for all voltage grades with 300 mm clearance between the bottoms of the trench cover and top of the cable. The depth and width of the trench shall vary depending upon the number of layers of cables and bending radius required for cables. Concrete cable trenches shall be filled with sand/ stone dust in hazardous area to avoid accumulation of hazardous gases and oil. RCC covers of trenches shall be effectively sealed to avoid ingress of chemical and oil. Removal of concrete covers where required for the purpose of cable laying and reinstating them in their proper position after cables are laid shall be done by electrical contractor.
Above Ground Cables Cables installed above grade shall be run in cable trays, clamped on walls, ceiling or structures and shall be run parallel or at right angles to beams, walls or columns. Each cable tray shall contain only one layer of cables as far as possible for power cables. However control cables may be laid in double layer in the cable trays.
Individual cable or small group of cables (upto 3 cables) which run along structures/ walls etc. shall be clamped by means of 16 SWG GI saddles on 25 x 6 mm sadle bars. Alternatively small group of cables can be taken through 60/100/150 mm slotted channel tray or channel ISMC-75/100. Cables shall be supported so as to prevent sagging. In general, distance between supports shall be approximately 300 mm for cables upto 25 mm diameter and maximum 450 mm for cables larger than 25 mm diameter to prevent the sagging of cables. Cables laid in supporting angle in cable trenches, structures, columns and vertical run of cable trays shall be suitably clamped by means of GI saddles/ clamps, whereas cables in horizontal run of cable tray shall be tied by means of nylon cords. Distance between supporting angles shall not exceed 600 mm. All cable trays and supporting steel structures shall be painted before laying of cables. The under surface shall be properly degreased, derusted, descaled and cleaned. The painting shall be done with two coats of approved bituminous aluminium paint unless otherwise specified.Where cables rise from trench to motor, lighting panel, control station, junction box etc. they shall be taken in PVC/ RCC pipe for mechanical protection upto a minimum of 300 mm above grade for outdoor area. Cable ends shall be carefully pulled through conduit to prevent damage to cable.
Following guide shall be used for sizing of PVC/ RCC pipe :
a). 1 cable in a pipe - 53% of pipe cross-sectional area occupied by cables.
b). 2 cables in a pipe - 31% of pipe cross-sectional area occupied by cables.
c). 3 cables in a pipe - 43% of pipe cross-sectional area occupied by cables.
d). 4 and above cables in a pipe - 40% of pipe cross-sectional area occupied by cables. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 23 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
After the cables are installed and all testing is complete, conduit ends above grade shall be plugged with a suitable weatherproof plastic compound/ bitumen/ suitable sealing compound. Alternatively rubber bushes shall be employed for the purpose of sealing. Fire proofing of end of power cables at least 1 meter at each end as per OISD norms for the Refinery and Petroleum industry, shall be carried out as per the recommendation of the paint supplier. Rates for the fire proofing of cables shall be included in the cable installation and no separate payment shall be made for the painting.
The drums under the custody of the contractor shall be neatly arranged in the yard near his site office. The drum shall not be rolled for transportation more than 10 mtr. Truck / Trailer shall be used for transportation for distance more than 10 mtr.
The cables shall be rolled out for equipment and cutting shall be as per site requirement. Cable jacks and cable rollers shall be used during laying of cable.
Electrical Contractor shall cut all cable length by actual measurement at site as per final route determined. Cable lengths indicated in Cable Schedules shall be used only to get an idea of length involved.
The cables shall be tested for insulation value before laying. Drum Schedule to be prepared by contractor.
Cables/ cable tray opening in walls and floors or through pipe sleeves from one area to another or one elevation to another shall be sealed by fire-proof sealing system. The fire- proof sealing system (FPSS) will effectively prevent the spread of fire from the flaming to non-flaming side, in the event of fire.
3.9.2 Terminations All XLPE cables upto 1100V grade shall be terminated at the equipment by means of compression type cable glands suitable for the cable size. They shall have a screwed nipple with electrical threads and check nut. The cables shall be identified close to their termination points at both the ends of cable and also along the route at recommended intervals, by cable tag numbers. All cable entries for outdoor termination shall be preferably through bottom. Power cables cores wherever colour coding is not available shall be identified with red, yellow and blue PVC tapes. Where copper to aluminium connections are made, necessary bimetallic washers shall be used. In case of control cables, all cores shall be identified at both ends by their terminal numbers by means of PVC ferrules suitable for core size. Wire numbers shall be as per schematic/ wiring/ inter-connection diagram. All unused spare cores of control cables shall be neatly bunched and ferruled with cable tag at both ends, for future use.
Contractor shall drill holes for fixing glands wherever necessary. Gland plate shall be of non-magnetic material/ aluminium sheet in case of single core cables. All unused cable entries on equipment/ panels shall be plugged/ sealed. The cable shall be terminated at electrical equipment/ switchboards through glands of proper size. The individual cores shall then be dressed and taken along the cables ways or shall be fixed to the panels with polyethylene straps. The cable glanding shall be done as per manufacturers instructions. Cable armour shall not be exposed after termination is complete. In case of termination of cables at bottom of a panel over a cable trench having no access from the bottom close fit holes shall be drilled in the gland plate for all the cables in one line, then gland plate shall be split in two parts along the centre line of holes. After fixing bottom plate, uncovered cable holes/ gaps shall be sealed with cold setting compound.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 24 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
Crimping of lugs to cable leads shall be done by hand crimping/ hydraulically operated tool as per requirement. Insulation of the leads shall be removed before crimping. Conductor surface shall be cleaned and shall not be left open. Suitable conducting jelly shall be applied on the conductor lead. Lugs shall enclose all strands of cable core. Cutting of strands shall not be allowed. The contractor shall bring to the notice of Engineer-in-charge any mismatch in cable glands, lugs provided with the equipment vis--vis to the cable size indicated in cable schedule for taking corrective action.
The cable joints in power & control cables shall be avoided as far as possible. In case a joint is unavoidable, the following shall be insured : The number of joints shall be restricted to minimize as far as possible. The location of joints shall be identified with permanent markers. No joints shall be allowed in hazardous areas without the approval of Engineer-in- charge.
The jointing and termination of low voltage power cables shall be carried out by trained personnel only. Jointing and termination of high voltage cables shall be done by skilled and experienced jointer duly approved by Engineer-in-charge. Only type tested termination kits of approved make shall be used.
No unauthorized repairs, modifications shall be carried out on the hazardous area equipment terminal boxes and junction boxes. Damaged enclosures of hazardous area equipment shall be brought to the notice of Engineer-in-charge. After termination is complete, all the bolts, nuts, hard wares of terminal box shall be properly placed in its position and tightened. Where required, cable sealing boxes intended to be used with the apparatus shall be filled with solid setting type bituminous compound unless otherwise specified. All power and control cables glands installed outdoor shall be provided with suitable sized shrouds and rates for the same shall be included in the scope of the termination of the cable glands. No separate payment is envisaged for the same.
3.9.3 Cable Trays 3.9.3.1 The Cable Trays shall be ladder type unless otherwise specified.
3.9.3.2 The Trays shall be painted with two coats of primer followed by two coats of final paint.
3.9.3.3 The Trays shall have suitable provision for clamping at an interval of 500 mm.
3.9.3.4 The Earthing Strip for the earthing ring shall be run along the side of the tray.
3.9.3.5 The connection between individual equipment to the ring shall be by bracing or with lugs.
3.9.3.6 The trays shall be supported as per installation drawings. If necessary, additional supports shall be provided. The supporting arrangement shall be approved by site engineer.
3.9.3.7 The bending of trays shall be smooth and the curvature sufficient for each bending of cables in it.
3.9.3.8 Electrical Cable Tray routing shall be co-ordinated by Electrical Contractor at site to check fouling with pipes, equipment, light fittings and instrument trays, etc. before fixing the trays.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 25 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
3.9.4 Cable Glands Cable glands shall be of nickel plated brass unless otherwise specified. The double compression type cable glands shall be used for indoor panels/ equipment (e.g. substation, control room etc). The cable glands for outdoor terminations shall be weather protected, double compression type. Cable gland forming a part of relevant FLP enclosure shall be FLP type, tested by CIMFR or other recognized independent testing laboratory and approved by CCoE/ DGMS or any other statutory authority as applicable. Indigenous FLP glands shall have valid BIS license as per the requirements of statutory authorities. The size of cable glands supplied shall be appropriate to the size of cable so that frame proofness of glands is retained. Entry thread of cable gland shall be compatible to the entry thread provided in the equipment (BS, ET, NPT, PG as applicable). If required, suitable reducers/ adopters shall be used.
3.9.5 Connectors Power cable terminations shall be made with crimped type tinned copper solder less lugs which shall be suitable for the cable size mentioned in cable schedule.
3.9.6 Ferrules Ferrules shall be of approved type and of size to suit core size mentioned and shall be employed to designate the various cores of control cable by the terminal numbers to which the cores are connected, for ease of identification. Ferrule shall be printed type.
3.9.7 Testing and Commissioning of Cables Before energising, the insulation resistance of every circuit shall be measured from phase to phase, phase to neutral and from phase/ neutral to earth. Where splices or terminations are required in circuits rated 650 volts, insulation resistance of each length of cable shall be measured before splicing and/ or terminating. After completion of splices and/ or terminations measurements shall be repeated. The insulation resistance of directly buried cables shall be measured before cable trenches are backfilled. Measurement shall be repeated after back filling. For cables upto 1.1 kV grade 1000V Meggar and for H.V. cables 2.5 / 5 kV Meggar shall be used.
D.C. High Voltage test shall be conducted on cables given below after installation. a). All 1100V grade power cables in which straight through joints have been made. b). All cables above 1100V grade.
D.C. High Voltage test shall be performed as detailed below in the presence of the Engineer-in-charge or his authorized representative only. Cables shall be installed in final position with the entire straight through joints complete. During the high voltage test, all other electrical equipment related to the cable installation, such as switches, instrument transformers, busbars etc. must be earthed and adequate clearance shall be maintained from the other equipment and framework to prevent flashover. In each test, the metallic sheath/ screen/ armour shall be connected to earth. All test readings shall be recorded and submitted to Engineer-in-charge.
3.10 Earthing The main earth grid conductor shall be hot galvanised M.S. flat unless otherwise specified. Sizes for main conductors shall be as indicated on the earthing layout drawing. Amount of galvanizing shall be 610gm per sq.metre. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 26 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
3.10.1 Earthing Network This consists of main earth conductor (grid conductor) forming a closed ring network with required number of earth electrodes connected to it to provide a common earth for electrical devices and metallic structures. From each earth electrode two distinct connections shall be made to the main earth conductor. The earth plates shall be used for taking multiple earth connections to two or more equipment.
The earth conductor shall be laid along cable trays / cable trench / pipe racks as indicated on the earthing layout drawing. Where lined cable trenches are available, the earth conductor shall be laid in the trenches and shall be firmly cleated to the sidewall of concrete trenches using GI clamps at interval of 400 mm to 500 mm and near to the termination end. The earthing conductor shall run along one of the cable trays along a cable route. The earthing conductor shall be suitably cleated and electrically bonded to all the other cable trays on the same cable route at a regular interval of 25 to 30 meter. The earthing for equipment shall be tapped from the main earth conductor and not from cable tray support structure. Earth conductor when laid underground shall be at a depth of 500mm below finished grade level.
Joints and tapping's in the main earth loop shall be made in such a way that reliable and good electrical connections are permanently ensured. All joints below grade shall be welded and shall be suitably protected by giving two coats of bitumen and covering with Hessian tape. Earth strip laid above ground shall be welded across straight through joints and joints shall be suitably protected by giving two coats of bitumen to avoid oxidation and insulation film formation of the strip surface. When two earth strips are to be jointed by means of welding, lap welding with an overlapping of strip equivalent to double the width of the strip and all four sides shall be continuously welded. All joints at tappings above ground shall be by means of connector/lugs. A minimum of two bolts of adequate size shall be used for this purpose. Earthing strip joints at earth plate and equipment shall be through GI bolts, nut etc.
3.10.2 Installation of Maintenance Free Earth Electrode Earth Electrode shall be installed as shown on installation standard and layout drawings. The location shown on the layout drawings are indicative. The exact location of earth electrodes in the field shall be determined by contractor in consultation with the Engineer- in-charge, depending on the soil strata and resistivity. Earth electrodes shall be located avoiding interferences with road, building foundation, column, pipelines etc. The civil area drawings shall be referred for this.
High quality tripod earthing shall be provided to conduct & dissipate the fault current as fast as possible. The triangular termination is made of a set of three copper-bonded steel earth rods of 2m each arranged in a triangular fashion and separated from each other by a distance at least equal to their driven depth and interconnected by a flat copper conductor (copper strip). For any one of tripod earthing electrode, inspection chamber shall be provided as indicated in drawing.
Electrodes shall preferably be located in a moist soil which has a fine texture, grain size and distribution. Wherever practicable the soil shall be dug up, all lumps broken and stones removed from the immediate vicinity of the electrodes and soil packed by watering and ramming as tight as possible.
The electrodes shall have a clean surface, not covered by paint, enamel, grease or other materials of poor conductivity.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 27 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
All earth electrodes shall be tested for earth resistance by means of standard earth test meter. The tests shall take place in dry months, preferably after a protracted dry spell.
The disconnect facility shall be provided for the individual earth electrode to check its earth resistance periodically. Location of earth electrodes shall be marked by permanent markers for easy identification. All earth Electrodes shall be serial numbered and also marked on 'As Built' drawing for future reference.
Individual earth electrodes shall be provided for each lightning arrestor.
Earthing system provided for concrete paved area by other agency where applicable; shall be connected to the plant earthing system below ground by minimum two earth connections. 3.10.3 Connection The earth system connections shall generally cover the following: - Equipment earthing for personnel safety - System neutral earthing - Static and lightning protection
The following shall be earthed. - System neutral - Current and potential transformer secondary neutral - Metallic non-current carrying parts of all electrical apparatus such as transformers, switchboards, bus ducts, motors, neutral earthing resistors, capacitors, UPS, battery charger panels, welding receptacles, power sockets, lighting/power panels, control stations, lighting fixtures etc. - Steel structures/ columns, rail loading platforms etc. - Cable trays and racks, lighting mast and poles - Storage tanks, spheres, vessels, columns and all other process equipment. - Fence and Gate for electrical equipment (e.g. transformer, yard etc.) - Cable shields and armour - Flexible earth provision for Wagon, Truck - Shield wire
Type & size of earth conductor shall be as follows:
Equipment Earthing Strip / Wire Size (a) Main Grid : GI strip, Size Based on calculations (b) Motor up to 3.7 kW : 2Nos., 8 SWG Solid wire (c) Motor 5.5 kW to 30 kW & Welding Receptacles : 2Nos., 25 sq.mm earthing cable (d) Motors 30 kW to 110 kW : 2 Nos., 120 sq.mm earthing cable (e) Motors above 110 kW : 2Nos., 185 sq.mm earthing cable (f ) Building columns, (vertical & horizontal), Loading Racks and pipe racks. : 40 x 5 Strip (Building Column-2Nos. Diagonally opposite, Loading Racks & Pipe rack- at every 30mt). VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 28 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
(g) Storage Tanks : 2 Nos. 50 x 6 mm Strips for Storage tanks (2/3Nos. depending on Tank diameter). (h) Vessels & Heat Exchangers : 2Nos., 10 mm (3/8) dia. Wire Rope (i ) Small Equipment & Instruments, Local Push Button Stations : 2Nos., 8 SWG Solid wire (j ) MV/LV Switchgear, Power Trans., Earth Grid around Substation, Main Grid Process Units 2Nos., 50 x 10 mm G.I. Strip ( k ) Main Earth Grid for Pump House / Tank Areas MCC Room etc. 50 x 10 mm G.I. Strip ( l ) Lightning conductor-down comers / Horizontal air termination : 25 x 6 mm Strip
Location of Earth Conductor : Buried / in Cable Trays Lightning Protection : For Administration, Control Room, Sub- station Building & High Masts. Air Termination : Yes Down Conductors : 32 x 6 mm thick G.I. Strip Roof (Horizontal) Conductor : 25 x 6 mm thick G.I. Strip
All process pipelines shall be bonded and earthed at the entry and exist points of battery limit of hazardous area.
