Instruction Manual

Authorized Electricians
blueplanet
XP10U-H4

Installation Instructions blueplanet XP10U-H4 Page 3
1 General Notes ............................................ 4
1.1 About this documentation .................................4
1.2 Design features .......................................................4
2 Safety ......................................................... 6
2.1 Intended use ............................................................6
2.2 Protection features ................................................ 7
2.3 Standards and regulations .................................. 7
3 Description ................................................ 8
3.1 How it works ............................................................8
3.2 Unit description ......................................................8
4 Technical Data .......................................... 11
4.1 Electrical Data ......................................................... 11
4.2 Mechanical Data ....................................................12
5 Transportation and Delivery ...................13
5.1 Delivery .....................................................................13
5.2 Transportation ........................................................13
6 Mounting the Inverter .............................14
7 Installing the Inverter ..............................16
7.1 Opening the connection area ......................... 16
7.2 Drilling holes for electrical and interface
connection .............................................................. 16
7.3 Carrying out the electrical connection .........17
7.4 Connecting the interfaces ................................22
7.5 Sealing the connection area ............................25
7.6 Starting up the inverter ......................................25
8 Confguration and Operation ................ 26
8.1 Controls ....................................................................26
8.2 Initial start-up ........................................................29
8.3 Menu structure......................................................29
8.4 Monitoring the inverter ..................................... 33
8.5 Performing a software update ........................ 35
9 Maintenance/Troubleshooting.............. 36
9.1 Visual inspection ..................................................36
9.2 Cleaning the inverter externally .....................36
9.3 Shutting down for maintenance and
troubleshooting ....................................................36
9.4 Faults ......................................................................... 37
9.5 Messages on the display and the
Fault LED ............................................................. 40
9.6 Replacing or cleaning the fan ......................... 44
10 Service ...................................................... 45
11 Shutdown/Disassembly .........................46
11.1 Shutting down the inverter ............................. 46
11.2 Deinstalling the inverter ................................... 46
11.3 Dismantling the inverter ................................... 46
12 Recycling and disposal ........................... 47
13 Appendix .................................................48
Installation Instructions
for authorized electricans
blueplanet
XP10U-H4
Contents
General Notes
Page 4 blueplanet Installation Instructions Powador 10.0 TL3, 12.0 TL3, 14.0 TL3_EN
1 General Notes
1.1 About this documentation
WARNING
Improper handling of the inverter can be hazardous
IMPORTANT SAFETY INSTRUCTIONS.
You must read and understand the operating instructions before you can install and use the
inverter safely.
This manual is intended for inverter model blueplanet XP10U-H4 and shall be followed during installation and main-
tenance of this inverter model.
1.1.1 Other Applicable Documents
During installation, observe all assembly and installation instructions for components and other parts of the system.
These instructions are delivered together with the respective components and other parts of the system.
Some of the documents which are required for registering and approving your photovoltaic (PV) system are
included with the operating instructions.
1.1.2 Retention of documents
SAVE THESE INSTRUCTIONS. These instructions and other documents must be stored near the system and be
available whenever they are needed.
1.2 Design features
1.2.1 Symbols used in this document
General hazard symbol Risk of fre or explosion
High voltage Risk of burns
Authorised electrician

The tasks indicated with this symbol may only be carried out by an authorised
electrician.
1.2.2 Description of safety instructions
DANGER
Imminent danger
Failure to observe this warning will lead directly to serious bodily injury or death.
WARNING
Potential danger
Failure to observe this warning may lead to serious bodily injury or death.
CAUTION
Low-risk hazard
Failure to observe this warning will lead to minor or moderate bodily injury.
General Notes
blueplanet Installation Instructions Powador 10.0 TL3, 12.0 TL3, 14.0 TL3_EN Page 5
CAUTION
Hazard with risk of property damage
Failure to observe this warning will lead to property damage.
1.2.3 Description of additional information
NOTICE
Useful information and notes
1.2.4 Description of action instructions
a) One-step actions or actions that can be carried out in any sequence:
Action instructions
Prerequisite(s) for your action(s) (optional)
Carry out action.
(Additional actions, if applicable)
Result of your action(s) (optional)
b) Multi-step action instructions that must be carried out in a fxed sequence:
Action instructions
Prerequisite(s) for your actions (optional)
1. Carry out action.
2. Carry out action.
3. (Additional actions, if applicable)
Result of your actions (optional)
Saf ety
Page 6 Installation Instructions blueplanet XP10U-H4
2 Safety
DANGER
Lethal voltages are still present in the terminals and leads of the inverter even after the
inverter has been switched of and disconnected.
Severe injuries or death if the leads and/or terminals in the inverter are touched.
Only authorised electricians who are approved by the supply grid operator may open, install and
maintain the inverter.
Keep the inverter closed when the unit is in operation.
Do not touch the leads and/or terminals when switching the unit on and of.
Do not make any modifcations to the inverter.
The electrician is responsible for observing all existing standards and regulations.
Keep unauthorized persons away from the inverter and PV system.
Be sure to observe IEC 60364-7-712:2002 (Requirements for special installations or locations solar photovoltaic
(PV) power supply systems) in particular.
Ensure operational safety by providing proper grounding, conductor dimensioning and appropriate protection
against short circuiting.
Observe the safety instructions on the inverter and in these operating instructions.
Switch of all voltage sources and secure them against being inadvertently switched back on before performing
visual inspections and maintenance.
When taking measurements while the inverter is live:
Do not touch the electrical connections.
Remove all jewellery from your wrists and fngers.
Ensure that the testing equipment is in safe operating condition.
Stand on an insulated surface when working on the inverter while it is switched on.
Modifcations to the surroundings of the inverter must comply with the applicable national and local standards.
When working on the PV generator, it is also necessary to switch of the DC voltage with the DC disconnector in
addition to disconnecting the PV generator from the grid.
2.1 Intended use
The inverter converts the DC voltage generated by the PV modules into AC voltage and leads this into the grid
feed-in. The inverter is built according to the state of the art and recognised safety regulations. Nevertheless,
improper use may cause lethal hazards for the operator or third parties, or may result in damage to the unit and
other property.
Operate the inverter only with a permanent connection to the public power grid.
Any other or additional use is not considered the intended use. This includes:
Mobile use
Use in rooms where there is a risk of explosion
Use in rooms where the humidity is higher than 95%
Operation outside of the specifcation intended by the manufacturer
Standalone operation.
Saf ety
Installation Instructions blueplanet XP10U-H4 Page 7
2.2 Protection features
For your safety, the following monitoring and protective functions are integrated into Powador inverters:
Overvoltage conductors/varistors to protect the power semiconductors from high-energy transients on the
grid and generator side
Temperature monitoring of the heat sink
EMC flters to protect the inverter from high-frequency grid interference
Grid-side grounded varistors to protect the inverter against burst and surge pulses
Islanding detection according to VDE 0126-1-1
2.3 Standards and regulations
Electrical conformity according to U.S., Canadian and international safety operating standards and code
requirements:
UL 1741-1:1999 Rev. May 2007
CSA 22.2 No. 107-1:2001 Rev 2006
IEEE Std. 1547-2003
IEEE Std. 1547.1-2005
FCC Part 15 Class B
NEC Sections 690 (ANSI/NFPA 70)
Directive concerning Electromagnetic Compatibility with Class B (Council Directive 2004/108/EC)
Low Voltage Directive (Council Directive 2006/95/EC)
The blueplanet inverter has complete on-board overcurrent, over-temperature and anti-islanding protection.
Descri pti on
Page 8 Installation Instructions blueplanet XP10U-H4
3 Description
3.1 How it works
The inverter converts the DC voltage generated by the PV modules into AC voltage and leads this into the grid
feed-in. The feed-in process begins when there is suf cient irradiance and a specifc minimum voltage is present
in the inverter. If, as nightfall approaches, the voltage drops below the minimum voltage value, feed-in mode ends
and the inverter switches of.
3.2 Unit description
3.2.1 Inverter as part of a PV system
3.2.1.1 System layout
v
Figure 1: Overview circuit diagram for a system with two inverters
KWh KWh
PV generator PV generator
Inverter Inverter
Safety
fuse
Safety
fuse
Consumer
Feed-in meter Reference
meter
Main switch
Grid connection
point
Selective main switch
Descri pti on
Installation Instructions blueplanet XP10U-H4 Page 9
3.2.1.2 A summary of the components
PV generator
The PV generator, i.e. the PV modules, converts the radiant energy of sunlight into electrical energy.
DC terminal point
Variants of parallel connection of several generator strings:
To a DC terminal point between the DC generator and inverter
Directly to the inverter (plug connectors for 4 (2x2) strings are provided on the inverter)
Directly to the PV generator with a positive and negative lead to the inverter
Line fuses
Safety fuses are suitable.
Feed-in meter
The feed-in meter is specifed and installed by the power supply company. Some power supply companies also
allow the installation of your own calibrated meters.
Selective main switch
If you have questions about the selective main switch, contact your power supply company.
3.2.2 Design of the inverter
1
2
3
4
5

