Sei sulla pagina 1di 14

15.

5 SUMMER AIR CONDITIONING-APPARATUS DEW POINT



In summer, the outside air temperature and humidity are both high. The room, therefore, gains
heat as well as moisture. It is thus required to cool and dehumidify the recirculated room air in
the air-conditioning apparatus either by the use of a cooling coil or by an air washer in which
chilled water is sprayed. The process follows the room sensible heat factor (RSHF) line. The
room sensible heat factor is the ratio of the room sensible heat to the room total heat

RSHF =



In a cooling and dehumidification process, the temperature at which the RSHF or condition
line intersects the saturation curve is called the room apparatus dew point (Room ADP). Thus

in Fig. 15.22 denotes the effective surface temperature

. The condition line i-S represents


the locus of all possible supply air states. One extremity of the condition line is i which would be
the supply air state with an infinite quantity of supply air. The other extremity is S which is the
supply state with the minimum supply air requirement corresponding to the given condition line.
It is not possible to have any other supply air state with a DBT lower or higher than the ADP on
the saturation curve which would satisfy the given condition line.







Fig. 15.22 Locus of supply air states for cooling and apparatus dew point

The minimum quantity of supply air will then be given by either of the following three
equations:

(15.27a)

=

(15.27b)

=

(15.27c)

In the case of an actual coil with a bypass factor of X, the leaving air state will be at s. It is
seen that the effect of the bypass factor is to decrease the difference in temperature between the
room air and supply air, and hence to increase the supply air quantity over its minimum value.
For any supply air state, the temperature difference (

) available to counteract the


room sensible heat load is called the dehumidified rise and the corresponding dehumidified air
quantity

which is equal to the quantity of the supply air, is obtained by the equation for
sensible heat balance, and considering the effect of bypass factor

(15.28)

It can also be found from the equations of latent heat or total heat balances.


15.5.1 Summer Air-Conditioning System with Ventilation Air-Zero Bypass Factor

The introduction of fresh outside air for the ventilation of conditioned space is necessary to
dilute the carbon dioxide and odours and other air contaminants for maintaining the purity of
room air. Accordingly, the simple air-conditioning system of Fig. 15.20 is modified, so that the
supply air to the room comprises fresh air and recirculated room air. An amount equivalent to the
fresh air is ejected from the room. The schematic diagram of the system is shown in Fig. 15.23,
and the processes for the cases of cooling and dehumidification are shown in Fig. 15.24.






Fig. 15.23 Schematic diagram of system with ventilation air

In Fig. 15.24, 0 and I represent the outside and inside air states and 1 is the state of air after
the mixing of recirculated room air with ventilation air. The mixture entering the conditioning
apparatus comprises recirculated room air

and ventilation air

. The room sensible heat


factor (RSHF) line is drawn from the inside condition i to intersect the saturation curve at room
ADP at 2. Point 2 represents the supply air state for a minimum rate of supply air. The line 1-2,
therefore, represents the condition line for the apparatus and is called the grand sensible heat
factor (GSHF) line. It is noted that the line i-2 is the condition line for the room or the RSHF line
and line 1-2 is the condition line for the apparatus or the GSHF line intersecting the saturation
curve at coil apparatus dew point (Coil ADP). Note that, in this case, the coil ADP and the room
ADP are the same.
In the absence of ventilation air the load on the air-conditioning apparatus is that due to the
room sensible heat and room latent heat. When ventilation air is used, there is an additional load
on the apparatus named the ventilation load equivalent to the change of state of the ventilation air
from the outside condition to inside condition. This becomes evident when we write for the total
load on the air-conditioning apparatus in terms of the change of state of the mixture air

from
1 to 2. Thus







Fig. 15.24 Summer air-conditioning processes with ventilation air and zero bypass factor

Q =

) =


= (

) +

) (15.29)

The first term on the right-hand side in Eq. (15.29) represents the room load and the second
term, the load due to the ventilation air as explained earlier. Accordingly, if

is the
outside ventilation air volume flow rate, then the outside air sensible heat (OASH) and outside
air latent heat (OALH) loads are

OASH =

= 0.0204

) (15.30)
OALH =

= 50

) (15.31)

Also for the outside air total heat (OATH), we have

OATH =

= OASH + OALH = 0.02

) (15.32)

Note: These equations apply to winter air conditioning as well.