Steel pipe racks in the process units and offsite area shall be earthed at every 24 meters.
Lightning protection shall be provided for the equipment, structures and buildings as shown on layout drawing. Self conducting structures shall not require separate aerial rod and down conductors. These shall however be connected to the earthing system at two or more points as shown on layout drawing. An independent earthing network shall be provided for lightning protection and this shall be bonded at least at two points with the main earthing network below ground. Lightning down conductor shall be brought to earth electrode in shortest straight path as feasible to minimise surge impedance.
The main earthing network shall be used for earthing of equipment to protect against static electricity. All medium and high voltage equipment (above 250V) shall be earthed by two separate and distinct connections with earth.
Plant instrument system clean earthing, UPS system clean/safety earth, Data concentrator panel, HMI etc shall be separate from the electrical earthing system.
All paint, scale and enamel shall be removed from the contact surface before the earthing connections are made.
All earthing connections for equipment earthing shall be preferably from the earth plate mounted above ground wherever provided.
Equipment foundation bolts shall not be used for earthing connection. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 29 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
Earth connections shall be made through compression type cable lugs/by welded lugs.
All hardware used for earthing installation shall be hot dip galvanised or zinc passivated. Spring washers shall be used for all earthing connections and all connections adequately locked against loosening.
Lighting fixtures and receptacles shall be earthed through the extra core provided in the lighting circuit/cable for this purpose. 3.10.4 Testing and Commissioning of Earthing System Earthing system / connections shall be tested as follows :
Resistance of individual earth electrodes shall be measured after disconnecting it from the grid by using standard earth test meggar. Earthing resistance of the grid shall be measured after connecting all the earth electrodes to the grid. The resistance value of an earth grid to the general mass of earth shall be as follows :
For the electrical system and equipment a value that ensures the operation of the protection device in the electrical circuit but not in excess of 4 ohms. However for plant grid, resistance value shall not be more than 1 ohm.
For lightning protection, the value of 5 ohms as earth resistance shall be desirable, but in no case it shall be more than 10 ohms.
The resistance to earth shall be measured typically at the following points : a) At each electrical system earth or system neutral earth. b) At each earth provided for structure lightning protections. c) At one point on earthing system used to earth electrical equipment enclosures. d) At one point on earthing system used to earth wiring system, enclosures, such as metal conduits and cable sheaths or armour. e) At one point on fence enclosing electrical equipment.
3.11 Lighting Installation 3.11.1 General The lighting fixtures in the plant shall be fed from lighting panel. All outdoor lighting shall be group controlled manually or through synchronous timer or photocell. Lighting wiring between panel and lighting fixtures shall be done with PVC insulated 3-core (phase, neutral and earth) copper conductor armoured cable for hazardous areas. All joints of conductors in Switch boards/ JBs Fittings shall be made only by means of approved mechanical connectors (nylon/PVC connectors). Bare twisted joints shall not be permitted any where in the wiring system.
The lighting layouts furnished by owner will indicate approximate locations of lighting fixtures. The electrical contractor shall determine, with approval of Engineer-in-Charge, the exact locations of each fixture in order to avoid interference with piping or other mechanical equipment and also with a view to obtain as much uniform illumination as practicable, and to avoid objectionable shadows.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 30 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
On walkways, platforms and other outdoor area, lighting fixtures shall be located nearer to landing of stairs or ladders, gauges, flow meters, panel boards and other equipment to provide proper illumination.
All outdoor cable terminations to outdoor junction boxes, panels, socket outlets etc. shall be through bottom or from side. Top entries for cables shall be avoided to avoid water entry. All cable glands for outdoor terminations shall be double compression type and the gland shall be covered with PVC or rubber boot shroud. All unused cable entries shall be plugged with suitable blanking plugs.
Mounting height of equipment shall be as under:-
Top of Switch Box : 200 mm from FFL (Finished floor level) Top of Lighting/Power Panel : 1800mm from FFL Lighting fixture : As indicated in layout drawing
Fixtures shall be firmly supported from the structures. Support clamps etc. may be bolted or welded to the existing steel work or metal inserts. In case of concrete structures, where metal inserts are not available, fixtures shall be suspended from concrete surfaces with the help of anchor fasteners. In such cases special care shall be taken to see that anchoring is firm.
Circuit cables in a group shall be cleated to structure by using galvanised strip clamps or cable run in cable trays wherever trays are available. Spacers and cleats shall be of required size to accommodate the cables. All hardware shall be galvanised or zinc passivated. Underground lighting cables (in paved areas) shall be taken in suitable GI sleeves buried at a minimum depth of 300mm from FFL. GI pipe sleeves shall be extended to 300mm above FFL. Exact termination/layout of GI pipes (for protection of cables) shall be decided at site as per site convenience in consultation with Engineer-in-charge.
Wiring for all outlet sockets shall be done with 3 cores of equal sizes for phase, neutral and earth. The terminals of switch sockets shall be suitable to receive the size of wire specified.
All lighting fixtures shall be provided with terminal block with required terminals suitable for connection of wire up to 2.5 sq. mm copper conductor.
The cable shall be straightened after unwinding it from the drum. All cables are clamped/ laid in straight run without any sag and kink.
3.11.2 Hazardous Area Installation Wiring in hazardous area shall be done by using minimum 2.5mm2 copper conductor armoured cable. Circuit wiring feeding hazardous areas shall be controlled by two pole switches/MCBs (for phase as well as neutral isolation).
Correct type of lighting equipment (fixtures and JBs) with regard to hazardous protection as specified in the drawing shall be installed for the areas classified as Zone 1, Zone 2 etc.
The terminations in the junction boxes and the lighting fittings shall be done avoiding possibility of loose connections due to vibrations. After the terminations are made the cover of the junction boxes and the lighting fittings shall be closed properly with all bolts and hard wares in correct position, retaining its explosion and weather protections. In fixtures having double cable entries, both the entries shall be used for looping in and looping out connection, thus minimising the use of a separate junction box. Wherever separate control VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 31 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
gear boxes (CG box) are provided looping in and looping out connections shall be through CG box, thus avoiding the use of an additional junction box. All unused cable entries shall be sealed with suitable plugs.
Circuit cables shall be firmly cleated in a group along columns/ beam/ladders/side channels/platform using 1.6mm thick GI saddles on 25x3 mm GI saddle bar at intervals of 400mm to 500mm for straight run and on either side close to bending and at both termination ends as per the directions of Engineer-in-charge. Where required 3 or more of cables shall be taken in perforated 100mm cable tray after getting the approval of Engineer- in-charge. Cables shall not be routed along hand rails.
Where fire proofing column/structures are encountered, all cabling shall be taken in GI pipes of required size and both ends shall be sealed, well before fire proofing is done. Similarly equipment such as lighting fixture, control gear box, lighting/ power panels, field call stations, junction boxes etc. shall be installed on suitable steel mounting frame/distance bracket, thereby avoiding direct contact with the concrete used for fire proofing.
Cable glands for terminating cable on flameproof equipment shall be of double compression FLP type. Any material/equipment specified to be supplied by contractor for installation in hazardous areas, shall be tested by CMRI and duly approved by CCOE or DGMS or any other applicable statutory authority. All indigenous FLP equipment shall also have valid BIS license as required by statutory authorities.
3.11.3 Testing and Commissioning of Lighting system 3.11.3.1 Lighting installation shall be tested and commissioned by installation contractor as per specifications. Precommissioning checks and tests shall include but not be limited to the following: (i) The insulation resistance of each circuit without the lamps (load) being in place shall be measured. (Between phases, phases to neutral, phase/ neutral to Earth). (ii) Current and voltage of all the phases shall be measured at the lighting panel bus bars with all the circuits switched on with lamps. If required load shall be balanced on the three phases. (iii) The earth continuity for all socket outlets shall be checked. A fixed relative position of the phase and neutral connections inside the socket shall be established for all sockets. (iv) After inserting all the lamps and switching on all the circuits, minimum and maximum illumination level shall be measured in the area and recorded. (v) It shall be ensured that switch provided for ON/OFF control of point (light/ fan/ socket) is only on LIVE side. (vi) Operation of ELCB's shall be checked.
Contractor shall duly fill in all the above test results and submit the test reports to Engineer- in-Charge in triplicate.
3.11.3.2. All lighting layout drawings shall be marked by contractor for 'AS BUILT STATUS' and two sets of hard copies plus 1 set of soft copy in CD, shall be submitted to Owner.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 32 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
4 Field Inspection, Testing and Commissioning 4.1 Contractor shall carry out complete field inspection, testing and commissioning of electrical equipment.
4..2 Before the completed installation or an addition to the existing installation is put into service, inspection / pre-commissioning checks and tests shall be carried out by contractor. In the event of defects being found out, the same shall be rectified and the installation retested as applicable.
4.3 The pre-commissioning inspection among other requirements shall include visual inspection, checking the workmanship of the installation, the rating of equipment, safety clearances, sizes of cables installed, conformance to the AFC document, soundness of switchgear bus connections, wiring properly dressed and labeled, sealing of unused cable entries, checking of all safety interlocks, control/interface functions as per requirement etc.
4.4 Visual inspection for soundness of bus bar connections of busducts, terminal connections of equipment/motor shall be carried out. It shall be ensured that no foreign materials are present inside busduct and equipment terminal boxes. After the visual inspection, all the covers of terminal boxes, inspection chambers shall be refitted with gaskets, bolts & nuts as per equipment manufacturer's instructions.
4.5 Pre-commissioning tests shall include but not be limited to the following: - Continuity test for each winding and power and control circuits. - Insulation test for each winding and power and control circuit - High voltage test for cables - Dielectric strength test on transformer oil. - Checking the correctness of wiring schemes, control circuit interlocks for intended functioning. - Verification of phase sequence. - Testing of all types of relays/releases for required operation. - Testing of measuring instruments for proper functioning. - Earth continuity test for all circuits. - Checking of safety features for correctness of operation etc. - Checking of all wired interface contacts (analog, digital input/output contacts) for TAS interface, at panel and equipment terminal chambers as applicable. (Electrical contractor shall co-ordinate with other agencies involved for the above and provide support services for checking interfaces of electrical equipment and the intended functioning) - Earth resistance measurement for each earth electrode, and the earthing system as a whole. - Lighting installation shall be tested for correct illumination levels, with the fittings installed. Fittings shall be operated only with specified type of a lamp or tube.
4.6 After the above tests and inspection are completed, control circuits shall be tested for correct operation under all operating combinations and proved correct before applying power to main circuits. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 33 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
4.7 A close visual inspection of electrical equipment in hazardous areas shall be made to ensure that equipment is suitable for the classified zone and gas group and correctly installed, with all covers, bolts, nuts and hardwares intact and there is no physical damage mark seen on the enclosure.
4.8 Site Acceptance Test procedure for specific equipment shall be furnished by the respective equipment vendor. The contractor shall provide necessary assistance to the equipment vendor to perform Site acceptance testing to enable the equipment vendor to perform the same.
4.9 All pre-commissioning checks and tests shall be carried out as per the directions of Engineer-in-charge. In addition to the equipment manufacturer's instructions, pre- commissioning check requirements shall also be complied. All tests shall be carried out by contractor in the presence of Owner's representatives.
4.10 The contractor shall bring to site all required tools, tackles, and testing instruments for carrying out field testing. Contractor shall use only calibrated measuring and test instruments and shall maintain calibration records.
4.11 The Insulation Resistance test values for various electrical equipment shall be as below:
4.11.1 Cables The insulation resistance test values for cables shall be as per following table:
Rated voltage of the Cable DC Test Voltage in Volts Minimum Insulation resistance in Mega ohms Lighting and power circuit wiring 250 1 650/1100V grade cables 1,000 10 1,900/3,300V grade cables 1,000 200 19,000/3 3000V grade cables 5,000 200
4.11.2 HV, LV and Miscellaneous Switchboards The insulation resistance test values for the switchboards shall be as per following table:
Rated voltage of the Switchboard DC Test Voltage in Volts Minimum Insulation resistance in Mega ohms 33,000V 5,000 200 415V 1,000 100 240V 500 10 110V 500 10
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 34 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
4.11.3 Generators and Motors The insulation resistance test values for the Generators and Motors shall be as per following table:
Rated voltage of the Generators and Motors DC Test Voltage in Volts Minimum Insulation resistance in Mega ohms at 40 C 3,300V 1,000 50 415V 1,000 15 240V 500 12
4.11.4 Transformers The insulation resistance test values for the Transformers shall be as per following table:
Rated voltage of the Transformers DC Test Voltage in Volts Minimum Insulation resistance in Mega ohms at 40 C Up to 600V 1,000 100 601 to 5000V 2,500 1,000 5001 to 15,000V 5,000 5,000 15001 to 35,000V 5,000 10,000
4.12 It shall be ensured that during insulation tests, electronic devices and components that are liable to get damaged on applied test voltage shall be disconnected from circuit. The instructions of equipment/panel manufacturer shall be followed strictly in this regard.
4.13 High-voltage testing
4.13.1 D.C. high voltage test shall be conducted as per following table on all H. V. feeder cables and also on 1100 V grade cables where straight through joints have been made.
Rated Voltage of Cable (kV) TEST VOLTAGE (kV) BETWEEN Duration (Minutes) U0/U* Any Conductor and Metallic Sheath/ Screen/Armour Conductor to Conductor (For Unscreened Cables)
0.65/1.1 3 3 5 1.9/3.3 5 9 5 19/33 60 - 5
* U 0 : Phase Voltage U : Line Voltage
4.13.2 The cable cores must be discharged on completion of DC high voltage test and cable shall be kept earthed until it is put into service.
4.13.3 DC test voltage for old cables shall be 1.5 times rated voltage or less depending on the age of cables, repair work or nature of jointing work carried out, etc. In any case, the test voltage shall not be less than the rated voltage.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 35 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
4.13.4 Provide commissioning assistance to the major equipment supplied vendor.
4.13.5 It shall be ensured that the electrical inspectorate approval is available before energising the equipment. 5 Contractor shall provide the following items in substation, as per Indian Electricity Rules: 5.1 First aid boxes containing ointments and medicines for immediate treatment of injuries (As prescribed by Indian Red Cross Society or equivalent).