Figure 2: Design of the inverter
Key
1 Operator panel 4 USB interface
2 Cover for the connection area 5 Mounting plate
3 Connection board
Descri pti on
Page 10 Installation Instructions blueplanet XP10U-H4
3.2.3 Electrical functions
3.2.3.1 Fault signal relay
A potential-free relay contact is integrated in the inverter. The contact closes as soon as there is a fault during
operation.
For the connection, see section 7.3 on page 26.
3.2.4 Interfaces
The inverter ofers the following interfaces for communication and remote monitoring:
RS485 interface
Ethernet interface
USB interface
S0 interface
You confgure the interfaces and the web server in the confguration menu.
3.2.4.1 RS485 interface
Use this monitoring variant if you cannot check the function of the system on-site on a regular basis, e.g. if your
place of residence is located a great distance from the system. To connect the RS485 interface, contact your
authorised electrician.
For monitoring your PV system using the RS485 interface, KACO new energy GmbH ofers the following units:
Powador-proLOG S to XL (optional)
Powador-proLOG allows you to monitor up to 31 inverters simultaneously. Depending on the product version,
Powador-proLOG sends yield and operating data by SMS or e-mail.
Powador-link RS485 (optional)
Use the Powador-link RS485 to bridge long distances between several inverters or between an inverter and the
Powador-proLOG by means of wireless radio transmission.
3.2.4.2 Ethernet interface
The monitoring can occur directly on the unit using the integrated Ethernet interface. A local web server is installed
in the unit for this purpose.
For monitoring a system comprising several inverters, we recommend you use an external data logging and
monitoring system.
3.2.4.3 USB interface
The USB connection of the inverter is a type A socket. It is located on the connection board on the underside of the
inverter under a cover. The USB connection is specifed to draw 100 mA of power. Use the USB interface for reading
out stored operating data and loading software updates using a FAT32-formatted USB stick.
3.2.4.4 S0 interface
The S0 interface transmits pulses between a pulsing counter and a tarif metering unit. It is a galvanically isolated
transistor output. It is designed according to DIN EN 62053-31:1999-04 (Pulse output devices for electromechanical
and electronic meters).
The S0 interface pulse rate can be chosen in three unit intervals (500, 1,000 and 2,000 pulses/kWh).
Techni cal Data
4 H - U 0 1 P X s l e v e L t u p n I
0 0 0 , 2 1 ] W [ r e w o p r o t a r e n e g V P . x a M
0 5 5 . . . 0 8 2 ] V [ o t ] V [ m o r f e g n a r P P M C D
* 0 5 5 . . . 0 0 2 ] V [ o t ] V [ m o r f e g n a r g n i t a r e p O
0 5 2 ] V [ e g a t l o v g n i t r a t S
) 0 0 6 o t t r a t s ( 0 0 6 ] V [ e g a t l o v t i u c r i c n e p O
x 2 ] A [ t n e r r u c d e t a r . x a M 18.6
18.6
Max. power per tracker [W]
10,200
2 x 2 s g n i r t s f o r e b m u N
2 s l o r t n o c P P M f o r e b m u N
e d o i d t i u c r i c - t r o h S d r a u g e f a s y t i r a l o P
I I y r o g e t a c e g a t l o v r e v o C D
Output Levels
0 0 0 , 0 1 ] A V [ r e w o p d e t a R
0 0 0 , 0 1 ] A V [ r e w o p . x a M
) A S U ( 0 8 4 / 7 7 2 ] V [ L - L / N - L e g a t l o v d i r G
4 0 3 - 4 3 2 ] V [ N - L e g n a r g n i t a r e p o e g a t l o v d i r G
1 . 2 1 x 3 ] A [ t n e r r u c d e t a R
1 . 2 1 x 3 ] A [ t n e r r u c . x a M
) 3 . 1 6 . . . 9 . 8 5 ( 0 6 ] z H [ y c n e u q e r f d e t a R
9 9 . > ) i h p s o c ( d a o l l l u f t a r o t c a f r e w o P
3 s e s a h p n i - d e e f f o r e b m u N
5 . 5 ] % [ r o t c a f n o i t r o t s i D
I I I y r o g e t a c e g a t l o v r e v o C A
General electrical data
4 . 7 9 ] % [ y c n e i c
0 . 7 9 ] % [ y c n e i c
5 . 1 < ] W [ t h g i n : n o i t p m u s n o c l a n r e t n I
0 2 ] W [ t a s t r a t s n i - d e e F
s s e l r e m r o f s n a r T n g i s e d t i u c r i C
o N t i n u r e m r o f s n a r T
c
s e Y y t i m r o f n o c E C
Tabelle 1: Electrical Data
Techni cal Data
Page 12 Installation Instructions blueplanet XP10U-H4
4.2 Mechanical Data
XP10U-H4
Display
LCD graphical display, 3 LEDs
Controls
4-way key, 2 keys
Interfaces
Ethernet, USB, RS485, S0
Fault signal relay
Potential-free NO contact, 277 V/1A
Connections for AC PCB terminal
PCB terminals inside the unit (max. cross section: 7 AWG)
DC connections
PCB terminals inside the unit (max. cross section: 11 AWG)
Connection for Ethernet cable connection
RJ45 connector
Optional DC connection
-
Ambient temperature range [F]
-13 ... 140 (-25C ... 60 C)
Storage temperature range [F]
-22 ... 158 (-30C ... 70C)
Humidity range (non-condensing) [%]
0 ... 95
Maximum installation elevation [ft above sea level]
6,561
Temperature monitoring
Yes
Cooling
Fan cooling
Protection class
NEMA 4
Degree of contamination
2
DC disconnect
Built-in
Housing
Aluminum cast
H x W x D [in]
27.2 x 16.5 x 7.9 (690 x 420 x 200 mm)
Total weight [lbs]
88 (40 kg)
Tabelle 2: Mechanical Data
Transportati on and Del i very
Installation Instructions blueplanet XP10U-H4 Page 13
5 Transportation and Delivery
5.1 Delivery
Every inverter leaves our factory in proper electrical and mechanical condition. Special packaging ensures that they
are transported safely. The shipping company is responsible for any transport damage that occurs.
Scope of delivery
1 inverter
1 wall bracket
1 connection board
1 installation kit
1 documentation set
Checking your delivery
1. Thoroughly inspect your inverter.
2. Immediately notify the shipping company in case of the following:
Damage to the packaging that indicates that the inverter may have been damaged
Obvious damage to the inverter
3. Immediately send a damage report to the shipping company.
The damage report must be delivered to the shipping company in writing within six days following receipt of the
inverter. We will be glad to help you, if necessary.
5.2 Transportation
WARNING
Impact hazard, risk of breakage to the inverter
Securely pack the inverter for transport.
Carefully transport the inverter using the the carrying handles of the pallet.
Do not subject the inverter to shocks.
For safe transportation of the inverter, use the holding openings in the carton.
Mounti ng the I nverter
Page 14 Installation Instructions blueplanet XP10U-H4
Authorised electrician
6 Mounting the Inverter
DANGER
Risk of fatal injury from fre or explosions
Fire caused by fammable or explosive materials in the vicinity of the inverter can lead to serious
injuries.
Do not mount the inverter in an area at risk of explosion or in the vicinity of highly fammable
materials.
CAUTION
Risk of burns from hot housing components.
Coming into contact with the housing can cause burns.
Mount the inverter so that it cannot be touched unintentionally.
Installation space
As dry as possible, climate-controlled, with the waste heat dissipated away from the inverter
Unobstructed air circulation
When installing the unit in a control cabinet, provide forced ventilation so that the heat is suf ciently dissipated
Easily accessible from the front and sides
Protected from direct sunshine outdoors
For easy operation, ensure during installation that the display is slightly below eye level.
Wall
With suf cient load-bearing capacity
Accessible for installation and maintenance
Made from heat-resistant material (up to 194F/90C)
Flame resistant
Minimum clearance during installation: see Fig. 6 on page 15 and Fig. 7 on page 15.
CAUTION
Use suitable mounting fxtures.
Only use the supplied mounting fxtures.
Mount the inverter upright on a vertical wall only.
NOTICE
Power reduction due to heat accumulation.
If the recommended minimum clearances are not observed, the inverter can have power regulation
and a protective shutdown due to insuf cient ventilation and the associated heat
Maintain minimum clearances.
Provide for suf cient heat dissipation.
Mounti ng the I nverter
Installation Instructions blueplanet XP10U-H4 Page 15
Authorised electrician
54 3/5
16
10 59/260
22 1/4
44 1/10
13
Figure 3: Instructions for wall mounting Figure 4: Drill stencil for wall mounting with
minimum clearances (inches)
1
2
3
1
0
in
1
0
in
1
0
in
Clearance from ceiling 20 in
Clearance from another inverter 27 3/5 in
Clearance from the foor 20 in
Clearance from another inverter 27 3/5 in
4
5
Figure 5: Minimum clearances/mounting plate
Key
1 Fixings for mounting 4 Detachment protector
