Sei sulla pagina 1di 21

Procedures for planning and installation of standpipe and hose systems for fire

protection of building homes and buildings



1. Scope
This standard covers the minimum requirements for installation and system standpipe
hydrants/hose in the building. This standard does not include requirements for periodic
inspection, testing, and maintenance of standpipe system.

4. The components of the system
4.1 General
Components of the system must be able to receive working pressure not less than the
maximum pressure generated in the relevant location in every state of the system,
including the pressure that occurs when a fire pump that is installed permanently is
working with the valve closed.
4.2 Pipe and Tube
When used steel pipe and connecting with welding according to applicable regulations,
the minimum nominal wall thickness for pressures up to 20.7 bars (300 psi) shall be in
accordance schedule 10 for pipe sizes up to 125 mm (5 inches); 3.40 mm (0.134
inches) for pipes of 150 mm (6 inches); and 4.78 mm (0.188 inches) for pipes of 200
mm (8 inches) and 250 mm (10 inches).
When connected with a steel pipe threaded fittings, the minimum wall thickness shall be
in accordance with schedule 30 pipe [in sizes 200 mm (8 inches) and larger] or
schedule 40 pipe [for pipe sizes less than 200 mm (8 inches)] and pressures up with
20.7 bar (300 psi).
Copper tube according to applicable regulations, must have a thick type K, L or M when
used in a standpipe system.
Curves of schedule 40 steel pipe and type K and L for copper tube is allowed when
made with no bending, damage, reducing the diameter, or other deviations from
spherical shape. The minimum bend radii must be 6 x diameter pipe for sizes 50 mm (2
inches) and smaller, and 5 x pipe diameter to the size of 65 mm (2 inches) and larger.


4.3 Connector
Another type of connector, investigated their suitability for use in the installation of the
standpipe has been registered, can be installed in accordance with applicable
regulations. Connector should be stronger if the pressure exceeds 12.1 bar (175 psi).
Exceptions:
1. Standard fittings of cast iron with a diameter of 50 mm (2 inches) or smaller are
allowed to be used at a pressure of not more than 20.7 bar (300 psi).
2. Standard fittings of cast iron with a diameter of 150 mm (6 inches) or smaller are
allowed to be used at a pressure of not more than 20.7 bar (300 psi).
Union should not be used on pipe larger than 50 mm (2 inches). Clutch is used for pipes
larger than 50 mm (2 inches). Reducer must be used when different pipe sizes.
4.4 Pipe Connection and fitting tools
Ribbon (tape) or similar substances should be used only on male threads. For
connecting pipe fire protection, welding methods must meet applicable regulations.
Exception:
Welding standpipe installed in the building which is under construction, is allowed only
when the construction is non-flammable, contains within it non-flammable, and the
welding process according to applicable regulations.

4.5 Hanger
Strap-hangers and the components must be made of materials that contain iron.
Exception:
The components of materials that do not contain iron which has been proven by fire
assay for use in fire hazard and registered for this purpose, and on par with the other
requirements of this section may be used.
Standpipe piping should be held appropriately on the structure of the building, which will
hold the additional burden of water-filled pipe plus a minimum of 114 kg (250 lbs.),
applied to the hook point. When standpipe piping is installed under the ducting, piping
must be held in a building or on a ducts retaining structure that have been prepared and
able to withstand the load ducted specific load.



Table 4.5.1.5.(a): The moment of inertia that is required for part of the trapeze. (Inch
3
)

Jarak gantungan trapis : distance of trapeze hanger
Diameter pipa (inci) : Pipe diameter (inch)

Note the table:
Values above for schedule 10 of pipe, while the value below to schedule 40 of pipe.
This table is based on the maximum allowable bending stress 15 KSI and load
concentration at the midpoint of the distance of hangers from 4.6 m (15 ft.) of water
pipes filled with water plus 113 kg (250 lb.).