5.2 Instructions of restoration of persons suffering from electric shock in English, Hindi and local language of the district shall be affixed in a conspicuous place. 5.3 Danger boards (HV., MV.) shall be provided on transformer gate, switchboards, entrance to switchgear room and at other places as required by Engineer-in-charge. 6 Miscellaneous equipment The miscellaneous equipment includes all the equipment which are not explicitly covered in equipment specification. This includes mainly following:
i) Protective rubber mats of appropriate grade. ii) First aid kit in a cabinet. iii) Danger/Caution boards. iv) Shock treatment Chart. v) Hand Gloves of appropriate grade. vi) Ceiling fans, Exhaust fans & Air Circulator. vii) Canopy viii) Anchor fastener ix) Insert Plates x) Sealing of pipes & Sealing plugs xi) Adaptor/Reducer xii) GI/PVC/Hume pipes xiii) Conduits & Accessories xiv) Structural Steel xv) Gravel spreading in Transformer(s) area. xvi) Rails for transformer(s). 7 List of Construction Equipment The contractor shall have all necessary construction equipment, tools and tackles and testing instruments to carry out the erection works and to commission the system as specified. These shall include but not be limited to the following and these shall be brought to site by contractor before the start of work. 7.1 Equipment: i. Portable grinder ii. Portable welding machine iii. Portable gas cutting / welding set. iv. Pipe threading machine. v. Pipe bending machine (hydraulic). vi. Portable drill machine suitable to take up drilling sizes as per requirement. vii. Dewatering pump sets (diesel driven). viii. Power Hacksaw. ix. Conduit dye set. x. Hydraulic crimping machine with round/ hexagonal dye set. VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-SP-ELE-009 Rev: B Page 36 of 36
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-SP-ELE-009.doc
xi. Hand crimping tool. xii. Portable electric blowers, vacuum cleaners. xiii. Miscellaneous items such as slings, pulleys, tarpaulins, wooden sleepers, ladders etc. as required. xiv. Safety belts, safety goggles and gloves. xv. Separate tool kit for each Electrician. xvi. Hydraulic/ Hand held grease gun. 7.2 Test Instruments i. Insulation tester 1000V hand driven. ii. Insulation tester 2500V motor/ hand driven. iii. Insulation tester 5000V motor/ hand driven. iv. Phase sequence indicator. v. Earth resistance tester. vi. Single phase variac. vii. 3 phase variac of adequate capacity. viii. Secondary and primary injection testing kit. ix. Multimeter, both analogue and digital. x. Portable Ammeters, Wattmeters, P.F. meters. xi. Portable Voltmeters. xii. Clip on meters of different ranges. xiii. Tacho-meter. xiv. Kelvins double bridge for measurement of very low resistance. xv. D.C. high pot test kit. xvi. A.C. high pot test kit. xvii. Oil filtration machine of adequate capacity. xviii. Lux Meter to measure illumination levels. xix. Breaker timing 3 pole kit. xx. Timers xxi. 100A D.C. milli volt drop (Contact resistance) kit. xxii. Vibration measuring instrument. xxiii. Thermo meters. 8 Clearance and Safety For every electrical switchboard, control panel, motor control centres, etc, that require back access the space behind the equipment shall generally be 1,000 mm but in no case be less than 762 mm. This space shall also be adequate to permit atleast a 90 degree opening of doors or hinged panels. In such cases where back clearances are provided, there shall be a passage-way from either end of the equipment clear to a height of 1,800 mm. Where the equipment are not required to be attended from the back, the equipment shall be placed along with wall / structure having clearances less than 200 mm. For all switchboards, control panels, motor control centres, a clear space of not less than 1,000 mm shall be provided in front of the equipment. In case where the equipment is provided with drawout unit, a minimum clearance of 2,000 mm shall be provided. For all electrical equipment a minimum clear headroom of 500 mm shall be provided. All electrical equipment operating on 415V or higher voltage shall be provided with caution notice boards of approved type and shall be affixed permanently in a conspicuous position. Where a group of equipment is located within a switch / control room or within a fenced area, the notice board shall be fixed at the entrance. In front of all the switch boards, rubber mats shall be provided for personal safety.
VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 22 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc
Appendix-G: Schedule of Quantity [Refer Doc. No. 254625-300-SC-ELE- 008 (Part A)] [Refer Doc. No. 254625-300-SC-ELE- 009 (Part B & C)] UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) FOUR POLE STRUCTURE 1 SUPPLY OF FOUR POLE STRUCTURE. FOUR POLE STRUCTURE SHALL BE WITH BRACINGS AND CROSS ARMS FOR SUPPORTING THE PIN / OR STRAIN INSULATORS. EACH POLE SHALL BE HEAVY DUTY RAIL (IRS - HSB) HAVING A UNIT WEIGHT OF 52 KG / METER. FOUR POLE STRUCTURE SHALL INCLUDE GOD, LA, EARTH SWITCH, CT, PT, METERING CUIBICAL, INSULATORS AND JUMPER ETC AS PER SPECIFICATIONS, SLD AND APSEB GUIDELINES . SET 1 2 SUPPLY OF 33KV ( E ) 3C X 400 Sq.mm STRANDED ALLUMINIUM CONDUCTOR SCREENED XLPE INSULATED ARMOURED CABLES EXTRUDED FRLS PVC OUTER SHEATHED WITH NECESSARY ACCESSORIES & 33kV OUTDOOR TYPE TERMINATION KITS. GENERALLY CONFORMING TO IS 7098 PART 2 FOR CONVERSION OF OVER HEAD LINE TO UNDER GROUND CABLE SYSTEM. MTR. 200 TWO RUNS EACH OF 100 Mtr. LOCAL CONTROL STATION FLAME PROOF LOCAL CONTROL STATIONS SUPPLY OF FLAME PROOF Ex-d FOLLOWING TYPE LOCAL CONTROL STATION SUITABLE FOR ZONE - 1 & 2 GASS GROUP II A & II B. TEMPERATURE CLASS - T3 IP-55. THE ENCLOSURE SHALL BE MADE OF CAST LIGHT METAL ALLOY WITH 2 NOS SUITABLE SIZE KNOCK OUTS FOR CABLE CONNECTION WITH CANOPY.
3 EMERGENCY STOP PUSH BUTTON TYPE A NO. 5 4 START / STOP PUSH BUTTON WITH LOCAL / REMOTE SELECTOR SWITCH & AMMENTIES TYPE B NO. 33 INDUSTRIAL TYPE LOCAL CONTROL STATION SUPPLY OF INDUSTRIAL FOLLOWING TYPE LOCAL CONTROL STATION THE ENCLOSURE SHALL BE MADE OF CAST LIGHT METAL ALLOY IP-55 WITH 2 NOS SUITABLE SIZE KNOCK OUTS FOR CABLE CONNECTION WITH CANOPY. 5 EMERGENCY STOP PUSH BUTTON TYPE C NO. 2 6 START / STOP PUSH BUTTON WITH LOCAL / REMOTE SELECTOR SWITCH & AMMENTIES TYPE D NO. 22 SOCKET OUTLETS SUPPLY OF FOLLOWING TYPE SWITCH- SOCKET OUTLETS. FLAMEPROOF Ex-d TYPE SUITABLE FOR ZONE-1 & ZONE-2, GAS GROUP IIA/IIB. TEMPERATURE CLASS - T3 IP-55 SWITCH SOCKET UNITS 7 63A TPN THREE PHASE 440VOLTS 5PINS SWITCH SOCKET OUTLETS NO. 13 INDUSTRIAL TYPE (NON FLAME PROOF ) IP-55 8 63A TPN THREE PHASE 440VOLTS 5PIN SOCKET OUTLET NO. 6 REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 1 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 9 16A SINGLE PHASE 240 VOLTS 3PIN SWITCH SOCKET OUTLETS NO. 5 10 16A, 240V SINGLE POLE SWITCH NO. 4 11 FLAMEPROOF RECHARGEABLE TORCHES NO. 4 12 NON-FLAMEPROOF RECHARGEABLE TORCHES NO. 4 MAINTENANCE FREE EARTHING & LIGHTNING PROTECTION SYSTEM EARTHING STRIPS SUPPLY OF HOT DIPPED GALVANISED (GI) BARE EARTH CONDUCTOR. GI COATING SHALL BE 85 MICRON 13 75 x 12 MM GI STRIP MTR. 1250 14 40 x 5 MM GI STRIP MTR. 400 15 50 x 10 MM GI STRIP MTR. 3800 16 50 x 6 MM GI STRIP MTR. 1040 17 25 x 6 MM GI STRIP MTR. 250 GI WIRE ROPES SUPPLY OF GI WIRE / WIRE ROPE OF STRANDED TYPE WIRES OF FOLLOWING SIZES 18 8 SWG GI WIRE MTR. 4728 EARTHING CABLES SUPPLY OF 600VOLT GRADE PVC INSULATED ALLUMINIUM CONDUCTOR UNARMOURED CABLES OF FOLLOWING SIZES. . 19 1C X 4 Sq.MM CABLE MTR. 800 20 1C X 25 Sq.MM CABLE MTR. 1310 21 1C X 120 Sq.MM CABLE MTR. 300 22 1C X 185 Sq.MM CABLE MTR. 160 MAINTENANCE FREE EARTHING PITS & PLATE EARTH ELECTRODE SUPPLY OF FOLLOWING EARTH ELECTRODES TRIPOD EARTH ELECTRODE: 23 TRIANGULAR TERMINATION CONSISTS OF A SET OF THREE COPPER-BONDED STEEL EARTH RODS OF 2M EACH ARRANGED IN A TRIANGULAR FASHION & SEPARATED FROM EACH OTHER BY A DISTANCE AT LEAST EQUAL TO THEIR DRIVEN DEPTH & INTERCONNECTED BY A FLAT COPPER CONDUCTOR (COPPER STRIP) WITH INSPECTION CHAMBER AS PER STANDARD INSTALLATION DRAWING. NO 78 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 2 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 G.I. PLATE EARTH ELECTRODE 24 G.I.PLATE ELECTRODE OF SIZE 600 x 600 x 10mmWITH 2 NOS. 50 x 6 mm G.I.EARTH STRIPS UP TO TEST LINK, CLASS B 50 mm DIA G.I.PIPE, FUNNEL WITH WIRE MESH FOR WATERING, ,SALT CHARCOAL, 12MM G.I.COVER WITH NECESSARY BRICK INSPECTION CHEMBER ETC. AS PER IS 3043, INCLUDING SUPPLY & INSTALLTION OF EARTH PIT MARKER. REFER ATTACHED STANDARD INSTALLATION DRAWING. NO 4 EARTH BUS 25 SUPPLY OF EARTH BUS MADE WITH 75 X 12MM GI. FLAT OF APPROXIMATE 850 MM. LENGTH INCLUDING DRILLING HOLE. REFER ATTACHED STANDARD INSTALLATION DRAWING. NO. 15 26 SUPPLY OF EARTH BUS MADE WITH 75 X 12MM GI. FALT OF APPROXIMATE 550MM.LENGTH AS REQUIRED INCLUDING DRILLING HOLE. REFER ATTACHED STANDARD INSTALLATION DRAWING. NO. 171 EARTH PIT MARKER 27 SUPPLY OF EARTH PIT MARKER INDICATING EARTH RESISTANCE & TESTED DATE, NEXT DUE DATE FOR TESTING. REFER ATTACHED STANDARD INSTALLATION DRAWING. NO. 78 GI CABLE TRAYS ALL THE CABLE TRAYS, BENDS AND BRANCHES, AS REQUIRED SHALL BE SUPPLIED / FABRICATED BY CONTRACTOR. RATE OF SUPPLY SHALL BE PAID ON THE BASIS OF RUNNING METER ON THE CABLE TRAY MEASUREMENT. NO SEPARATE RATE WILL BE PAID FOR BENDS AND BRANCHES. TRAY COVERS SHALL BE PROVIDED FOR TOP MOST TRAY IN OUT DOOR AREAS. LADDER TYPE TRAYS SUPPLY OF GI LADDER TYPE CABLE TRAYS OF FOLLOWING SIZES : 28 300 MM WIDE GI TRAY MTR. 286 29 500 MM WIDE GI TRAY MTR. 1425 30 900 MM WIDE GI TRAY MTR. 1660 GI TRAY COVER SUPPLY OF FRP TRAY COVERS TO SUIT FOLLOWING TRAY SIZES : 31 300MM WIDE GI TRAY MTR. 160 32 500MM WIDE GI TRAY MTR. 1216 33 900MM WIDE GI TRAY MTR. 960 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 3 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 SUPPLY OF CABLES OF VARIOUS GRADES (HT/LT) AND TYPES (XLPE / PVC) 33 kV CABLES 33KV ( E ) EARTHED STRANDED ALLUMINIUM CONDUCTOR SCREENED XLPE INSULATED ARMOURED CABLES EXTRUDED FRLS PVC OUTER SHEATHED GENERALLY CONFORMING TO IS 7098 PART 2 34 3C X 300 SQMM A2XFaY MTR. 310 POWER CABLES POWER CABLES: 600/1100V GRADE, XLPE INSULATED, AL/CU. CONDUCTOR ARMOURED, EXTRUDED PVC INNER SHEATHED & EXTRUDED FRLS PVC OUTER SHEATHED CONFORMING TO IS 7098 - PART 1. 