0 valutazioniIl 0% ha trovato utile questo documento (0 voti)
108 visualizzazioni62 pagine
Feeder automation is the monitoring and control of devices located out on the feeders themselves. FISR provides the means to restore service to some customers before field crews arrive on the scene.
Feeder automation is the monitoring and control of devices located out on the feeders themselves. FISR provides the means to restore service to some customers before field crews arrive on the scene.
Feeder automation is the monitoring and control of devices located out on the feeders themselves. FISR provides the means to restore service to some customers before field crews arrive on the scene.
Automation Recent Trends in Feeder Automation Seminar IEEE PES Miami Chapter Miami, Florida June 2, 2005 John M c Donald john.mcdonald@kema.com KEMA, Inc. K E M A , I N C . 2 Introduction Distribution Feeder Automationis the monitoring and control of devices located out on the feeders themselves Line reclosers Load break switches Sectionalizers Capacitor banks Line regulators K E M A , I N C . 3 Main Feeder Automation Applications Automated Feeder Switching Volt/VAR Management (Discussed in next Seminar Module) K E M A , I N C . 4 Automated Feeder Switching Monitoring and control of electrically operableswitches located outside the substation fence Automated feeder switching usually involves remote control from a centralized location (I.e., control center) Operation can be fully automatic, with no manual intervention K E M A , I N C . 5 Primary Application FISR Fault Location, Isolation, and Service Restoration Use of automated feeder switching to: Detect feeder faults Determine the fault location (between 2 switches) Isolate the faulted section of the feeder (between 2 feeder switches) Restore service to healthy portions of the feeder K E M A , I N C . 6 Fault Location, Isolation, & Service Restoration (FISR) When a permanent fault occurs, customers on healthy sections of the feeder may experience a lengthy outage FISR provides the means to restore service to some customers before field crews arrive on the scene Overall Objective: Reduce outage duration for customers on unfaulted (healthy) sections of the feeder Fault Occurs Customer Reports Outage Field Crews On-Scene Travel Time Fault Located Fault Investigation & Patrol Time Power Restored to Customers on Healthy Sections of Feeder Time to Perform Manual Switching Repair Time Feeder Back to Normal 5 10 minutes 15 30 minutes 15 20 minutes 10- 15 minutes 45 75 minutes K E M A , I N C . 7 Fault Location, Isolation, & Service Restoration (FISR) Fault Occurs Customer Reports Outage Field Crews On-Scene Travel Time Fault Located Fault Investigation & Patrol Time Power Restored to Customers on Healthy Sections of Feeder Time to Perform Manual Switching Repair Time Feeder Back to Normal 5 10 minutes 15 30 minutes 15 20 minutes 10 - 15 minutes 45 75 minutes Fault Occurs Feeder Back to Normal Power Restored to Customers on Healthy Sections of Feeder Travel Time 15 30 minutes 1 - 4 Hours Repair Time 1 - 4 Hours 1 to 5 minutes 5 - 10 minutes Patrol Time Customer Reports Outage 5 10 minutes K E M A , I N C . 8 FISR How It Works K E M A , I N C . 9 FISR How It Works K E M A , I N C . 10 FISR How It Works K E M A , I N C . 11 FISR How It Works K E M A , I N C . 12 FISR How It Works K E M A , I N C . 13 FISR How It Works K E M A , I N C . 14 Reliability Improvement Benefit Actual experience for one KEMA Client: 63% SAIDI (outage duration) improvement 56% SAIFI (outage frequency) improvement FISR compares favorably with other reliability improvement measures in bang for the buck and overall effectiveness K E M A , I N C . 15 Other Uses of Automated Switches Load Shedding Can shed one section of the feeder if necessary Feeder Reconfiguration Use switches to balance load between feeders Cold Load Pickup Can pick up feeder load one section at a time Intelligent Substation Bus Transfer Transfer load to another substation following transformer failure (Substation automation application) K E M A , I N C . 16 System Components Distribution SCADA system (if necessary) Remote controlledfeeder switches (load break, recloser, sectionalizer, etc.) - RCS Normally-closed line switches Normally-open tie switches Feeder RTU or Controller Fault detector unit or current sensor Two-way communication facilities ( Sp.Spectrum MAS K E M A , I N C . 