Table 4.5.1.5.(b): Moment of inertia of the common trapeze hanger

Pipa : Pipe ; in : inch ; inci3 : inch3 ; besi siku : brackets ; skedul ; schedule

Size or other forms that have a moment of inertia equal to or greater than angle iron or
pipe may be used. All brackets must be used with a longer vertical side. Part of the
trapeze hanger must be secured to prevent the launch. If a pipe is hung on a pipe
trapeze hanger with a diameter less than the diameter of the pipe that is on hold, rings,
straps or clevis hangers with the size adjusted to the pipe barrier must be used at both
ends.
Expansion holder registered to hold the pipes in concrete construction can be used in
the horizontal position of the beam. In concrete having gravel or rock fragments
(aggregates), expansion holder may be used in a vertical position, to hold the pipes with
a diameter of 100 mm (4 inches) or less. To hold the pipe with a diameter of 125 mm (5
inches) and larger, expansion holder, if used in a vertical position, must be installed
alternately with hangers that are connected directly to the structure, such as frame
construction or little beams, or sides of concrete beams. If no part of the structure that
can be used, with a pipe diameter of 125 mm (5 inches) and larger can all be hold by
expansion holder in the vertical position, but should be spaced no more than 3 m (10 f).
Expansion holder should not be used in the ceiling of gypsum material or the like, or the
slag concrete.
Exception:
Expansion holder can be used in concrete slag on the branch pipe, alternating equipped
with bolts or hangers attached to the beam.

Framework of concrete on concrete and welding frame
Representative sample of concrete as the frame must be tested to determine the frame
can withstand a minimum of 341 kg (750 lb.) for pipe 50 mm (2 inches) or smaller, 454
kg (1000 lb.) for pipe 65 mm (2 inches), 80 mm (3 inches) and 90 mm (3 inches)
and 545 kg (1200 lb.) for pipe 100 mm (4 inches) or 125 mm (5 inches).

Trunks and U hangers
Table 4.5.4.1 Size of Hanger Trunk
Pipe Size
(inches)
Trunk Diameter
inches mm
Up to and including 4 3/8 9.5
5,6, and 8 12.7
10 and 12 5/8 15.9


Table 4.5.4.3.1
Pipe Size
(inches)
Trunk Diameter
Bending Hook Welding Hook
inches mm inches mm
Up to and including 4 3/8 9.5 3/8 9.5
5,6, and 8 12.7 12.7
10 and 12 19.1 12.7


Table 4.5.4.5 The dimensions of ceiling the flange screws and U hangers
Pipe Size Flange with 2 Screws
Up to 2 inches Wood screw no. 18 x 1 inch

Pipe Size Flange with 3 Screws
Up to 2 inches Wood screw no. 18 x 1 inch
2 , 3, 3 inches Screw 3/8 inches x 2 inches
4, 5, 6 inches Screw inches x 2 inches
8 inches Screw 5/8 inches x 2 inches

Pipe Size Flange with 4 Screws
Up to 2 inches Wood screw no. 18 x 1 inch
2 , 3, 3 inches Screw 3/8 inches x 1 inches
4, 5, 6 inches Screw inches x 2 inches
8 inches Screw 5/8 inches x 2 inches

Pipe Size U Hanger
Up to 2 inches Wood screw no. 16 x 2 inches
2 , 3, 3 inches Screw inches x 3 inches
4, 5, 6 inches Screw inches x 3 inches
8 inches Screw 5/8 inches x 3 inches


Table 4.5.4.6 The minimum size of bolts and screws
Pipe Size Size of bolts or screws The length of the screws used
with wood beams
inches mm inches mm
Up to 2 inches 3/8 9.5 2 64
2 inches until
6 inches
12.7 3 76
8 inches 5/8 15.9 3 76
When the thickness of beams or girder is not possible to use a screw length of 65 mm
(2 inches), with a screw length of 50 mm (2 inches) may be used with distance
between hangers not more than 3 m (10 ft.).
Table 4.5.4.9 Thickness of boards and beams or wide of girder
Pipe Size Size of bolts or screws The length of the screws used
with wood beams
inches mm inches mm
Up to 2 inches 3/8 9.5 2 64
2 inches until
3 inches
12.7 3 76
8 inches 5/8 15.9 3 76

Rod screws should not be used to hold pipes larger than 150 mm (6 inches). All the
holes for the screw rod should all first be drilled in a 3.2 mm (81 inches) smaller than the
diameter of the base of the threaded screw.
4.6 Valve
All valves controlling the water supply and the connection to the standpipe must be of
registered pointer valve type. The valve should not be closed in less than 5 seconds
when closed quickly ranging from fully open state.
4.7 hose box
In the closet, hose connections shall be placed so that no less than 25 mm (1 inch)
distance between any part of the closet and the valve stem when the valve is in any
position from fully open to fully close.
Each connection hose is provided for use by occupants of the building (system of class
II and class III), must be fitted with a length of no more than 30 m (100 ft.) in accordance
registered to a diameter of 40 mm (1 inches), straight, can be folded or not, fire hose
attached and ready for use.
Each hose box of 40 mm (1 inch) supplied with hose of 40 mm (1 inch) should be
installed with registered racks or other approved storage facility. Each hose box 40 mm
(1 inches) must be attached with a roll of registered continuous flow.
Firefighter connection must be registered to working pressure equal to or greater than
the pressure required by the needs of the system. Each firefighter connection shall have
two inlets at least 65 mm (2 inch) with screw according to applicable regulations.
Exceptions:
If the local firefighter is using a different connection than specified, connector that is in
accordance with the local firefighter equipment must be used and the minimum size
should be 65 mm (2 inches).

