Victorian
Service and Installation Rules
2014
22
Tonight we will cover:
the variations between the 2005 and the 2014 versions of the
Service and Installation Rules.
go over certain selected areas within the new SIRs
remove confusion and Highlight areas where major non-
compliance often occurs.
Service and Installation Rules NECA
January - February - March 2014
Welcome
33
Where do the Service and Installation Rules (SIR) fit in?
Under the Sale and Distribution Code, Known as the Distributors
reasonable technical requirements.
Traditionally cover off supply connection methods, metering
and supply arrangements.
Service and Installation Rules NECA
January - February - March 2014
SIR Fit
44
Service and Installation Rules NECA
January - February - March 2014
Compliance
Do I need to comply with the SIRs are they mandatory?
Yes you shall comply;
If you do not comply then FIP (fuse in pocket) usually
applies. No Supply.
For safe connection and metering of electrical
installations you are required to comply with the Sale
and Distribution Code.
Remember any delays will effect your customer.
55
Service and Installation Rules NECA
January - February - March 2014
Application
The Victorian Service & Installation Rules apply to all connections to the
electricity supply networks operated by Electricity Distributors:
CitiPower,
Jemena Electricity Network,
Powercor Australia Ltd,
SP AusNet and
United Energy.
The objective of these Rules is to:
provide Victorian electricity customers with industry agreed reasonable
technical requirements that;
meet all legislative and Electricity Distribution Code requirements
for the supply and metering related aspects of any connection to
the Victorian Distributors electricity supply networks.
66
Service and Installation Rules NECA
January - February - March 2014
Public Notice - Availability of the 2014
Service and Installation Rules
The 2014 SIR are applicable from 1
st
January 2014 with a three month
period of transition allowing the trade to adopt and employ the changes in
the new document. There may be exceptional circumstances, if a
connection post 31
st
March 2014 exists where a REC wishes to have the
2005 rules applied an SIR exemptions must be submitted by a written
request detailing the reasons why non-compliance with the 2014 Rules is
sought.
An exception to the 2005 Rules will not be automatically granted, electrical
work associated with the exception should be discontinued until approval
from the Distributor is received.
17/04/2014
2
77
Service and Installation Rules NECA
January - February - March 2014
Service and Installation Rules Committee.
Members of the SIR rewrite Committee are;
The five Distributions Companies.
Each permitted two representatives.
Institute of Electrical Inspectors Australia.
Mark Aitken
Energy Safe Victoria.
Simon OLeary
National Electrical and Communications Association (NECA)
Victoria.
Brian Cross (Twin Electrics)
Roy Sands NECA Victoria.
88
Service and Installation Rules NECA
January - February - March 2014
Changes General - Major
Metering
The arrival of Smart Meters has altered;
the numbers of meters on a panel
separate time clocks no longer required on a meter
panel
Location of metering neutral Link
New remote read meters (Smart Meters) now require;
an aerial location
communication gear etc.
99
Service and Installation Rules NECA
January - February - March 2014
Changes General Major cont.
Protection Devices
The Safety Installation Regulations changed the Mandatory
location of Supply Protection Devices, Supply Capacity
Control Devices and Occupancy Disconnection Devices.
10 10
Service and Installation Rules NECA
January - February - March 2014
2014 SIRs General
Document Sections
Same as 2005 edition minimal rearrangement.
Code of practice Fuse Removal rewritten.
Ok - but distributors must train call center people
(ESV requirement.)
Indexs
Main index at front of book.
Each section has a detailed index at the front of each section.
11 11
Service and Installation Rules NECA
January - February - March 2014
2014 SIRs General
Table and Figure numbers;
Table and figure numbers have been renumbered to reflect
the clause that they refer too, where a clause has more than
one, table or figure then they are numbered in order prefixed
by the identification table or figure and clause number i.e.
Figure 7.4-A
Figure 7.4-B.
Figure 7.4-C
Table 7.4-1
Figure 7.4-D
etc..
12 12
Service and Installation Rules NECA
January - February - March 2014
Changes - Section One (1)
Clause 1.3 (definitions)
New Advanced Metering Infrastructure (AMI)
Renamed Determined Maximum Demand to Allocated Maximum
Demand.