35 1C X 630 A2XWaY MTRS. 53850 36 2C x 4 SQ.MM. A2XWY MTRS. 515 37 2C x 10 SQ.MM. A2XWY MTRS. 1735 38 2C x 25 SQ.MM. A2XFY MTRS. 425 39 3C x 2.5 SQ.MM. Cu2XWY MTRS. 7000 40 3C x 16 SQ.MM. A2XFY MTRS. 1500 41 3C x 25 SQ.MM. A2XFY MTR. 1985 42 3C x 50 SQ.MM. A2XFY MTR. 1555 43 3C x 70 SQ.MM. A2XFY MTR. 2275 44 3C x 95 SQ.MM. A2XFY MTR. 5485 45 3C x 120 SQ.MM. A2XFY MTR. 3455 46 3C x 150 SQ.MM. A2XFY MTR. 6115 47 3C x 185 SQ.MM. A2XFY MTR. 1625 48 3C x 240 SQ.MM. A2XFY MTR. 360 49 3.5C x 35 SQ.MM. A2XWY MTR. 4515 50 3.5C x 50 SQ.MM. A2XFY MTR. 1355 51 3.5C x 70 SQ.MM. A2XFY MTR. 1155 52 3.5C x 95 SQ.MM. A2XFY MTR. 3000 53 3.5C x 120 SQ.MM. A2XFY MTR. 4390 54 3.5C x 240 SQ.MM. A2XFY MTR. 1125 55 4C x 2.5 SQ.MM. Cu2XFY MTRS. 22650 56 4C x 4 SQ.MM. Cu2XFY MTRS. 220 57 4C x 10 SQ.MM. A2XFY MTRS. 1050 58 4C x 16 SQ.MM. A2XFY MTRS. 2500 59 4C x 25 SQ.MM. A2XFY MTRS. 3455 60 4C x 35 SQ.MM. A2XFY MTRS. 1135 61 4C x 95 SQ.MM. A2XFY MTRS. 130 62 4C x 185 SQ.MM. A2XFY MTRS. 2170 63 4C x 240 SQ.MM. A2XFY MTRS. 7125 64 4C x 300 SQ.MM. A2XFY MTRS. 4525 CONTROL CABLES CONTROL CABLES: 600/1100V GRADE, PVC INSULATED,COPPER CONDUCTOR, WITH EXTRUDED PVC INNER SHEATHED, EXTRUDED FRLS PVC OUTER SHEATHED FRLS CONFORMING TO IS 1554 (PART 1). P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 4 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 65 3C x 2.5 SQ.MM. YWY MTRS. 15415 66 4C x 2.5 SQ.MM. YWY MTRS. 640 67 7C x 2.5 SQ.MM. YWY MTRS. 18230 TERMINATIONS OF HT & LT CABLES HT TERMINATION KIT SUPPLY OF REPUTED MAKE HEAT SHRINKABLE HT TERMINATION KITS FOR FOLLOWING SIZES OF CABLES. INDOOR TYPE HEAT SHRINKABLE HT END TERMINATION KITS SUITABLE FOR 33 kV GRADE XLPE INSULATED ALUMINIUM CONDUCTOR CABLES OF FOLLOWING SIZES 68 3C X 300 A2XFaY NO. 8 OUTDOOR TYPE HEAT SHRINKABLE HT END TERMINATION KITS SUITABLE FOR 33 kV GRADE XLPE INSULATED ALUMINIUM CONDUCTOR CABLES OF FOLLOWING SIZES. 69 3C X 300 A2XFaY NO. 2 SUPPLY OF FLAMEPROOF TYPE DOUBLE COMPRESSION (INDOOR) NICKEL PLATED BRASS CABLE GLAND, CRIMPING TYPE TINNED COPPER LUGS & PVC/XLPE CABLE HOODS OF FOLLOWING CABLES LV POWER CABLE SIZES: 70 3C x 2.5 SQ.MM. Cu2XWY NO. 214 71 3C x 16 SQ.MM. A2XWY NO. 8 72 3C x 25 SQ.MM. A2XFY NO. 7 73 3C x 50 SQ.MM. A2XFY NO. 4 74 3C x 70 SQ.MM. A2XFY NO. 6 75 3C x 95 SQ.MM. A2XFY NO. 9 76 3C x 120 SQ.MM. A2XFY NO. 13 77 3C x 150 SQ.MM. A2XFY NO. 24 78 3C x 185 SQ.MM. A2XFY NO. 6 79 3C x 240 SQ.MM. A2XFY NO. 1 80 3.5C x 35 SQ.MM. A2XWY NO. 21 81 3.5C x 50 SQ.MM. A2XFY NO. 5 82 3.5C x 70 SQ.MM. A2XFY NO. 3 83 3.5C x 95 SQ.MM. A2XFY NO. 8 84 3.5C x 120 SQ.MM. A2XFY NO. 12 85 3.5C x 240 SQ.MM. A2XFY NO. 7 86 4C x 2.5 SQ.MM. Cu2XWY NO. 15 87 4C x 10 SQ.MM. A2XFY NO. 4 88 4C x 16 SQ.MM. A2XFY NO. 13 89 4C x 25 SQ.MM. A2XFY NO. 13 90 4C x 35 SQ.MM. A2XFY NO. 4 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 5 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 91 4C x 185 SQ.MM. A2XFY NO. 6 92 4C x 240 SQ.MM. A2XFY NO. 15 93 4C x 300 SQ.MM. A2XFY NO. 8 LV CONTROL CABLE SIZES: 94 3C x 2.5 SQ.MM. YWY NO. 54 95 7C x 2.5 SQ.MM. YWY NO. 63 SUPPLY OF INDSTRIAL TYPE DOUBLE COMPRESSION (OUTDOOR) NICKEL PLATED BRASS CABLE GLAND, CRIMPING TYPE TINNED COPPER LUGS & PVC/XLPE CABLE HOODS OF FOLLOWING CABLES LV POWER CABLE SIZES: 96 1C X 630 A2XWaY NO. 380 97 2C x 4 SQ.MM. Cu2XWY NO. 20 98 2C x 10 SQ.MM. A2XWY NO. 10 99 2C x 25 SQ.MM. A2XFY NO. 2 100 3C x 2.5 SQ.MM. Cu2XWY NO. 124 101 3C x 16 SQ.MM. A2XWY NO. 8 102 3C x 25 SQ.MM. A2XFY NO. 7 103 3C x 50 SQ.MM. A2XFY NO. 4 104 3C x 70 SQ.MM. A2XFY NO. 6 105 3C x 95 SQ.MM. A2XFY NO. 9 106 3C x 120 SQ.MM. A2XFY NO. 13 107 3C x 150 SQ.MM. A2XFY NO. 24 108 3C x 185 SQ.MM. A2XFY NO. 6 109 3C x 240 SQ.MM. A2XFY NO. 1 110 3.5C x 35 SQ.MM. A2XWY NO. 21 111 3.5C x 50 SQ.MM. A2XFY NO. 5 112 3.5C x 70 SQ.MM. A2XFY NO. 3 113 3.5C x 95 SQ.MM. A2XFY NO. 8 114 3.5C x 120 SQ.MM. A2XFY NO. 12 115 3.5C x 240 SQ.MM. A2XFY NO. 7 116 4C x 2.5 SQ.MM. Cu2XWY NO. 303 117 4C x 4 SQ.MM. A2XFY NO. 4 118 4C x 10 SQ.MM. Cu2XFY NO. 6 119 4C x 16 SQ.MM. A2XFY NO. 13 120 4C x 25 SQ.MM. A2XFY NO. 13 121 4C x 35 SQ.MM. A2XFY NO. 4 122 4C x 95 SQ.MM. A2XFY NO. 4 123 4C x 185 SQ.MM. A2XFY NO. 8 124 4C x 240 SQ.MM. A2XFY NO. 15 125 4C x 300 SQ.MM. A2XFY NO. 8 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 6 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 LV CONTROL CABLE SIZES: 126 3C x 2.5 SQ.MM. YWY NO. 54 127 4C x 2.5 SQ.MM. YWY NO. 18 128 7C x 2.5 SQ.MM. YWY NO. 63 LIGHT FITTINGS: NOTE:SUPPLY OF POLES TO BE EXCLUDED.THIS IS CATEGORISED SEPERATELY UNDER "LIGHTING POLES" SUPPLY OF FLAMEPROOF EXD TYPE SUITABLE FOR ZONE 1 & 2 GAS GROUP IIA / IIB TEMPERATURE CLASS T-3 WELLGLASS FIXTURE IP - 55, WITH LAMP, INTEGRAL CONTROL GEAR BOX/ NON-INTEGRAL WITH SEPARATE CONTROL GEAR BOX, WIRE GUARD & SUITABLE FOR SUSPENDED, BRACKET, POLE MOUNTING. FIXING BRACKETS SHALL BE PROVIDED. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3NOS. OF ENTRIES SUITABLE FOR 3Cx2.5 SQ.MM. YWY CABLE AND 1NO. SEALING PLUG. 129 2 X 26 W CFL - Cat. Ref. CGL-FWL12226IH/B or Equivalent NO. 24 130 150W (MH) - Cat. Ref.FWL 1215MHIH/A or Equivalent NO. 75 131 250W (MH) (Non-Integral with separate Control Gear Box & Fuses) - Cat. Ref. FWL 12/A NO. 49 SUPPLY OF INDUSTRIAL WELLGLASS FIXTURE IP - 55, WITH LAMP, INTEGRAL CONTROL GEAR BOX/ NON-INTEGRAL WITH SEPARATE CONTROL GEAR BOX, WIRE GUARD & SUITABLE FOR SUSPENDED, BRACKET, POLE MOUNTING. FIXING BRACKETS SHALL BE PROVIDED. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3NOS. OF ENTRIES SUITABLE FOR 3Cx2.5 SQ.MM. YWY CABLE AND 1NO. SEALING PLUG. 132 2 X 26 W CFL NO. 7 133 150W MH (INTEGRAL) NO. 17 134 250W MH (NON-INTEGRAL) WITH SEPARATE CONTROL GEAR BOX & FUSES. NO. 18 POST TOP LANTERN LIGHTINGS 135 SUPPLY OF INDUSTRIAL TYPE, POST TOP LANTERN FITTINGS, WITH 125W HPMV TYPE WITH CONICAL COVER, ELECTRONIC CONTROL GEAR (CAT. REF. PHILIPS-HPC101/125 HPF OR EQUIVALENT). FIXING BRACKETS SHALL BE PROVIDED. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3NOS. OF ENTRIES SUITABLE FOR 3Cx2.5 SQ.MM. 2XWY CABLE AND 1NO. SEALING PLUG. SUPPLY SHALL BE INCLUSIVE OF NECESSARY HARDWARE. NO. 4 136 BOLLARD FIXTURES - (CAT. REF. PHILIPS-HCS360 1 X PL-C 18W OR EQUIVALENT) NO. 60 SUPPLY OF INDUSTRIAL FLUROSCENT (FTL) FIXTURE, WITH LAMP, BALLAST, SUITABLE FOR SUSPENDED/ SURFACE/ BRACKET MOUNTING. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3 NOS. OF ENTRIES SUITABLE FOR 3CX2.5 SQ.MM CABLE & 1 NO. SEALING PLUG. P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 7 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 137 2 X 36W FTL - Cat. Ref. CGL-IGP 1424HSB or Equivalent NO. 8 138 SUPPLY OF INDUSTRIAL FLUROSCENT (FTL) FIXTURE, WITH LAMP, BALLAST SUITABLE FOR BRACKET MOUNTING WITH NECESSARY SUPPORTS FOR TRANSFORMER YARD. NO. 4 Cat. Ref. CGL-IGP 1424HSB or Equivalent SUPPLY OF INDUSTRIAL FLOOD LIGHT FIXTURE,WITH LAMP, INTEGRAL CONTROL GEAR BOX & FUSES. NON CORROSIVE HIGH PRESSURE DIE CAST ALUMINIUM HOUSING WITH LOW COPPER CONTENT , HOT DIP GALVANISED STEEL MOUNTING BRACKET AND COMPLETE WITH ALL THE ACCESSORIES. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3NOS. OF M20 ENTRIES AND 1NO PLUG. 139 400W MH MOUNTED ON 11 MTR. POLE NO. 3 Cat. Ref. CGL-FAI40IH/MH or Equivalent 140 NON-FLAMEPROOF CHARGEABLE EMERGENCY LIGHTS NO. 5 CONTROL ROOM TERMINAL IN-CHARGE ROOM MCC ROOM-2 MAIN SUBSTATION LIGHTING POLES SUPPLY OF LIGHTING POLE AND ACCESSORIES. 141 MS TUBULAR/ OCTAGONAL LIGHTING POLE, HOT NO. 65 DIP GALVANISED, 5M HEIGHT FROM FINISHED GROUND LEVEL. FOR WELLGLASS FIXTURE (125/250W ) WITH ALL ACCESSORIES 142 MS TUBULAR/ OCTAGONAL LIGHTING POLE, HOT NO. 3 DIP GALVANISED, 11M HEIGHT FROM FINISHED GROUND LEVEL. FOR WELLGLASS FIXTURE (400W ) WITH ALL ACCESSORIES JUNCTION BOX SUPPLY OF FLAMEPROOF EXD TYPE SUITABLE FOR ZONE 1 & 2 GROUP IIA / IIB. TEMPERATURE CLASS T-3 JUNCTION BOX WITH ACCESSORIES AS INDICATED BELOW. ENCLOSURE OF JUNCTION BOX SHALL BE MADE UP OF CAST LIGHT METAL ALLOY. JUNCTION BOX SHALL INCLUDE NECESSARY TERMINALS FOR TERMINATING REQUIRED NUMBER OF CABLES AND WITH SUITABLE ENTRIES. 16 AMP. CLAMP TYPE TERMINALS OF ELMEX MAKE OR EQUIV. SHALL BE PROVIDED FOR ALL JBs. JB SHALL HAVE AN EXTERNAL EARTH TERMINAL. JB SHALL BE COMPLETE WITH REQUIRED SHORTING LINKS FOR LOOP IN LOOP OUT OF CABLES. P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 8 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 CONTRACTOR SHALL TAKE THE APPROVAL OF THE DIMENSIONS FOR THIS JUNCTION BOX FROM SITE ELECTRIAL ENGINEER. 143 4 WAY, WITH TERMINALS TO BE SUITABLE FOR NO. 1 ACCOMODATING ONE 3.5Cx50 SQ.MM. INCOMING CABLES AND 3 NOS. 3Cx35 SQ.MM. OUTGOING CABLES. WITH PLUGS 144 4 WAY, WITH TERMINALS TO BE SUITABLE FOR NO 1 ACCOMODATING ONE 3.5Cx70 SQ.MM. INCOMING CABLES AND 3 NOS. 3Cx35 SQ.MM. OUTGOING CABLES. WITH PLUGS 145 4 WAY, WITH TERMINALS TO BE SUITABLE FOR NO 4 ACCOMODATING ONE 3.5Cx95 SQ.MM. INCOMING CABLES AND 3 NOS. 3Cx35 SQ.MM. OUTGOING CABLES. WITH PLUGS 146 4 WAY, WITH TWO M20 ENTRIES AND ONE M16 ENTRY. NO. 174 TERMINALS TO BE SUITABLE FOR ACCOMODATING 3Cx2.5 SQ.MM. OUTGOING CABLES WITH PLUGS PANEL: SUPPLY OF FOLLOWING 415V PANELS. THE PANELS SHALL BE INDOOR, FLOOR/WALL MOUNTED WITH BOTTOM/TOP CABLE ENTRY. 147 CAPACITOR PANEL WITH CAPACITORS & APFC CONTROLLED SYSTEM - FLOOR MOUNTED AS PER SLD & SPECIFICATIONS NO. 1 148 POWER DISTRIBUTION PANEL - PDP FLOOR MOUNTED AS PER SLD & SPECIFICATION NO. 2 149 MAIN LIGHTING DISTRIBUTION PANEL-MLDP WITH ENERGY SAVER WITH TIMER & CONTACTOR FOR OUTDOOR LIGHTING FEEDERS AS PER SLD & SPECIFICATION (COMPARTMENTALISED, FLOOR MOUNTED, SINGLE FRONT PANEL) NO. 1 150 EMERGANCY LIGHTING DISTRIBUTION PANEL WITH ENERGY SAVER WITH TIMER & CONTACTOR FOR OUTDOOR LIGHTING FEEDERS AS PER SLD & SPECIFICATION (COMPARTMENTALISED, FLOOR MOUNTED, SINGLE FRONT) NO. 1 151 YARD LIGHTING DISTRIBUTION PANEL WITH ENERGY SAVER ALONG WITH TIMER FOR LIGHTING AS PER SLD & SPECIFICATION NO. 1 LIGHTING DISTRIBUTION BOARDS-LDB [WALL MOUNTED] P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 9 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 FLAME PROOF ExD TYPE SUITABLE FOR ZONE 1 & ZONE 2 GAS GROUP IIA / IIB, TEMPERATURE CLASS T-3. THE ENCLOSURE SHALL BE MADE OF CAST LIGHT METAL ALLOY WITH SUITABLE SIZE KNOCK OUT FOR CABLE CONNECTION WITH CANOPY. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARDWARE AND EXCLUDING SUPPLY OF STEEL STRUCTURE. TPN INCOMER WITH 3 NOS OF RCC Bs FOR EACH PHASE AND SP OUT-GOING MCB (16kA) FOR LIGHTING. OPERATING KNOB SHALL BE PROVIDED ON TOP SURFACE OF LDB AS PER SLD AND SPECIFICATION 152 12 WAY NO. 4 153 18 WAY NO. 4 NORMAL INDUSTRIAL TYPE OUT DOOR - IP-55 LIGHTING DISTRIBUTION BOARD (LDB) HAVING 2MM THICK SHEET STEEL. TPN INCOMER WITH 3 NOS OF RCCBs FOR EACH PHASE & SP OUT-GOING MCB (16KA) FOR LIGHTING AS PER SLD AND SPECIFICATION 154 12 WAY NO. 2 155 18 WAY NO. 1 SMALL POWER DISTRIBUTION BOARD - SDB (WALL MOUNTED) NORMAL INDUSTRIAL TYPE OUT DOOR IP-55 SMALL POWER DISTRIBUTION BOARD (SDB) HAVING 2MM THICK SHEET STEEL. INCOMER WITH 3 NOS OF RCCBs FOR EACH PHASE & SP OUT- GOING MCB (16KA) FOR LIGHTING 156 18 WAY NO. 7 157 POWER DISTRIBUTION PANEL FOR MOVs FLOOR MOUNTED AS PER SLD & SPECIFICATION NO. 1 158 OUTDOOR POWER DISTRIBUTION BOARD FOR MOVs FLOOR MOUNTED AS PER SLD & SPECIFICATION NO. 9 415 V BUSDUCT SUPPLY OF FOLLOWING BUSDUCTS. SCOPE AS PER SPECIFICATION AND EQUIPMENT LAYOUT INCLUDES SUPPLY OF CONNECTIONS AT TRANSFORMER END AS WELL AS SWITCHGEAR END, FLEXIBLE LINKS, CANOPY AND BUSDUCT SUPPORTING ARRANGEMENTS. 159 BUSDUCT NO. BD-01 NO. 1 RATING : TPN 415V, 3200 AMPS. NO.OF BENDS = 4 OUTDOOR LENGTH : HORIZONTAL= 2.6 Mtr. VERTICAL= 4.5 Mtr. INDOOR LENGTH : HORIZONTAL= 2.2 Mtr. VERTICAL= 1.2 Mtr. P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 10 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 160 BUSDUCT NO. BD-02 NO. 1 RATING : 415V, 3200 AMPS. NO.OF BENDS = 4 OUTDOOR LENGTH : HORIZONTAL= 2.6 Mtr. VERTICAL= 4.5 Mtr. INDOOR LENGTH : HORIZONTAL= 6.2 Mtr. VERTICAL= 1.2 Mtr. FANS ALONG WITH ACCESSORIES SUPPLY OF EXHAUST FAN WITH STARTER. EXHAUST / FRESH AIR FAN 161 450 DIA. SINGLE PHASE, 240V AC EXHAUST FAN NO 27 PIPES GI PIPES SUPPLY CLASS-B GI PIPE OF SIZES AS SPECIFIED BELOW TO BE FIXED ON WALL STEEL STRUCTURE BURRIED IN GROUND, LAID IN TRENCHES FOR PROTECTION OF CABLES EARTHING CONDUCTORS OF INCLUDING BENDING, THREADING, COUPLING, WELDING, CLAMPING AS REQUIRED. 162 75 MM DIA GI PIPE MTR. 25 163 150 MM DIA GI PIPE MTR. 20 PVC PIPES SUPPLY OF PVC PIPES OF SIZES AS SPECIFIED BELOW TO BE FIXED ON WALL OR STEEL STRUCTURE FOR CABLES IN WALL OR STEEL STRUCTURE FOR CABLES INCLUDED BENDING AS REQUIRED. 164 75 MM DIA GI PIPE MTR. 25 165 150 MM DIA PVC PIPE MTR. 110 HUME PIPES SUPPLY OF HUME PIPES OF INNER DIA. AS SPECIFIED BELOW TO BE LAID BURIED UNDERGROUND FOR PROTECTION OF CABLES / EARTHING CONDUCTORS WITH REQUIRED COUPLING RINGS. 166 150 MM DIA HUME PIPE MTR. 25 167 200 MM DIA HUME PIPE MTR. 25 168 300 MM DIA HUME PIPE MTR. 25 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 11 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) REMARKS SR. NO. DESCRIPTION UNIT QTY. SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART A : SUPPLY OF EQUIPMENT IN CONTRACTORS SCOPE Rev B VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Doc No: 254625-300-SC-ELE-008 STRUCTURAL STEEL SUPPLY OF 169 STRUCTURAL STEEL IN FORMS OF M.S. TON 35 ANGLES, CHANNELS, BEAMS, FLATS, ETC. FOR SUPPORTING VARIOUS ITEMS / EQUIPMENT SUCH AS SWITCHGEARS, PANELS, CABLE TRAYS, PUSH BUTTON STATIONS, LOCAL CONTROL BOXES, LOCAL CONTROL PANELS, JUNCTION BOXES, DISTRIBUTION BOARDS, LIGHTING FITTINGS. NOTES:- PAYMENT AGAINST SUPPLY OF ALL ITEMS SHALL BE AS PER EXECUTED QTY. & RECONCILATION WILL BE DONE AT FINAL BILLING STAGE. NECESSARY DEDUCTIONS SHALL BE MADE FOR CHANGE IN QTY. HENCE VENDOR TO ASCERTAIN ACTUAL QTY. OF ELECTRICAL ITEMS TO BE SUPPLIED BEFORE PROCURING. PAYMENT AGAINST SUPPLY OF CABLES SHALL BE AS PER EXECUTED QTY & RECONCILATON WILL BE DONE AT FINAL BILLING STAGE. ANY EXCESS SUPPLY OF CABLE SHALL BE PROPERTY OF CONTRACTOR & SAME SHALL NOT BE PAID FOR. IF PAYMENT IS DONE DURING RUNNING BILLS AGAINST SUPPLY, NECESSARY DEDUCTIONS SHALL BE MADE FOR QTY. HENCE VENDOR TO ASCERTAIN ACTUAL QUANTITY OF CABLE TO BE SUPPLIED BEFORE PROCURING. IT SHALL BE VENDORS RESPONSIBILITY TO MAKE SUITABLE DRUM SCHEDULE BASED ON SITE ROUTING & ACTUAL REQUIREMENT. STRAIGHT THROUGH JOINTS SHALL NOT BE ACCEPTABLE. UNDER EXCEPTIONALLY LONG LENGTHS STRAIGHT THROUGH JOINTS CAN BE ACCEPTED BY SITE ENGINEER AT HIS DISCRETION. HOWEVER COST FOR SUPPLY & INSTALLATION OF STRAIGHT THROUGH JOINT WILL BE AT RISK & COST OF VENDOR. ANY PART OF EQUIPMENT OR COMPONENT NOT SPECIFICALLY MENTIONED IN SOQ, BUT REQUIRED FOR MAKING THE INSTALLATION COMPLETE, SAFE AND RELIABLE SHOULD BE PROVIDED BY THE CONTRACTOR AT NO EXTRA COST. P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 Page 12 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) NOTE : INSTALLATION RATE SHALL INCLUDE SUPPLY OF CONSUMABLES AND HARDWARE AND EXCLUDING SUPPLY OF STRUCTURAL STEEL SINCE THIS IS CATEGORISED SEPERATELY. FOUR POLE STRUCTURE 1 INSTALLATION, TESTING AND COMMISSIONING OF FOUR POLE STRUCTURE. FOUR POLE STRUCTURE SHALL BE WITH BRACINGS AND CROSS ARMS FOR SUPPORTING THE PIN / OR STRAIN INSULATORS. EACH POLE SHALL BE HEAVY DUTY RAIL (IRS - HSB) HAVING A UNIT WEIGHT OF 52 KG / METER. FOUR POLE STRUCTURE SHALL INCLUDE GOD, LA, EARTH SWITCH, CT, PT, METERING CUIBICAL, INSULATORS AND JUMPER ETC AS PER SPECIFICATIONS , SLD AND APSEB GUIDELINE. SET 1 2 LAYING OF 33KV ( E ) 3C X 400 Sq.mm STRANDED ALLUMINIUM CONDUCTOR SCREENED XLPE INSULATED ARMOURED CABLES EXTRUDED FRLS PVC OUTER SHEATHED WITH NECESSARY ACCESSORIES & 33kV OUTDOOR TYPE TERMINATION KITS. GENERALLY CONFORMING TO IS 7098 PART 2 FOR CONVERSION OF OVER HEAD LINE TO UNDER GROUND CABLE SYSTEM. MTR. 200 TWO RUNS EACH OF 100 Mtr. LOCAL CONTROL STATION FLAME PROOF LOCAL CONTROL STATIONS INSTALLATION, TESTING & COMMISSIONING OF FLAME PROOF Ex- d FOLLOWING TYPE LOCAL CONTROL STATION SUITABLE FOR ZONE - 1 & 2 GASS GROUP II A & II B. TEMPERATURE CLASS - T3 IP- 55. THE ENCLOSURE SHALL BE MADE OF CAST LIGHT METAL ALLOY WITH 2 NOS SUITABLE SIZE KNOCK OUTS FOR CABLE CONNECTION WITH CANOPY. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARDWARE AND EXCLUDING SUPPLY OF STRUCTURAL STEEL
3 EMERGENCY STOP PUSH BUTTON TYPE A NO. 5 4 START / STOP PUSH BUTTON WITH LOCAL / REMOTE SELECTOR SWITCH & AMMENTIES TYPE B NO. 33 INDUSTRIAL TYPE LOCAL CONTROL STATION INSTALLATION, TESTING & COMMISSIONING OF INDUSTRIAL FOLLOWING TYPE LOCAL CONTROL STATION THE ENCLOSURE SHALL BE MADE OF CAST LIGHT METAL ALLOY IP-55 WITH 2 NOS SUITABLE SIZE KNOCK OUTS FOR CABLE CONNECTION WITH CANOPY. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARDWARE AND EXCLUDING SUPPLY OF STRUCTURAL STEEL 5 EMERGENCY STOP PUSH BUTTON TYPE C NO. 2 6 START / STOP PUSH BUTTON WITH LOCAL / REMOTE SELECTOR SWITCH & AMMENTIES TYPE D NO. 22 SOCKET OUTLETS INSTALLATION,TESTING AND COMMISSIONING OF FOLLOWING TYPE SWITCH- SOCKET OUTLETS. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARD WARE AND EXCLUDING SUPPLY OF STRUCTURAL STELL. FLAMEPROOF Ex-d TYPE SUITABLE FOR ZONE-1 & ZONE-2, GAS GROUP IIA/IIB. TEMPERATURE CLASS - T3 IP-55 SWITCH SOCKET UNITS VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 13 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. 7 63A TPN THREE PHASE 440VOLTS 5PINS SWITCH SOCKET OUTLETS NO. 13 INDUSTRIAL TYPE (NON FLAME PROOF ) IP-55 8 63A TPN THREE PHASE 440VOLTS 5PIN SOCKET OUTLET NO. 6 9 16A SINGLE PHASE 240 VOLTS 3PIN SWITCH SOCKET OUTLETS NO. 5 10 16A, 240V SINGLE POLE SWITCH NO. 4 MAINTENANCE FREE EARTHING & LIGHTNING PROTECTION SYSTEM EARTHING STRIPS INSTALLATION OF HOT DIPPED GALVANISED (GI) BARE EARTH CONDUCTOR OF FULLY WELDED AND COATED WITH TWO COATS OF BITUMEN PAINT. THE GI COATING SHALL BE 85 MICRON. TERMINATION SHALL BE BOLTED GI STRIP TO BE LAID IN GROUND, ON TRAY, CLEATED ALONG BRICK WALL / RCC WALL / STRUCTURE, ETC. DRILLED AND FIXED WITH 'J' BOLT ON TOP OF ASBESTOS ROOF, ETC. THE INSTALLATION RATE SHALL INCLUDE SUPPLY OF ALL HARDWARES MATERIAL. 11 75 x 12 MM GI STRIP MTR. 1250 12 40 x 5 MM GI STRIP MTR. 400 13 50 x 10 MM GI STRIP MTR. 3800 14 50 x 6 MM GI STRIP MTR. 1040 15 25 x 6 MM GI STRIP MTR. 250 GI WIRE ROPES INSTALLATION OF GI WIRE / WIRE ROPE OF STRANDED TYPE WIRES OF FOLLOWING SIZES. END TERMINATION TO BE BOLTED AFTER LUGGING WITH SUITABLE SOLDER TYPE ALUMINIUM LUGS. THE INSTALLATION RATE SHALL INCLUDE SUPPLY OF LUGS AND ALL HARDWARES MATERIAL. 16 8 SWG GI WIRE MTR. 4728 EARTHING CABLES INSTALLATION OF 600 V CABLES OF FOLLOWING SIZES WITH SUPPLY OF LUGS & ALL HARDWARE MATERIALS. 17 1C X 4 Sq.MM CABLE MTR. 800 18 1C X 25 Sq.MM CABLE MTR. 1310 19 1C X 120 Sq.MM CABLE MTR. 300 20 1C X 185 Sq.MM CABLE MTR. 160 MAINTENANCE FREE EARTHING PITS & PLATE EARTH ELECTRODE INSTALLATION, TESTING & COMMISSIONING OF EARTH PITS INCLUDING ALL CIVIL WORK SUCH AS EXCAVATION BORING FOR THE FOLLOWING TYPE. REFER ATTACHED STANDARD INSTALLATION DRAWINGS. P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 14 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. NOTE:- CONTRACTOR TO SUBMIT NECESSARY TEST CERTIFICATES FOR ALL EARTH PITS & COMPLETE EARTHING SYSTEM AFTER COMPLETION OF WORK. TRIPOD EARTH ELECTRODE: 21 TRIANGULAR TERMINATION CONSISTS OF A SET OF THREE COPPER-BONDED STEEL EARTH RODS OF 2M EACH ARRANGED IN A TRIANGULAR FASHION & SEPARATED FROM EACH OTHER BY A DISTANCE AT LEAST EQUAL TO THEIR DRIVEN DEPTH & INTERCONNECTED BY A FLAT COPPER CONDUCTOR (COPPER STRIP) WITH INSPECTION CHAMBER AS PER STANDARD INSTALLATION DRAWING. NO 78 G.I. PLATE EARTH ELECTRODE 22 G.I.PLATE ELECTRODE OF SIZE 600 x 600 x 10mm WITH 2 NOS. 50 x 6 mm G.I.EARTH STRIPS UP TO TEST LINK, CLASS B 50 mm DIA G.I.PIPE, WITH FUNNEL AND WIRE MESH FOR WATERING, ,SALT CHARCOAL, 12MM G.I.COVER WITH NECESSARY BRICK INSPECTION CHEMBER ETC. AS PER IS 3043, INCLUDING SUPPLY & INSTALLTION OF EARTH PIT MARKER AS PER ENCLOSED DRAWING. REFER ATTACHED STANDARD INSTALLATION DRAWING. NO 4 EARTH BUS 23 INSTALLATION OF EARTH BUS MADE WITH 75 X 12MMGI. FLAT OF APPROXIMATE 850 MM. LENGTH INCLUDING DRILLING HOLE & INSTALLED ON TRAY INCLUDIMG PAINTING WITH BITUMINOUS PAINT AS REQUIRED. REFER ATTACHED STANDARD INSTALLATION DRAWINGS. NO. 15 24 INSTALLATION OF EARTH BUS MADE WITH 75 X 12MM GI. FLAT OF APPROXIMATE 550MM.LENGTH INCLUDING DRILLING HOLE INSTALLED ON TRAY INCLUDIMG PAINTING WITH BITUMINOUS PAINT AS REQUIRED. REFER ATTACHED STANDARD INSTALLATION DRAWING. NO. 171 EARTH PIT MARKER 25 INSTALLATION OF EARTH PIT MARKER INDICATING EARTH RESISTANCE & TESTED DATE, NEXT DUE DATE FOR TESTING. REFER ATTACHED STANDARD INSTALLATION DRAWING. NO. 78 GI CABLE TRAYS INSTALLATION SHALL INCLUDE ALIGNING, JOINING, [INCLUDING BENDS AND BRANCHES] ALONG WITH NECESSARY ACCESSORIES & HARDWARE. - RATE OF INSTALLATION SHALL BE PAID ON THE BASIS OF RUNNING METER ON THE CABLE TRAY MEASUREMENT. NO SEPARATE RATE WILL BE PAID FOR BENDS AND BRANCHES. LADDER TYPE TRAYS INSTALLATION OF GI LADDER TYPE CABLE TRAYS OF FOLLOWING SIZES : 26 300 MM WIDE GI TRAY MTR. 286 27 500 MM WIDE GI TRAY MTR. 1425 28 900 MM WIDE GI TRAY MTR. 1660 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 15 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. GI TRAY COVER INSTALLATION OF GI TRAY COVERS TO SUIT FOLLOWING TRAY SIZES : 29 300MM WIDE GI TRAY MTR. 160 30 500MM WIDE GI TRAY MTR. 1216 31 900MM WIDE GI TRAY MTR. 960 HV & LV CABLE LAYING ON TRAYS LAYING AND DRESSING OF CABLES OF VARIOUS GRADES (HT / LT) AND TYPES (PVC / XLPE) IN READY TRENCH/ TRAYS SUPPORTED ON PIPE RACK STRUCTURES AT VARIOUS LOCATIONS, IN CABLE CELLAR INSIDE SUBSTATION. THE SCOPE INCLUDES SUPPLY AND FIXING OF ALUMINIUM STRIP NUMBER TAGS. SUPPLY AND FIXING OF GI SADDLE AND CLAMPS ON TRAYS AND NECESSARY HARDWARES. THE CABLE LAYING WORK SHALL INCLUDE TRANSPORTATION OF CABLE DRUMS FROM OWNER'S STORE, CUTTING OF CABLE LENGTH AS PER ACTUAL MEASUREMENT AND CABLE SCHEDULE, RETURNING OF UNUSED CABLES TO THE OWNERS STORE DULY MEASURED IN THEIR PRESENCE. 