Computerized Control System
for refrigerating compressors
Instruction Manual
COMSAB II - TREND
95.12
0178-405-EN
1
Instruction Manual
COMSAB II - TREND
Computerized Control System
for refrigerating compressors
2 0178-405-EN
Preface
The present instruction manual, that covers
the COMSAB II-T (SABROE/TREND) gate-
way, describes how to install the unit and
how to use the SABROE/TREND protocol
0178-405.
COMSAB II-T gives the user access to read
and write data in the following SABROE com-
pressor control units: PROSAB II, UNISAB
S/R/RT/RTH and UNISAB II.
SABROE REFRIGERATION A/S
P.O. Box 1810, DK-8270 Hjbjerg
Chr. Xs Vej 201, rhus, Denmark
Phone:
Telefax: +45 86 27 44 08
+45 86 2712 66
Telex: 86 87 40
PRODUCT DIVISION
0178-405-EN
3
Contents
Preface 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Port 1 - RS485 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Port 2 - RS232 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trend system setup 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protocol 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Message format 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Text Alarms 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Suppervisor Request 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reply from the COMSAB II - T 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Point Lay-out for the COMSAB II - T 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Point Lay-out 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Points to read/write 15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Note the following 19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compressor control modes 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compressor modes 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control systems 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multisab state 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of alarm/warnings 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Note the following 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 0178-405-EN
Installation:
COMSAB II-T is installed as shown in the fi-
gure below.
You would need:
-- A 2 vire power cable.
-- A 5 vire RS232 cable.
-- A 2 vire screened RS485 communication
cable.
(See the instruction book Installing a data
communications cable for the right com-
munication cable type).
-- Cable between CNC + nodes and be-
tween CNC + node and TREND 945 sys-
tem (PC).
0178-405-EN
5
Overview
Power cable
24 VAC/VDC
CNC + node
COMSAB II-T
J6 J7 J2
J5
J4 J3 J1
CPU51 Interface Code
Diodes
Port 3
Port 2 Port 1 Power
RS232 cable
RS485 cable
UNISAB/PROSAB II
1 2 Max 14
RS485 BUSS
4 1 9 1 9 1
TREND (ring) network
TREND
IQ Station
CNC + protocol
TREND
Supervisor 945/921
Current loop
CNC +
The CNC-node is used to attach the
COMSAB II-T onto TREND Network. The
Node has its own individual address within
the TREND Network.
There are no jumpers or switches on
COMSAB II-T witch have to set before
operation.
Place the COMSAB II-T, the RS232 cable
and the RS485 communication cable in a
distance of minimum 30 cm from contactors,
high power cables or any other unit radiating
electromagnetic noise.
6 0178-405-EN
Power:
COMSAB II-T has to be supplied with either
15-28 VAC or 18-40 VDC on plug J1:
Power
Ground
J1
1 2 3 4
+ --
24 VAC or DC
Pin #1: Chassis (Ground connection)
Pin #2: AC / DC +
Pin #3: AC / DC --
Pin #4: Not connected
Port 1 -- RS485:
The plug (J3) connections are:
Pin #1: Gnd Signal ground.
Pin #2 + 8: Tx/Rx + Transmit/Receive Data.
Pin #4 + 6: Tx/Rx -- Transmit/Receive Data.
Port 1
1 2 3 4 5 6 7 8 9
Gnd TX+Data TX--Data RX--Data RX+Data
TX+Term. TX-Term. RX-Term. RX+Term.
+ --
J3
Cable screen
In order to terminate the communication, pins
2 + 3 and pins 4 + 5 must be connected to-
gether -- as shown.
The baud rate between COMSAB II-T and
Danbuss is setup automaltically to be the
same as configured in the UNISAB/PROSAB
connected to the RS485 network. The setting
in UNISAB II must be 1200 and 9600 baud.
0178-405-EN
7
Port 2 -- RS232:
The data transmission to CNC+node is
based on the RS232C async serial standard.
Note that two Busy out and Busy in hand-
shake signals are being used.
Port 2
1 2 3 4 5 6 7 8 9
Gnd TxD RxD
J4
Received Data Signal ground Flow control Transmitted Data
Busy out Busy in
Gnd Rx Tx CTS DTR
7 2 20 5 3 D-25 male
TREND CNC+node
Pin #1: Gnd Signal ground.
Pin #2: TxD Transmitted Data.
Pin #8: RxD Received Data.
Pin #4: Busy out Flow control
Pin #6: Busy in Flow control
The data format is: 8 data bit, 1 stop bit and
even parity.
