Height above sea level H m.a.s.l. Density Maximum values for the input parameters - At altitudes above sea level with, "H < Hmax", the routine can handle relative humidities "f" greater than the given value "f Max ". The maximum values of tdb Max = 96 C the dry bulb temperature, relative humidity and height above sea level, are defined in order to obtain an acceptable maximum number of iterations. These f Max = 50 % range limitations are required only in the functions calculating the wet bulb temperature (functions 16, 36, 46 and 56). H max = 5300 m.a.s.l. - The numbers in square brakets indicate the number of the function in the VBA environment Group 1 Group 2 tdb, f , H tdb, twb, H tdb C tdb 37.80 C tdb 37.8 f % f 31.5 % f 31.4 H m s.n.m. H 10.0 m H 10.0 x kg/kg x 0.01294 [11] x 0.0129 v m 3 /kg v 0.900 [12] v 0.900 r kg/m 3 r 1.125 [13] r 1.125 tdp C tdp 17.82 [14] tdp 17.82 ent kJ/kg ent 71.1 [15] ent 71.0 twb C twb 23.88 [16] twb 23.88 Psychrometric Functions_Resume Groups Absolute humidity x kg w/kg da Dew point temperature tdp Specific volume v m 3 /kg da Specific enthalpy ent r kg /m 3 Wet bulb temperature twb - At altitudes above sea level with, "H < Hmax", the routine can handle relative humidities "f" greater than the given value "f Max ". The maximum values of the dry bulb temperature, relative humidity and height above sea level, are defined in order to obtain an acceptable maximum number of iterations. These range limitations are required only in the functions calculating the wet bulb temperature (functions 16, 36, 46 and 56). - The numbers in square brakets indicate the number of the function in the VBA environment Group 3 Group 4 tdb, x, H ent, x, H C tdb 37.80 C tdb 37.80 [48] [27] f 31.5 [37] f 31.5 [47] m H 10.0 m H 10.0 m [21] x 0.0129 kg/kg x 0.0129 kg/kg [22] v 0.900 [32] v 0.900 [42] [23] r 1.125 [33] r 1.125 [43] [24] tdp 17.82 [34] tdp 17.82 [44] [25] ent 71.05 [35] ent 71.05 kJ/kg C twb 23.88 [36] twb 23.88 [46] Psychrometric Functions_Resume Groups Rev. cjc. 21.02.2014 C kJ/kg da C - At altitudes above sea level with, "H < Hmax", the routine can handle relative humidities "f" greater than the given value "f Max ". The maximum values of the dry bulb temperature, relative humidity and height above sea level, are defined in order to obtain an acceptable maximum number of iterations. These Group 5 tdb, ent, H tdb 37.8 C f 31.5 [57] H 10.0 m x 0.0129 [51] v 0.900 [52] r 1.125 [53] tdp 17.82 [54] ent 71.05 KJ/kg twb 23.88 [56] Psychrometric Functions_Resume Groups