The break-up of the load on the air conditioning apparatus is now as follows:
Room Load
Sensible RSH
Latent RLH
Total RTH = RSH + RLH
Ventilation Load
Sensible OASH
Latent OALH
Total OATH = OASH + OALH
Air-conditioning Equipment Load
Total sensible TSH = RSH + OASH
Total latent TLH = RLH + OALH
Grand total GTH = TSH + TLH

In Fig. 15.24, the process line 1-2 represents the grand sensible heat factor line for the
process in an air-conditioning apparatus. The grand sensible heat factor is the ratio of the total
sensible heat to the grand total heat. Thus

GSHF =



Example 15.6 The air-handling units of an air-conditioning plant supplies a total of 4500 cmm
of dry air which comprises by weight 20 percent fresh air at 40 C DBT and 27C WBT, and 80
percent recirculated air at 25C DBT and 50 per cent RH. The air leaves the cooling coil at
13C saturated state. Calculate the total cooling load, and room heat gain.

Solution Refer to Fig. 15.24. From the psychrometric chart the following conditions are noted:

Condition DBT
C
WBT
C
RH
%
Sp. Hu.
g w.v/kg g.a.
Enthalpy
kJ /kg d.a.
Outside 40 27 17.2 85
Inside 25 50 10.0 50.8
ADP 13 100 9.4 37.0

Condition of air entering the cooling coil

= 0.2 (17.2) + 0.8 (10) = 11.44 g w.v/kg d.a.


= 0.2 (85) + 0.8 (50.8) = 57.64 kJ/kg d.a.


= 0.2 (40) + 0.8 (25) = 28C


Specific volume of air entering the cooling coil

= 0.869

/kg d.a.

Mass flow rate of air entering the cooling coil

= 86.31 kg d.a./s
Total cooling load
Q =

) = 86.31 (57.64 37) = 1781.4 kW


Fresh air load

) = 0.2 (86.31) (85 50.8) = 590.4 kW


Room heat gain
RTH =

= 1781.4 590.4 = 1191 kW



Note A point to be noted here is that the fresh air load is a significant part of the cooling load.
In the present case, it is 33 per cent. In some applications such as operation theatres in hospitals
where 100 per cent fresh air is taken, it is of overriding importance. In cinema halls and theatres
also, the predominant load is due to occupancy and fresh air. In such cases, the peak load occurs
when the outside wet bulb temperature is maximum. This usually occurs between 2 and 5 p.m.

Example 15.7 An air-conditioned space is maintained at 27C DBT and 50 per cent RH. The
ambient conditions are 40C DBT and 27C WBT. The space has a sensible heat gain of 14 kW.
Air is supplied to the space at 7C saturated.
Calculate:
(i) Mass of moist air supplies to the space in kg/h.
(ii) Latent heat gain of space in kW.
(iii) Cooling load of the air washer in kW if 30 per cent of the air supplied to the space is fresh,
remainder being recirculated.

Solution Refer to Fig. 15.24. From the psychrometric chart.

Condition DBT
C
WBT
C
RH
%
SP. Hu.
g w.v/kg d.a.
Enthalpy
kJ /kg d.a.
Outside 40 27 17.2 85
Inside 27 50 11.2 56.1
Supply 7 100 6.2 23.0

(i) Mass of dry air supplied to space

= 2467 kg d.a./h
Ratio of moist air to dry air in supply air = (1 +

) = 1.0062
Mass of moist air supplied to space
m = (1 +

= 1.0062 (2467) = 2482 kg/h


(ii) Latent heat gain of space

= 8.57 kW

(iii) For point 1

= 0.7 (27) + 0.3 (40) = 30.9C


On the line joining o to I, locate point 1 at 30.9C. Then, from the psychrometric chart

= 64.9 kJ /kg d.a.


Cooling load of the air washer

) =

(64.9 23.0) = 28.71 kW



15.5.2 Summer Air-conditioning System with Ventilation Air-Bypass Factor X

In the case when the bypass factor of cooling and dehumidifying apparatus is not zero, it is
evident from Fig. 15.24 that if the surface temperature is

, viz., equal to room ADP, the leaving


air state 2 will not be at S; it will be on the line joining 1 to S. Hence the supply air state will not
lie on the room sensible heat factor line which is essential to satisfy the room sensible and latent
heat load requirements. In such a case, which usually occurs in actual practice, it will be
necessary to lower the apparatus dew point, i.e., the effective surface temperature of the air-
conditioning apparatus, as shown in Fig. 15.25, in such a way that the leaving air state 2 lies on
the RSHF line i-S, and also the new surface temperature

or coil ADP is such that the following


condition for the bypass factor X is satisfied.