Note that the COMSAB II-T is functioning as
a DTE (Data Terminal Equipment).
The baud rate between COMSAB II-T and
CNC+node is set up automatically, the baud
rate setting in the CNC+node must be19.200
baud.
8 0178-405-EN
Trend system setup:
To run a SABROE demo program, which is
availably by request, it is suggested that the
node connected to the 945 supervisor PC
has no. 20, and that the node connected to
COMSAB II-T has no. 21.
The number is setup by using the DIP switch
on the TREND node.
In the program group 945 Manager the pro-
gram 945 Outstation Organiser is run to de-
fine the outstations no. 20 and 21.
The baud rate between CNC+ and
COMSAB II-T must be set to 19200 baud.
To run the SABROE demo program, then
start the program 945 User Pages in the
program group 945 Manager
Then open the file ..\945\data\:
sab000_t.upg to test point 0-19
sab300_t.upg to test compr. 1, point 1-20
sab320_t.upg to test compr. 1, point 21-40
sab340_t.upg to test compr. 1, point 41-60
sab360_t.upg to test compr. 1, point 61-80
sab380_t.upg to test compr. 1, point 81-99
COMSAB II-T
TREND CNC+node
TREND CNC+node
#21
#20
Tx- Tx+ Rx-- Rx+
Rx-- Rx+ Tx-- Tx+
2 3 5 20 7
2 3 5 20 7
D-25 male
D-25 female
PC 945 supervisor
D-25 male
Diodes:
There are 4 diodes on COMSAB II-T, with the
following function:
Yellow (Idle)
-- Flashes -- syncronized with net activity on
port 1 (RS485).
Green (Frame err.)
-- Light when COMSAB II-T is receiving data
on port 1 (RS485).
Red (Overfl.)
-- Light when COMSAB I-TI is master.
Yellow (Power)
-- Light when power is on.
0178-405-EN
9
Protocol:
SABROE protocol 0178-405 describes the
data communication between a central
TREND computer or IQ station and a
COMSAB II - TREND module.
This protocol allows TREND to retrieve data
from an UNISAB or a PROSAB control panel,
through the COMSAB II-T module. The pro-
tocol always waits to get polled by the central
computer.
Exept for the Text Alarms it never starts a
communication by it self.
The communication is based on the central
computer sending a telegram ( a message )
to the COMSAB II-T module.
Message format:
The communication between TREND Net-
work and COMSAB II-T only support the fol-
lowing formats:
S Random Communications ( Read / Write )
S Text Alarms
S Supervisor request
and follows the specification listed in TREND
CNC+ Interface Development
Note:
Extended addressing are not supported.
S Max. total message length is 100 bytes.
The Protocol are asumed to be like this:
STD Dest Source T1 T2 T3 Class X1 X2 Datafield ETX
Random Mess. no (mode) Extended
Comm. (returned) adressing
=z (not used)
Dest: Address of COMSAB II-T
node
Source: Address of TREND device.
Will be used as Dest. in
REPLY.
Class: ENQ = 05 = read
FF = 12 = reply
EOT = 04 = write
Read:
TREND reads values from UNISAB/PROSAB
by sending a Class = ENQ message:
STX - Dest - Source - T1 - T2 T3 - ENQ -
X1 X2 - Index Index Index ..... list - ETX
Datafield will consist of a list of index
numbers, where each index is referring to
certain point in a certain compressor. The
structure of the index number is as follows.
10 0178-405-EN
Index: 3 bytes ( 1 byte Item type
+ 2 bytes TIN number )
where:
1. byte: Item type: (Analog = CAN = 18H )
2. byte: 2 + Compressor number 1 to 12
(decimal value)
(max. 12 compressors)
3. byte: Point number
1 to 99 (decimal value)
... ref.
SABROE Table 0171-405-EN/TREND -
Points to Read/Write.
The reply (FF) from COMSAB II-T will be:
STX - Dest Source - T1 - T2 T3 - FF -
X1 X2 - Data Data Data .... list - ETX
Datafield will consist of a packed list of
points - corresponding to the received index
list, each point coded to 3 bytes (format
TRN) for analog points. Only format TRN are
used.
Alarms (1-5) and Warnings (1-5) are read as
point number 21 to 25 and 26 to 30, where
the alarm number ( i.e. #31 to #54 ) are re-
turned as data.
Alarm no #31 is Low suction pressure.
........