33 kV, STRANDED AL CONDUCTOR, SCREENED, XLPE INSULATED, ARMOURED CABLES, EXTRUDED FRLS PVC OUTER SHEATHED GENERALLY CONFIRMING TO IS 7098 - PART 2. 32 3C X 300 A2XFaY MTR. 90 POWER CABLES: 600/1100V GRADE, XLPE INSULATED, AL/ CU. CONDUCTOR, ARMOURED, EXTRUDED PVC INNER SHEATHED & EXTRUDED FRLS PVC OUTER SHEATHED CONFORMING TO IS 7098 - PART 1. 33 1C X 630 A2XWaY MTRS. 5385 34 2C x 4 SQ.MM. A2XWY MTRS. 52 35 2C x 10 SQ.MM. A2XWY MTRS. 173 36 2C x 25 SQ.MM. A2XFY MTRS. 42 37 3C x 16 SQ.MM. A2XFY MTR. 150 38 3C x 25 SQ.MM. A2XFY MTR. 200 39 3C x 50 SQ.MM. A2XFY MTR. 155 40 3C x 70 SQ.MM. A2XFY MTR. 227 41 3C x 95 SQ.MM. A2XFY MTR. 550 42 3C x 120 SQ.MM. A2XFY MTR. 350 43 3C x 150 SQ.MM. A2XFY MTR. 610 44 3C x 185 SQ.MM. A2XFY MTR. 160 45 3C x 240 SQ.MM. A2XFY MTR. 35 46 3.5C x 35 SQ.MM. A2XWY MTR. 450 47 3.5C x 50 SQ.MM. A2XFY MTR. 140 48 3.5C x 70 SQ.MM. A2XFY MTR. 110 49 3.5C x 95 SQ.MM. A2XFY MTR. 300 50 3.5C x 120 SQ.MM. A2XFY MTR. 440 51 3.5C x 240 SQ.MM. A2XFY MTR. 110 52 4C x 2.5 SQ.MM. Cu2XFY MTRS. 2260 53 4C x 4 SQ.MM. Cu2XFY MTRS. 20 54 4C x 10 SQ.MM. A2XFY MTRS. 100 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 16 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. 55 4C x 16 SQ.MM. A2XFY MTRS. 250 56 4C x 25 SQ.MM. A2XFY MTRS. 350 57 4C x 35 SQ.MM. A2XFY MTRS. 100 58 4C x 95 SQ.MM. A2XFY MTRS. 15 59 4C x 185 SQ.MM. A2XFY MTRS. 220 60 4C x 240 SQ.MM. A2XFY MTR. 720 61 4C x 300 SQ.MM. A2XFY MTR. 450 CONTROL CABLES: 600/1100V GRADE, PVC INSULATED,COPPER CONDUCTOR, WITH EXTRUDED PVC INNER SHEATHED, EXTRUDED FRLS PVC OUTER SHEATHED FRLS CONFORMING TO IS 1554 (PART 1). 62 3C x 2.5 SQ.MM. YWY MTRS. 1540 63 4C x 2.5 SQ.MM. YWY MTRS. 65 64 7C x 2.5 SQ.MM. YWY MTRS. 1820 HV & LV CABLES DIRECTLY BURIED IN GROUND LAYING AND DRESSING OF CABLES OF VARIOUS GRADES (HT / LT) AND TYPES (PVC / XLPE) OF CABLES DIRECTLY BURIED IN GROUND AT VARIOUS LOCATIONS. THE SCOPE INCLUDES SUPPLY AND FIXING OF CABLE ROUTE MARKER. SUPPLY AND FIXING OF CABLE PROTECTION TILES OR FIRE PROOF INTERLOCKED BRICKS WITH CEMENT& RIVER SAND ON THE SURFACE, BACK FILLED CABLE TRENCHES AND NECESSARY HARDWARE. THE CABLE LAYING WORK SHALL INCLUDE TRANSPORTATION OF CABLE DRUMS FROM OWNER'S STORE, CUTTING OF CABLE LENGTH AS PER ACTUAL MEASUREMENT AND CABLE SCHEDULE, RETURNING OF UNUSED CABLES TO THE OWNERS STORE DULY MEASURED IN THEIR PRESENCE. 33 kV, STRANDED AL CONDUCTOR, SCREENED, XLPE INSULATED, ARMOURED CABLES, EXTRUDED FRLS PVC OUTER SHEATHED GENERALLY CONFORMING TO IS 7098 - PART 2. 65 3C X 300 A2XFaY MTR. 220 POWER CABLES: 600/1100V GRADE, XLPE INSULATED,AL/CU. CONDUCTOR, ARMOURED, EXTRUDED PVC INNER SHEATHED & EXTRUDED FRLS PVC OUTER SHEATHED FRLS CONFORMING TO IS 7098 - PART 1. 66 1C X 630 A2XWaY MTRS. 48465 67 2C x 4 SQ.MM. A2XWY MTRS. 463 68 2C x 10 SQ.MM. A2XWY MTRS. 1562 69 2C x 25 SQ.MM. A2XFY MTRS. 383 70 3C x 2.5 SQ.MM. Cu2XWY MTRS. 2800 71 3C x 16 SQ.MM. A2XFY MTR. 1350 72 3C x 25 SQ.MM. A2XFY MTR. 1785 73 3C x 50 SQ.MM. A2XFY MTR. 1400 74 3C x 70 SQ.MM. A2XFY MTR. 2048 75 3C x 95 SQ.MM. A2XFY MTR. 4935 76 3C x 120 SQ.MM. A2XFY MTR. 3105 77 3C x 150 SQ.MM. A2XFY MTR. 5505 78 3C x 185 SQ.MM. A2XFY MTR. 1465 79 3C x 240 SQ.MM. A2XFY MTR. 325 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 17 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. 80 3.5C x 35 SQ.MM. A2XWY MTR. 3840 81 3.5C x 50 SQ.MM. A2XFY MTR. 1140 82 3.5C x 70 SQ.MM. A2XFY MTR. 980 83 3.5C x 95 SQ.MM. A2XFY MTR. 2700 84 3.5C x 120 SQ.MM. A2XFY MTR. 3950 85 3.5C x 240 SQ.MM. A2XFY MTR. 1015 86 4C x 2.5 SQ.MM. Cu2XFY MTRS. 19250 87 4C x 4 SQ.MM. Cu2XFY MTRS. 185 88 4C x 10 SQ.MM. A2XFY MTRS. 890 89 4C x 16 SQ.MM. A2XFY MTRS. 2125 90 4C x 25 SQ.MM. A2XFY MTRS. 3105 91 4C x 35 SQ.MM. A2XFY MTRS. 1035 92 4C x 95 SQ.MM. A2XFY MTRS. 115 93 4C x 185 SQ.MM. A2XFY MTRS. 1950 94 4C x 240 SQ.MM. A2XFY MTR. 6405 95 4C x 300 SQ.MM. A2XFY MTR. 4075 CONTROL CABLES: 600/1100V GRADE, PVC INSULATED,COPPER CONDUCTOR, WITH EXTRUDED PVC INNER SHEATHED, EXTRUDED FRLS PVC OUTER SHEATHED CONFORMING TO IS 1554 (PART 1). 96 3C x 2.5 SQ.MM. YWY MTRS. 12330 97 4C x 2.5 SQ.MM. YWY MTRS. 575 98 7C x 2.5 SQ.MM. YWY MTRS. 15490 LV CABLES CLEATED ON WALL / SLAB / STRUCTURE CLEATING OF CABLES OF VARIOUS GRADES (HT / LT) AND TYPES (PVC / XLPE) OF CABLES ON WALL / STRUCTURE / SLAB. SCOPE SHALL INCLUDE FIXING OF CLAMP,MATERIAL, SUPPLY OF CABLE, IDENTIFICATION TAG. POWER CABLES: 600/1100V GRADE, XLPE INSULATED,AL/CU. CONDUCTOR, ARMOURED, EXTRUDED PVC INNER SHEATHED & EXTRUDED FRLS PVC OUTER SHEATHED CONFORMING TO IS 7098 - PART 1. 99 3C x 2.5 SQ.MM. Cu2XWY MTRS. 4200 100 3.5C x 35 SQ.MM. A2XWY MTR. 225 101 3.5C x 50 SQ.MM. A2XFY MTR. 75 102 3.5C x 70 SQ.MM. A2XFY MTR. 65 103 4C x 2.5 SQ.MM. Cu2XFY MTRS. 1140 104 4C x 4 SQ.MM. Cu2XFY MTRS. 15 105 4C x 10 SQ.MM. A2XFY MTRS. 60 106 4C x 16 SQ.MM. A2XFY MTRS. 125 CONTROL CABLES: 600/1100V GRADE, PVC INSULATED,COPPER CONDUCTOR, WITH EXTRUDED PVC INNER SHEATHED, EXTRUDED FRLS PVC OUTER SHEATHED CONFORMING TO IS 1554 (PART 1). 107 3C x 2.5 SQ.MM. YWY MTRS. 1545 108 7C x 2.5 SQ.MM. YWY MTRS. 920 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 18 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. TERMINATIONS OF HT & LT CABLES HT TERMINATION KIT TERMINATION OF HT CABLE WITH REPUTED MAKE HEAT SHRINKABLE HT TERMINATION KITS FOR FOLLOWING SIZES OF CABLES. SCOPE ALSO INCLUDES PREPARATION FOR CONNECTION (CRIMPING OF SUITABLE LONG SHRUNK LUG) AND HIGH POT TESTING INDOOR TYPE HEAT SHRINKABLE HT END TERMINATION KITS SUITABLE FOR 33 kV GRADE XLPE INSULATED ALUMINIUM CONDUCTOR CABLES OF FOLLOWING SIZES 109 3C X 300 SQ.MM A2XFaY NO. 8 OUTDOOR TYPE HEAT SHRINKABLE HT END TERMINATION KITS SUITABLE FOR 33 kV GRADE XLPE INSULATED ALUMINIUM CONDUCTOR CABLES OF FOLLOWING SIZES. 110 3C X 300 SQ.MM A2XFaY NO. 2 TERMINATION OF LT PVC/XLPE INSULATED CABLES INCLUDING INSTALLATION OF FLAMEPROOF TYPE DOUBLE COMPRESSION (INDOOR) NICKEL PLATED BRASS CABLE GLAND, CRIMPING TYPE TINNED COPPER LUGS & PVC/XLPE CABLE HOODS. LV POWER CABLE SIZES: 111 3C x 2.5 SQ.MM. Cu2XWY NO. 214 112 3C x 16 SQ.MM. A2XWY NO. 8 113 3C x 25 SQ.MM. A2XFY NO. 7 114 3C x 50 SQ.MM. A2XFY NO. 4 115 3C x 70 SQ.MM. A2XFY NO. 6 116 3C x 95 SQ.MM. A2XFY NO. 9 117 3C x 120 SQ.MM. A2XFY NO. 13 118 3C x 150 SQ.MM. A2XFY NO. 24 119 3C x 185 SQ.MM. A2XFY NO. 6 120 3C x 240 SQ.MM. A2XFY NO. 1 121 3.5C x 35 SQ.MM. A2XWY NO. 21 122 3.5C x 50 SQ.MM. A2XFY NO. 5 123 3.5C x 70 SQ.MM. A2XFY NO. 3 124 3.5C x 95 SQ.MM. A2XFY NO. 8 125 3.5C x 120 SQ.MM. A2XFY NO. 12 126 3.5C x 240 SQ.MM. A2XFY NO. 7 127 4C x 2.5 SQ.MM. Cu2XWY NO. 15 128 4C x 10 SQ.MM. A2XFY NO. 4 129 4C x 16 SQ.MM. A2XFY NO. 13 130 4C x 25 SQ.MM. A2XFY NO. 13 131 4C x 35 SQ.MM. A2XFY NO. 4 132 4C x 185 SQ.MM. A2XFY NO. 6 133 4C x 240 SQ.MM. A2XFY NO. 15 134 4C x 300 SQ.MM. A2XFY NO. 8 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 19 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. LV CONTROL CABLE SIZES: 135 3C x 2.5 SQ.MM. YWY NO. 54 136 7C x 2.5 SQ.MM. YWY NO. 63 TERMINATION OF LT PVC/XLPE INSULATED CABLES INCLUDING INSTALLATION OF INDUSTRIAL TYPE DOUBLE COMPRESSION (OUTDOOR) NICKEL PLATED BRASS CABLE GLAND, CRIMPING TYPE TINNED COPPER LUGS & PVC/XLPE CABLE HOODS. LV POWER CABLE SIZES: 137 1C x 630SQ.MM A2XWaY NO. 380 138 2C x 4 SQ.MM. Cu2XWY NO. 20 139 2C x 10 SQ.MM. A2XWY NO. 10 140 2C x 25 SQ.MM. A2XFY NO. 2 141 3C x 2.5 SQ.MM. Cu2XWY NO. 124 142 3C x 16 SQ.MM. A2XWY NO. 8 143 3C x 25 SQ.MM. A2XFY NO. 7 144 3C x 50 SQ.MM. A2XFY NO. 4 145 3C x 70 SQ.MM. A2XFY NO. 6 146 3C x 95 SQ.MM. A2XFY NO. 9 147 3C x 120 SQ.MM. A2XFY NO. 13 148 3C x 150 SQ.MM. A2XFY NO. 24 149 3C x 185 SQ.MM. A2XFY NO. 6 150 3C x 240 SQ.MM. A2XFY NO. 1 151 3.5C x 35 SQ.MM. A2XWY NO. 21 152 3.5C x 50 SQ.MM. A2XFY NO. 5 153 3.5C x 70 SQ.MM. A2XFY NO. 3 154 3.5C x 95 SQ.MM. A2XFY NO. 8 155 3.5C x 120 SQ.MM. A2XFY NO. 12 156 3.5C x 240 SQ.MM. A2XFY NO. 7 157 4C x 2.5 SQ.MM. Cu2XWY NO. 303 158 4C x 4 SQ.MM. Cu2XFY NO. 4 159 4C x 10 SQ.MM. A2XFY NO. 6 160 4C x 16 SQ.MM. A2XFY NO. 13 161 4C x 25 SQ.MM. A2XFY NO. 13 162 4C x 35 SQ.MM. A2XFY NO. 4 163 4C x 95 SQ.MM. A2XFY NO. 4 164 4C x 185 SQ.MM. A2XFY NO. 8 165 4C x 240 SQ.MM. A2XFY NO. 15 166 4C x 300 SQ.MM. A2XFY NO. 8 LV CONTROL CABLE SIZES: 167 3C x 2.5 SQ.MM. YWY NO. 54 168 4C x 2.5 SQ.MM. YWY NO. 18 169 7C x 2.5 SQ.MM. YWY NO. 63 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 20 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. LIGHT FITTINGS: NOTE:INSTALLTION OF POLES TO BE EXCLUDED.THIS IS CATEGORISED SEPERATELY UNDER "LIGHTING POLES" INSTALLTION, TESTING & COMMISSIONING OF FLAMEPROOF EXD TYPE SUITABLE FOR ZONE 1 & 2 GAS GROUP IIA / IIB TEMPERATURE CLASS T-3 WELLGLASS FIXTURE, WITH LAMP, INTEGRAL CONTROL GEAR BOX/ NON-INTEGRAL CONTROL GEAR BOX, WIRE GUARD & SUITABLE FOR SUSPENDED, BRACKET, POLE MOUNTING. FIXING BRACKETS SHALL BE PROVIDED. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3NOS. OF ENTRIES SUITABLE FOR 3Cx2.5 SQ.MM. YWY CABLE AND 1NO. SEALING PLUG. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARDWARE AND EXCLUDING SUPPLY OF STRUCTURAL STEEL. 