New Common Area.
New - Occupancy Disconnection Device.
New - Owners Corporation.
New Private Aerial Line added to align with Electricity Safety Act.
Replaced - Private Overhead Electricity Line (POEL) with Private
Aerial Line.
17/04/2014
3
13 13
Service and Installation Rules NECA
January - February - March 2014
Changes - Section One (1) cont.
Clause 1.3 (definitions) Continued.
Renamed Supply Connection Facility to Service Connection
Facility.
Renamed Service Protection Device to Supply Protection
Device.
Removed Supply Disconnection Device.
Removed Underground Reticulated Distribution (URD)
Now - Network Underground.
14 14
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Four (4) old section (5).
Subdivisions clause title 2005
changed to Multiple Occupancy Buildings or Subdivisions
(application)
2005 Clause rewritten to clarify the intent and application.
Forms;
Electrical Work Request - Updated.
Application for Abolishment of Electricity Supply Updated.
Reconnection of Electricity Supply New Form.
Photovoltaic (Solar) Generator Connection Form. New Form
Note: - not in SIR Book available from each Distributor.
Limitations (in part);
Not more than 4.6 or 5Kw single phase.
Not more than 30% load of supplying transformer.
15 15
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Five (5) old section (4).
Section 5 of the 2014 edition is the old section and has been expanded
to now include clauses located throughout sections of the 2005 book.
This has achieved the grouping of all the common requirements into
the one section.
Section 5 now contains; (Formerly section 7 of 2005 edition)
No Go Zone
Underground Cables
Sub Stations
Poles & Overhead lines
Service pits
Supply Isolation
16 16
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Five (5) old section (4).
Section 5 now contains;
Sealing and Locking from section 8 of the 2005 edition
Redrafted Clause to make intention clear.
1.6mm to 2.00mm hole for seals to be provided.
Segregation from section 8 of the 2005 edition
Redrafted Clause to make intention clear permanent
Provision for Sealing - New Clause
Passage for sealing now required to be double insulated or
segregated from live parts.
Provision for padlock - New Clause
Requirement now for 6mm diameter hole to be provide for
Distribution company padlock.
Private electric lines on public land from section 7 of the 2005
edition
Equipment required to be accepted Amended clause
Clause now specifies the meter temperature limits and
operating range
17 17
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Five (5) old section (4).
Private Aerial Lines ( PAL ) New Clause
Clause includes the requirement of the Electrical Safety Act and
Regulations in relation to low bush fire and high bush fire risk areas
Construction of PAL to be in accordance with the Act, Regulations
and the Wiring Rules
Included the requirement for fault and emergency restoration of the
defective PAL
Advise that serious non-compliance will be disconnected on
declared days of total fire ban.
18 18
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6) Alternative Supplies.
Supply Arrangement Diagrams amended.
Second last paragraph now includes location and operation of
alternative supply, e.g. Solar Installations.
Alternativesuppliesare: anelectricitysupplydirectfromgeneratorsorother
equipmentwhichprovideanelectricitysupplynotdeliveredbyaDistribution
Network.
Thesealternativesuppliesincludeembeddedgenerators,standbygenerators,
regenerativebrakingsystems,inverterconnectedgeneratorsusingvariousenergy
sourcessuchasphotovoltaic,windorfuelcell,uninterruptiblepowersupplies
(UPS)andenergystoragesystems.
Note:Anembeddedgeneratorisdefinedasageneratorthatcanelectrically
connecttoorsynchronisewiththedistributionnetworkorisregisteredwiththe
AustralianEnergyMarketOperator(AEMO).
17/04/2014
4
19 19
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6) Alternative Supplies.
All alternative supplies must comply with The Electricity Safety Act and (Installations)
Regulations, Codes made under the Electrical Industry Act and relevant Australian
Standards and these Rules.
A host of additional standards are also applicable to components and sub systems
including rotation machines, earthing, switchgear and fuses, transformers, cabling,
labelling etc. Alternative supplies that are also embedded generators must comply with
Codes made under the National Electricity Rules and specific Generator Connection
Standards issued by each Distributor.
20 20
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6) Alternative Supplies.