Write:
TREND writes values to UNISAB/PROSAB
by sending a Class = EOT message:
STX - Dest Source - T1 - T2 T3 - EOT -
X1 X2 - Index Data Index Data .... list -
ETX
Datafield will consist of a list of pairs of a 3
byte index number followed by a 3 byte
(TRN) data field, where the index is referring
to certain point in a certain compressor.
The structure of the index number is as fol-
lows.
Index: 3 bytes ( 1 byte Item type +
2 bytes TIN number )
where:
1. byte: Item type: (Analog = CAN = 18H )
2. byte: 2 + Compressor number
1 to 12 (decimal value)
(max. 12 compressors)
3. byte: Point number
1 to 99 (decimal value)
... ref.
SABROE Table 0171-405-EN/TREND -
Points to Read/Write, point with write access
is marked with x in the R/W collum.
Data: 3 bytes (TRN) number
Text Alarms:
An alarm text string are sent (uninvited) from
COMSAB II-T at the first alarm on a com-
pressor. This is done by sending a (Class =
EOT and T1 =F ) Text Alarm Communica-
tions message:
STX - Dest Source - T1 - T2 T3 - EOT -
X1 X2 - SABROE COMPRESSOR NO. **
_STOPPED DUE TO AN ALARM -
_00:00_00/00/00<CR> -
O000x000_xx**<CR> - ETX
Supervisor Request:
TREND Supervisor 945/921 identifies the
COMSAB II-T node by sending a Class =
ENQ and T1 = w message:
STX - Dest Source - w - T2 T3 - ENQ
X1 X2 - ETX
0178-405-EN
11
The reply (Class = FF) from COMSAB II-T
will be:
STX - Dest Source w - T2 T3 - FF -
X1 X2 - D00000/0_ - ETX
Reply from the COMSAB II-T:
Data written to UNISAB II is checked in the
UNISAB II, if the value exceed the limits that
are build into UNISAB II (se UNISAB II
instruction book for reference) then UNISAB
II accepts and returns the lowest or highest
limit value depending on which limit is ex-
ceeded.
Data written to UNISAB I or PROSAB II is
checked in the COMSAB II-T, if the value ex-
ceed the limits that are build into COMSAB
II-T (se note 17 after the Read/write tabel
and UNISABI / PROSAB II instruction book
for reference) then COMSAB II-T returns a
error message.
Point lay out for the COMSAB II-T:
Points in COMSAB II-T is addressable from
both IQ-stations (partly) and Supervisor 945x
stations, where:
-- TREND IQ- station(s) or Supervisor 921
are addressing analog points from 0 to
255.
-- TREND Supervisor 945 is addressing
analog points from 0 to 9999.
Points with write access is marked with
an x in the R/W collum in the read/write
table.
12 0178-405-EN
Point Lay out
TREND point
no.
SABROE
Compressor no.
Access points.
0-19 1 Read only:
0. Disch. gas temperature
1. Oil temperature
2. Suction gas superheat
3. Brine temperature
4. Suction pressure C/R
5. Disch. pressure C/R
6. Oil pressure
7. Capacity position
8. Motor current
9. Running hours
10. Oil filter differential mode
11. Compressor mode
Read/write:
12. Start sequence no
13. Set point 1, suction pressure
14. Neutral zone, suction pressure
15. Set point 1, brine temperature (15)
16. Neutral zone, brine temperature
17. Set point for capacity (16)
18. Start compressor (13)
19. Stop compressor (14)
20-39 2 Same as for compressor 1
40-59 3 Same as for compressor 1
60-79 4 Same as for compressor 1
0178-405-EN
13
TREND point
no.
SABROE
Compressor no.
Access points.
80-99 5 Same as for compressor 1
100-119 6 Same as for compressor 1
120-139 7 Same as for compressor 1
140-159 8 Same as for compressor 1
160-179 9 Same as for compressor 1
180-199 10 Same as for compressor 1
200-219 11 Same as for compressor 1
220-239 12 Same as for compressor 1
254 COMSAB II-T Read/write:
LAN address TEXT ALARMS
255 COMSAB II-T Read/write:
NODE address TEXT ALARMS
261 COMSAB II-T Suct. system 1 regulator - only PII/ UI
262 COMSAB II-T Suct. system 2 regulator -
263 COMSAB II-T Suct. system 3 regulator -
264 COMSAB II-T Suct. system 4 regulator -
265 COMSAB II-T Suct. system 5 regulator -
266 COMSAB II-T Suct. system 6 regulator -
267 COMSAB II-T Suct. system 7 regulator -
268 COMSAB II-T Suct. system 8 regulator -
269 COMSAB II-T Suct. system 9 regulator -
270 COMSAB II-T Suct. system 10 regulator -
271 COMSAB II-T Suct. system 11 regulator -
272 COMSAB II-T Suct. system 12 regulator -
273 COMSAB II-T Suct. system 13 regulator -
274 COMSAB II-T Suct. system 14 regulator -
14 0178-405-EN
Point Lay-out - Supervisor 945 only
Overview for point numbering 0300-1499
For detailed description of Point access in each group, see the table Point to READ/WRITE
TREND point
no.