5. System Requirements
5.1 General
The number and arrangement of standpipe equipment for proper protection is ruled by
local conditions, such as; occupancy, character, building construction and building
entrance. Authorized institutions should be asked his advice in connection with the
required type of system, class system and special requirements.

5.2 Standpipe system Type
Automatic dry standpipe system
Automatic dry standpipe system should be dry standpipe system normally filled with
compressed air, regulated through the use of equipment, such as dry pipe valve, to
allow water into the piping system to be automatic at the opening of the hose valve. The
water supply for an automatic dry standpipe system shall be capable of supplying the
needs of the system.
Automatic wet standpipe system
Automatic wet standpipe system must be wet standpipe system that has a water supply
capable of supplying the system needs to be automatic.
Automatic Semi dry standpipe system
Automatic Semi dry standpipe system should be dry standpipe system regulated
through the use of tools, such as a flood valve (deluge), to allow water into the system
piping upon activation of a remote control device is placed on the connection hose.
Remote control activation tool must be fitted on each hose connection. The water
supply for dry standpipe system shall be capable of supplying the needs of the system.
Manual dry standpipe system
Manual dry standpipe system shall be dry standpipe system that does not have a
permanent water supply that integrates with the system. Manual dry standpipe systems
require water from a fire pump (or the like) to be pumped into the system through the
fire department connection to supply the needs of the system.
Manual wet standpipe system
Manual wet standpipe system shall be a wet standpipe system connected to a water
supply that is small for the purpose of maintaining water within the system but do not
have the ability to supply water to the system requirements.
5.3 Classes of standpipe system
Class I
The system must provide a hose connection size of 63.5 mm (2 inch) to supply water
used by firefighters and they who were trained.
Class II
The system must provide a hose box size 38.1 mm (1 inches) for the supply of water
that is used primarily by the building occupants or by firefighters for initial action.
Class III
The system must provide a hose box size 38.1 mm (1 inches) to supply water used
by building occupants and hose connection size of 63.5 mm (2 inches) to supply
water to the larger volumes to be used by firefighters or those who trained.
Exceptions:
Hose with the minimum size of 25.4 mm (1 inch) are allowed to be used for hose boxes
on the use of lighter fire rate with the approval of the competent authority.
If the entire building is protected with an approved automatic sprinkler system, hose box
used by the occupants of the building is not required. It depends on the approval of the
competent authority.
5.4 Requirements for manual standpipe system
Manual Standpipe system should be used in high-rise buildings. Manual Standpipe
system can only be used for fire. Manual standpipe systems shall not be used for class
II or class III.
5.5 Requirements for dry standpipe system
Dry standpipe should be used only if the piping, especially when the water can freeze.
Dry standpipe system shall not be used for class II or class III.


5.6 Meter
Spring type pressure gauge with a diameter of 89 mm (3 inches) must be connected
to the beam pipe of the fire pump and public drains the tank to the press, the air pump
that supplies the tank press, and at the top of each standpipe. The meter should be
placed in an appropriate place so that water cannot freeze. Each meter must be
controlled with a valve that has an arrangement for disposal.

6. Installation requirements
Dry standpipe must not be connected to the building wall or column mounted on the wall
amplifier. Standpipe system shall not penetrate through the dangerous areas and
should be placed so that it is protected from mechanical damage and fire.
In buildings installed with an approved automatic sprinkler system, hose connection
lateral piping with diameters up to 63.5 mm (2 inches) and Pipelines that connect the
standpipe hose connections to 38.1 mm (1 inches) are not required to be protected.
Connections to public water systems must be controlled by a pointer valve pole from the
approved type that are placed not less than 12 m (40 ft.) from the protected building. All
valves are clearly marked to indicate maintained during controlled.
Exceptions:
If the valve cannot be stored at less than 12 m (40 ft.) from the building, this valve
should be installed in an approved location, easy to read and accessible, especially
in the event of a fire does not become damaged.
If the pointer valve pole cannot be used, the valve may be used underground.
Valves placed directly, easy to open and easy to care controlled by clearly marked
on the served building.
Firefighter connection shall be installed as follows:
a) Wet standpipe system automatic and manual wet.
On the system side of the control valve system, back holder valve, or any pump,
but on the supply side of any isolating valves
b) Automatic dry standpipe system.
On the system side of the control valve and back holder valve, and the supply side
of the dry pipe valve.
c) The system semi-automatic dry standpipe.
On the system side of the flood valve.
d) Manual dry standpipe system.
Directly connected to the piping system.