Generally all alternative supplies shall:
* Be arranged to disconnect from and not back energise the Distributor's
network and service and metering equipment if electricity supply from the
network is de-energised (unless explicitly allowed by the Distributor).
* Have electrical characteristics compatible with the relevant Distributor's
network
* Not interfere with supply quality to other customers or the Distributor's
network.
* Not adversely affect the safety of Distributor employees, customers or the
public.
* Not be connected on the line side of metering equipment.
* Not create a break in the neutral conductor between the Distributor's
network and the MEN connection.
21 21
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6) Alternate Supplies.
IsolationdevicesshallbeinstalledinaccordancewithAustralianStandards,butshall
alsosatisfythefollowing:
* Isolation devices shall be located either on the switchboard to which the
inverter ac. output connects or as close as practical to the switchboard and
cannot be located in a difficult to find position.
* The isolation device must be capable of locking in the open position using a
Padlock with a hasp/shaft diameter up to 5.5mm without requiring additional
apparatus. If a locking device (e.g. "lock dog") is added to a MCB as a method
of locking, it shall be permanently secured in an appropriate position.
Isolation Devices
22 22
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6) Alternate Supplies.
d) For a multiple occupancy installation, a label shall be installed at the
protection devices within un-rnetered switchboards for all circuits that supply
an occupancy containing an inverter system.
e) At the main switchboard and all distribution switchboards to which the
embedded generator is connected.
Where a switchboard is located directly adjacent to a metering panel one
label may be adequate if the label is clearly visible when working on the
metering panel or the switchboard.
Sample labels are shown in Figure 6.9-A, (Typical Labelling
Requirement). Additional labelling within an installation will also be required
to comply with AS3000, AS4777 and other Australian Standards applicable
to generation systems.
23 23
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection requirements
The Electricity Safety Act requires service lines to be protected by
protective equipment that can isolate each of the active conductors of an
electrical installation and prescribes their location.
For Overhead supplies Network Overhead
Underground URD supplies Network Underground
Supplied direct from a sub-station sub-stations
24 24
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection Devices (SPD).
Main Principle to be achieved.
The customer shall install and maintain an assembly to
accommodate supply protection device/s (SPD) in
accordance with the Electricity Safety (Installations)
Regulations, these Rules and the obligations of the Distributor
to connect and disconnect electrical installations.
17/04/2014
5
25 25
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection Devices (SPD).
A Supply Protection Device shall
Minimise any adverse conditions which may affect other customers
electrical installations and the distribution system. The SPD must
ensure adequate protection is provided up to the electrical protective
equipment of the electrical installations they supply.
Note: In some cases Distributors may utilise their HV protection
equipment for supply protection. It will be necessary to confirm
the supply protection arrangement with the relevant distributor
at the design stage of the electrical installation.
Also
Enable the Distributor to connect, disconnect and isolate each active
conductor supplying the electrical installation for commercial and/or
safety reasons; and not exceed one device per phase
26 26
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection Devices (SPD).
Assemblies to accommodate LV Supply Protection Devices (SPD)
The customer is responsible for the provision of an assembly to
accommodate Supply Protective Device/s (SPD) provided by the
Distributor. This equipment must be of an acceptable type as
required by these Rules and shall be located and installed in
accordance with the relevant requirements of the current Electricity
Safety Act and Regulations.
Access
The assembly for the purpose of accommodating the SPD shall be
installed in a position where convenient and unhindered access is
readily available for the Distributor to safely operate and work on the
device/s at all hours, unless otherwise agreed by the Distributor.
27 27
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection Devices (SPD).
SPDs and Assemblies
SPD/s and the assemblies shall in part:-
(a) be of a type acceptable to the Service and Installation Rules
Management Committee or the relevant Distributor;
conform to the requirements of the appropriate Australian or
International Standard for the type of device employed;
(c) be installed in accordance with the requirements of the
Electricity Safety Act, Regulations and these Guidelines;
(d) be installed so as to comply with the minimum height
requirement of consumers terminals connected to the distributors
service cables,
28 28
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection Devices (SPD).
be selected with regard to the conditions, taking account of the nature
of the supply (i.e. overhead, underground):
(f) have a rated short circuit current capacity equal to or greater than
the prospective short circuit current at the point it is installed;
(g) have, or be installed with, facilities for sealing un-metered
connections to prevent unauthorised access;
(h) be maintained by the customer in accordance with the
manufacturers specifications.