2 X 26 W CFL - (Cat. Ref. CGL-FWL12226IH/B or Equivalent) WITH FOLLOWING MOUNTING TYPE 170 GROUND POLE MOUNTED NO. 24 BRACKET/ CEILING MOUNTED NO. STRUCTURE MOUNTED NO. 150W MH - (Cat. Ref. FWL 1215MHIH/A or Equivalent) NO. WITH FOLLOWING MOUNTING TYPE GROUND POLE MOUNTED NO. 171 BRACKET/ CEILING MOUNTED NO. 75 STRUCTURE MOUNTED NO. 250W MH (Non-Integral with separate Control Gear Box & Fuses) - Cat. Ref. FWL 12/A NO. WITH FOLLOWING MOUNTING TYPE 172 GROUND POLE MOUNTED NO. 49 BRACKET/ CEILING MOUNTED NO. STRUCTURE MOUNTED NO. INSTALLTION, TESTING & COMMISSIONING OF INDUSTRIAL WELLGLASS FIXTURE, WITH LAMP, INTEGRAL CONTROL GEAR BOX/ NON-INTEGRAL CONTROL GEAR BOX, WIRE GUARD & SUITABLE FOR SUSPENDED, BRACKET, POLE MOUNTING. FIXING BRACKETS SHALL BE PROVIDED. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3NOS. OF ENTRIES SUITABLE FOR 3Cx2.5 SQ.MM. YWY CABLE AND 1NO. SEALING PLUG. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARDWARE AND EXCLUDING SUPPLY OF STRUCTURAL STEEL. 2 X 26 W CFL WITH FOLLOWING MOUNTING TYPE P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 21 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. 173 GROUND POLE MOUNTED NO. 7 BRACKET/ CEILING MOUNTED NO. STRUCTURE MOUNTED NO. 150W MH - (INTEGRAL) NO. WITH FOLLOWING MOUNTING TYPE GROUND POLE MOUNTED NO. 174 BRACKET/ CEILING MOUNTED NO. 17 STRUCTURE MOUNTED NO. 250W MH - (NON-INTEGRAL) WITH SEPARATE CONTROL GEAR BOX & FUSES. NO. WITH FOLLOWING MOUNTING TYPE 175 GROUND POLE MOUNTED NO. 16 176 BRACKET/ CEILING MOUNTED NO. 2 STRUCTURE MOUNTED NO. POST TOP LANTERN LIGHTINGS 177 INSTALLTION, TESTING & COMMISSIONING OF INDUSTRIAL TYPE, POST TOP LANTERN FITTINGS, WITH 125W HPMV TYPE WITH CONICAL COVER, ELECTRONIC CONTROL GEAR (CAT. REF. PHILIPS-HPC101/125 HPF OR EQUIVALENT). FIXING BRACKETS SHALL BE PROVIDED. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3NOS. OF ENTRIES SUITABLE FOR 3Cx2.5 SQ.MM. 2XWY CABLE AND 1NO. SEALING PLUG. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARDWARE. NO. 4 178 BOLLARD FIXTURES - (CAT. REF. PHILIPS-HCS360 1 X PL-C 18W OR EQUIVALENT) NO. 60 INSTALLATION, TESTING & COMMISSIONING OF INDUSTRIAL TYPE, FLUROSCENT (FTL) FIXTURE, WITH LAMP, BALLAST, SUITABLE FOR SUSPENDED, SURFACE, BRACKET MOUNTING. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3 NOS. OF ENTRIES SUITABLE FOR 3CX2.5 SQ.MM CABLE & 1 NO. SEALING PLUG. INSTALLATION SHALL BE INCLUSSIVE OF ALL NECESSARY HARDWARE. 179 2 X 36W FTL - Cat. Ref. CGL-IGP 1424HSB or Equivalent NO. 8 180 INSTALLATION OF INDUSTRIAL FLUROSCENT (FTL) FIXTURE, WITH LAMP, BALLAST SUITABLE FOR BRACKET MOUNTING WITH NECESSARY SUPPORTS FOR TRANSFORMER YARD. NO. 4 Cat. Ref. CGL-IGP 1424HSB or Equivalent INSTALLTION, TESTING & COMMISSIONING OF INDUSTRIAL FLOOD LIGHT FIXTURE,WITH LAMP, INTEGRAL CONTROL GEAR BOX & FUSES. NON CORROSIVE HIGH PRESSURE DIE CAST ALUMINIUM HOUSING WITH LOW COPPER CONTENT , HOT DIP GALVANISED STEEL MOUNTING BRACKET AND COMPLETE WITH ALL THE ACCESSORIES. LOOP IN LOOP OUT FACILITY SHALL BE PROVIDED WITH MINIMUM 3NOS. OF M20 ENTRIES AND 1NO PLUG. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARDWARE. P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 22 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. 181 400W MH MOUNTED ON 11 MTR. POLE - Cat. Ref. CGL- FAI40IH/MH or Equivalent NO. 3 182 NON-FLAMEPROOF CHARGEABLE EMERGENCY LIGHTS TO BE PROVIDED IN THE FOLLOWING AREAS: NO. 5 CONTROL ROOM NO. 1 TERMINAL IN-CHARGE ROOM NO. 1 MCC ROOM-2 NO. 1 MAIN SUBSTATION NO. 2 LIGHTING POLES INSTALLATION OF LIGHTING POLE AND ACCESSORIES INCLUSSIVE OF MARSHALLING BOX/ JUNCTION BOX, SUPPLY OF PVC INSULATED FLEXIBLE WIRE BETWEEN MARSHALLING BOX/ JUNCTION BOX AND LIGHTING FITTING AND ALL NECESSARY HARDWARE. ALL OTHER CIVIL WORK, AS REQUIRED, INCLUDING EXCAVATION, PROVIDING SHUTTERING, FOUNDATION, DEWATERING, CONCRETE PEDESTAL ETC. SHALL BE BY ELECTRICAL CONTRACTOR. 183 MS TUBULAR/ OCTAGONAL LIGHTING POLE, HOT NO. 65 DIP GALVANISED, 5M HEIGHT FROM FINISHED GROUND LEVEL. FOR WELLGLASS FIXTURE (125W / 250W ) WITH ALL ACCESSORIES 184 MS TUBULAR/ OCTAGONAL LIGHTING POLE, HOT NO. 3 DIP GALVANISED, 11M HEIGHT FROM FINISHED GROUND LEVEL. FOR WELLGLASS FIXTURE (400W ) WITH ALL ACCESSORIES JUNCTION BOX INSTALLATION OF FLAMEPROOF EXD TYPE SUITABLE FOR ZONE 1 & 2 GROUP IIA / IIB. TEMPERATURE CLASS T-3 JUNCTION BOX WITH ACCESSORIES AS INDICATED BELOW. ENCLOSURE OF JUNCTION BOX SHALL BE MADE UP OF CAST LIGHT METAL ALLOY. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARDWARE AND EXCLUDING SUPPLY OF STRUCTURAL STEEL. 185 4 WAY, WITH TERMINALS TO BE SUITABLE FOR NO. 1 ACCOMODATING ONE 3.5Cx50 SQ.MM. INCOMING CABLES AND 3 NOS. 3Cx35 SQ.MM. OUTGOING CABLES. WITH PLUGS 186 4 WAY, WITH TERMINALS TO BE SUITABLE FOR NO 1 ACCOMODATING ONE 3.5Cx70 SQ.MM. INCOMING CABLES AND 3 NOS. 3Cx35 SQ.MM. OUTGOING CABLES. WITH PLUGS 187 4 WAY, WITH TERMINALS TO BE SUITABLE FOR NO 4 ACCOMODATING ONE 3.5Cx95 SQ.MM. INCOMING CABLES AND 3 NOS. 3Cx35 SQ.MM. OUTGOING CABLES. WITH PLUGS 188 4 WAY, WITH TWO M20 ENTRIES AND ONE M16 ENTRY. NO. 174 TERMINALS TO BE SUITABLE FOR ACCOMODATING 3Cx2.5 SQ.MM. OUTGOING CABLES WITH PLUGS P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 23 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. PANEL: INSTALLATION, TESTING AND COMMISSIONING OF FOLLOWING 415V PANELS. THE PANELS SHALL BE INDOOR, FLOOR/WALL MOUNTED WITH BOTTOM/TOP CABLE ENTRY. INSTALLATION SHALL BE INCLUSIVE OF NECESSARY HARDWARE AND EXCLUDING SUPPLY OF STEEL STRUCTURE 189 CAPACITOR PANEL WITH CAPACITORS & APFC CONTROLLED SYSTEM - FLOOR MOUNTED AS PER SLD & SPECIFICATIONS NO. 1 190 POWER DISTRIBUTION PANEL - PDP FLOOR MOUNTED AS PER SLD & SPECIFICATION NO. 2 191 MAIN LIGHTING DISTRIBUTION PANEL-MLDP WITH ENERGY SAVER WITH TIMER & CONTACTOR FOR OUTDOOR LIGHTING FEEDERS AS PER SLD & SPECIFICATION (COMPARTMENTALISED, FLOOR MOUNTED, SINGLE FRONT PANEL) NO. 1 192 EMERGANCY LIGHTING DISTRIBUTION PANEL WITH ENERGY SAVER WITH TIMER & CONTACTOR FOR OUTDOOR LIGHTING FEEDERS AS PER SLD & SPECIFICATION (COMPARTMENTALISED, FLOOR MOUNTED, SINGLE FRONT) NO. 1 193 YARD LIGHTING DISTRIBUTION PANEL WITH ENERGY SAVER ALONG WITH TIMER FOR LIGHTING AS PER SLD & SPECIFICATION NO. 1 LIGHTING DISTRIBUTION BOARDS-LDB [WALL MOUNTED] FLAME PROOF ExD TYPE SUITABLE FOR ZONE 1 & ZONE 2 GAS GROUP IIA / IIB, TEMPERATURE CLASS T-3. THE ENCLOSURE SHALL BE MADE OF CAST LIGHT METAL ALLOY WITH SUITABLE SIZE KNOCK OUT FOR CABLE CONNECTION WITH CANOPY. TPN INCOMER WITH 3 NOS OF RCC Bs FOR EACH PHASE AND SP OUT-GOING MCB (16kA) FOR LIGHTING. OPERATING KNOB SHALL BE PROVIDED ON TOP SURFACE OF LDB AS SLD AND SPECIFICATION. 194 12 WAY 4 195 18 WAY 4 NORMAL INDUSTRIAL TYPE OUT DOOR - IP-55 LIGHTING DISTRIBUTION BOARD (LDB) HAVING 2MM THICK SHEET STEEL WITH SUITABLE SIZE KNOCK OUT FOR CABLE CONNECTION WITH CANOPY. TPN INCOMER WITH 3 NOS OF RCCBs FOR EACH PHASE & SP OUT-GOING MCB (16KA) FOR LIGHTING AS PER SLD AND SPECIFICATION 196 12 WAY NO. 2 197 18 WAY NO. 1 SMALL POWER DISTRIBUTION BOARD - SDB (WALL MOUNTED) P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 24 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. NORMAL INDUSTRIAL TYPE OUT DOOR IP-55 SMALL POWER DISTRIBUTION BOARD (SDB) HAVING 2MM THICK SHEET STEEL WITH SUITABLE SIZE KNOCK OUT FOR CABLE CONNECTION WITH CANOPY. INCOMER WITH 3 NOS OF RCCBs FOR EACH PHASE & SP OUT-GOING MCB (16KA) FOR LIGHTING 198 18 WAY NO. 7 199 POWER DISTRIBUTION PANEL FOR MOVs FLOOR MOUNTED AS PER SLD & SPECIFICATION NO. 1 200 OUTDOOR POWER DISTRIBUTION BOARD FOR MOVs FLOOR MOUNTED AS PER SLD & SPECIFICATION NO. 9 415 V BUSDUCT INSTALLATION, TESTING AND COMMISSIONING OF FOLLOWING BUSDUCTS. SCOPE AS PER SPECIFICATION AND EQUIPMENT LAYOUT INCLUDES TRANSPORTATION TO THE PLACE OF INSTALLATION, ASSEMBLY AND JOINING OF SHIPPING SECTIONS, CONNECTIONS AT TRANSFORMER END AS WELL AS SWITCHGEAR END INCLUDING FIXING OF FLEXIBLE LINKS, CANOPY AND BUSDUCT SUPPORTING ARRANGEMENTS. WALL CUTOUTS SHALL BE SUITABLY SEALED. 201 BUSDUCT NO. BD-01 NO. 1 RATING : TPN 415V, 3200 AMPS. NO.OF BENDS = 4 OUTDOOR LENGTH : HORIZONTAL= 2.6 Mtr. VERTICAL= 4.5 Mtr. INDOOR LENGTH : HORIZONTAL= 2.2 Mtr. VERTICAL= 1.2 Mtr. 202 BUSDUCT NO. BD-02 NO. 1 RATING : 415V, 3200 AMPS. NO.OF BENDS = 4 OUTDOOR LENGTH : HORIZONTAL= 2.6 Mtr. VERTICAL= 4.5 Mtr. INDOOR LENGTH : HORIZONTAL= 6.2 Mtr. VERTICAL= 1.2 Mtr. FANS ALONG WITH ACCESSORIES INSTALLTION, TESTING & COMMISSIONING OF EXHAUST FAN WITH STARTER. EXHAUST / FRESH AIR FAN 203 450 DIA. SINGLE PHASE, 240V AC EXHAUST FAN NO 27 SAFETY EQUIPMENTS RUBBER MATS (SUPPLY AND INSTALLATION) RUBBER MAT SHALL BE CHEQUERED TYPE AS PER RELEVANT INDIAN STANDARD RUBBER MATS SHALL BE SUPPLIED IN UNROLLED CUT PIECES (MATS SHALL NOT BE SUPPLIED IN ROLLED FORM) CUTTING OF RUBBER MATS SHALL BE DONE AT FACTORY AND NOT AT SITE. P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 25 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. 204 415 VOLT GRADE RUBBER MAT OF WIDTH MTR. 78 900 MM. MAXIMUM PIECE LENGTH - 2.4 MTRS. CUT IN FACTORY 205 33 KV GRADE RUBBER MAT OF WIDTH 900 MTR. 4 MM. EACH CUT PIECE OF 1100 MM LENGTH CUT IN FACTORY SHOCK TREATMENT CHART 206 SUPPLY & INSTALLATION OF PRINTED AND NO. 4 FRAMED SHOCK TREATMENT CHART IN ENGLISH AND LOCAL LANGUAGE CAUTION BOARDS SUPPLY & INSTALLATION OF METALLIC CAUTION BOARDS AS PER RELEVANT IS OF VOLTAGE GRADE AS GIVEN BELOW IN ENGLISH AND LOCAL LANGUAGE 207 440V CAUTION BOARD NO. 10 208 33 KV CAUTION BOARD NO. 4 FIRST AID KIT 209 SUPPLY & INSTALLATION OF FIRST AID KIT SETS 3 TO BE KEPT ON WOODEN STAND AND SHALL BE SUITABLE FOR 10 PERSONS HAND GLOVES (SUPPLY AND INSTALLATION) 210 500V ELECTRIC GRADE RUBBER GLOVES PAIR 2 211 33kV GRADE HAND GLOVES PAIR 1 MISCELLANEOUS ITEMS (SUPPLY AND INSTALLATION) CANOPY SUPPLY & INSTALLATION OF CANOPY FOR OUTDOOR MOTORS, CANOPY SHALL BE MADE UP OF FRP. SHAPE, SIZE, LEGS, LOUVERS, HANDLES ETC. AS PER SITE REQUIREMENT. CANOPY FOR OUTDOOR MOTORS WITH DIFFERENT KW RATINGS AS SPECIFIED BELOW. FRAME SIZE OF CANOPY SHALL BE ONE FRAME HIGHER THAN MOTOR FRAME SIZE. 212 MOTOR RATING UPTO 3.7KW NOS. 3 213 MOTOR RATING ABOVE 5.5KW & UPTO 30KW NOS. 27 214 MOTOR RATING ABOVE 30KW & UPTO 110KW NOS. 15 215 MOTOR RATING ABOVE 110KW NOS. 8 ANCHOR FASTNER SUPPLY AND INSTALLATION OF ANCHOR FASTNER FOR SUPPORTING / FIXING CABLE TRAY SUPPORTS & MISCELLANEOUS ELECTRICAL SWITCHGEAR (SAMPLE SHALL BE APPROVED BY SITE ENGINEER) 216 6 MM DIA. 60 MM LONG NO. 25 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 26 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. 