2 Mounting plate 5 Suspension brackets (back of housing)
3 Screws for mounting
Mounting the inverter
1. Mark the positions of the drill holes using the cut-outs in the mounting plate.
NOTICE: The minimum clearances between two inverters, or the inverter and the ceiling/foor have already
been taken into account in the drawing.
2. Fix mounting plate to the wall with the supplied mounting fxtures.
Make sure that the mounting plate is oriented correctly.
3. Hang the inverter on the mounting plate using the suspension brackets on the back of the housing.
4. Fix the inverter with the enclosed screws to the detachment protector at the connection area.
The mounting of the inverter is complete. Continue with the installation.
I nstal l i ng the I nverter
Page 16 Installation Instructions blueplanet XP10U-H4
Authorised electrician
7 Installing the Inverter
DANGER
Lethal voltages are still present in the terminals and leads of the inverter even after the
inverter has been switched of and disconnected.
Severe injuries or death if the leads and terminals in the inverter are touched.
Only authorised electricians who are approved by the supply grid operator may open and install the
inverter.
The inverter must be mounted in a fxed position before being connected electrically.
Observe all safety regulations and the currently applicable technical connection specifcations of
the responsible power supply company.
Disconnect the AC and DC sides.
Secure them against being inadvertently switched back on.
Assure that the AC and DC sides are completely voltage-free.
Connect the inverter only after the aforementioned steps have been taken.
NOTICE
Install the inverter in accordance with NEC, ANSI/NFPA 70.
7.1 Opening the connection area
Opening the connection area
You have mounted the inverter on the wall.
1. Unscrew the four Torx screws from the front side of the connection cover.
2. Pull down the connection cover.
Carry out the electrical connection.
7.2 Drilling holes for electrical and interface connection
The inverter is shipped with a connection board. You are required to drill holes into the board to accomodate the
AC, DC and interface connection leads.
In order to avoid interference between current-carrying leads and interface cables, adher to the following drawing:
3
2
1
4
Figure 6: Connection board
I nstal l i ng the I nverter
Installation Instructions blueplanet XP10U-H4 Page 17
Authorised electrician
Key
1 Connection area for DC leads 3 Connection area for AC leads
2 Connection area for interface and
grounding leads
4 USB port
7.3 Carrying out the electrical connection
Make the connection to the PV generator and the grid connection via the PCB terminals in the connection area of
the inverter. Maintain the following conductor cross-sections:
AC connection DC connection
Max. conductor cross-section without wire sleeves 6 AWG 8 AWG
Max. conductor cross-section with wire sleeves 7 AWG 11 AWG
Length of insulation to be stripped of 2/5 in 3/5 in
7.3.1 Connecting the inverter to the power grid
The grid connection leads are connected on the right side of the connection area (see fgure 7).
DANGER
Risk of fatal injury due to electric shock
Severe injuries or death will result if the live connections are touched.
Disconnect the inverter from all power sources before you insert the grid power lead into the unit.
CAUTION
Risk of fre
Insuf cient over current protection can increase the risk of fre.
Connect only to a circuit provided with a 64A branch circuit over current protection in accordance
with the national electrical code ANSI/NFPA 70.
Recommended conductor cross-sections and fuse protection of NYM leads for fxed wiring according to
VDE 0100 part 430
We recommend the following conductor cross-sections for cable lengths up to 60 ft:
AWG 4 up to AWG 10, 75 Copper Wire. Larger cross-sections schould be used for longer leads. 25A breaker.
This unit is provided with fxed trip limits and shall not be aggregated above 30kw on a single point of common
connection.
NOTICE
The installation shall indicate that wiring methods in accordance with the NEC, ANSI/NFPA 70 are to
be used.
NOTICE
Use copper conductors only.
I nstal l i ng the I nverter
Page 18 Installation Instructions blueplanet XP10U-H4
Authorised electrician
NOTICE
When the lead impedance is high (i.e. long grid-side leads), the voltage at the grid terminals of the
inverter will increase during feed-in to the grid. The inverter monitors this voltage. If it exceeds the
country-specifc line overvoltage limit value, the inverter switches of.
Ensure that the lead cross-sections are suf ciently large or that the lead lengths are suf ciently
short.
Making the grid connection
Drill a hole for the AC leads into the connection board.
1. Remove the outer cladding of the AC leads.
2. Insert the AC leads through the hole into the connection area through the conduit pipe.
3. Strip the insulation from the AC leads.
4. Open the locks of the PCB terminals.
5. Connect the leads in accordance with the labelling of the PCB terminals.
6. Close the locks of the PCB terminals.
7. Check that all connected leads are tightly seated.
The inverter is now connected to the power grid.
NOTICE
An AC-side disconnection unit must be provided in the fnal installation. This disconnection unit
must installed in such a manner that access to it is possible at any time without hindrance.
If a residual current circuit breaker is necessary due to the installation specifcation, then a type A AFI
(AC/DC-sensitive residual current circuit breaker) must be used.
7.3.2 Connecting the PV generator
Connect the PV generator to the 4 DC positive and the 4 DC negative connection terminals in the connection area
of the inverter.
DANGER
Risk of fatal injury due to contact voltages.
During installation: Electrically disconnect the DC positive and DC negative from the protective
earth (PE).
Removing the connection without previously disconnecting the inverter from the DC generator can
result in a hazard to health and damage to the inverter.
WARNING
No internal GFDI.
This unit is not provided with a GFDI (ground-fault detector-interrupter). The inverter must be used
with an external GFDI device as required by the article 690 of the national electrical code for the
installation location.
I nstal l i ng the I nverter
Installation Instructions blueplanet XP10U-H4 Page 19
Authorised electrician
MPP
tracker A
MPP
tracker B
Figure 7: Connection terminals for DC positive and DC negative leads
7.3.2.1 Before the connection
Ensure that there is no ground fault
1. Determine the DC voltage between the
Protective earth (PE) and the positive lead of the PV generator
Protective earth (PE) and the negative lead of the
PV generator
If stable voltages can be measured, there is a ground fault in the DC generator or its wiring. The ratio between the
measured voltages gives an indication as to the location of this fault.
2. Rectify any faults before taking further measurements.
3. Determine the electrical resistance between the
Protective earth (PE) and the positive lead of the PV generator
Protective earth (PE) and the negative lead of the PV generator
Low resistance (< 2 M) indicates a high-ohm ground fault of the DC generator.
4. Rectify any faults before connecting the DC generator.
7.3.2.2 Maximum input power
The input power of the inverter is limited only by the maximum input current of 18.6 A per input. This causes the
maximum input power per path to increase with the input voltage.
A detailed table with power values as a function of the DC voltage can be found in the appendix.
NOTICE
The overall power of the unit continues to be limited. If one input is connected to more than
P(DCmax)/2, the maximum input power of the second input decreases accordingly. Take care that
the maximum input power is not exceeded.
I nstal l i ng the I nverter
Page 20 Installation Instructions blueplanet XP10U-H4
Authorised electrician
7.3.2.3 Recommended standard connection
Equal MPP voltages must be applied to input 1 and 2, as well as inputs 3 and 4. The MPP voltages of the two DC
paths can be diferent. They are tracked by separate, independently operating MPP trackers (MPP trackers A and B).
(n
1
=n
2
, n
3
=n
4
).
Electrical data for standard connection
Connection of the DC inputs Number of modules per string n
1
=n
2
, n
3
=n
4
P
max
per string < 6 kW
MPP trackers A+B together < 12 kW
I
max
< 18.6 A per tracker
MPP tracker A MPP tracker B
U
M
P
P