29 29
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection Devices (SPD).
1.5.5.3.1 Acceptable Fuse Assemblies and Fuse Cartridges
NH Fuse Holder
1 Phase
FOLCB
80A Max
Multiphase
FOLCB
100A Max
Panel
Mounted Fuse
100A Max
2A Barrel Cartridge
Diameter 22mm
2A-100A Max
Stick Operated
FSD
Hand Operated FSD DIN Cartridges
63A-630A
NH Fuse Handles
30 30
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection Devices (SPD).
Fuse Cartridges
All fuse cartridges shall be supplied by the Distributor.
Subject to approval by the relevant Distributor, Miniature Combined
Fuse Switches may be used, however they shall be provided by
the customer.
Fuse carrier assemblies rated at up to 100A shall be capable of
accepting 22mm barrel fuse cartridges of Type 2a.
Fuse carrier assemblies rated in excess of 100A shall be suitable for
use with Din type NH blade fuse cartridges.
All fuse cartridges to AS/NZS 60269.2.1, or a recognised equivalent
17/04/2014
6
31 31
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection Devices (SPD).
Assembl y Types
Fused Overhead Line Connector Boxes
Panel Mounted Fuses
Panel mounted fuse base and carriers shall be of a minimum
continuous rating of 100 Amp, 500 Volt
Fused Switch Disconnector (FSD)
Stick operated FSDs shall be suitable for mounting on either a
pole or building faade
Hand operated FSDs shall be suitable for mounting within the
standard service connection facility
32 32
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Protection Devices (SPD).
Prohibited Fuses
Stick Operated, Panel Mounted Fuses are a specific form of panel
mounted fuse originally designed for mounting on a connection box
mounted on the underside of a shop veranda.
These fuses are no longer acceptable for use as an SPD or
occupancy disconnection device for new connections, alterations or
additions to existing electrical installations.
33 33
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Capacity Control Device.
Supply Capacity (Maximum Demand by Limitation)
Supply Capacity Control Device (SCCD)
Capacity Control and types
Electrical installations shall be arranged in accordance with the Wiring Rules
so as not to exceed 130% of the Distributors nominated supply capacity for
more than 2 hours by one of the following means:
Moulded case circuit breakers with a fixed thermal trip unit setting
of 130%.
Miniature circuit breakers with a fixed thermal trip unit setting of
145%.
These circuit breakers must be de-rated to achieve 130% of the
nominated supply capacity.
Adjustable circuit breakers are acceptable provided the thermal trip unit is
set to a level equal to the nominated supply capacity and the overload
duration is set as agreed with the distributor.
34 34
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Capacity Control Device.
Maximum Demand Limitation Device/s (SCCD)
Circuit breakers shall:
Be installed on the main switchboard in accordance with the
Electricity Safety Act and Regulations, the Wiring Rules,
and these Rules;
Be arranged to ensure the aggregate rating of the devices
does not exceed the supply capacity where multiple
devices are used; and
Be provide with a sealing facility when adjustable.
35 35
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Capacity Control Device.
Supply Capacity Control Device SCCD
The 2009 Safety Installation Regulations no longer permit a switch
ahead of the Installation Main Switch/s.
-Therefore the SCCD cannot be located on the meter panel or meter
board and shall be the Main Switch or the summation of the Main
Switches, where multiple main switches are used.
36 36
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Six (6).
Supply Capacity Control Device.
Consumers Mains Overload and Short Circuit requirement
As per Clause 2.5.1.1 of AS/NZS3000:2007 consumers mains are to
have overload and short circuit (overcurrent) protection.
This is best achieved by using circuit breaker/s as the Main Switch or
summation of the Main Switches to be equal to or less than the current
carrying capacity of the consumers mains.
Hint. Use the main switch/es as both consumers mains protection and the
distribution companies SCCD.
17/04/2014
7
37 37
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Seven (7).
General Statement 7.1. new
Type of Service new
Network - underground - new
Network - Overhead new
Sub-stations new
Selection of connection Type amended
Clause remains the same heading reflects the information
contained within the clause.