SABROE
Compressor no.
Access points.
300-399 1 All READ and WRITE points as specified in the
folowing TABLE Points to READ/WRITE.
(I.e. 100 points/compressor)
400-499 2 Same
500-599 3 Same
600-699 4 Same
700-799 5 Same
800-899 6 Same
900-999 7 Same
1000-1099 8 Same
1100-1199 9 Same
1200-1299 10 Same
1300-1399 11 Same
1400-1499 12 Same
0178-405-EN
15
Points to READ/WRITE:
NAME OF VALUE: COMSAB II-T Available on: Data format
R/W POINT PII/UI U-II Range UNIT
Suction gas temp. 1 X X I C
Disch. gas temp. 2 X X I C
Oil temp 3 X X I C
Suct.pressure 4 X X I BAR
Disch.pressure 5 X X I BAR
Suct.pressure 6 X X I C/R
Disch.pressure 7 X X I C/R
Capacity position 8 X X I %
Volume slide position 9 X(7) X I %
Motor current 10 X X I Amps
Universal regulator 11 X I %
Oil filter diff.pressure (s) /
intermediate pressure (r)
12 X(8) X I BAR
Suct. gas superheat 13 X X I C
Brine /intermediate
temperature
14 X(9) X I C
Running hours 15 X(10) X(10) UI Hours
Alarm 1 16 X X B (4)
Alarm 2 17 X X B (4)
Alarm 3 18 X X B (4)
Alarm 4 19 X X B (4)
Alarm 5 20 X X B (4)
Warning 1 21 X X B (4)
Warning 2 22 X X B (4)
Warning 3 23 X X B (4)
Warning 4 24 X X B (4)
Warning 5 25 X X B (4)
Compressor mode 26 X X B (3)
16 0178-405-EN
NAME OF VALUE: COMSAB II-T Available on: Data format
R/W POINT PII/UI U-II Range UNIT
Control mode 27 X X B (2)
Startsequence no. x 28 X X B 0-14
System for this unit x 29 X X B 1-14
Which control system 30 X X B (5)
Oil pressure 31 X X I BAR
MultiSab state 32 (X) (X) B (6)
Preceding compr 33 (X) (X) B 1-14
Next compr. 34 (X) (X) B 1-14
Cmp to follow the next 35 (X) (X) B 1-14
Selected sysregulator 36 X X B 1-14
Communication errors 37 X X I %
Not used 38 I
Disch. gas superheat 39 X I C
Switch reg. SP1/SP2 40 X B 0-1
Set point actual, suct. press. 41 X I C/R
Setp.1, suct. press. x 42 X X I C/R
Setp. 2, suct. press. x 43 X X I C/R
N.zone, suct. press x 44 X X I C/R
P.band, suct. press. x 45 X I C/R
Set point actual, brine temp 46 X X I C
Set point 1, brine temp. x 47 X(15) X I C
Set point 2, brine temp. x 48 X(15) X I C
N.zone, brine temp x 49 X X I C
P. band, brine temp. x 50 X I C
Set point actual, discharge 51 X I C/R
Set point 1, discharge x 52 X I C/R
Set point 2, discharge x 53 X I C/R
N. zone, discharge x 54 X I C/R
P. band, discharge x 55 X I C/R
0178-405-EN
17
NAME OF VALUE: COMSAB II-T Available on: Data format
R/W POINT PII/UI U-II Range UNIT
Set point actual, external 56 X I %
Set point 1, external x 57 X I %
Set point 2, external x 58 X I %
N. zone, external x 59 X I %
P. band, external x 60 X I %
Set point 1, oil pressure x 61 X I BAR
Set point 2, oil pressure x 62 X I BAR
Switch motor SP1/SP2 63 X B 0-1
Set point 1, motor curr. x 64 X I Amps
Set point 2, motor curr. x 65 X I Amps
Ext. starting permission -
normal
66 X B 0-1
Ext. starting permission -
instant
67 X B 0-1
Start request OK (PMS) 68 X B 0-1
Set point 1, oil temp. - cooling x 69 X I C
Set point 2, oil temp. - heating x 70 X I C
N. zone, oil temp. x 71 X I C
P. band, oil temp. x 72 X I C
Set point 1, suct. gas
superheat
x 73 X I C
Set point 1, disch. gas temp. x 74 X I C
Set point 1, volume slide 75 X I %
Run time since last start 76 X UI Sek(11)
77
78
Software version 79 X I
Start-start delay x 80 X I Sek
Stop-start delay x 81 X I -