A firefighter connection for each standpipe system should be placed no more than 30 m
(100 ft.) from the nearest yard hydrants are connected to an approved water supply.
Firefighter connection shall be placed not less than 45 cm (18 inches), not more than
120 centimeters (48 inches) above the ground beside, side road or ground surface.

6.4 Pipe Holder

Standpipe should be held by a complementary tool that plugs directly into the standpipe.
Horizontal piping of a standpipe hose connection to a length of more than 450 mm (18
inches) should be provided hanger.

7. Design
7.3 The location of hose connections
Hose Connection and hydrant boxes should not be blocked and must be located not
less than 0.9 m (3 feet) or more than 1.5 m (5 feet) above the floor surface.
Class 1 System
The location of hose connections .
Connection hose and hydrant boxes should not be blocked and must be located not
less than 0.9 m ( 3 feet ) or more than 1.5 m ( 5 feet ) above the floor surface .

System class I.
The system is equipped with Class I hose connections to the size of 65 mm ( 2
inches ) at the following places :
At each landing between the two floors on any required fire stairs.
on each side of the wall adjacent to the horizontal exit openings
In each exit path (passageway) at the entrance of the area of building leading to the
canal (passageway).
The covered mall buildings, at the entrance to each exit path or exit corridors and
entrances to public heading to the mall.
On the floor of the top fire stairs with a stair that can reach the roof, and if the stair
cannot reach the roof, then the additional hose connections of 65 mm (2 inches)
must be provided to the furthest standpipe (calculated hydraulically) to fulfill the
purposes of testing.
when the farthest and the non-protected by a sprinkler part of the floor or level that
the distance from the required exit exceeds 45.7 m (150 feet) or the farthest floor /
level and protected by a sprinkler that the distance exceeding 61 m (200 feet) of the
required exit, additional hose connections shall be provided at approved places, and
required by the local firefighter.

Class II System
Class II systems shall be equipped with a hose hydrant box with the size of 40 mm (1
inches) in such a way that every part of the floor on the building was 39.7 m (130 feet)
from hose connections that are provided with a 40 mm (1 inches) hose.

Class III Systems
Class III systems shall be equipped with hose connections as required for the system of
class I and class II systems.

7.4 Number of standpipe
In any required fire stairs, it must be equipped with its own standpipe.

7.6 The minimum size of the standpipe.
Size standpipe system for class I and class III should be sized at least 100 mm (4
inches). Standpipe that is part of the combined system must be sized at least 150 mm
(6 inches). For the whole building that is equipped with sprinklers, and has a
combination standpipe system that is calculated hydraulically, the minimum size of its
standpipe is 100 mm (4 inches).

Standpipe system should be one of the following:
a) Hydraulically designed to obtain the flow rate of water at a residual pressure of 6.9
bar (100 psi) at the farthest output of the hose connection of 65 mm (2 inches)
that is calculated hydraulically, and 4.5 bar (65 psi) at the farthest point of the
hydrant box of 40 mm (1 inch) that is calculated hydraulically. If the competent
authority allows the pressure lower than 6.9 bar (100 psi) for hose connection sizes
of 65 mm (2 inches), based on suppression tactics, the pressure can be reduced
to a minimum 4.5 bar (65 psi).

b) the size of the pipe with the flow rate required by the residual pressure of 6.9 bar
(100 psi) at the farthest end of the hose with the size of 65 mm (2 inches) and a
pressure of 4.5 bar (65 psi) at the farthest end of the hose with a size of 40 mm (1
inches), designed in accordance as shown in table 7.7.b. The design that uses pipe
schedules, should be limited to wet standpipe of the building that are not categorized
as high buildings.