17 Remote Controlled Switches Integrated Load Break Switch J oslyn Vacuum Switch S&C Omni Rupter G&W SF6 Switch Line Recloser Cooper recloser K E M A , I N C . 18 Non Integrated Load Break Switches (Retrofit Motor Operators) K E M A , I N C . 19 Padmount Switches Can add motor or solenoid operating mechanism Open 2 sec/close 5 sec Mounting of radio antenna can be a problem (remote the antenna) K E M A , I N C . 20 Feeder Remote Terminal Unit DAQ Polaris GE Harris DART Metso Polecat K E M A , I N C . 21 Fault Detectors Determines that a fault has occurred downstream (further from the substation) Must be able to identify the fault before its cleared by fault interrupting devices (a few cycles) System must capture this information for further processing Must be able to detect all kinds of faults Phase faults Ground faults current may be less than normal load must use residual current K E M A , I N C . 22 Current & Voltage Sensors Sensors Measure single/three phase line currents and voltages and reports these measurements to local controller or RTU Accuracy at least + or - 3% Suitable for measuring fault current May be incorporated in the switch Must detect fault before its cleared Lindsey Current Sensor Fisher Pierce Line Post Sensor K E M A , I N C . 23 Fault Indicators Fault Indicators Clamp on style Current inrush restraint Fault settings Bi-directional Detect fault before clearing Reset conditions Time Restoration of voltage or current Output signal to feeder RTU Radio signal Fiber optic/metallic cable Local indicator visible from ground level Fisher Pierce Edison Controls FCI K E M A , I N C . 24 Pictures of Fault Indicators K E M A , I N C . 25 Radio Transmitter Style Fault Indicator K E M A , I N C . 26 Communication Facilities System requires reliable 2-way communication facilities to feeder locations Common approaches: Licensed UHF MAS radio Unlicensed Spread spectrum radio (PTP, MAS, store-and-forward network, Ethernet radio) Cellular telephone (CDPD, 3G cellular) Commercial services (Cellnet, Telemetrics, etc.) K E M A , I N C . 27 Hockey Puckantenna for padmounts K E M A , I N C . 28 Store and Forward Network Radio K E M A , I N C . 29 Use of Optical Fiber Increasing interest in using Optical Fiber to handle communications with feeder switches Municipal utilities installing fiber for cable television and other applications want to exploit this for DA Fiber capacity probably overkill for for feeder switching application but if its available, use it! K E M A , I N C . 30 Control Panels Open/Close Pushbuttons Switch status (open/closed) indicators Alarm indicators Local/remote switch Operations counter K E M A , I N C . 31 Switch Power Supply Power source dedicated voltage transformer connect to local secondary circuit Backup Power Supply Provides ability to operate switch when associated feeder is dead Should specify a required number of operations with the power off (biggest power drain is radio transmitter) Maintenance free rechargeable battery packs Temperature compensated battery charger Self monitoring capability K E M A , I N C . 32 Feeder Automation Categories Approaches categorized on how control is performed: Manual Semi-Automatic Fully Automatic K E M A , I N C . 33 Feeder Automation Categories MANUAL No automatic control System delivers information (recommendations) to Dispatcher Dispatcher executes recommended actions Pros Simpler than fully automatic Good starter approach until confidence is built up Cons Takes longer to restore service (3 5 minutes) Communication time (both ways) Dispatcher decision time Difficult for dispatcher to manage many switches during emergencies involving multiple disturbances K E M A , I N C . 34 Feeder Automation Categories SEMI-AUTOMATIC Mix of automatic and supervised control Example FA system automatically isolates fault and performs upstream restoration Dispatcher supervises downstream restoration activities based on FA system recommendations Pros Simpler than fully automatic Natural progression from Manual approach Where most utilities end up Upstream customers restored in less than 1 minute Cons Takes longer to restore downstream service (3 5 minutes) Difficult for dispatcher to manage many switches during emergencies involving multiple disturbances K E M A , I N C . 