1
Installation Manual
3
0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 1
3M
TM
FireDam
TM
Intumescent Coating WB 1000
2
1. Product Description page 3
2. Instruction page 3
3. Specifications page 3
4. Precautions & Limitations page 4
5. Packaging & Shelf Life page 4
6. Preparatory Work page 4
7. Masking page 4
8. Primers page 5
9. Application Rates page 5
10. Coverage page 6
11. Topcoats page 7
12. Precautions & Safe Handling Information page 7
13. Maintenance page 7
Index
0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 2
3M
TM
FireDam
TM
Intumescent Coating WB 1000
3
3M
TM
FireDam
TM
Intumescent Coating WB 1000 is a single component water-based thin film coating to fireproof interior
structural steel.
3M
TM
FireDam
TM
Intumescent Coating WB 1000 for steel should be installed by trained and certified 3M authorized applicators.
3M
TM
FireDam
TM
Intumescent Coating WB 1000 is listed by independent test agencies such as ULC and UL and is tested to,
and passes the criteria of, Standard Fire Tests of Building Construction and Materials, CAN/ULC-S101-07 Edition (ANSI/UL
263 13TH Edition, ASTM E119-2000 Edition).
Typically Specified Division
Division 7
Section 07812 Intumescent Fire Resistive Material
Related Sections
Section 05100 Structural Steel
Section 05120 05500 Structural steel and metal fabrications with reference to primer receiving fire protection materials
Section 07811 Spray-Applied Fire Resistive Material
Section 09900 Painting
Fire Test Designs
3M
TM
FireDam
TM
Intumescent Coating WB 1000 was tested by ULC/UL on a large scope of columns, beams, floor assemblies
and passed.
Refer to the ULC/UL Directory for the 3M
TM
FireDam
TM
Intumescent Coating WB 1000 designs or please contact 3M.
1. Product Description
2. Instruction
3. Specifications
0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 3
3M
TM
FireDam
TM
Intumescent Coating WB 1000
4
3M
TM
FireDam
TM
Intumescent Coating WB 1000 for steel must be stored indoor in dry conditions between 10C and 40C.
Protect from frost and freezing, excessive heat and strong radiant sunlight. Not intended for exterior applications.
Comply with manufacturing recommendations for temperature and humidity conditions before, during and after installation of
reproong. Refer to section 9. Application Rates & Conditions
Packaging: Volume 18.9 liter (5 gal.) / Weight per pail: 61.6 Lbs (27.8 Kg)
Shelf Life
3M
TM
FireDam
TM
Intumescent Coating WB 1000 shelf life is 6 months in original unopened containers from date of packaging
when stored above 10C (50F).
Lot numbering: First digit = last digit of year
Second to fourth digit = 3 digit day of the year (from 001 to 365/366)
Fifth indicator = dash symbol (-)
Sixth to eighth = batch # (may only be 1 or 2 digits long)
3M
TM
FireDam
TM
Intumescent Coating WB 1000 for steel should be installed with an Airless spray pump such as Spraytech
EP2355 or Graco 1595 / Ultra Max 795 or brush. All surfaces receiving the 3M
TM
FireDam
TM
Intumescent Coating WB 1000 for
steel should be thoroughly cleaned of oil, grease, dirt, loose paint, loose mill scale and any other matter that will impair bond.
Existing Conditions:
(1) Verify existing conditions and substrates before starting work. Correct unsatisfactory conditions before proceeding.
(2) Proceed with installation only after steel components are primed with compatible recommended primer.
*Refer to section 8. Primers
Provide masking and drop cloths to prevent contamination of adjacent surfaces by reproong material.
5. Packaging & Shelf Life
6. Preparatory Work
7. Masking
4. Precautions & Limitations
0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 4
3M
TM
FireDam
TM
Intumescent Coating WB 1000
5
General instructions for installing 3M
TM
FireDam
TM
Intumescent Coating WB 1000 for steel include confirmation of primer
compatibility such as recommended Alkyd and Epoxy primers to receive 3M
TM
FireDam
TM
Intumescent Coating WB 1000.