=

3
5
0

-

8
0
0

V
n
1
n
2
n
3
n
4
= =
U
M
P
P

=

3
5
0

-

8
0
0

V
Figure 8: Recommended standard connection
7.3.2.4 Parallel input connection
The DC inputs can also be connected in parallel. Only strings with identical MPP voltage can be connected in
parallel (n
1
=n
2
=n
m
).
The maximum input current rises to 37.2 A for parallel connection.
In case of a parallel input connection, MPP trackers A and B must be bridged. If input 1 is connected to input 2 and
input 3 is connected to input 4, then there is no parallel operation and the maximum input current continues to be
18.6 A. Parallel operation is automatically recognized by the inverter.
I nstal l i ng the I nverter
Installation Instructions blueplanet XP10U-H4 Page 21
Authorised electrician
Electrical data for parallel connection
Connection of the DC inputs Number of modules per string n
1
=n=n
m
P
max
< 12kW
I
max
< 37.2 A
MPP tracker A MPP tracker B
U
M
P
P

=

3
5
0

-

8
0
0

V
...
n
1
n
2
n
m
= =
MPP tracker A MPP tracker B
U
M
P
P

=

3
5
0

-

8
0
0

V
...
n
1
n
2
n
m
= =
Figure 9: Parallel input connection in the
generator junction box
Figure 10: Parallel input connection with Y adapter,
short circuit of MPP tracker B
7.3.2.5 Unconnected inputs
NOTICE
If one of the MPP trackers (A or B) is not used it must be short-circuited. Otherwise, faults can occur
in the self-test of the unit and the feed-in operation is not guaranteed. This does not lead to damage
to the unit.
The recommended standard connection or the parallel input connection should be selected as
a matter of course before an MPP tracker is short-circuited and therefore remains unused.
I nstal l i ng the I nverter
Page 22 Installation Instructions blueplanet XP10U-H4
Authorised electrician
7.3.2.6 Connecting the PV generator
DANGER
Risk of fatal injury due to electric shock
Severe injuries or death will result if the live connections are touched. When there is irradiance, DC
voltage is present on the open ends of the DC leads.
Do not touch the open ends of the leads.
Avoid short circuits.
Connecting the PV generator
Drill one hole for each DC negative and DC positive lead into the connection board.
1. Remove the outer cladding of the DC leads.
2. Insert the DC leads into the connection area through the conduit pipes.
3. Strip the insulation from the DC leads.
4. Connect the leads to the PCB terminals in accordance with the labelling.
The inverter is connected to the PV generator.
7.3.3 Grounding the housing
An optional grounding of the housing is possible at the grounding point provided for that purpose in the connec-
tion area of the inverter. Please observe any national installation regulations in this regard.
Ground the housing of the inverter, if necessary, at the grounding point provided for that purpose in the connection
area of the inverter. It is marked with the symbol.
Figure 11: Grounding point in the connection area
Grounding the housing
Drill a hole for the grounding lead into the connection board.
1. Remove the outer cladding from the grounding lead.
2. Insert the grounding lead into the connection area through the conduit pipe.
3. Remove the insulation from the grounding lead.
4. Furnish the stripped lead with an M6 ring cable lug.
5. Screw the ring cable lug to the grounding point with an M6 screw.
6. Check for frm seating of the lead.
7.4 Connecting the interfaces
All interface connectors are located on the connection board. Drill holes for the conduits into the connection
board.
I nstal l i ng the I nverter
Installation Instructions blueplanet XP10U-H4 Page 23
Authorised electrician
DANGER
Risk of fatal injury due to electric shock
Severe injury or death from improper use of the interface connections and non-observance of
protection class III.
The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with
protection class III.
NOTICE
When laying the interface connection cables, note that too little clearance to the DC or AC leads can
cause interference during data transfer.
RS485 S0 ERR
B A B A + - + -
Ethernet
RCL
Figure 12: Connection area: Connection and pinout of the interfaces
7.4.1 Connecting the RS485 bus
blueplanet
Inverters
Terminal unit
blueplanet
Inverters
blueplanet
Inverters
Kaco
proLOG
Communication
230 VAC
Figure 13: RS485 interface wiring diagram
I nstal l i ng the I nverter
Page 24 Installation Instructions blueplanet XP10U-H4
Authorised electrician
NOTICE
Diferent manufacturers interpret the standard on which the RS485 protocol is based in diferent
ways. Note that the wire designations (- and +) for wires A and B can be diferent depending on the
manufacturer.
NOTICE
Calculating ef ciency by measuring the current and voltage values leads to unusable results due to
the tolerances of the measurement devices. The sole purpose of these measured values is to monitor
the basic operation of the system.
Connecting the RS485 bus
Maximum length of the RS485 wiring: 1,200 m under optimal conditions.
Maximum number of connected bus devices: 31 inverters + 1 data monitoring unit.
Use twisted, shielded data lines.
Recommendation (using wire sleeves)
LI2YCYv (TP) black for laying cable outside and in the ground 2 x 2 x 0.5
LI2YCY (TP) grey for dry and moist spaces 2 x 2 x 0.5
Drill a hole for the RS485 connection cable into the connection board.
1. Thread the connection cable through the hole.
2. Connect the connection cable to the connection terminals provided (see fgure 16 on page 23).
3. Connect the following to all inverters and Kaco-proLOG as follows:
Wire A (-) with wire A (-) and
Wire B (+) with wire B (+) (see fgure 17 on page 23)
4. Activate the terminating resistor on the terminal unit.
7.4.2 Connecting the remote control line for the power supply company
This connection can be used in the future by your power supply company as an optional remote control line. When
connecting, please observe the polarity (see fgure 16 on page 23).
Maximum contact load: 10-24 VDC, 10 mA.
7.4.3 Connecting the S0 output
An S0 pulse output is located on the communication board. Use this output to control accessories such as a large
display, for example. The pulse rate of the output is adjustable.
Connecting the S0 output
Drill a hole for the S0 connection cable into the connection board.
1. Thread the connection cable through the hole.
2. Connect the connection cable to the connection terminals.
7.4.4 Connecting the Ethernet interface
NOTICE
Use a suitable category 5 network cable. The maximum length of a network segment is 100 m.
Ensure that the cable is correctly assigned. The Ethernet connection of the inverter supports auto-
sensing. You can use both crossed and 1:1 Ethernet connection cables.
I nstal l i ng the I nverter
Installation Instructions blueplanet XP10U-H4 Page 25
Authorised electrician
Connecting an Ethernet cable to the inverter
Drill a hole for the Ethernet connection cable into the connection board.
1. Thread the connection cable through the hole.
2. Connect the connection cable to the Ethernet interface (see fgure 16 on page 23).
Connecting the inverter with the network
Connect the Ethernet cable to the inverter.
Confgure the Ethernet interface in the confguration menu.
Connect the Ethernet cable to the network or a computer.
Confgure the Ethernet settings and web server in the Settings menu.
7.4.5 Connecting the fault signal relay
The contact is designed as am N/O contact. Maximum contact load: DC 30 V/1 A,AC: 277 V/1 A
Connecting the fault signal relay
Drill a hole for the fault signal relay connection cable into the connection board.
1. Thread the connection cable through the hole.
2. Connect the connection cable to the connection terminals.
7.5 Sealing the connection area
1. Screw the connection board to the inverter with the fve Torx screws.
2. Place the connection cover on the connection area of the inverter.
3. Screw in the four Torx screws on the front side of the connection cover.
7.6 Starting up the inverter
DANGER
Lethal voltages are still present in the terminals and leads of the inverter even after the
inverter has been switched of and disconnected.
Severe injuries or death if the leads and terminals in the inverter are touched.
Only authorised electricians who are approved by the supply grid operator may start up the inverter.
7.6.1 Switching on the inverter
The inverter has been mounted and electrically installed.
The cover for the connection area is grounded and closed.
The PV generator is supplying a voltage > 250V.
1. Connect the grid voltage using the external circuit breakers.
2. Connect the PV generator using the DC disconnector (0 1).
The inverter begins to operate.
During the initial start-up: Follow the instructions on the inverter display.
Conf i gurati on and Operati on
Page 26 Installation Instructions blueplanet XP10U-H4
8 Confguration and Operation
8.1 Controls
The inverter has a backlit LCD as well as three status LEDs. The inverter is operated using six keys.
1
2
3
4
5
6
7
Figure 18: Control panel
Key
1 Operating LED 5 4-way key
2 Feed-in LED 6 Enter key
3 Fault LED 7 ESC key
4 LCD
8.1.1 LED indicators
The three LEDs on the front of the inverter show the diferent operating states.
The LEDs can take on the following states:
LED illuminated LED fashing LED not illuminated
The LED indicators show the following operating states:
Operating state LEDs Display Description
Start The green Operating LED is illuminated
if an AC voltage is present,
independently of the DC voltage.
Feed-in start Power fed into the grid
or measured values
The green Operating LED is illuminated.
The green Feed-in LED is illuminated
after the country-specifc waiting period*.
The inverter is ready to feed in, i.e. is on
the grid.
You can hear the line relay switch on.
* The waiting period ensures that the generator voltage continuously remains above the power delivery limit of
250V.
For the country-specifc waiting times, see section 4.3 on page 16.
Conf i gurati on and Operati on
Installation Instructions blueplanet XP10U-H4 Page 27
Operating state LEDs Display Description
Feed-in operation Power fed into the grid
or measured values
The green Operating LED is illuminated.
The green Feed-in LED is illuminated.
The Feed-in icon appears on the
desktop.
The inverter feeds into the grid.
Non-feed-in
operation
Status message The display shows the corresponding
message.
Voltage Fault message The display shows the corresponding
message.
The red Fault LED is illuminated.
8.1.2 Graphical display
The graphical display shows measured values and data and allows the confguration of the inverter using a graphi-
cal menu. In normal operation, the backlighting is switched of. As soon as you press one of the control keys, the
backlight is activated. If no key is pressed for an adjustable period of time, it switches of again. You can also perma-
nently activate or deactivate the backlighting. In sleep mode, the inverter deactivates the display regardless of the
selected setting.
NOTICE
Depending on the tolerances of the measuring elements, the measured and displayed values
are not always the actual values. However, the measuring elements ensure maximum solar yield.
Due to these tolerances, the daily yields shown on the display may deviate from the values on the
grid operators feed-in meter by up to 15%.
After being switched on and after the initial start-up is complete, the inverter displays the start screen (the desktop).
If you are in the menu and do not touch the control keys for two minutes, the inverter returns to the desktop.
For information about initial start-up, see section 8.2 on page 29.