35 Feeder Automation Categories FULLY AUTOMATIC All fault isolation and restoration activities performed automatically No dispatcher intervention Pros Possible to restore all service in less than one minute Less burden on Dispatcher to manage the switching activities Cons Most complex approach Acceptance difficulties Ranges from Why not? to Over my dead body K E M A , I N C . 36 Feeder Automation Architecture Standalone Automatic Switches Reclosers, sectionalizers Centralized System Switches controlled by central DMS/SCADA Substation Centered Approach Substation unit controls switches on associated feeders Peer to Peer Arrangement Groups of switches communicate to determine appropriate switching actions K E M A , I N C . 37 System controlled by central SCADA Acquire data fromfield devices Process data in SCADA system Issue supervisory control commands Comm. Tower Workstation Centralized Feeder Automation Can be manual, semi-automatic, or fully-automatic K E M A , I N C . 38 Centralized Feeder Automation Conceptual Block Diagram SCADA Server Basic SCADA Functionality Feeder Automation Application Server Feeder Models Distribution Power Flow Load Estimator Topology Processor FLISR Application Software Switch Order Management Substation and Feeder Devices Fault indicator status, currents, voltages Device Control Commands Geogaphic Information System (GIS) Real-Time Data Feeder equipment data, topology information Dispatcher Console Equipment status and loading Switching Actions Central SCADA System K E M A , I N C . 39 ACS Feeder Automation K E M A , I N C . 40 Some Vendors That Use the Centralized FA Approach Advanced Control Systems (ACS) Areva (formerly Alstom) SNC Lavalin ECS (SLECS) Survalent (former Quindar) Siemens Telvent-Abengoa (formerlyMetso) K E M A , I N C . 41 Central Scheme Pros & Cons Pros Operators retain control Operators are always informed Considerably more operating flexibility Fewer restrictions (e.g., number of switches controlled) Better ability to handle abnormal situations No unnecessary switching Additional functionality possible Non-outage switching Feeder load balancing K E M A , I N C . 42 Central Scheme Pros & Cons Cons Requires a distribution SCADA system Requires an extensive communication infrastructure Requires electrical models updated via GIS K E M A , I N C . 43 Substation Centered Approach Comm. Tower Local HMI RTU/PLC SCADA EMS Substation O P T IO N A L System controlled by Substation PLC or RTU Acquire data fromfield devices Process data in substation Issue supervisory control commands as needed to field devices Can be manual, semi- automatic, or fully- automatic K E M A , I N C . 44 GE Feeder Automation Scheme K E M A , I N C . 45 Substation Centered Vendors General Electric Novatech K E M A , I N C . 46 Substation Centered Pros/Cons Pros - Fairly easy to set up and maintain - Doesnt require electrical feeder models - Doesnt require central SCADA - Lowest cost alternative - Cons - Difficulty in handling complex situations - Heavily loaded feeders where load must be split up - Limited number of switches controlled - Requires substation feeder communications K E M A , I N C . 47 Peer-to-Peer Arrangement Network of Distributed Controllers Acquire local data via local sensors Acquire remote data via peer-to-peer communications with other controllers Process data locally Open/close associated switch as needed Primarily intended for fully-automatic operation K E M A , I N C . 48 Peer-to-Peer Arrangement No SCADA central station required Most implementations have remote monitoring Switching decisions made automatically prior to lockout based on: Extended loss of voltage Through fault current Prefault loading Dispatcher User Interface Optional Control Center Interface K E M A , I N C . 49 S&CIntelliTEAMI Original IntelliTEAM Capabilies: Teams can have up toseven switches Only two sources of power allowed Teams must contain only one open switch No switch can be in multiple teams Not adaptable to multiple source topology K E M A , I N C . 