Note: Primers containing zinc metal are generally not recommended.
Apply 3M
TM
FireDam
TM
Intumescent Coating WB 1000 only to primed surfaces. Site conditions and end-use may dictate spe-
cific primer specifications. Follow primer manufacturers instructions.
Refer to the 3M
TM
FireDam
TM
Intumescent Coating WB 1000 fire test design information to determine the minimum dry film
thickness required for the size and orientation of steel element to be protected and for the required fire resistance rating.
3M
TM
FireDam
TM
Intumescent Coating WB 1000 should be applied in sufficient wet film thicknesses to achieve the required fire
resistive rating with as many passes as necessary, to attain required (DFT) dry film thickness.
3M FireDam Intumescent Coating WB 1000 should not be applied when relative humidity exceeds 80% or the surface to
be coated is less than 3C above the dewpoint. The product is recommended to be applied only when temperatures are above
10C or 50F.
To ensure an even coating thickness, the desired thickness should be achieved by the application of successive coats of
no more than 500 microns dft (760 microns wft) per coat. Apply in sufficient thickness to achieve rating to uniform density
and texture.
The completed dry film thickness should be checked to ensure the required thickness has been applied.
When multiple coats of 3M FireDam Intumescent Coating WB 1000 are required to achieve the prescribed dry film
thickness, adequate drying time between the coats should be allowed. At 20C the minimum overcoating time is typically
4-6 hours. (The time will vary depending upon the prevailing temperature, relative humidity, air movement and thickness
of material applied).
9. Application Rates
8. Primers
0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 5
3M
TM
FireDam
TM
Intumescent Coating WB 1000
6
Chart based on laboratory results of 3M
TM
FireDam
TM
Intumescent Coating WB 1000.
Metric
Area (sq. meter) Volume / Pail (L) Volume % WFT (mm) DFT (mm)
10 18.93 1.89
20 18.93 0.95
30 18.93 0.63
40 18.93 0.47
50 18.93 0.38
60 18.93 0.32
70 18.93 0.27
80 18.93 0.24
90 18.93 0.21
100 18.93 0.19
10. Coverage
Imperial
Area (sq. feet) Volume / Pail (gal) Volume % WFT (mil) DFT (mil)
100 5 66 80.21
200 5 40.10
300 5 26.74
400 5 20.05
500 5 16.04
600 5 13.37
700 5 11.46
800 5 10.03
900 5 8.91
1000 5 8.02
0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 6
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
52.94
26.47
17.65
13.23
10.59
8.82
7.56
6.62
5.88
5.29
1.25
0.62
0.42
0.31
0.25
0.21
0.18
0.16
0.14
0.12
3M
TM
FireDam
TM
Intumescent Coating WB 1000
7
A compatible topcoat with 3M
TM
FireDam
TM
Intumescent Coating WB 1000 is recommended for all installations, in order to give
the desired colour. All topcoats should be applied in accordance with the topcoat manufacturers recommendations.
Either acrylic or silicone alkyd paint to match surroundings are recommended.
Ensure the 3M
TM
FireDam
TM
Intumescent Coating WB 1000 is thoroughly dry before application of topcoat.
Follow approved working practices. Wear government approved respirators and proper clothing, reading all warning labels, and
follow instruction on the MSDS.
No maintenance is required when installed in accordance with the 3M installation manual. Once installed, if any section of the
3M
TM
FireDam
TM
Intumescent Coating WB 1000 is damaged, the damaged section should be repaired (touched up) by a 3M
trained and certified applicator.
11. Topcoats
12. Precautions & Safe Handling Information
13. Maintenance
0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 7
8
3M Fire Protection Products
r i F d n a M 3 . c n I a d a n a C M 3 eDam are trademarks of 3M.
London, Ontario, Canada Used under licence in Canada.
r s t h g i r l l A M 3 , 8 0 0 2 0 4 8 1 5 6 2 0 0 8 eserved. Printed in Canada
1009-03119E c i / a c . m 3 . w w w
0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 8

Potrebbero piacerti anche