1
2
3
4
5
6
7
8
Figure 19: Desktop
Key
1 Current date 6 Status bar
2 Current power 7 Current time
3 Menu indicator 8 Feed-in indicator
4 Daily yield
5 Annual yield
Conf i gurati on and Operati on
Page 28 Installation Instructions blueplanet XP10U-H4
8.1.3 Control keys
You operate the inverter using the 4-way key and the OK and ESC control keys.
8.1.3.1 Desktop
Opening the menu
The inverter is operating.
The LCD is showing the desktop.
Press the right arrow key.
The menu opens up over the desktop from left to right.
Displaying the daily output
The inverter is operating.
The LCD is showing the desktop.
Press the down arrow key.
The LCD displays the daily yield in a diagram.
To return to the desktop, press any key.
8.1.3.2 Inverter menu
Selecting a menu item
You have left the desktop. The inverter displays the menu.
Use the up and down arrow keys.
Opening a menu item or a setting
Use the right arrow key and the OK key.
Jump to the next higher menu level/discard changes
Press the left arrow key or the ESC key.
Selecting an option
Use the right and left arrow keys.
Changing an option/the value of an input feld
Use the keys with the up and down arrows.
Saving changed settings
Press the OK key.
Conf i gurati on and Operati on
Installation Instructions blueplanet XP10U-H4 Page 29
8.2 Initial start-up
When started for the frst time, the inverter displays the confguration assistant. It takes you through the settings
necessary for the initial start-up.
NOTICE
After successful completion of the confguration, the confguration assistant does not appear again
when the inverter is restarted. You can then change the country setting only in the password-pro-
tected parameter menu. The other settings can still be changed in the confguration menu.
NOTICE
The sequence of the settings required for initial start-up is preset in the confguration assistant.
Initial confguration
In order to select a setting, press the up and down keys.
To select the next menu item, press the OK key.
To return to the most recently selected menu item, press the ESC key.
Carry out the required settings.
Press the OK key in the last menu item.
You have completed the initial confguration. The inverter begins to operate.
8.3 Menu structure
8.3.1 Display on the LCD
1
3
4
2
Figure 20: Main menu
Key
1 Display of the menu level (0, 1, 2, 3) 3 Active menu (example: main menu)
2 Designation of the active menu 4 Menu items of the next lower menu level
Settings
Information
Vendor
Main menu
Measurements Generator
Grid
Power control
Unit temperature
Yield counter
Yield today
Total yield
Conf i gurati on and Operati on
Page 30 Installation Instructions blueplanet XP10U-H4
8.3.2 Menu structure
Icons used:
0 1 2 3
Menu level (0, 1, 2, 3) Password-protected menu
Display menu Submenu available
Option menu

