Interesting Electric Power Utility Events, Challenges, & Concerns Brian Clowe CenterPoint Energy Houston, TX If you forget everything else
Not just specific lessons learned, but troubleshooting tactics and real world uses of analytic tools
Promote discussion between peers in any protective relay industry Additional Topics in the Paper Firmware Revision Management, Methods Directional Comparison Blocking EM/IED Circuit Breaker Failure Initialization Signaling Trip Signal Monitor vs Separate Circuits Protection of Multiple Circuit Breakers in One IED
Power System Background Harmonics
CNP has installed Dynamic VAR delivery systems From experience, on-site background harmonic voltage levels are useful for DVAR equipment rating Electronic Metering Device up to 51 st
harmonic CCVT/CCPD Inductive/Wound PT Swept Frequency Response Analysis Normally utilized for transformer characterization and damage assessment, SFRA equipment is based on vector network analysis equipment Generates a sweep of frequencies and makes a measurement of the response PT is accurate at 60Hz expected a flat response up to limit Three devices were tested 80,500V primary voltage rating Two multi-ratio secondary windings 67V or 115V output
20LOG10(80,500/115) 57dB 20LOG10(80,500/67) 62dB
Narrowing in on the band of interest, the trend of the response upward to a resonance at around 2600Hz is more pronounced. As the trend began at 400Hz, the data also became less consistent and an increase in deviation resulted at 400-600Hz. Percent error from 60Hz for the 115V secondary were: +/- 5% error from 20-400Hz +12% -8% error from 400-600Hz
Event The ERCOT requirements for UFLS consists of three blocks of frequencies, each requiring a percentage of total load to be shed as the measured frequency of the transmission system line voltage dips below the threshold Diagram of System Area Large motors coasting down not only created the slow decaying of voltage magnitude over time, but also a ramping down of the frequency Relay setting change TRIP = (Freq < [59.3Hz]) AND NOT(Freq < [50Hz])
Measured frequency below 50Hz is not considered a recoverable system wide under- frequency event
50Hz blocking element was implemented system wide Custom Relay Operation Curves CNP makes use of custom protection curves to mimic existing device curves during coordination
Curve data is entered at discrete multiples of pickup
IED must approximate a curve between data points
Automatic Reclosing Initiation An issue was discovered during field testing
IED had a stringent reclose initiate timing requirement
The built-in automatic reclosing logic is monitoring the status of the breaker to be reclosed
When the reclose is not initiated within 30ms of the breaker changing status, the reclosing is locked out This is not user configurable performance characteristic
Multiple scenario testing programs were helpful in discovering Event
Negative Sequence Directionality - Seq > 0 Seq
Setting 50FP/50RP is the threshold for the current level detector that enables forward/reverse decisions for both the negative- and zero-sequence voltage-polarized directional elements. If the magnitude of 3I2 or 3I0 is greater than 50FP/50RP, the corresponding directional element can process a forward/reverse decision.
This calculation, being non-directional, is not limited to a mutually exclusive result and both 50QF and 50QR may be active at the same time. Tradeoffs for increasing the setting value include: Improved security during faults with abnormally high negative sequence where 32Q is not expected to operate Reduced sensitivity during faults with abnormally low negative sequence where 32Q is expected to operate
Compare setting a2 with |I2|/|I1|
Similar tradeoffs to 50FP/50RP + Security for faults with significant I1
a2 compensates for highly unbalanced systems. Unbalance is typical in systems that have many untransposed lines. This factor also helps prevent misoperation during current transformer saturation.
If the relay measures the apparent negative-sequence impedance (z2) less/greater than Z2F/Z2R, the relay declares the unbalanced fault to be forward/reverse.
One snapshot in time The IED does not directly compare z2 to the threshold setting values of Z2F & Z2R. An additional calculation is made to create a threshold value that adjusts based on measured V2 & I2 values. The effect of the equations is to widen the difference between the threshold values as a fault moves away from the impedance origin. Conversely, as a fault moves closer to the impedance origin, the spread between the thresholds is reduced.