Delay before start x 82 X I -
18 0178-405-EN
NAME OF VALUE: COMSAB II-T Available on: Data format
R/W POINT PII/UI U-II Range UNIT
Delay before stop x 83 X I -
Suct. press. ramp function x 84 X I -
Slide max. down time (s)/
Delay up (r)
x 85 X I -
Prelubrication (s)/
Delay down (r)
x 86 X I -
PMS feed back x 87 X I -
Start High press. x 88 X I -
89
Compressor type 90 X I 1-50
Refrigerant type 91 X B 1-8
Regulation mode x 92 X B 1-6
Automatic start x 93 X B 0-1
Automatic stop x 94 X B 0-1
Prelubrication 95 X B 0-1
Compressor no. 96 X B 0-14
Regulation master choise x 97 X B 0-1
Economizer x 98 X B 0-1
99
0178-405-EN
19
Note the following:
X: Valid for this control system:
PII/UI = PROSAB II and UNISAB
S/ R/ RT/ RTH.
UII = UNISAB II.
Range: I = Integer, ie. data range
-- 32268 -- + 32267
UI= Unsigned integer, ie.data
range 0 -- 65535
B = Byte, ie. data range
-- 128 -- + 127 or 0 -- 255.
(s) Only screw compressors.
(r) Only reciprocating compressors.
(1): Only when hardware option
available.
(2): See TABLE OF COMPRESSOR
CONTROL MODES.
(3): See TABLE OF COMPRESSOR
MODES.
(4): See TABLE OF ALARM/WARN-
INGS.
In the UNISAB/PROSAB all alarms,
i.e. a alarm number, are stored in an
alarm-queue, containing max. 5
alarms.
The first (oldest) alarm are stored
in alarm 1 (read point 16), the
next alarm in alarm 2 (read point
17) and the last (newest) alarm are
stored in alarm 5 (read point 20) -
see read/write table.
To read the UNISAB II alarm-queue
you will have to do the following:
Read point 16. If there isnt any
alarm in the UNISAB II then the re-
ply will be a 0 (zero).
If there is one (or more) alarms in
the UNISABII then the reply will be
the number of the oldest alarm, i.e. a
alarm number from 31 to 70 - see
the table of alarm/warnings.
To see if there are more than one
alarm in the queue, then read read
point 17, then point 18, 19 and 20,
until the reply from the COMSAB II-T
is a 0 (zero).
The same procedure is used when
reading the warnings-que.
(5): See TABLE OF CONTROL SYS-
TEMS.
(6): See TABLE OF MULTISAB
STATES.
(7): Only PROSAB II and UNISAB S.
For UNISABS this is a calculated
value. Not a measured value.
(8) Only PROSAB II, UNISAB S and
UNISABR.
(9) Not UNISAB R.
(10) Running hours are internally read as
hours x 1 for UNISAB II and as
hours x 1 for PROSAB II and
UNISAB S/ R/ RT/ RTH.
(11) Run time since last start are read in
sec. (i.e. max run time is ~18 hours).
(13) START COMPRESSOR,
point = 18 .. ,
must have datafield = 1
20 0178-405-EN
Start conditions are:
- Control mode = Remote + Config/
Auto Start = YES or NO
- Compressor mode = Ready
(14) STOP COMPRESSOR,
point = 19 .. ,
must have datafield = 0
Stop conditions are:
- Control mode = Remote + Con fig/
Auto Stop = YES or NO
- Compressor mode = Running
(-overload/suct.lim./disch.lim.) etc.
(15) Reads actual brine set point if
PROSAB II or UNISAB S/R/RT/RTH.
(16) It is only possible to enter capacity
control mode if:
- Control mode = Remote
In capacity control mode start no. is
set to zero.
To leave capacity control mode you
will have to write a set point 1 or 2 to
the suction-, brine-, discharge or ex-
ternal-regulator, then the regulator
(mode) will change back to default
and the start no. will be set back to
the original value.