Menu
level
Display/settings Action in this menu/meaning
Desktop Desktop Press the right arrow key.
0 1 2 3 0
Measurements menu Open the menu: Press the right arrow key or the OK key.
0 1 2 3 1
Generator Displays the DC-side voltage, amperage and power.
0 1 2 3 1
Grid Displays the AC-side voltage, amperage and power.
0 1 2 3 1
Unit temperature Displays the temperature in the inverter housing.
0 1 2 3 1
Yield counter
Displays the yield in kWh.
Reset the counter using the Reset key.
0 1 2 3 1
Yield today Displays the yield of the current day up to now.
0 1 2 3 1
Total yield Displays the total yield up to now.
0 1 2 3 1
CO2 savings Displays the calculated CO
2
savings (in kg).
0 1 2 3 1
Oper. hours counter
Displays the duration of operation in hours.
Reset the counter using the Reset key.
0 1 2 3 1
Oper. time today Displays the duration of operation on the current day.
0 1 2 3 1
Total op. time Displays the total operating time.
0 1 2 3 1
Log data view
Open the menu: Press the right arrow key or
the OK key.
0 1 2 3 2
Daily view
Displays the recorded operating data graphically.
1. Select the measured value to be displayed.
Supported measured values:
Grid power P(grid)
DC power per string P(PV) 1-2
DC voltage per string U(PV) 1-2
Unit temperature
2. Select a date.
3. Press the OK key.
The display shows the selected data.
Press any key to return to the previous menu.
Conf i gurati on and Operati on
Installation Instructions blueplanet XP10U-H4 Page 31
Menu
level
Display/settings Action in this menu/meaning
0 1 2 3 2
Monthly view
Displays the recorded operating data graphically.
1. Select a date.
2. Press the OK key.
The display shows the selected data.
Press any key to return to the previous menu.
0 1 2 3 2
Yealy view
Displays the recorded operating data graphically.
1. Select a date.
2. Press the OK key.
The display shows the selected data.
Press any key to return to the previous menu.
0 1 2 3 2
Save to USB
In this menu, you can export the saved operating data to a
connected USB storage device.
You have connected a USB storage device to the inverter.
1. Select the data to be exported (year, month or day) with the
4-way key.
2. Press the OK key.
The inverter writes the data to the USB storage device.
0 1 2 3 0
Settings menu
Open the menu: Press the right arrow key or
the OK key.
0 1 2 3 1
Language Select the desired language for the user interface.
0 1 2 3 1
Defne total yield
You set the total yield to a freely selectable value, for example,
when you have received a replacement unit and want to continue
the recording from the present value.
Select the Save button and confrm with the
OK button.
0 1 2 3 1
Interface
If the inverter is a terminal unit: Activate termination (Bus
termination menu item)
Assign a unique RS485 bus address to the inverter
(proLOG address menu item). The address must not coincide
with that of another inverter or a proLOG unit.
0 1 2 3 1
S0 pulse rate Set the pulse rate of the S0 connection.
0 1 2 3 1
Logging interval Set the time between two log data recordings.
0 1 2 3 1
Log data backup
The inverter supports the backing up of all recorded yield data to a
connected USB storage device.
Activate or deactivate log data backup.
0 1 2 3 1
Display
Confgure the contrast setting for the display.
Set the length of time without user input after which the
backlighting of the LCD switches of.
Alternatively: Permanently activate or deactivate backlighting
by selecting On or Of.
0 1 2 3 1
Date & time
Set the time and date.
NOTICE: For self-diagnostic purposes, the inverter carries out a
daily restart at midnight. To avoid having a restart occur during
feed-in operation and to always obtain reliable log data, ensure
that the time is correctly set.
Conf i gurati on and Operati on
Page 32 Installation Instructions blueplanet XP10U-H4
Menu
level
Display/settings Action in this menu/meaning
0 1 2 3 1
Ethernet
Assign a unique IP address.
Assign a subnet mask.
Assign a gateway.
0 1 2 3 1
Webserver Activate or deactivate the integrated webserver.
0 1 2 3 0
Parameters menu
Press the right arrow key or the OK key.
NOTICE: The inverter does not display the Parameters menu in
the standard confguration. To display the menu:
1. Open the menu.
2. Simultaneously hold down the up and down keys for several
seconds.
0 1 2 3 1
Country
1. Input the four-character password via the 4-way key. The
password is unit-specifc.
2. Confrm the entry with the OK key.
3. Set the desired country setting.
NOTICE: This option infuences the country-specifc operating
settings of the inverter. Please consult KACO service for further
information.
0 1 2 3 1
Grid type/
guideline
If available, select the type of grid applicable to the use of the
inverter.
0 1 2 3 1
DC starting volt.
The inverter begins feed-in as soon as this PV voltage is present.
Set the starting voltage.
0 1 2 3 1
Const. volt. ctrl
Ofers the possibility of deactivating the MPP seek mode in order
to operate the inverter with a constant DC voltage.
Activate or deactivate MPP seek mode.
Set value for constant voltage control (200 - 800 V).
NOTICE: The possible input power is reduced at voltages lower
than 350voltage. The input current is limited to 18.6 A per input.
0 1 2 3 0
Information menu
Open the menu: Press the right arrow key or
the OK key.
0 1 2 3 1
Inverter type Displays the type designation of the inverter.
0 1 2 3 1
SW version Displays the installed software version.
0 1 2 3 1
Serial number Displays the serial number of the inverter.
0 1 2 3 1
Display country
Displays the selected country setting.
Optional: Displays the grid type if a grid type has been selected.
0 1 2 3 0
Vendor menu The display shows information about the unit manufacturer.
Conf i gurati on and Operati on
Installation Instructions blueplanet XP10U-H4 Page 33
8.4 Monitoring the inverter
The inverter has an integrated web server. This makes it possible to monitor and record the operating state and
yield of your PV system.
You can display the recorded data via:
The integrated LCD
The integrated web server using an Internet-capable device connected to the Ethernet interface of the inverter
You can read the recorded data using a storage medium connected to the USB interface of the inverter, e.g. a USB
stick.
8.4.1 USB interface
Use an external USB storage device to read operating data saved in the inverter.
8.4.1.1 Reading log data
NOTICE
The USB interface is approved solely for usage with USB fash memories (USB sticks). The maximum
available current is 100 mA. If a device with a higher power requirement is used, the power supply for
the USB interface automatically shuts down to protect the inverter from damage.
Reading log data
1. Connect a suitable USB storage device to the USB interface on the underside of the inverter.
2. Open the Log data view menu.
3. Select the Save to USB item.
4. Select the desired log data using the 4-way key.
5. Press the OK key.
The inverter saves the selected log data to the USB storage device.
8.4.2 Web server
The inverter has an integrated web server. After confguration of the network and activation of the web server in
the confguration menu, you can open the web server from an Internet browser. The language version of the web
site delivered by the browser is dynamically adapted, based on the pre-set language preferences in your Internet
browser. If your Internet browser requests a language that is unknown to the inverter, the web server uses the menu
language set in the inverter.
8.4.2.1 Setting up the web server
Confguring the Ethernet interface
You have connected the inverter to your network.
1. Open the Settings/Ethernet menu.
2. Assign a unique IP address.
3. Assign a subnet mask.
4. Assign a gateway.
5. Save your settings.
Conf i gurati on and Operati on
Page 34 Installation Instructions blueplanet XP10U-H4
8.4.2.2 Using the web server
To avoid problems with incompatibility, use the most recent version of your Internet browser.
NOTICE
You can also access the web server of the inverter via the Internet. To do this, additional settings of
your network confguration, particularly your Internet router, are required.
Note that communication with the inverter is carried out over an unsecured connection, particularly
in the case of a connection over the Internet.
Calling up the web server
Confgure the Ethernet interface.
Connect the Ethernet interface.
1. Open an Internet browser.
2. In the address feld of the Internet browser, enter the IP address of the inverter and call up the site.
The Internet browser displays the start screen of the web server.
After it has been called up, the web server displays information about the inverter as well as the current yield data.
The web server supports the display of the following measurement data and yield data:
Feed-in power Generator power
Status Generator voltage
Grid power Unit temperature
Grid voltage
In order to display and export yield data, proceed as follows:
Select the display period
1. Call up the web server.
2. Select the display period by choosing one of the keys: day view, month view, year view or overall view.
Filtering display data (day view only)
1. Call up the web server.
2. Select the day view.
3. To show or hide measured values, select or deselect the corresponding checkboxes in the Select display
area.
Exporting data
1. Filter the display data if necessary.
2. Select the display period if applicable (day, month, year or overall view).
3. Click the Export data key.
4. Save the fle.
NOTICE
Regardless of the display data selected in the Select display area, an export fle always contains all
measurement data and yield data available for the selected period.
Conf i gurati on and Operati on
Installation Instructions blueplanet XP10U-H4 Page 35
8.5 Performing a software update
You can update the software of the inverter to a new version via the integrated USB interface. Us a FAT32-formatted
USB stick to do this. Do not use any storage media, such as an external hard disk, with an external power supply.
NOTICE
Ensure that the power supply of the AC and DC sides is active. It is only possible to update all
components of the inverter to the most current software version in this operating state.