X =








Fig. 15.25 Summer air-conditioning process with ventilation air and finite bypass factor

It will be seen that the effect of the bypass factor is to lower the ADP of the surface, and
hence to decrease the coefficient of performance of the refrigerating machine. It is also seen that
the position of the grand sensible heat factor line is changed. This is explained in greater detail in
Sec. 19.7. The supply air temperature

is now increased to leaving air temperature

. Further,
the dehumidified rise now is

. The dehumidified air quantity may be calculated


accordingly, which will be found to be more than that of the apparatus with a zero bypass factor.
The recirculated air quantity can then be calculated by the difference of the dehumidified
(supply) air and ventilation air quantities. Since ventilation air quantity is fixed according to
requirement, this leads to a variation in the recirculated air quantity. The greater the BPF, the
more the recirculated air quantity. As a result, point 1 after mixing, shifts closer towards i.

Example 15.8 A building has the following calculated cooling loads:
RSH gain = 310 kW
RLH gain = 100 kW
The space is maintained at the following conditions:
Room DBT = 25C
Room RH = 50%
Outdoor air is at 28C and 50% RH. And 10% by mass of air supplied to the building is
outdoor air. If the air supplied to the space is not to be at a temperature lower than 18C, find:
(a) minimum amount of air supplied to space in

.
(b) Volume flow rates of return (recirculated room) air, exhaust air, and outdoor air.
(c) State and volume flow rate of air entering the cooling coil.
(d) Capacity, ADP, BPF and SHF of the cooling coil.

Solution Refer to Fig. 15.25. Room SHF is 0.756.
Draw room SHF line. Its intersection with t = 18C vertical gives supply air state point s
which is the same as coil leaving air state point 2. From psychrometric chart

= 50.5 kJ/kg d.a.,

= 41.2 kJ/kg d.a.,


= 0.836

/kg d.a.

= 92.0 kJ/kg d.a.


(a) Supply air quantity and volume flow rate (minimum)

= 44.09 kg/s

= (44.09) (0.836) = 36.86


(b) Quantity and volume flow rate of outdoor/exhaust air.

= 0.1

= 0.1 (44.09) = 4.41 kg/s


= 4.41 (0.91) = 4.01


Quantity and volume flow rate of return air

= 44.09 4.41 = 39.68 kg/s


= 39.68 (0.86) = 34.05


Here,

= 0.91 and

= 0.86

kg d.a. are the specific volumes of outdoor and indoor air


respectively.
(c) State of air entering cooling coil

= 0.9

+ 0.1

= 0.9 (25) + 0.1 (38) = 26.3C


= 19.2C at 26.3C DBT on the line joining i to o


= 0.865 from psychrometric chart


= 54.6 kJ/kg d.a.


Volume flow rate of air entering the cooling coil

= 44.09 (0.865) = 38.14


(d) Refrigerating capacity of the coil

= GTH =

) = 44.09 (54.6 41.2) = 591 kW


Coil ADP is obtained by the intersection of the line joining 1 to 2 with the saturation curve.
Thus

= 9C
BPF and SHF of the coil
BPF =

= 0.52
GSHF =

= 0.533

Note Room SHF of 0.756 is normal. But GSHF of 0.533 is very low. This is due to high OALH;
because of the outside air being very humid and hot,

= 21 g/kg d.a. and

= 92.0 kJ/kg d.a.


Low GSHF and high BPF of the coil chosen, viz., 0.52 has resulted in low ADP of 9C. This
would result in low evaporator temperature and high power consumption of the refrigerating
machine. It would be better to choose a coil of low BPF. That would require a higher coil ADP
and evaporator temperature, and hence would give better performance. But, then the supply air
temperature would be lower than 18C, and quantity of supply air would be reduced.

