2X135MW

DATE SHEET-A:specific Data


S.No Description Particulars
1 A.C.



motor
: 6.6 Kv
2. Type & rating
Type of motor : squirrel cage

Duty cycle/designation
Normal/energy efficient
: continuos
Rated voltage & variation : Rated voltage 10
Rated frequency & % variation :50Hz5%
3. Efficiency at rated voltage & frequency
Full load % :>90%
4. Preformance
Method of starting DOL
Starting current at rated voltage < 6.0 p.u.
Motor torque at 70% of rated voltage Minimum full load torque
Pull out torque of the motor
Atleast 205 of full load
torque

Motor operation from hot condition without
injurious heating at 80% rated voltage at
Motor terminal
: minium 5 minutes
5. Constuction
Type of ventilation Self ventilated
Degree of protecion of enclosure IP-55
Method of cooling
Totally enclosed fan cooled
(tefc) water cooled
Insulation class
:class f with temp.rise
restricted to class b
torpicalized : yes
6. Motor termimal box
Type detachable
Time : 0.2sec
7. Accessory terminal box
Cable glands furnished : required



2X135MW



S.No Description Particulars
1. manufacture XEMC
2. Type and frame size & design code no. YKKL450-4
3. Nos.required
4. Application
5. Specification & codes
6. Capacity for

i) for specified climatic conditions50
50
ii) at 40 ambient
7.
8.
Location for installation
Type of enclosure & ventilation
Self ventilated
9. Degree of protection IP55
10. Type of duty S1
11. No.of phases,frequency & voltage 3,50Hz,6.6kv
12. Permissible variations in
(a) Voltage 10%
(b) Frequency 5%
(c) combined 10%
13. At rated voltage & frequency
(a) full load current 40.1A
(b) full load speed 1496rpm
(c) no load current 13.9A
14.
Minimum permissible voltage durring starting
80% Un
15.
Maximum permissible time at minimum
permissible voltage during running at full
load

16.
Maximum permissible time at 75% of rated
voltage during running at full load.

17. Whether motor stalls at 70% of rated







2X135MW



S.No Description Particulars
Voltage
18. Efficiency & power factor
load
(% of full load)

Efficiency Power Factor
100 94% 0.87
50 93.5% 0.86
25 92% 0.8
0
At start

Duty point 94% 0.87
19. Stator winding
i) connection Star wiring

ii) type & nos.of terminals Brought out
U.V.W

iii) resistance between terminals at
20

iv) resistance per phase at 20 1.1696
v) inductance perphase
vi) capacitance per phase
20.
Starting current as % of full load current
iwith 1S tolerance
650%
ii)without IS tolerance
21. Torque at full load in Kgm 295
22. Break away torque in % of full load torque 200%
23. Pull up torque in % of full load torque 80%
24.
Pull out torque in % of full load torque

25.
Starting time in sec.
Without mechanism coupled or mechanism
coupled through hydraulic coupling when
6s






2X135MW



S.No Description Particulars

It may be presumed that load is transferred to
motor shaft only after attanining almost full
speed

i) with rated voltage
ii) with 80 of rated voltage
iii) with 110 of rated voltage
26.
Starting time in sec.

With mechanism coupled through flexible
coupling

i) with rated voltage 6s
ii) with 80 of rated voltage 11s
iii) with 110 of rated voltage 5s
27. Safe stall time (hot motor)
i) with rated voltage 4.9s
ii) with 80 of rated voltage 8.2s
iii) with 110 of rated voltage 4.0s
28. Safe stall time (cold motor)
i) with rated voltage 6.5s
ii) with 80 of rated voltage 11s
iii) with 110 of rated voltage 5.4s
29.
Limiting motor temperature to determine safe
stall time

30.
Permissible maximum accelerating time (hot
motor)

i) with rated voltage
ii) with 80 of rated voltage
iii) with 110 of rated voltage
31.
Permissible maximum accelerating time(cold
motor)

i) with rated voltage
ii) with 80 of rated voltage
iii) with 110 of rated voltage
32. Insulation





2X135MW



S.No Description Particulars
i) class of insulation
ii) material & treatment of insulation
33.
Whether insulation is suitable for 415V,6.6
KV,ungrounded system