CAUTION
Damage to the inverter
The update can fail if the power supply is interrupted during the update process.
Parts of the software or of the inverter itself can then be damaged.
Do not interrupt the DC and AC power supply during the update process.
Preparing for the software update
1. Download the software update fle from the KACO web site and store it on your hard disk.
2. Extract the update fle (.ZIP) completely onto the USB stick.
Perform software update.
Perform software update.
Prepare for the software update.
Ensure supply of DC and AC power.
1. Connect USB stick to the inverter.
The message Confguration found. Would you like to load it? appears on the display.
2. If you would like to perform the update, select the Yes button.
The inverter begins the update.
The update can take several minutes. The Operating LED fashes during the update process. The inverter may
restart several times. The update is completely loaded when the display screen shows the desktop.
The inverter then returns to feed-in mode. You can check the success of the update in the menu:
Display software version
Open the Information/SW version menu
The inverter will display the versions and checksums of the currently loaded software.
Mai ntenance/Troubl eshooti ng
Page 36 Installation Instructions blueplanet XP10U-H4
9 Maintenance/Troubleshooting
9.1 Visual inspection
Inspect the inverter and the leads for visible damage and pay attention to the operating status display of the
inverter. In case of damage, notify your installer. Repairs may only be carried out by authorised electricians.
NOTICE
Have your installer check for proper operation of the inverter at regular intervals.
9.2 Cleaning the inverter externally
DANGER
Lethal voltages in the inverter
Serious injuries or death if moisture enters the inverter.
Only use objects that are free of moisture to clean the inverter.
The inverter should only be cleaned on the outside.
Cleaning the inverter
Do not use compressed air.
Use a vacuum cleaner or a soft brush to remove dust from the fan cover and from the top side of the inverter
on a regular basis.
Remove dust from the ventilation inlets if necessary.
9.3 Shutting down for maintenance and troubleshooting
DANGER
Lethal voltages are still present in the terminals and leads of the inverter even after the
inverter has been switched of and disconnected.
Severe injuries or death if the leads and terminals in the inverter are touched.
When there is irradiance, DC voltage is present on the open ends of the DC leads. Arcing may occur if
the DC leads are disconnected while under a load.
Only authorised electricians who are approved by the supply grid operator may open and maintain
the inverter.
Observe all safety regulations and the currently applicable technical connection specifcations of
the responsible power supply company.
Disconnect the AC and DC sides.
Secure the AC and DC sides from being switched on again.
Do not touch the open ends of the leads.
Avoid short circuits.
Open the inverter only after these two steps are complete.
After shutdown, wait at least 30 minutes before working on the inverter.
Authorised electrician
Mai ntenance/Troubl eshooti ng
Installation Instructions blueplanet XP10U-H4 Page 37
CAUTION
Destruction of the DC connection
The connection terminals can be destroyed by arcing if disconnected under load.
It is absolutely necessary that the shutdown sequence be carried out in the correct order.
Shutting down the inverter
1. Switch of the grid voltage by deactivating the external circuit breakers.
2. Disconnect the PV generator using the DC disconnect.
DANGER! The DC leads remain live.
Ensure that there is no voltage present on the grid connection terminals.
9.4 Faults
9.4.1 Procedure
DANGER
Lethal voltages are still present in the terminals and leads of the inverter even after the
inverter has been switched of and disconnected.
Severe injuries or death if the leads and terminals in the inverter are touched.
When a fault occurs, notify an authorised electrician approved by the supply grid operator or
KACO new energy, Inc. Service.
The operator can only carry out actions marked with a B.
In case of power failure, wait for the system to automatically restart.
Notify your electrician if there is an extended power failure.
9.4.2 Rectifying faults
Fault Cause of fault Explanation/remedy By
The display is
blank and the
LEDs do not
light up.
Line voltage not
available
Check whether the DC and AC voltages are within the
permitted limits (see Technical Data).
E
Notify KACO Service.
E
Tabelle 5: Troubleshooting
O = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must only be carried out by a service employee of KACO new energy, Inc.
Mai ntenance/Troubl eshooti ng
Page 38 Installation Instructions blueplanet XP10U-H4
Fault Cause of fault Explanation/remedy By
The inverter
stops feeding
into the grid
shortly after
being switched
on, even though
there is irradi-
ance.
Faulty grid
separation relay
in the inverter.
If the grid separation relay is defective, the inverter will
recognize this during the self-test.
Ensure that there is suf cient PV generator power.
E
If the grid separation relay is defective have it replaced
by KACO Service.
Notify KACO Service.
K
The inverter is
active but does
not feed into the
grid. The display
indicates a line
failure.
Grid-feed is
interrupted due
to a grid fault.
Due to a grid fault (grid impedance too high, over/undervolt-
age, over/underfrequency), the inverter stopped the grid-feed
and disconnected from the grid for safety reasons.
Change the line parameters within the permitted operat-
ing limits (see the Start-Up section).
E
The line
fuse trips.
The line fuse
capacity is
too low.
In cases of high irradiance, the inverter exceeds its rated
current for a short period, depending on the PV generator.
Select the capacity of the inverters pre-fuse to be
somewhat higher than the maximum feed-in current
(see the Installation section).
E
Contact the grid operator if the grid failure constantly
occurs.
E
Damage to
the inverters
hardware.
If the line fuse immediately trips when the inverter goes into
feed-in mode (after the start-up period is complete), the invert-
ers hardware is probably damaged.
Contact KACO Service to test the hardware. E
The inverter
displays an
impossible daily
peak value.
Faults in the grid. The inverter continues to operate as normal without losses
to the yield, even when an erroneous daily peak value is
displayed. The value is reset overnight.
To immediately reset the value, switch the inverter of and
on again by disconnecting it from the grid and switching
of the DC.
E
Daily yields do
not correspond to
the yields on the
feed-in meter.
Tolerances of
the measuring
elements in
the inverter.
The measuring elements of the inverter have been selected
to ensure maximum yields. Due to tolerances, the daily yields
shown may deviate from the values on the feed-in meter by
up to 15%.
No action. -
Tabelle 5: Troubleshooting
O = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must only be carried out by a service employee of KACO new energy, Inc.
Mai ntenance/Troubl eshooti ng
Installation Instructions blueplanet XP10U-H4 Page 39
Fault Cause of fault Explanation/remedy By
The inverter is
active but does
not feed into the
grid. Display:
Waiting for
feed-in
Generator
voltage too low
Grid voltage
or PV generator
voltage
unstable.
The PV generator voltage or power is not suf cient for
feed-in (solar irradiance is too low).
The inverter checks the line parameters before the feed-in
process begins. The length of the switch-on time difers by
country according to applicable standards and regulations
and can take several minutes.
The starting voltage may have been set incorrectly.
Adjust starting voltage in the Parameter menu if required.
E
Noise emission
from the inverter.
Particular ambient
conditions.
When there are certain ambient conditions, the units may emit
audible noises.
Line interference or grid failure caused by particular loads
(motors, machines, etc.) which are either connected to the
same point on the grid or located in the vicinity of the
inverter.
In cases of volatile weather conditions (frequent switching
between sunny and cloudy conditions) or strong irradiance,
a light hum may be audible due to the increased power.
Under particular grid conditions, resonances may form
between the units input flter and the grid, which may be
audible even when the inverter is switched of.
These noise emissions do not afect the operation of the
inverter. They do not lead to loss of ef ciency, failure, damage
or to a shortening of the units service life.
People with very sensitive hearing (particularly children) are
able to hear the high-frequency hum caused by the inverters
operating frequency of approximately 17 kHz.
No action.
In spite of high
irradiance, the
inverter does
not feed in the
maximum power
into the grid.
The device is too
hot and the power
is reduced.
Because the temperatures inside the unit are too high, the
inverter reduces its power to prevent damage to the unit. Note
the technical data. Ensure unhindered convection cooling from
the exterior. Do not cover the cooling fns.
Provide for suf cient cooling of the unit.
Do not cover the cooling fns.
O, E
Tabelle 5: Troubleshooting
O = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must only be carried out by a service employee of KACO new energy, Inc.
Mai ntenance/Troubl eshooti ng
Page 40 Installation Instructions blueplanet XP10U-H4
9.5 Messages on the display and the Fault LED
Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The minimum triggering
levels are determined by standards. The inverter must switch of if the permitted values are undershot or exceeded.
9.5.1 Display of status and fault messages
Display Fault LED (red)
FS (fault status) ON
Fault signal relay has switched.
Feed-in was ended due to a fault.
OS (operating status) OFF
The fault signal relay deenergizes again.
The inverter feeds back into the grid again
after a country-specifc time period.
On the display you can fnd details regarding the fault or operating status or the data that was recorded through the
RS485 interface.