50 S&CIntelliTEAMII IntelliTEAMII Capabilities: A team is now a line segment bounded by switches Teams can include up to8 switches Teams can have up to8 separate sources of supply Switches canbelong to multiple teams K E M A , I N C . 51 Peer to Peer Pros and Cons Pros Doesnt require: Central SCADA system Feeder models supported by GIS interface Extensive communications infrastructure Speed of operation (30 seconds or less) Costs less than central approach Primary application is FISR, but not limited to this Can be fully functional feeder SCADA system K E M A , I N C . 52 S&C Electric J ungle Mux Terminal Server D20 Spread SpectrumRadio Substation S&C 5800 Switch Controller S&C 5800 Switch Controller S&C 5800 Switch Controller J ungleMux Terminal Server D20 Spread SpectrumRadio Substat ion S&C 5800 Switch Controller S&C 5800 Switch Controller S&C 5800 Switch Controller Survalent Master ProxyServer J ungle Mux Firewall Logic Module J ungle Mux Terminal Server D20 Spread SpectrumRadio Subst ati on S&C 5800 Switch Controller S&C5800 Switch Controller Control Center S&C 5800 Switch Controller Broadband Fibreoptic Network Sys tem Architecture K E M A , I N C . 53 Peer to Peer Pros and Cons Cons Lack of operator visibility and control Can add SCADA interface (most utilities do!) Communication difficulties Peer-to-peer communications among pole top units can be a challenge! Single vendor solution Costs more than substation centered approach Some unnecessary switching involved Switches in a team open regardless of fault location Then close back in as necessary May fail to close? Extra mechanical operations? K E M A , I N C . 54 Feeder Automation Training Simulator K E M A , I N C . Practical Matters to Consider K E M A , I N C . 56 Tradeoff: Permanent vs. Momentary Outages Definitions: Permanent: Duration > threshold Momentary: Duration < threshold Use of FISR will: Improve permanent outage statistics SAIDI, SAIFI, CAIDI Make momentary outage statistics worse MAIFI Most utilities are willing to accept this tradeoff! K E M A , I N C . 57 Limitations on Transferring Load to Adjacent Feeders It is often difficult to transfer all the healthy load to adjacent feeders without causing overloads and/or voltage problems Especially true during peak load period May need to split load being transferred to alternative sources May require additional automated switches to accomplish FISR objectives at certain times of the day K E M A , I N C . 58 Diminishing Returns Additional reliability improvement benefit declines dramatically as more switches are added Reliability Improvement vs. Cost 0 500 1000 1500 2000 2500 3000 0 20000 40000 60000 80000 100000 Cost ($) C u s t
O u t a g e
M i n u t e s
I m p r o v e m e n t K E M A , I N C . 59 Importance of Switch Placement Predicted reliability improvement varies widely with switch placement strategy Variation observed for sample case: SAIDI - 22% SAIFI - 31% MAIFI - 23% Small change in placement (a few hundred feet) produced a 5% change in SAIDI! K E M A , I N C . 60 First Segment Fault Detection Always an issue! System requires a lockout for fault signal from the substation to trigger feeder switching activities Fault has occurred Feeder protection has completed its automatic reclosing cycle Works best if a protective relay IED is available in the substation and can be interfaced to the FISR system K E M A , I N C . 61 Non-Fault vs Fault Tripping System must be ale to distinguish between non fault and fault tripping of the substation circuit breaker/recloser Fault Tripping A feeder fault has occurred or supply has been lost due to a transmission substation fault FISR should attempt to restore service Non-Fault Tripping Substation CB tripped for reasons other than a feeder fault Manual operation by switching personnel or supervisory control from the control center Underfrequency/undervoltage load shedding FISR should not attempt to restore service K E M A , I N C . 62 Safety Issues Safety for workers and general public must not be compromised!!! Operating practices and procedures must be reviewed and modified if necessary to address presence of automatic switchgear Safety related recommendations: Requirement for visible gap No automatic closures after two minutes have elapsed following the initial fault System disabled during maintenance (live line) work