38 38
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Seven (7).
Overhead Services amended
Old clause 7.4, new title along with title changes for figures and
tables.
Raiser bracket shown with closed loop, not hook as previous,
where the maximum of 60 degree angle (vertical or horizontal)
cannot be achieved.
Distances from POA to FSD 750mm, FOLCB 500mm max.
39 39
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Seven (7).
Supply Protection Type and Location.
What needs to be considered:
Capacity of the supply;
Distribution reticulation system (OH or UG); or,
Installation supplied directly from a distribution substation
The type of SPA required;
Who is responsible for providing the SPA;
The location of the SPA and SPD.
40
SPD SupplyFromanAerialServiceCable
Supply
Current
Rating
Per
Phase
Supply To
Supply
Protection
Assemblies
Responsibility
for the
provision of
Supply
Protection
Assembly
Supply
Protection
Device
Types
Provided
by the
Distributor
SPD Location
1 Ph
<80A
Building
or
Structure
FOLCB Customer
Type 2a
Fuse
Building or Structure
In accordance with
Figure 7.4-B
See Note
1
<100A
>100A <170A FSD Customer
Sizes 00, 2 and 3
Din type NH fuses
<100A
Private Pole
(On Private
Property in Low
Bushfire Risk
Areas)
Pole CB to
POEL
FOLCB to
underground
consumer mains
Customer
Type 2a Fuse if a
FOLCB is applicable
In accordance with Figure 7.4-C
>100A <170A
Pole CB to
POEL
Pole FSD to
underground
consumer mains
Customer
Sizes 00, 2 and 3
Din type NH fuses if
a FSD is applicable
Note1 Where agreed and installed above commercial premise veranda in accordance with the current rules (POA on Buildings) additional
requirements are that fuses can be operated with a 600mm vertical standard fuse stick, sealing facilities are provided to restrict access to
unmetered terminals, and Occupancy Disconnection Devices are provided in accordance with the VSIR Section 8.
41
SPD SupplyfromaServicePitConnectedto
UndergroundorOverheadDistribution
Supply
Current
Rating
Per Phase
Distribution
Reticulation
Supply
Protection
Assemblies
Responsibility
for the provision
of Supply
Protection
Assembly
Supply
Protection
Device Types
Provided by
the Distributor
SPD Location
100A
URD Area or
U/G from O/H
Panel Mounted
Fuse/s
Customer
Type 2a
Number of devices
must not exceed one
device per phase
Meter Panel
O/H Reticulation
conversion to
Underground
Reticulation or
U/G from O/H
FOLCB Customer Type 2a
A point where an overhead line was
previously connected
>100A
< 170A
Special
Circum-
stances &
By
Agreement
Only
URD
Areas
FSD
Customer
Sizes 00, 2
and 3 Din
type NH
fuses
1. As close as practicable to the
applicable property boundary; or,
2. at or within 3m of the
consumers terminals; or,
3. in a position at or next to the
distributors metering equipment.
O/H Areas
O/H Areas
Note: (Dedicated
service only)
Distributor On Distribution Company Pole
O/H Reticulation
conversion to
Underground
Reticulation or
U/G from O/H
Customer
A point where an overhead line was
previously connected
42
SPD SupplyfromaServicePitConnectedto
UndergroundorOverheadDistribution
Supply
Current
Rating
Per Phase
Distribution
Reticulation
Supply
Protection
Assemblies
Responsibility
for the provision
of Supply
Protection
Assembly
Supply
Protection
Device Types
Provided by
the Distributor
SPD Location
100A
URD Area or
U/G from O/H
Panel Mounted
Fuse/s
Customer
Type 2a
Number of devices
must not exceed one
device per phase
Meter Panel
O/H Reticulation
conversion to
Underground
Reticulation or
U/G from O/H
FOLCB Customer Type 2a
A point where an overhead line was
previously connected
>100A
< 170A
Special
Circum-
stances &
By
Agreeme
nt Only
URD Areas
FSD
Customer
Sizes 00,
2 and 3
Din type
NH fuses
1. As close as practicable to the applicable
property boundary; or,
2. at or within 3m of the consumers
terminals; or,
3. in a position at or next to the distributors
metering equipment.