9.5.2 Status and fault signals
The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs.
Status Display Explanation Action By
OS 1 Waiting for feed-in Self test: Grid parameters and genera-
tor voltage are being checked.
- -
OS 2 Generator voltage
too low
Generator voltage and power are too
low; situation before transition into
night shutdown
- -
OS 7 Self-test Checks the shutdown of the power
electronics as well as the line relay
before feed-in mode. The self-test
consists of three successive individual
tests with the status 7, 75 and 8.
- -
OS 75 Self-test
OS 8 Self-test
FS 10 Temperature in
unit too high
In case of overheating, the inverter
switches of. Possible causes:
Ambient temperature too high
Fans covered
Inverter defect
Cool of the vicinity
of the inverter.
Uncover the fans.
Notify your autho-
rised electrician.
O
O
E
OS 11 Measured values Power limitation: If the generator
power is too high, the inverter limits
itself to the maximum power (e.g. in
the midday hours if the generator has
been too largely dimensioned).
- -
Tabelle 6: Operating states and fault messages on the display
OS = operating status, FS = fault status;
O = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must only be carried out by a service employee of KACO new energy, Inc.
Mai ntenance/Troubl eshooti ng
Installation Instructions blueplanet XP10U-H4 Page 41
Status Display Explanation Action By
FS 18 Resid. current
shutdown
Residual current was detected.
The feed-in was interrupted.
Notify your autho-
rised electrician.
E
FS 19 Generator
insulation fault
There is an insulation fault on the PV
generator. The feed-in was inter-
rupted.
Notify your electri-
cian if the fault
occurs several times.
E
FS 30 Voltage
trans. fault
The current and voltage measure-
ments in the inverter are not plausible.
- -
FS 32 Fault
Self-test
The internal grid separation relay test
has failed.
Notify your autho-
rised electrician if
the fault occurs
several times.
E
FS 33 Fault
DC feed in
The DC feed-in has exceeded the
permitted value. This DC feed-in can
be adopted from the grid onto the
inverter so that no fault occurs.
Notify your autho-
rised electrician if
the fault occurs
several times.
E
FS 34 Internal communi-
cation error
A communication error has occurred
in the internal data transmission.
Notify your autho-
rised electrician.
E
Check the data
cable.
FS 35 Protect.
shutdown SW
Protection shutdown of the software
(AC overvoltage, AC overcurrent,
DC link overvoltage, DC overvoltage,
DC overtemperature).
Not a fault. Grid-related
shutdown, the grid
connects again auto-
matically.
-
FS 36 Protect.
shutdown HW
Protection shutdown of the hardware
(AC overvoltage, AC overcurrent,
DC link overvoltage).
Not a fault.
Grid-related shutdown,
the grid connects again
automatically.
-
FS 38 Generator over-
voltage error
The voltage of the DC generator is too
high. The PV generator is incorrectly
dimensioned.
Notify your autho-
rised electrician.
E
FS 41 Line failure:
undervolt. L1
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
Notify your autho-
rised electrician.
E
FS 42 Line failure:
overvolt. L1
The voltage of a grid phase is too high,
the grid cannot be fed into.
The phase experiencing failure is
displayed.
Notify your autho-
rised electrician.
E
FS 43 Line failure:
undervolt. L2
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
Notify your autho-
rised electrician.
E
FS 44 Line failure:
overvolt. L2
The voltage of a grid phase is too high,
the grid cannot be fed into.
The phase experiencing failure is
displayed.
Notify your autho-
rised electrician.
E
Tabelle 6: Operating states and fault messages on the display
OS = operating status, FS = fault status;
O = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must only be carried out by a service employee of KACO new energy, Inc.
Mai ntenance/Troubl eshooti ng
Page 42 Installation Instructions blueplanet XP10U-H4
Status Display Explanation Action By
FS 45 Line failure:
undervolt. L3
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
Notify your autho-
rised electrician.
E
FS 46 Line failure:
overvolt. L3
The voltage of a grid phase is too high,
the grid cannot be fed into.
The phase experiencing failure is
displayed.
Notify your autho-
rised electrician.
E
FS 47 Line failure:
line-to-line volt
The measured line-to-line voltage is
outside of the tolerance limits.
FS 48 Line failure:
Underfrequency
Grid frequency is too low.
This fault can be grid-related.
Notify your autho-
rised electrician.
E
FS 49 Line failure:
Overfrequency
Grid frequency too high.
This fault can be grid-related.
Notify your autho-
rised electrician.
E
FS 50 Line failure:
average voltage
The grid voltage measurement
according to EN 50160 has exceeded
the maximum permitted limit
value.
Notify your autho-
rised electrician.
E
FS 57 Waiting for
reactivation
Waiting time of the inverter after a
fault.
Inverter does not switch
on again until a country-
specifc time has
elapsed.
FS 58 Control board
overtemp.
The temperature inside the unit was
too high. The inverter switches of to
prevent damage to the hardware.
Provide for suf cient
ventilation.
E
FS 59 Self test error A fault occurred during a self test. Notify your autho-
rised electrician.
E
OS 60 Generator voltage
too high
The inverter does not begin feeding
into the grid until the PV voltage falls
below a specifed value.
- -
OS 61 External limit (%) The external limit Power control was
activated by the grid operator.
The inverter limits its power.
- -
OS 63 Measured values P(f)/frequency-dependent power
reduction: Frequency-dependent
power reduction is activated with
the activation of the BDEW Medium
Voltage Directive (Mittelspannungs-
richtlinie). Power reduction starts
at a frequency of 50.2Hz.
- -
OS 64 Measured values Output current limiting: The AC
current is limited once the specifed
maximum value has been reached.
- -
FS 67 Fault power
section 1
There is a fault in the power section. Notify your autho-
rised electrician.
E
Tabelle 6: Operating states and fault messages on the display
OS = operating status, FS = fault status;
O = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must only be carried out by a service employee of KACO new energy, Inc.
Mai ntenance/Troubl eshooti ng
Installation Instructions blueplanet XP10U-H4 Page 43
Status Display Explanation Action By
FS 70 Fan error Fan 1 is malfunctioning. Replace defective
fan
E
FS 73 Standalone
grid err.
Standalone mode was detected. -
-
OS 74 External
idle power
requirement
The grid operator limits the feed-in
power of the inverter.
-
-
Tabelle 6: Operating states and fault messages on the display
OS = operating status, FS = fault status;
O = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must only be carried out by a service employee of KACO new energy, Inc.
Mai ntenance/Troubl eshooti ng
Page 44 Installation Instructions blueplanet XP10U-H4
9.6 Replacing or cleaning the fan
The inverter is equipped with 1 axial fan. It is located in the upper right area of the housing.
Replace the fan:
In case of heavy soiling
If it is defective
Removing the fan
1. Ensure complete disconnection on the AC and DC
sides.
2. Wait until the fan is no longer turning.
3. Unscrew the Torx crews of the side housing cover
(Figure 15 on page 44).
4. Remove the side housing cover.
5. Unplug the fan plug.
6. Remove the side housing cover with the fan from the
housing.
7. Remove the fan from the side housing cover by pull-
ing it away from the cover.
Install the replacement fan.
Figure 15: Removing the side housing cover
Installing the fan
You have removed the defective fan.
Replace the fan only with a fan recommended by
KACO. Ask KACO Service if necessary.
1. Insert the replacement fan into the fan holding
fxture (see Figure 16 on page 44).
2. Plug in the fan plug.
3. Place the side housing cover on the unit.
4. Fasten the side housing cover to the unit with the
Torx screws.
5. Check that the fttings are secure and that the termi-
nals are well seated.
The replacement fan is ready for operation.
Figure 16: Replacing the fan
Servi ce
Installation Instructions blueplanet XP10U-H4 Page 45
10 Service
We place special emphasis on the quality and longevity of our inverters, starting even in the product development
phase. More than 60 years of experience in the feld of power converters support us in this philosophy.
However, in spite of all quality assurance measures, faults may occur in rare cases. In such cases, KACO new energy,
Inc. will provide you with the maximum possible support. KACO new energy, Inc. will make every efort to remedy
such faults in an expeditious manner and without a great deal of bureaucracy.
If you need help solving a technical problem with one of our KACO products, please contact our service hotline.
Please have the following information ready so that we can help you quickly and ef ciently:
Inverter type/serial number
Fault message shown on the display/Description of the fault/Did you notice anything unusual?/What has already
been done to analyse the fault?
Module type and string circuit
Date of installation/Start-up report
Consignment identifcation/Delivery address/Contact person (with telephone number)
You will fnd our warranty conditions on our website.
http://www.kaco-newenergy.com/service/warranty
From there, you can easily navigate to our international websites by clicking on the appropriate fag.
Please use our website to register your unit within 24 months:
http://www.kaco-newenergy.com/service/warranty/online-warranty-registration
On this page as well, you can click on the appropriate fag to easily reach the website for your own nation.
In this manner, you can assist us in providing you with the quickest service possible.
We have prepared a form for complaints. It is located at
http://www.kaco-newenergy.com/service/technical-support
Hotlines
Technical problem resolution Technical consultation
+1 866 KACO SOLAR +1 866 KACO SOLAR
Shutdown/Di sassembl y
Page 46 Installation Instructions blueplanet XP10U-H4
Authorised electrician
11 Shutdown/Disassembly
11.1 Shutting down the inverter
DANGER
Lethal voltages are still present in the terminals and leads of the inverter even after the
inverter has been switched of and disconnected.
Severe injuries or death if the leads and terminals in the inverter are touched.
When there is irradiance, DC voltage is present on the open ends of the DC leads. Arcing may occur
if the DC leads are disconnected while under a load.
It is absolutely necessary that the shutdown sequence be carried out in the correct order.
After shutdown, wait at least 30 minutes before working on the inverter.
When working on photovoltaic modules, in addition to disconnecting from the grid, always
disconnect the DC main switch.
Disconnecting the grid voltage is not enough.
Shutdown sequence
1. Switch of the grid voltage by deactivating the external circuit breakers.
2. Disconnect the PV generator using the DC disconnector.
DANGER! The DC leads remain live.
Ensure that there is no voltage present on the grid connection terminals.
11.2 Deinstalling the inverter
Shut down the inverter.
1. Open the connection area.
2. Remove the interface cables.
3. Detach DC connection plugs.
4. Detach AC connection leads from the connection terminals.
5. Pull out the leads.
The deinstallation of the inverter is complete. Continue with dismantling.
11.3 Dismantling the inverter
Shut down the inverter.
Deinstall the inverter.
1. Detach screw from the detachment protector.
2. Remove the inverter from the mounting plate.
3. Securely pack the inverter if it is to be further used,
or
have the inverter professionally disposed of.
Recycl i ng and di sposal
Installation Instructions blueplanet XP10U-H4 Page 47
12 Recycling and disposal
For the most part, both the inverter and the corresponding transport packaging are made from recyclable materials.
KACO does its best to ensure our vendors follow a low carbon manufacturing process as we do ourselves. It is not
always possible but if you have questions about our products or the components in our products dont hesitate to
call +1 866 KACO SOLAR and ask.
Hallo. Dies ist ein Test der nderungsverfolgung.
Device
Do not dispose of faulty inverters or accessories together with household waste. Ensure that the old unit and, where
applicable, any accessories are disposed of in a proper manner. Most areas have public electronic waste disposal
and/or recycling plants. Feel free to contact KACO at +1 866 KACO SOLAR to request information about e-waste
recycling in your area.
Packaging
Ensure that the transport packaging is recycled.
Appendi x
Page 48 Operating Instructions blueplanet XP10U-H4
13 Appendix
Input power per input (in W. Max. current: 18.6 A.)
DC voltages (in V) XP10U-H4 DC voltages (in V) XP10U-H4
280 5208 720 10200
290 5394 730 10200
300 5580 740 10200
310 5766 750 10200
320 5952 760 10200
330 6438 770 10200
340 6324 780 10200
350 6510 790 10200
360 6696 800 10200
370 6882 570 10200
380 7068 580 10200
390 7254 590 10200
400 7440 600 10200
410 7626 610 10200
420 7812 620 10200
430 7998 630 10200
440 8184 640 10200
450 8370 650 10200
460 8556 660 10200
470 8742 670 10200
480 8928 680 10200
490 9114 690 10200
500 9300 700 10200
510 9486 710 10200
520 9672 720 10200
530 9858 730 10200
540 10044 740 10200
550 10200 750 10200
560 10200 760 10200
670 10200 770 10200
680 10200 780 10200
690 10200 790 10200
700 10200 800 10200
710 10200
Appendi x
Operating Instructions blueplanet XP10U-H4 Page 49
Connection examples
Input 1 Input 2 Input 3 Input 4
Voltage Power Voltage Power Voltage Power Voltage Power
400 V 3500W 400 V 3500W 700 V 3500W 700 V 3500W
600 V 7000W Unconnected 500 V 7000W Unconnected
500 V 12800W Unconnected Bridged to 1 Unconnected
500 V 5000W 500 V 5000W Unconnected 750 V 4000W
750 V 6000W 750 V 6000W 350 V 1000W 350 V 1000W
600 V 6000W Unconnected Short-circuited Short-circuited
Invalid connections
Invalid switching states are shown in the following table with a dark background:
Input 1 Input 2 Input 3 Input 4
Voltage Power Voltage Power Voltage Power Voltage Power
400 V 3500W 700 V 3500W 400 V 3500W 700 V 3500W
600 V 7000W 600 V 7000W Unconnected Unconnected
500 V 12800W Bridged to 1 Unconnected Unconnected
600 V 6000W Short-circuited Short-circuited Unconnected
Appendi x
Page 50 Operating Instructions blueplanet XP10U-H4
Notes
Appendi x
Operating Instructions blueplanet XP10U-H4 Page 51
Notes
KACO new energy (866) 522 6765 kacoinfo@kaco-newenergy.com www.kaco-newenergy.com
T
h
e

t
e
x
t

a
n
d


g
u
r
e
s

r
e


e
c
t

t
h
e

c
u
r
r
e
n
t

t
e
c
h
n
i
c
a
l

s
t
a
t
e

a
t

t
h
e

t
i
m
e

o
f

p
r
i
n
t
i
n
g
.


S
u
b
j
e
c
t

t
o

t
e
c
h
n
i
c
a
l

c
h
a
n
g
e
s
.


E
r
r
o
r
s

a
n
d

o
m
i
s
s
i
o
n
s

e
x
c
e
p
t
e
d
.

3
0
0
1
9
0
4
-
0
1
-
1
1
1
2
0
9
|
J
t
t
m
N
t
J
4
t
m
4
m
m
m
m
t
N
M
T

Potrebbero piacerti anche