Sei sulla pagina 1di 1

Written dimensions on these drawings shall have precedence over scaled dimensions.

Contractor shall verify and be responsible for all dimensions and conditions on the job. OB+Architecture Inc. must be notified immediately in writing of any variation from the dimensions and conditions shown on these drawings. Field verify all conditions prior to laying out or fabricating associated work. Bring to the architect's attention any deviation from designed conditions and field conditions prior to ordering
materials and installing work, and cooperate with architect to modify such conditions at no additional cost to the owner, architect or architect's consultants. Shop details must be submitted to the architect's office and reviewed by the architect prior to ordering materials, fabrication and delivery to the job site, unless otherwise provided for under the specific contractual agreement between the architect and client. OB+Architecture Inc. expressly reserves its common law copyright and other

AIR CONDITIONING UNIT SCHEDULE


FAN DATA DX. COOLING COIL DATA ELECTRIC HEATING COIL ELECTRICAL
MIN
AREA OUTSIDE MBH MBH TOTAL
CFM EXT. HP KW STAGES MOCP VOLTS PHASE EER SEER MANUFACTURER/MODEL WEIGHT SEE NOTE #
AC # SERVED AIR TOT SENS MCA
E.S.P.
LOBBY
AC - 1 EXAM 180 2000 1 60 9 1 37.5 45 208 3 13 TRANE TSC060 1, 3 - 9 ROOF CAP
RECEPTION
AC - 2 TREATMENT 200 2400 2 72 13.5 1 54.8 60 208 3 11.3 TRANE TSC072 1, 4, 6 - 12
property rights in these documents. These documents are not to be reproduced, changed, or copied in any form or manner whatsoever, nor are they to be assigned to a third party without first obtaining the written permission and written consent of OB+Architecture Inc. In the event of unauthorized use of these documents by a third party, the third party shall hold OB+Architecture Inc. harmless and agrees to remunerate OB+Architecture Inc.

AC - 3 KENNEL 200 1000 0.5 30 7.5 1 69 70 208 1 13 TRANE 4TCC3030 1, 3 - 9 CANT STRIP BY
GENERAL
AC - 4 DOG WARD 295 9.7 12 15 120 1 14.3 FRIEDRICH MO9YF 2, 7, 8 CONTRACTOR PREFAB 18 GA
AC - 5 CAT WARD 295 9.7 12 15 120 1 14.3 FRIEDRICH MO9YF 2, 7, 8 ROOFING BY GALV. STL. STRUCT.
GENERAL ROOF CURB.
CONTRACTOR
NOTES: WOOD NAILER
INSULATION
1. PACKAGED SLAB-MOUNTED A/C UNIT WITH HORIZONTAL DUCT CONNECTIONS
2. DUCTLESS SPLIT SYSTEM HEAT PUMP WITH 9.7 MBH HTG, 8.2 HSPF, WASHABLE FILTERS, WIRELESS REMOTE, AND R410A. OUTDOOR AIR
PT WOOD BLOCK
DUCTED FROM AC-2.
3. STANDARD MOTOR AND DRIVE
4. MOTORIZED OUTDOOR AIR DAMPER 2" x 2" x 1/4"
5. 1" 30% EFFICIENT PLEATED FILTERS WITH ACTIVATED CARBON EQUAL TO DAYTON RELIABLE
6. FOIL FACED INSULATION SUPPORT ANGLE-
7. SINGLE POINT WIRING KIT COORDINATE
8. NEC DISC. BY ELECTRICAL TRADE LOCATIONS AND
9. 7 DAY, TIME OF DAY PROGRAMMABLE THERMOSTAT WITH OVER-RIDE OPENING SIZES
10. OVERSIZED MOTOR AND DRIVE WITH STRUCTURE
11. 2" 30% EFFICIENT PLEATED FILTERS WITH ACTIVATED CARBON EQUAL TO DAYTON RELIABLE
12. PROVIDE UNIT-MOUNTED SA DUCT SMOKE DETECTOR WITH RELAY INSTALLATION COMPLIES WITH
NOTES:
120 MPH WIND LOAD PER FBC
1. COORDINATE ROOF
PENETRATIONS AND
WATER PROOFING
WITH GENERAL
VENTILATOR SCHEDULE CONTRACTOR.
issued: ADVANCE REVIEW 21 JULY 2008
ROOF CURB DETAIL A/C UNIT ANCHORAGE
1 SCALE: NO SCALE 5 SCALE: NO SCALE revised:

ROOF / METAL DECK

ROOF CAP 3
8" WASHER
STRAP TO STRUCT.
WOOD 3
8"
x 5" LAG BOLT THRU
UNIT RAIL INTO WOOD NUT, BOLT, WASHER
ON CURB @ 6" ON
CENTER
2" WIDE STRAP
CURB (GALV. STEEL)

NOTES: ROOF CENTRAL


1.
2.
3.
ROOF CURB
BIRD SCREEN
ALL-ALUMINUM WALL PROP. FAN WITH OSHA INLET GUARD AND 120 VAC MOTOR-OPERATED SHUTTER
GALV. STEEL ROUND
(UNINSULATED) FLORIDA
4. STARTER AND DISCONNECT BY ELECTRICAL TRADE
5. CEILING EXHAUST FAN W / ALUMINUM CEILING GRILLE, BACKDRAFT DAMPER & SPEED CONTROLLER
6. INTERLOCK WITH LIGHT SWITCH
ROOF CAP - CURB TIE DOWN DETAIL DUCT HANGER DETAIL
7.
8.
9.
CONTROL WITH ON/OFF SWITCH
INTERLOCK BOTH OUTDOOR AIR MOTOR-OPERATED DAMPERS, EF-1, EF-2, AND WALL SWITCH
GRAVITY EXHAUST VENTILATOR
2 SCALE: NO SCALE 6 SCALE: NO SCALE

OUTDOOR AIR (OA) CALCULATIONS


SEAL SPIN-IN FITTING
WITH MASTIC.
CLEANOUT

AHU & A/C


ANIMAL
VETERINARY
STAFF
@ 20 CFM
RECEPTION /
WAITING @ 20 CFM
50% FACTOR FOR
EVENTS LESS THAN 3 HR
TOTAL OA REQD TOTAL OA SPEC
SPIN-IN FITTING WITH
VOLUME DAMPER (WHERE
SHOWN ON PLAN)
4" (A/C UNITS)
3" (AHUs) HOSPITAL
MIN. 1.5" WIDE
GALV. STRAP CLEANOUT
AC - 1 address: 1201 ALAFAYA TRAIL

AC - 2 NECK MOUNTED VOLUME


OVIEDO, FLORIDA
DAMPER (WHERE SHOWN
ON PLANS)
AC - 3 32765
CEILING

project
RIGID DUCT
SEE PLAN FOR number: 2007-12
(LOW DIFFUSER
PRESSURE) ROUTING

DIFFUSER, REGISTER, GRILLE SCHEDULE


FACE SIZE NECK SIZE TITUS MODEL NO. SEE NOTE NO.
DIFFUSER DETAIL CONDENSATE DRAIN DETAIL
for such use in an amount equal to the original fee for the original documents, plus legal fees, court costs, collection fees and other costs.

3 SCALE: NO SCALE 7 SCALE: NO SCALE

MECHANICAL ENGINEER
A. PETER TANKEL, P.E.
ROOF/METAL DECK 702 DENTON ROAD
WINTER PARK, FL 32792
PE 41231
2" WIDE GALV. STEEL
STRAP TO BAR JOIST (TYP)
STRUCTURE
#10 SELF TAPPING SHEET MIN. #12 GALV. STEEL
GALV. STEEL DUCT METAL SCREWS WIRE title:
THROUGH DUCT WALL
R-6 (INSULATED) HVAC DETAILS,
2" THICK 1# DENSITY
F.G. DUCT WRAP 2" WIDE GALV. CALCULATIONS &
NOTES: WITH GLASS FAB
AND MASTIC JOINTS
CHANNEL
SCHEDULES
1. COORDINATE FRAME TYPE WITH ARCHITECT SPECIFIED CEILING / WALL TYPE. drawn:
2. STEEL CONSTRUCTION, OFF WHITE FINISH.
1.5" DUCTBOARD JLP
R-6.0 (GLASS FAB/
3. PROVIDE MANUAL VOLUME DAMPER ACCESSIBLE THROUGH NECK. reviewed:
MASTIC) OB / RG
4. ALUMINUM CONSTRUCTION, OFF WHITE FINISH.
5. RETURN AIR FILTER GRILLE WITH 1" T/A FIBERGLASS MEDIA.
date:
6. SQUARE TO ROUND INSULATED ADAPTOR.
21 JULY 2008
7. SIGHT-PROOF DOOR GRILLE.
TRAPEZE DETAIL TRAPEZE DETAIL
4 SCALE: NO SCALE 8 SCALE: NO SCALE
lman:
PS-M3.1
sheet setup:
MOJA-HVAC
sheet
number:

M3.1