Example 15.9 The conditioning plant of a room consists of a fresh air intake, a cooling coil-
followed by a mixing chamber or the cooled fresh air and recirculated room air, and a supply
fan as shown in Fig. 15.26. The cooling coil handles all fresh air and has a BPF of 0.1. (See also
Sec. 23.7).
The ratio of fresh air to recirculated air is determined by modulating dampers. The other
data is as follows:
Inside conditions : DBT = 24C, RH = 50%
Outside conditions : DBT = 30C, WBT = 23.3C
Heat gains : RSH = 14.7 kW, RLH = 3 kW
Supply air quantity : 191 cmm
Neglecting temperature changes in the fan and duct, determine:
(i) DBT and moisture content of supply air.
(ii) Mass flow rate of moist air supplied to room.
(iii) DBT and moisture content of air leaving cooling coil.
(iv) Load on the cooling coil.








Fig. 15.26 Conditioning plant for Example 15.9
Solution (iii) The processes are shown in Fig. 15.27
RSHF =

= 0.831
This is the slope of line i-s-2. However, it is not possible to fix points s and 2 at this stage.
But, we know that
BPF =


= 0.1






Fig. 15.27 Processes in Example 15.9

Accordingly, point 2 can be fixed by trial and error on the RSHF line. However, the
following construction is simpler and more accurate. Draw line o-i and extend it to A such that:


= 0.1
And then draw AS parallel to RSHF line i s. Intersection with saturation curve gives coil
ADP of 11.1C at S. Join 0 S. It cuts i s extended at 2. Thus, we get condition of air leaving
coil as:

= 12.2C,

= 8.5 g/kg d.a.,

= 33.8 kJ/kg d.a.


(i) DBT and moisture content of supply air


RTH =

) =

(48.8

) = 17.7
This equation can be solved by trial and error. Thus, point s can be located on RSHF line. It is
found that:

= 0.856

/kg d.a.,

= 20C,

= 43.8 kJ/kg d.a.,

= 9.1 g/kg d.a.


(ii) Mass flow rate of moist air supplies to room

(1 + 0.0091) = 3.753 kg/s


(iv) Fresh air through coil

+ (

(12.2) +

(24) =

(20)

= 76.1 kg/min = 1.268 kg/s =


Load on cooling coil
GTH =

) = 1.268 (69.8 33.8) = 45.7 kW



Example 15.10 Given for a conditioned space:
Room sensible heat gain = 20 kW
Room latent heat gain = 5 kW
Inside design conditions: 25C DBT, 50% RH
Bypass factor of the cooling coil = 0.1
The return air from the space is mixed with the outside air before entering the cooling coil in
the ratio of 4 : 1 by weight. Determine:
(i) Apparatus dew point.
(ii) Condition of air leaving cooling coil.
(iii) Dehumidified air quantity.
(iv) Ventilation air mass and volume flow rates.
(v) Total refrigeration load on the air conditioning plant.

Solution Refer to Fig. 15.25. From psychrometric chart

Condition DBT
C
WBT
C
RH
%
Sp. Hu.
g w.v/kg
d.a.
Enthalpy
kJ /kg d.a.
Sp. Vol.

/kg d.a.
Outside 43 27.5 17.0 87.5 0.922
Inside 25 50 10.0 50.8

Condition of air entering the cooling coil

= 0.8

+ 0.2

= 0.8 (10) + 0.2 (17) = 11.4 g w.v./d.a.


= 0.8 (50.8) + 0.2 (87.5) = 598.1 kJ/kg d.a.


= 0.8 (25) + 0.2 (43) = 28.6C


(i) and (ii). Both parts have to be worked out together. There are two methods. One method
is to draw the RSHF line and then draw a line from 1 to S on the saturation curve so that
(S 2)/(1 2) are given in the ratio of 1 : 9. Another method is to do the same thing using
calculations as given below.
Ratio of room sensible and latent heats

(I)
Relations for bypass factor

= 0.1 (II)

= 0.1 (III)
Solving Eqs (I), (II) and (III) by iteration for

and

, we obtain

= 11.8C (Corresponding

= 8.6 g w.v./kg d.a.)


= 13.5C

= 0.0089 kg w.v./kg d.a.