O/H Areas
O/H Areas
Note:
(Dedicated
service
only)
Distributor
On Distribution
Company Pole
O/H Reticulation
conversion to
Underground
Reticulation or
U/G from O/H
Customer
A point where an overhead line was
previously connected
17/04/2014
8
43
SPD SupplyFromanUndergroundServiceCable
ConnectedtoanUndergroundorOverhead
Distribution(NoPit)
Supply
Current
Rating
Per Phase
Distributor
Reticulation
Supply
Protection
Assemblies
Responsibility
for the provision
of Supply
Protection
Assembly
Supply
Protection
Device Types
Provided by
the Distributor
SPD location as Determined
by the Distributor
>100A
URD
Areas
FSD
Customer
Sizes 00, 2
and 3 Din
type NH
fuses
1. As close as practicable to the
applicable property boundary: or,
2. at or within 3m of the
consumers terminals (Supply
Connection Facility) supplying
UG consumers mains: or,
3. in a position at or next to the
distributors metering equipment.
O/H Areas
O/H Areas
Note: (Dedicated
service only)
Distributor On Distribution Company Pole
UG Service supplied
directly from a
Substation
Note: (Dedicated
service line)
FSD or Circuit
Breaker
Distributor
Sizes 00, 2 and 3 Din
type NH fuses or CB
At the Substation
44
SPD SupplyFromanUndergroundServiceCable
ConnectedtoanUndergroundorOverhead
Distribution(NoPit)
Supply
Current
Rating
Per Phase
Distributor
Reticulation
Supply
Protection
Assemblies
Responsibility
for the provision
of Supply
Protection
Assembly
Supply
Protection
Device Types
Provided by
the Distributor
SPD location as Determined
by the Distributor
>100A
URD Areas
FSD
Customer
Sizes 00, 2
and 3 Din
type NH
fuses
1. As close as practicable to the
applicable property boundary: or,
2. at or within 3m of the consumers
terminals (Supply Connection Facility)
supplying UG consumers mains: or,
3. in a position at or next to the
distributors metering equipment. O/H Areas
O/H Areas
Note:
(Dedicated
service
only)
Distributor
On Distribution
Company Pole
UG Service supplied
directly from a
Substation
Note: (Dedicated
service line)
FSD or Circuit
Breaker
Distributor
Sizes 00, 2 and 3 Din
type NH fuses or CB
At the Substation
45
SPD SupplyfromanIndoor,Kiosk,GroundorPoleType
Substationlocatedwithinthepropertyitsupplies
Supply
Current
rating
Per Phase
Substation
Type
Supply
Protection
Assemblies
Responsibility for
the provision of
Supply Protection
Assembly
Supply
Protection
Device Types
Provided by the
Distributor
SPD Location
>100A
Kiosk,
Indoor,
Ground
Type
FSD
MCCB
ACB
HV
Protection
Distributor
Sizes 00, 2 and 3 Din
type NH fuses
Installed within the
Substation
See Note
1
MCCB
ACB
HV Protection
100A
Pole Type 2
FOLCB
Customer
Type 2a Fuses
On Distribution Company Pole
> 100A FSD
Sizes 00, 2 and 3 Din
type NH fuses
In some cases Distributors may utilise their HV protection equipment for service protection.
It will be necessary to confirm the service protection arrangement with the relevant distributor at the design stage of the electrical installation.
Note1 Electricity Safety (Installations) Regulations, Regulation 235 Installation of protective equipment
(3) In the case of electricity supplies provided directly from a substation, protective equipment must be installed within the substation.
Note 2 The use of a pole mounted circuit breaker is not permitted to be used as a supply protection device for underground lines forming consumers mains
46 46
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Seven (7).
Electrical Installations on Public Land New .
New clause details to depth of labeling required for electrical
installations located on public land.
Un-metered Consumers Mains and Sub-mains new
New clause gives information, guidance and requirements for
Consumers Mains regarding;
Cables and conductors.
General
Prepared in accordance with the safety Act,
Regulations, wiring Rules and the additional
requirements of the SIR,s
ESR and Fire rated cables - not covered consult the
Distributor
47
Changes SectionSeven(7).