(17) Min/max limits for values written to
PROSAB II or UNISAB I.
Point No. Min-limit Max-limit Unit
12 + 28 1 14 -
29+261
-274
1 14 -
12 + 42
+ 43
-200 100 C/R
15 + 47
+ 48
- 70 210 C
14+16
+44+49
0 100 C
17 0 100 %
18 1 1 -
19 0 0 -
0178-405-EN
21
COMPRESSOR CONTROL MODES:
Control mode = 0 = STOPPED
Control mode = 1 = MANUAL CONTROL
Control mode = 2 = AUTOMATIC CON-
TROL
Control mode = 3 = REMOTE CONTROL
COMPRESSOR MODES:
Mode = 0 = NO UNIT CONNECTED
Mode = 1 = READY
Mode = 2 = RUNNNING
Mode = 3 = STARTING
Mode = 4 = SHUTDOWN
Mode = 5 = PAUSE
Mode = 6 = PRELUB
Mode = 7 = CAPACITY SLIDE DOWN
Mode = 8 = RUNNING -- OVERLOAD
Mode = 9 = RUNNING DISCH. PRESSURE
LIMITATION
Mode = 10 = RUNNING SUCT. PRESSURE
LIMITATION
Mode = 11 = STOPPED
CONTROL SYSTEMS:
Type = 0 = NO SYSTEM
Type = 1 = PROSAB II
Type = 2 = UNISAB, recip. compr.
Type = 3 = UNISAB, screw compr.
MULTISAB STATE:
Mode = 0 = NO PERMISSION TO START
Mode = 1 = DO NOT START (1)
Mode = 2 = MAY START (1)
Mode = 3 = RUNS AT 100 % CAPACITY
Mode = 4 = LEAD COMPRESSOR
Mode = 5 = LAG COMPRESSOR
Mode = 6 = STOPPING
Mode = 7 = RUNS, BUT WITHOUT
LEAD-LAG CONTROL
Mode = 8 = STOPPING --
RAMPS CAPACITY UP
Mode = 9 = STOPPING --
RAMPS CAPACITY DOWN
Note:
(1) MULTISAB STATE mode 1 and 2 are
reversed in PROSAB II.
22 0178-405-EN
Table of alarm/warnings
Id Alarm/warning text Alarm Warning
#31 Low suction pressure X X
#32 High suction pressure X(7)
#33 Low suction superheat X X
#34 High suction superheat X(8) X(8)
#35 Low discharge pressure X
#36 High discharge pressure X X
#37 High discharge temperature X X
#38 Low oil pressure X X
#39 Low brine-/interm. temperature X X
#40 Low discharge temperature X(8)
#41 Low oil temperature X X
#42 High oil temperature X X
#43 High oil filter diff. press. 2) X X
#44 Oil system error 2) X
#45 Capacity error 2)+4) X
#46 Compressor motor overload X
#47 Compressor motor error X
#48 Oil pump error 2)+3) X(7)
#49 High motor temperature X
#51 Prom error X (5)
#52 Ram error X (5)
#53 Cpu error X (5)
#54 Sensor error X (5)
#55 PMS error X (6)
#56 No start permision X (6)
#57 High differential pressure 1) X (6) X (6)
#58 High brine-/interm. temperature X (6) X (6)
#59 High oil pressure 1) X (6) X (6)
#60 High intermediate pressure 1) X (6) X (6)
#61 Low intermediate pressure 1) X (6) X (6)
#62 Full-flow pump error 2)+3) X (6)
#64 Oil rectifier error 2) X (6)
#65 Wrong start no. in sequence X (6)
#66 Diagnose EEPROM error X (6)
0178-405-EN
23
#67 Low external input signal X (6) X (6)
#68 High external input signal X (6) X (6)
#69 Low discharge superheat X (6) X (6)
#70 Discharge pressure overload X (6)
Note the folowing:
(1): Only Reciprocating Compressors
(2): Only Screw Compressors
(3): The alarm will function as a warning
when the compressor is running, i.e.
after prelubrication.
(4): The alarm will only stop the com-
pressor in mode remote/multisab,
in mode manual or auto the com-
pressor will not be stoppet, i.e. the
alarm will function as a warning.
(5): Alarm/warning
#51 - #54 only for PROSAB II.
(6): Alarm/warning
#55 - #70 only for UNISAB II.
(7): Not UNISAB S/R/RT/RTH
(8): Not PROSAB II