(iii) Dehumidified air quantity


= 85.25
(iv) Specific volume of supply air

= 0.822

/kg d.a.
Mass flow rate of supply air

= 1.729 kg d.a./s
Mass flow rate of fresh air

= 0.2

= 0.2 (1.729) = 0.346 kg d.a./s


Volume flow rate of fresh air

(60) = (0.346) (0.922) (60) = 19.12 cmm


(v) Outside air total heat
OATH =

) = 0.346 (87.5 50.8) = 12.7 kW


Total refrigeration load on the air conditioning plant
GTH = RTH + OATH = (20 +5) + 12.7 = 37.7 kW

15.6 WINTER AIR CONDITIONING

In winter, the building sensible heat losses are partially compensated by the solar heat gains and
the internal heat gains such as those from occupancy, lighting, etc. Similarly, the latent heat loss
due to low outside air humidity is more or less offset by the latent heat gains from occupancy.
Thus in winter, the heating load is likely to be less than the cooling load in summer. However,
the actual situation both in summer and winter depends on the swing of the outside temperature
and humidity with respect to the inside conditions.
Further, certain sensible heat gains (negative loads) such as the solar heat may not be present
at the time of peak load, and hence they are not counted. On the other hand, latent heat gains
from occupancy, etc., are always present and should be taken into account. As a result, the
design heating load for winter air conditioning is present dominantly sensible.
In general, the process in the conditioning apparatus for winter air conditioning for comfort
involves heating and humidifying. Two of the typical process combinations are:
(i) Preheating the air with steam or hot water in a coil followed by adiabatic saturation and
reheat.
(ii) Heating and humidifying air in an air washer with pumped recirculation and external
heating of water followed by reheat.
The processes for the two systems are shown in Fig. 15.28. The first system with preheating
and adiabatic saturation follows processes 1 2 and 2 3 respectively. The second system
replaces the two processes with heated water spray in the air washer and the process line is 1 3.
The leaving air state 3 from the air may be affected by the saturation efficiency. The reheating
process 3 s is common to both. The supply air states should lie on the room sensible heat factor
line. It is, therefore, determined by the RSHF and by the choice of supply air rate which is
usually known from summer air-conditioning calculations.







Fig. 15.28 Winter air-conditioning processes

Example 15.11 In an industrial application for winter air conditioning, an air washer is used
with heated water spray followed by a reheater. The room sensible heat factor may be taken as
unity. The design conditions are:
Outside: 0C DBT and dry
Inside: 22C DBT and 50% RH
Room heat loss: 703 kW
The following quantities are known from the summer design.
Ventilation air 1600 cmm
Supply air 2800 cmm
Spray water quantity 500 kg/min
The air washer saturation efficiency is 90 per cent. The make-up water is available at 20C.
Calculate:
(i) The supply air condition to space.
(ii) The entering and leaving air conditions at the spray chamber.
(iii) The entering and leaving spray water temperatures.
(iv) The heat added to the spray water.
(v) The reheat, if necessary.

Solution Refer to Fig. 15.29
(i) Supply air temperature


+ 22 = 34.2C
A RSHF = 1 line from the room condition i can be drawn as shown in Fig. 15.29.
Intersection with the 34.2C DBT line locates the supply air state. The supply air WBT is found
to be 19.6C, and its specific humidity

to be 0.0082 kg/kg d.a.













Fig. 15.29 Figure for Example 15.11

(ii) Entering air conditions (calculate from the volume flow rates).

= 9.43C
Similarly,

= 0.0035 kg w.v./kg d.a.


Wet bulb temperature of entering air (from psychrometric chart)

= 4.8C
Specific humidity of leaving air

= 0.0082 kg w.v./kg d.a.


Expression for saturation or humidifying efficiency


0.9 =



which gives the specific humidity at the wetted-surface temperature

as

= 0.00873 kg w.v./kg d.a.


From the psychrometric chart

= 11.8C
Dry bulb temperature of leaving air

) +

= 0.9 (11.8 9.43) + 9.43 = 11.6C


Wet bulb temperature of leaving air (from the psychrometric chart)

= 11.5C
(iii) The temperature of the leaving spray water and the wet bulb temperature of the leaving air
may be taken to be the same. Hence, the leaving spray water temperature

= 11.5C.
Energy balance of the air washer

) =

(33.0 18.2) = (500) (4.187) (

= 34
(iv) Make-up water

) =

(0.0082 0.0035) = 14.95 kg/min



Heat added to make-up water

(4.187) (34 20) = 14.61 kW


Heat added to raise temperature of spray water

(4.187) (34 11.5) = 785.1 kW


Heat added to spray water
Q =

= 14.61 + 785.1 = 799.71 kW


(v) Reheat = 0.0204

) = 0.0204 (2800) (34.2 11.6) = 1290.9 kW

Potrebbero piacerti anche