217 8 MM DIA. 75 MM LONG NO. 30 218 10 MM DIA. 100 MM LONG NO. 25 219 12 MM DIA. 150 MM LONG NO. 30 INSERT PLATE SUPPLY AND INSTALLATION OF INSERT PLATE AS PER INDIAN STANDARDS & INSTALLATION (WITH THE HELP OF METALLIC ANCHOR FASTNER) FOR SUPPORTING LIGHT FITTING, SMALL CABLE TRAY AND MISCELLANEOUS ELECTRICAL ITEMS 220 100 x 100 x 8 MM THICK 25 221 150 x 150 x 6 MM THICK 25 222 150 x 150 x 10 MM THICK 25 SEALING OF PIPES IN SAFE AREA FILLING OF GI / PVC / HUME PIPE ENDS WITH INSULATING WOOL ASBESTOS BLANKET FIBRE GLASS WASTES AND SEALING THE SAME WITH BITUMEN BASED WATERPROOF COMPOUND. CONTRACTOR SHALL QUOTE FOR LABOUR CHARGES BASED ON NUMBER OF PIPE ENDS TO BE SEALAED OF THE FOLLOWING SIZES. INSTALLATION RATE SHALL INCLUDE ALL CONSUMABLES INCLUDING BITUMEN COMPOUND. 223 75 MM DIA PIPE NOS. 20 224 150 MM DIA PIPE NOS. 25 225 200 MM DIA PIPE NOS. 20 226 300 MM DIA PIPE NOS. 25 ADAPTOR / REDUCER SUPPLY & INSTALLATION OF FLAMEPROOF TYPE ADAPTOR / REDUCER FOR HAZARDOUS AREA EQPTS SUITABLE FOR APPLICATION IN ZONE-1 & ZONE-2 AREA AND TEMPERATURE CLASS T-3. ADAPTOR SHALL BE ONE SIDE THREADED AS PER THE THREADS ON EQUIPMENT AND OTHER END TO SUIT CABLE GLANDS (AS PER SITE REQUIREMENT) 227 1" x 3/4" NOS. 25 228 1 1/4" x 1" NOS. 15 229 1 1/4" x 3/4" NOS. 20 230 1 1/2" x 1" NOS. 10 231 2" x 1 1/2" NOS. 15 SEALING PLUG SUPPLY & INSTALLATION OF METALLIC (MS) SEALING PLUG FOR UNUSED CABLE ENTRIES IN MOTORS, JUNCTION BOXES, ETC. OF FOLLOWING SIZES. (AS PER SITE REQUIREMENT) 232 3/4" ET NOS. 25 233 1" ET NOS. 15 234 1 1/4" ET NOS. 20 235 1 1/2" ET NOS. 10 236 2" ET NOS. 15 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 27 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. PIPES GI PIPES INSTALLATION OF CLASS-B GI PIPE OF SIZES AS SPECIFIED BELOW TO BE FIXED ON WALL STEEL STRUCTURE BURRIED IN GROUND, LAID IN TRENCHES FOR PROTECTION OF CABLES EARTHING CONDUCTORS OF INCLUDING BENDING, THREADING, COUPLING, WELDING, CLAMPING AS REQUIRED. 237 75 MM DIA GI PIPE MTR. 25 238 150 MM DIA GI PIPE MTR. 20 PVC PIPES INSTALLATION OF PVC PIPES OF SIZES AS SPECIFIED BELOW TO BE FIXED ON WALL OR STEEL STRUCTURE FOR CABLES IN WALL OR STEEL STRUCTURE FOR CABLES INCLUDED BENDING AS REQUIRED. 239 75 MM DIA GI PIPE MTR. 25 240 150 MM DIA PVC PIPE MTR. 110 HUME PIPES INSTALLATION OF HUME PIPES OF INNER DIA. AS SPECIFIED BELOW TO BE LAID BURIED UNDERGROUND FOR PROTECTION OF CABLES / EARTHING CONDUCTORS WITH REQUIRED COUPLING RINGS. 241 150 MM DIA HUME PIPE MTR. 25 242 200 MM DIA HUME PIPE MTR. 25 243 300 MM DIA HUME PIPE MTR. 25 STRUCTURAL STEEL INSTALLATION & FABRICATION OF 244 STRUCTURAL STEEL IN FORMS OF M.S. TON 35 ANGLES, CHANNELS, BEAMS, FLATS, ETC. FOR SUPPORTING VARIOUS ITEMS / EQUIPMENT SUCH AS SWITCHGEARS, PANELS, CABLE TRAYS, PUSH BUTTON STATIONS, LOCAL CONTROL BOXES, LOCAL CONTROL PANELS, JUNCTION BOXES, DISTRIBUTION BOARDS, LIGHTING FITTINGS, ETC. INCLUDING DRILLING, WELDING, GROUTING, GRINDING, CHIPPING, BOLTING WITH SUPPLY OF REQUIRED HARDWARE. FABRICATED AND INSTALLED STRUCTURAL STEEL SHALL BE SUITABLY PAINTED WITH 2 COATS OF FINSIH EPOXY PAINT AFTER APPLYING 2 COATS OF PRIMER. FINISH PAINT SHADE SHALL BE SAME AS THAT OF MAIN STRUCTURE OR WILL BE AS PER SITE ENGINEER'S APPROVAL SURFACE PREPARATION: BRUSHING & CLEANING PRIMER TYPE : EPOXY BASED (EPILUX - 610 OR EQ. - 50 MICRON) FINISH PAINT : EPOXY POLYAMIDE HIGH BUILD (EPILUX 89 OR EQ.) 125 MICRON FINISH PAINT SHADE : AS PER SITE REQUIREMENT P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 28 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. FREE ISSUE ITEMS - INSTALLATION NOTE : INSTALLATION RATE SHALL INCLUDE SUPPLY OF CONSUMABLES AND HARDWARE AND EXCLUDING SUPPLY OF STRUCTURAL STEEL SINCE THIS IS CATEGORISED SEPERATELY. INDOOR HT SWITCHGEAR INSTALLATION, TESTING AND COMMISSIONING ASSISTANCE OF FOLLOWING FREE ISSUE INDOOR HT SWITCHGEAR. SCOPE INCLUDES TRANSPORTATION FROM THE OWNER'S STORE TO THE PLACE OF INSTALLATION, ERECTION ON BASE FRAME / FOUNDATION,ASSEMBLING OF VARIOUS SHIPPING SECTIONS, ALIGNING, LEVELLING, FIXING / GROUTING / WELDING TO THE BASE FRAME OR INSERT PLATES PROVIDED ON THE FLOOR. SCOPE ALSO INCLUDES INTERCONNECTION OF SHIPPING SECTIONS AND INTER PANEL WIRING BETWEEN SHIPPING SECTIONS, TESTING AND CALIBRATION OF ALL THE CT'S, PT'S, RELAYS, METERS AND ENERGISING OF THE SWITCHGEAR AT RATED VOLTAGE. INSTALLATION RATE SHALL INCLUDE SUPPLY OF GI CONSUMABLES AND HARDWARE AND EXCLUDING SUPPLY OF STRUCTURAL STEEL. 245 33KV MAIN SWITCHGEAR APSEB PANEL NO. 1 246 33KV SWITCHGEAR (1 I/C & 2 O/Gs) HPCL PANEL NO. 1 TRANSFORMER INSTALLATION, TESTING, COMMISSIONING OF FOLLOWING 2 WINDING TRANSFORMER ON READY MADE FOUNDATION. THIS SHALL INCLUDE TRANSPORTING FROM OWNER'S ISSUE POINT, UNLOADING FROM TRUCK (IF ARRIVED AFTER MOBILISATION OF CONTRACTOR ) SITE ASSEMBLING OF LOOSE SUPPLIED ACCESSORIES AND FILLING OF OIL, TOPPING UP WITH OIL (INCLUDING FILTRATION), SUPPLY & SPREADING OF 25 mm GRAVELS AS PER THE REQUIREMENT. 247 2000 KVA, 33/0.433KV, DYn11, 6.25% WITH OFF CIRCUIT TAP CHANDER DISTRIBUTION TRANSFORMER FOR PLANT LOAD NO. 1 248 2000 KVA, 33/0.433KV, DYn11, 6.25% WITH OFF CIRCUIT TAP CHANDER DISTRIBUTION TRANSFORMER FOR ELECTRICAL HEAT TRACING LOAD NO. 1 415 V LOW VOLTAGE SWITCHGEARS. INSTALLATION, TESTING AND COMMISSIONING ASSISTANCE OF FOLLOWING INDOOR LV SWITCHGEAR. THE PANELS ARE MOUNTED ON THE FLOOR CUT OUTS. THE EQUIPMENT FOUNDATION LAYOUT IS TO BE CARRIED BY CONTRACTOR (THE DWGS. WILL BE GIVEN TO THE SUCCESSFUL BIDDER). HOWEVER FOR ANY CHANGES IN PANEL DIMENSIONS AT A LATER STAGE ,SUITABLE ASSUMPTIONS ARE TO BE MADE IN CONSULTATION WITH SITE ENGINEER TO PLACE PANEL SUPPORT BASED ON THE SHIPPING SECTION. 249 PMCC-1 (AS PER SLD) NO. 1 PCC (AS PER SLD ) 250 TANK TRUCK FILLING MCC (AS PER SLD) NO. 1 251 TANK WAGON FILLING MCC (AS PER SLD) NO. 1 252 SHIPPING/ BUNKERING MCC (AS PER SLD) NO. 1 P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 29 of 30 UNIT RATE TOTAL AMOUNT (Rs.) (Rs.) VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL Rev B Doc No: 254625-300-SC-ELE-009 SCHEDULE OF QUANTITY FOR ELECTRICAL BULKS PART B : INSTALLATION OF EQUIPMENT IN CONTRACTORS SCOPE REMARKS SR. NO. DESCRIPTION UNIT QTY. BATTERY & BATTERY CHARGER PANELWITH DCDB INSTALLATION, TESTING & COMMISSIONING ASSISTANCE OF FOLLOWING INDOOR TYPE, FLOOR MOUNTED PANELS WITH BOTTOM CABLE ENTRY & ASSOCIATED BATTERIES. 253 110V, DC BATTERY. INSTALLATION SHALL INCLUDE POSITIONING OF STAND, STAND INSULATORS, CELL INSULATORS, LEVELLING, FIXING OF NUMBER PLATS, INTERCONNECTION OF CELLS (INTERCONNECTING LINKS SHALL BE SUPPLIED BY BATTERY SUPPLIER). SCOPE ALSO INCLUDES FILLING OF ACID, FIRST CHARGING, DISCHARGING, CAPACITY TEST AND RECHARGING OF BATTERY AS PER THE PROCEDURES PRESCRIBED BY MANUFACTURER. INTERCONNECTION OF BATTERY BANK WITH BATTERY BREAKER. SET 1 254 BATTERY CHARGER WITH DCDB PANEL NO. 1 (FLOAT CHARGER, FLOAT CUM BOOST CHARGER & DCDB ) TESTING, COMMISSIONING OF MOTORS TESTING AND COMMISSIONING OF FOLLOWING LT MOTORS. 415V, SQUIRREL CAGE, INDUCTION MOTORS
255 MOTORS RATING UPTO 3.7 KW NO. 3 256 MOTORS RATING ABOVE 5.5 KW UPTO 30 KW NO. 27 257 MOTORS RATING ABOVE 30 KW UPTO 110 KW NO. 15 258 MOTORS RATING ABOVE 110 KW NO. 8 NOTE:- VENDOR HAS TO MARK NUMBERS ON EACH EARTHING PIT. VENDOR HAS TO PROVIDE TEST CERTIFICATES FOR EACH EARTHING PITS. PAYMENT AGAINST INSTALLATION OF ALL ITEMS SHALL BE AS PER EXECUTED QTY. & RECONCILATION WILL BE DONE AT FINAL BILLING STAGE. NECESSARY DEDUCTIONS SHALL BE MADE FOR CHANGE IN QTY. PAYMENT AGAINST INSTALLATION OF CABLES SHALL BE AS PER EXECUTED QTY. & RECONCILATION WILL BE DONE AT FINAL BILLING STAGE. IF PAYMENT IS DONE DURING RUNNING BILLS AGAINST INSTALLATION, NECESSARY DEDUCTIONS SHALL BE MADE FOR ANY EXCESS QTY. OF INSTALLATION CABLES. P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\Schedule of Qty for Electrical Bulks-BO-Rev.B_08.10.09 30 of 30 VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 23 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc Appendix H : Recommended List of vendors 33kV Power Cables : Finolex cables/ Universal Cables/ Cable Corporation of India Ltd/ ASIAN/ TORRENT/ KEI/ RPG Cables Co. L.V. Power & Control Cables : Polycab cables/ Finolex cables/ Universal Cables/ Cable Corporation of India Ltd/ ASIAN/ TORRENT/ KEI/ RPG Cables Co. Cable Gland : Baliga/ Hawke/ Victory/ BEECO/ FCG/ COMET/ HMI/ Power Engg. Cable Lug : DOWELLS/ Usha Ismal/ JENSON GI Cable Trays : Super Reinforced Plastics Associates Engg. Corp./ GRIP INDIA/ SSB Industries/ ERCON Composites/ General Composutes/ Indiana/ Enduro Flameproof : Local Control Station : FEPL/ Baliga/ FCG Power Industries/ Flameproof Control Gear Light Fixtures & Accessories : FEPL/ Baliga/ FCG Power Industries/ Flameproof Control Gear/ Sudhir Switchgear Junction Boxes : FEPL/ Baliga/ FCG Power Industries/ Flameproof Control Gear/ Sudhir Switchgear Sub-Lighting & Power Panels (SLDB, SELDB, SPDB) : FEPL/ Baliga/ FCG Power Industries/ Flameproof Control Gear/ Sudhir Switchgear Plugs & Sockets : FEPL/ Baliga/ FCG Power Industries/ Flameproof Control Gear/ Sudhir Switchgear Industrial : Local Control Station : FEPL/ Baliga/ FCG Power Industries/ Flameproof Control Gear/ Mansu/ Pushtron Light Fixtures & Accessories : Philips/ Crompton Greaves/ Bajaj Electricals/ Wipro Junction Boxes : Power Controls/ Sudhir Switchgear/ Flexpro/ ELECMECH/ ELMA/ FCG Power Industries Sub-Lighting & Power Panels (SLDB, SELDB, SPDB) : MDS/ INDO ASIAN Switchgears/ Havells/ Standard/ Legrand India Plugs & Sockets : Bhartia Cutler Hammer/ Best & Crompton/ Schneider Electric India Ltd/ RB (Ryrol Burn)
Gang Operated Switches & Isolators : ABB/ KRUGGS/ S&S Power/ Danke/ Dreishcher Panickar/ Hivelum Industries/ CGL/ Sterling Isolators/ Kiran Textiles Lightning Arrestor : ELPRO International Ltd/ ALSTOM/ OBLUM Electrical Industries/ ATLAS/ WS Industries/ CGL/ ABB PIN Insulator, Porceilin Bushes/ Disc/ Post Insulators : Jaya Shree Insulators/ Modern Insulators/ ALSTOM/ Shesasayee Industries/ WS Industries Termination/ Jointing Kit : Cable Corporation of India Ltd/ Raychem/ M-Seal/ Pidilite Busduct : MK Engg./ Stardrive/ Globe Electricals/ ELECMECH/ Elpro APFC Panel/ LDP with Energy Saver/ PDP : Popular Switchgear Pvt.Ltd./ NEEL Industrial Systems Pvt. Ltd/ ELECMECH/ S&S Power Switchgear/ MK Engg./ ELMA Energy Saver NEEL Industrial Systems Pvt. Ltd / Duex Energy ACB : Siemens / L&T / ABB / Schnieder VISAKH MARKETING INSTALLATION RESITEMENT PROJECT - BLACK OIL TERMINAL
Doc No: 254625-300-RQ-ELE-003 Rev: B Page 24 of 25
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\Procurement\Electrical Bulk\Electrical Work Tender\08.10.09\Editable\254625-300-RQ-ELE-003.doc