34.
Temperature rise under normal conditions over
50 ambient temperature

i) by resistance method

ii)by thermometer method

35. Method of starting
36. Permissible starting duty cycles
37. Stator thermal time constant
38. Maximum permissible voltage
During high speed bus transfer & special
Design feature

39.
Time required for voltage to decay down
To when driving voltage is removed

i) At 50% of rated voltage
ii) At 40% of rated voltage
iii) At 25% of rated voltage
iv) At 0% of rated voltage
Method of cooling
40. Details of water cooling system
i) no. of cooler
ii) water requirement per cooler
iii) losses removed by cooler
iv) Max.permissible temperature of
Cooling water at inlet
v) max.permissible temperature of
Cooling water at outlet
vi) maximum permissible pressure at
Water outlet







2X135MW



S.No Description Particulars

vii) water pressure drop through the cooler


viii) temp.of cold air coming out & entering
the machine for permissible cooling water
Temperature of 31


ix) temp.rise of water through cooler


x) air pressure drop through the cooler


xi) temp.rise of water through cooler


xii) protection against leakage of water


xiii) arrangement to ensure the water flow

Bearings
i) number
ii) type
iii) lubrication system


iv) quantity of lubricant reqd.for both the
bearings

v) life in hours at rated speed
vi) recommended lubricant
vii) inlet oil pressure
viii) inlet oil pressure
ix) temp. rise of oil
x) Max.permissible temp.of bearing
xi) Max.permissible temp.of oil


xii) permissible running time without
forced oil at full load & full speed


xiii) whether bearings are provided
With 4 wire,platinum RTD having






2X135MW



S.No Description Particulars

100-ohm resistance at 0 for
remote temp.indication


xiv) whether bearing are provided
with local temperature indicator
Having two adjustable contacts rated
For 2A at 240V AC or 0.2A at 220V
DC
Yes / No
xv) If forced lub.oil system provided Yes / No

i)Qty of lubricant required for initial
Filling


ii) recommended period after which
lubricant should be replaced

iii) Bearing cooling water requirement

iv)max.permissible bearing cooling
Water inlet temp.(permissible)


v) max.permissible bearing cooling
water outlet temp

41.
Terminal designation correspond to direction
Of rotation(facing driving end)
Clockwise
42.
Terminal boxes with accessories separate
Terminal boxes provided

i) main Yes
ii) space heaters Yes
iii) winding temp. detectors Yes
iv) bearing temp.detectors Yes
v) moisture detectors Yes
43.
vi) neutral terminals
Main terminal box details

i) type & nos.

ii) fault level permissible for 0.25 sec







2X135MW



S.No Description Particulars
iii) location
iv) cable gland size & no.
v) direction of cable entry
44. Space heater
i) number
ii) location
iii) capacity of each
iv) total power requirement
45. v) voltage
Details of 4 wire platinum RTD having 100
Ohm resistance at 0 for winding
temp.detector

i) nos.provided
ii) location
46.
Whether CTs for differential protection are
provided
No

i) if Yes,no.of CTs supplied
alongwith motors C.T. details

a) C.T. ratio
b) knee point voltage
ii) S.C. withstand capacity
47. Type of mounting
48. Shaft orientation
49. Shaft extension
50. Grounding pads size nos.& location
51. Method of coupling to driven mechanism
52.
53.
Motor GD
2
Lifting device

54. Weight
i) weight of stator(wonud)





2X135MW



S.No Description Particulars
ii) weight of rotorwound
iii) weight of base plate
iv) weight of cooler
v) net weight of motor
55. Shipping dimensions & weight
56. Thermometer provided
i) in cold air path
ii) in hot air path
iii) for measurement of oil temp.
57. Characteristic curves furnished
i) speed vs.current at rated voltage No
ii) speed vs.torque at 110%,100%, No
90% and 80% of rated voltage
iii) thermal withstand curve for hot &
cold conditions
Yes / No
iv) efficiency vs.load Yes / No
v) P.F.Vs.load Yes / No
vi) current vs.time Yes / No
vii) negative phase sequence curve Yes / No
58. Drawings furnished
i) general arrangement of motor
ii) main terminal box showing the method
Of terminating the incoming cables

iii) instruction manuals
59. Rotor design as per specs