Table 7.7.b. Minimum pipe diameter (in inches), in terms of total distance and total
accumulated flow pipe
Total of flow accumulation The farthest distance from the output (inches)
Gallon/minutes Liter/minutes <15.2 m 15.2 30.5 >30.5 m
100 379 2 2 3
101-500 382 1893 4 4 6
501-750 1896 2839 5 5 6
751-1250 2843 4731 6 6 6
1251 and above 4735 and above 8 8 8

7.8 The maximum pressure for hose connection
Where the residual pressure in the output at the size of 40 mm (1 inches) of the hose
connection that is available for use by the occupants exceed 6.9 bar (100 psi), the
pressure regulating device that has been tested must be provided to limit the residual
pressure at the required flow, at a pressure of 6.9 bar (100 psi).
When the static pressure in the hose connections exceed 12.1 bar (175 psi), the
pressure regulating device that has been tested must be provided to limit static pressure
and residual pressure, at the end of the hose connections of 40 mm (1 inches) that
are available for use by the occupants, pressurized at 6.9 bar (100 psi), and a pressure
of 12.1 bar (175 psi) on the other hose connections.

7.9 The minimum flow rate
System class I and class III
For systems class I and class III, the minimum flow rate of the furthest hydraulic
standpipe should be 1893 liters/min (550 Gallon/minutes). The minimum flow rate for
additional standpipe should be 946 liters/min (250 Gallon/minutes) for each standpipe,
which the amount does not exceed 4731 liters/min (1250 Gallon/minutes). If the floor
area is over 7432 m
2
(80000 feet
2
), the next furthest standpipe must be designed to be
able to handle 1983 liters/min (500 Gallon/minutes).

Hydraulic calculations and determination of pipe sizes for each standpipe must be
based on the provision of 946 liters/min (250 Gallon/minutes) that is in both furthest
hydraulic hose connections on the standpipe outlet and on top of each other standpipe
in accordance with the required minimum residual pressure.
The joint supply piping must be calculated to fulfill the required flow rate of the entire
standpipe that are connected to the piping system, with the number that is not exceed
4,731 liters / min (1,250 Gallon/minutes).

Class II system.
For Class II systems, the minimum flow rate for the furthest standpipe which is
calculated hydraulically is 379 liters/min (100 Gallon/minutes). Additional flow is not
required if there is more than 1 (one) standpipe.
Hydraulic calculations and determination of pipe sizes for each standpipe shall be
based on providing 379 liters/min (100 Gallon/minutes) in the hydraulic hose
connections on the farthest standpipe. The joint Supply piping that serves a double
standpipe must be calculated for the supply of 379 liters/min (100 Gallon/minutes).

7.10 Equivalent pipe length of valves and fittings for hydraulic system design.

Table 7.10.1 should be only used where the factor C of the Hazen-Williams is 120. For
other values of C, the value in the table must be multiplied by a factor shown in Table
7.10.2 (a). Table 7.10.2 (b) shows the C factor of the pipe material that is commonly
used. Permission must be sought from the competent authority for the use of other C
values.

Table 7.10.1 : Equivalent pipe length
Fitting and valve Fitting and valve presented in equivalent pipe length (feet)
1 1 1 2 2 3 3 4 5 6 8 10 12
Elbow 45
0
1 1 1 2 2 3 3 3 4 5 7 9 11 13
Standard Elbow 90
0
2 2 3 4 5 6 7 8 10 12 14 18 22 27
Long Elbow 90
0
1 2 2 2 3 4 5 5 6 8 9 13 16 18
Tee or cross (turning
angle 90
0
)
3 5 6 8 10 12 15 17 20 25 30 35 50 60
Butterfly valve 6 7 10 12 9 10 12 19 21
Gate valve 1 1 1 1 2 2 3 4 5 6
One direction swing
valve
5 7 9 11 14 16 19 22 27 32 45 55 65
Rounded valve 46 70
Angle valve 20 31


Table 7.10.2.(a): Adjustment factor for C
C Value 100 130 140 150
Multiply Factor 0.713 1.16 1.33 1.51

Table 7.10.2 (b): Values of C from Hazen-Williams
Pipe or Tube C Value


Standpipe for exhaust with size of 76 mm (3 inches) that is permanently mounted
adjacent to each standpipe and is equipped with a pressure regulation equipment to
allow testing of any equipment. Standpipe for disposal must be installed with the tee 80
mm x 65 mm (3 inches x 2 inches).


Figure A.6.3.: Firefighter connection for wet standpipe


Figure A.7.1. (A): single zone system

Figure A-7.1. (B): two-zone system


Figure A-7.1. (C): multi-zones system


Figure A.7.3.2. (A).: Location on ladder fire hose connection.


Figure A.7.3.2. (b).: Location hose connections on the horizontal exit


Figure A.7.3.2. (c).: Location hose connection in the exit passageway

Potrebbero piacerti anche