UNMETEREDMAINSANDSUBMAINS
ConductorTypes
Softdrawncopperonlyupto16mmtobe7strands,
greaterthan16mmandupto35mmtobe18strands
minimum.
ConductorSizes
Sharedpitmax35mmSoleuseordedicatedpit50mm
Meteringmin4mmmax35mm
Controlwiring2.5mm
Colour anddoubleInsulation newrequirements
Colour CodesandSleeving,Useheatshrinkfixedsleeving,
tapenotpermitted,Neutralblack,1
st
activeRed,2
nd
activeWhite3
rd
ActiveBlue.
48 48
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Seven (7).
Color Identification
SDI Cables - with Sheath
Minimum length of identification 100mm placed between 150mm and
250mm from end of cable.
SDI Cables no Sheath (One layer of reinforced insulation) colour
identification for entire length within terminating enclosure.
Sheathed Multi-core Cables
Correct colour of cores no additional requirements.
Incorrect colour of cores heat shrink entire length and crutch seal
fitted.
Single Insulated Conductors
Coloured in accordance with the rule and entire length within
terminating enclosure.
Joints in Un-metered Cables and Conductors table
extended to include terminating facility sealing or padlock
facility to be provided.
17/04/2014
9
49
Changes SectionSeven(7).
UndergroundMainsandSubmains
MinimumInsulationResistance
Nochange50Megohmreducingtominof5MegOhm
overdistance.
WiringSystems
Samerequirements,oneconduitortwodifferentphases
ineachconduit,cableslessthan95mm2shallnotbe
directburied.
Backfilling
Backfillingoftrenchrequiredpriortosupplybeing
connected.
TerminationwithinaServicePit
Nowincludestherequirementtotakeadequate
precautionsifhandlinglive conductors.
50 50
Service and Installation Rules NECA
January - February - March 2014
Multiple Occupancy Buildings and
Subdivision Supply Arrangements Section 7.
Required Information:
The customer must provide the following information;
the electrical contractors electrical installation wiring plan
(as described in Section 7.8.3 of the current Victorian
Service & Installation Rules); and
the plan of subdivision if already subdivided; or
the proposed plan of subdivision if the land is in the
process of being subdivided; or
a prospective plan of subdivision showing all proposed lot
boundaries and common property.
51
SupplyArrangementExample#1 Section7.
DualOccupancy:
prospective
subdivisionnot
incorporatingcommon
property;
ownerordeveloperto
provideadraftplanof
subdivision;
separatesuppliesmust
beprovided.
51
Service and Installation Rules NECA
January - February - March 2014
52
SupplyArrangementExample#2 Section7.
DualOccupancy:
prospective
subdivision
incorporatingcommon
property;
singlesupplypoint;
commonmetering
enclosure/main.
Service and Installation Rules NECA
January - February - March 2014
52
53
SupplyArrangementExample#3 Section7.
FourLotsubdivision
incorporating
commonproperty:
Landaffectedbythe
ownerscorporation
includeslots1,2and
commonproperty
Lots3and4arenot
affectedbytheOwners
Corporation,therefore,
theycanbesupplied
separately
53
Service and Installation Rules NECA
January - February - March 2014
54
SupplyArrangementExample#4 Section7.
FourLotsubdivision
incorporating
commonproperty:
Landaffectedbyowners
corporationsincludeslots
2,3,4andcommon
property
Lot1isnotaffectedbyany
OwnersCorporation,
therefore,itcanbe
suppliedseparately
Lot1canbesuppliedeither
overheadorunderground
54
Service and Installation Rules NECA
January - February - March 2014
17/04/2014
10
55
SupplyArrangementExample#5 Section7.
FourLotsubdivision
incorporating
commonproperty:
landaffectedbytheowners
corporationincludeslots1,
2,3,4andcommon
property
singlesupplypoint
commonmetering
enclosure/main
switchboard
Service and Installation Rules NECA
January - February - March 2014
55
56 56
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Seven (7).
Multiple Occupancy Buildings and Subdivision Supply
Arrangements new
Plan
Provision of Plan by Customer.
Multiple Occupancy Buildings
Point of Supply
Consumers Terminals
Metering Arrangements
Possible Sub-division of Building or Land
Labeling
Wiring Arrangements
Un-metered Connections and Equipment.
57 57
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
Timber Panels Boards Clause extended
Now includes the old Alterations and Additions requirements.
Meter Enclosures - Clause extended
Additional dot point re;
Construction and location, not to cause metering equipment to
exceed it temperature limits.
58 58
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
Protection Against Damage to, and Interference with Metering
Equipment, - location of meter enclosure and the need to lock them.
Direct Connected Meter, Limits of Current Carrying Capacity amended
Was part of Determination of Meter Type in the 2005 edition.
Now requires maximum demand to be limited to 100Amps and not
be exceeded.
Installations reaching 90Amps continuous to strongly consider
installation of LV CT Metering.
59 59
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
Meters Temperature Limits of Specified Operating Range
amended
Now requires the temperature range to be complied with;
Direct Connected Meter (class 1 or 1.5) -10 to +60
o
C
LV CT and HV Connected Metering (class 0.2 or 0.5) -10 to +45
o
C
Where meters are enclosed within switchboard the temperature rise
above ambient is to be limited to;
Direct Connected meters 25
o
K
LV CT and HV Connected Meters 10
o
K
60 60
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
Figure 8.9-A clause 8.9 Amended new figure
17/04/2014
11
61 61
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
62 62
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
Specific Situation Requirements new clause applies to single
occupancies only.
Single Occupancy
Isolation single occupancy commercial only where there is no
access (verandah) additional fuses permitted on meter panel.
Meter panels
All meters to be contained on a single meter panel.
Meter Locations
Domestic no change, same as previous
Commercial/Industrial new located outside unless no
suitable external position available. (next slide)
Labelling no change, same as previous. address on
meter panel.
63 63
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
Specific Situation Requirements new clause (Continued)
Meter Locations
Commercial/Industrial
New figure 8.10-B Small/Medium Individual
Commercial/Industrial Installations Acceptable Meter
Locations
Dot point 3 (three) of clause 8.10. within a suitable
location in the building where suitable locations
outside of the building do not exist.
64 64
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
65 65
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
Grouping of meters - New title
Was part of Multiple Occupancy Electrical Installations in the 2005 edition.
Clause reconfigured.
Table 8.10-2 - Amended)
Old Tables 8.2 and 8.3 consolidated into one table.
Occupancy Disconnection Device 8.10.12 (a) and (b) New clauses
Details when and where the devices are required.
66 66
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
LV Current Metering New Section/Clause numbers
Clearances Changed LV CT Meter panel heights.
17/04/2014
12
67 67
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
C/T chamber busbars
C/T Enclosure General Specifies busbar arrangements within CT
Enclosures.
Busbars shall be installed in the one direction within the C/T chamber i.e.
enter the C/T chamber vertically then they remain vertical until the busbars
have exited the C/T chamber.
68 68
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
C/T Fuses clause amended
Clause expanded to include the requirement for safe operation of fuse
carriers.
69 69
Service and Installation Rules NECA
January - February - March 2014
Changes - Section Eight (8) Metering.
Section 8 now includes new clause 8.12; - Metering Communications
Equipment.
Communications Cabling, Communications equipment power cabling
and antenna cabling.
Communications Devices.
External or Remote Antenna.
Customer and third party provided Communication Equipment (e.g.
HAN repeater)
70 70
Service and Installation Rules NECA
January - February - March 2014
Changes 2005 to 2014 SIRs.
The End
Question Time
(Metering Diagrams Follow)
71 71
Service and Installation Rules NECA
January - February - March 2014
72 72
Service and Installation Rules NECA
January - February - March 2014
17/04/2014
13
73 73
Service and Installation Rules NECA
January - February - March 2014
74 74
Service and Installation Rules NECA
January - February - March 2014
75 75
Service and Installation Rules NECA
January - February - March 2014
76 76
Service and Installation Rules NECA
January - February - March 2014
77 77
Service and Installation Rules NECA
January - February - March 2014
78 78
Service and Installation Rules NECA
January - February - March 2014
Changes 2005 to 2014 SIRs.
Direct connected meters
An approved panel mounted fuse/s adjacent to the occupancy meter.
Current Transformer meters
An approved switch or circuit breaker.