2.

Measurement Reading Screens


In normal operation the user is presented with one of the measurement reading
screens out of several screens. These screens may be scrolled through one at a
time in incremental order by pressing the Up keyand in decremental order
by pressing Down key.
Measured Parameters
SystemVoltage
SystemCurrent
Frequency
Voltage VL1-N(4wire only)
Voltage VL2-N(4wire only)
Voltage VL3-N(4wire only)
Voltage VL1-L2
Voltage VL2-L3
Voltage VL3-L1
Current L1
Current L2
Current L3
Active Energy (8 Digit resolution)
Units of measurement
Volts
Amps
Hz
Volts
Volts
Volts
Volts
Volts
Volts
Amps
Amps
Amps
kWh
TABLE 1:
15000501_Rev. B 08/12
3 Phase (3Wire / 4Wire)
Three Phase Multi-function Digital Meter
Installation & Operating Instructions
Section Contents
1. Introduction
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
3.2 Set Up Screens
3.2.1 SystemType
3.2.2 Potential Transformer Primary value
3.2.3 Current Transformer Primary value
3.2.4 Current Transformer Secondary value
3.2.5
3.2.6 Reset
3.2.7 RS 485 DeviceAddress
3.2.8 Auto Scrolling
3.2.9 LowCurrent noise cutoff
3.2.10 RS 485 Baud Rate
3.2.11 RS 485 Parity selection
Energy Display on modbus
3.2.12 Energy Digit Rollover(reset) count
8. Specification
6. Installation
6.1 EMC Installation Requirements
6.2 Case Dimensions and Panel Cut-out
6.3 Wiring
6.4 Auxiliary Supply
6.5 Fusing
6.6 Earth / Ground Connections
7. Connection Diagrams
9. Connection for Optional RS 485 (Modbus)
ModBus ( RS 485 ) option 4.
1. Introduction
This instrument is a panel mounted 96 x 96mmDIN Quadratic Digital
metering systemfor the measurement important electrical parameters like
AC Voltage, AC Current, Frequency, Power, Energy(Active / Reactive / Apparent) .
The instrument integrates accurate measurement technology (All Voltages &
Current measurements are True RMS upto 15th Harmonic) with 3 line 4 digits
Ultra high brightness LEDdisplay.
The instrument can be configured and
programmed at site for the following : PT
Primary, CT Primary, CT Secondary (5A or
1A) and 3 phase 3Wor 4Wsystem.
The front panel has two push buttons through
which the user may scroll through the
available measurement readings, reset the
energy , Min/Max (SystemVoltage
and SystemCurrent) and configure the product.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
Down Up
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Active Power (System/ Phase (4 wire only) )
Reactive Power (System/ Phase ) (4 wire only)
Apparent Power (System/ Phase ) (4 wire only)
Power Factor (System/ Phase ) (4 wire only)
Kwatts
KVAr
KVA
Screen 5 : Neutral current ( for 4Wonly ) ,
Screen 7 : Active Energy
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Screen 8 : Reactive Energy
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Screen 9 : Apparent Energy
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Enter Password, first digit entered, prompt for second
digit.
(* Denotesthat decimal point will beflashing).
Usethe Down keytoscroll thevalueof thesecond
digit from0throughto9, thevaluewill wrapfrom9
roundto0.
Pressthe Up keytoadvancetonext digit.
3. Programming
The following sections comprise step by step procedures for configuring the
Instrument for individual user requirements.
To access the set-up screens press and hold the
Key simultaneously for 5 seconds. This will take the User into the Password
Protection Entry Stage (Section 3.1).
3.1. Password Protection
Password protection can be enabled to prevent unauthorised access to set-up
screens, by default password protection is not enabled.
Password protection is enabled by selecting a four digit number other than 0000,
setting a password of 0000 disables the password protection.
Downand Up
Enter Password, prompt for first digit.
(* Denotesthat decimal point will beflashing).
Pressthe Down keytoscroll thevalueof thefirst digit
from0throughto9, thevaluewill wrapfrom9roundto0.
Pressthe Up keytoadvancetonext digit.
Inthespecial casewherethePasswordis0000 pressing
the Up keywhenpromptedfor thefirst digit will
advancetothePasswordConfirmed screen.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Enter Password, seconddigit entered, prompt for third
digit.
(* Denotesthat decimal point will beflashing).
Usethe Down keytoscroll thevalueof thethird
digit from0throughto9, thevaluewill wrapfrom9
roundto0.
Pressthe Up keytoadvancetonext digit.
Enter Password, thirddigit entered, prompt for fourth
digit.
(* Denotesthat decimal point will beflashing).
Usethe Down keytoscroll thevalueof thefourth
digit from0throughto9, thevaluewill wrapfrom9
roundto0.
Pressthe Up keytoadvancetoverificationof the
password.
Enter Password, fourthdigit entered, awaiting
verificationof thepassword.
Passwordconfirmed.
Pressing Down keywill advancetotheNew/
changePassword entrystage.
Pressingthe Up keywill advancetothe Set up
screen. (Seesection3.2).
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
5.
kVArh Reactive Energy (8 Digit resolution)
Apparent Energy (8 Digit resolution)
Screen 12 : Phase Power (R)
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reactive/ Apparent /Active
( for 4Wonly )
Screen 13 : Phase Power (Y)
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reactive/ Apparent /Active
( for 4Wonly )
Screen 14 : Phase Power (B)
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reactive/ Apparent /Active
( for 4Wonly )
Screen 15 : Phase Power Factor
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
(Phase R / Y / B) ( for 4Wonly )
Phaser Diagram
Screen 2 : Line to Neutral Voltages
(for 4 wire only)
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
KVArh
Screen 4 : Line Currents
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
KVArh
Screen 1 : Systemscreen
(SystemVoltage, SystemCurrent,
SystemActive Power)
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
KVArh
Screen 3 : Line to Line Voltages
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
x1000
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
KVArh
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Sys. Power Factor Frequency,
KVArh
Screen 6 : SystemPower ( Reactive,
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
x1000
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Apparent, Active)
KVArh
Screen 10 : Min Sys Voltage &Current
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
KVArh
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Screen 11 : Max Sys Voltage
&Current
KVArh
Amp Neutral Current ( 4 wire only )
kVAh
RISH M aster 3428
Pressing Up keysetsthedisplayedvalueand
will advancetotheReset menu . (Seesection3.2.6)
Energy Display OnModbus Confirmation.
Thisscreenwill onlyappear followinganedit of the
Energy Display OnModbus.
VRY
KVAr
Sys
V
KW
VBR
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
PhY
x1000
Hz
KVAh
PhY
Note : Default value is set to 1 i.e. Energy on Modbus will be in
terms of Wh/VArh/VAh/Ah resp.
Pressingthe Down keywill enter the
OnModbusEdit stagebyblankingthebottomlineof the
display.
Energy Display
Pressing Up keyacceptsthepresentsvalue
andadvancestotheReset menu (Seesection3.2.6).
3.2.5. Energy Display on modbus
Pressingthe Down keywill enter theEnergy Display
OnModbusEdit modeandscroll thevaluethroughthevalues
1,2&3wrappingbackto1
1: EnergyInWh
2: EnergyinKWh
3: EnergyinMWh.
Pressingthe Up keyadvancestotheReset menu
(Seesection3.2.6).
VRY
KVAr
Sys
V
KW
VBR
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
PhY
x1000
Hz
KVAh
PhY
Thisscreen enableuser toset energyintermsof Wh/ KWh/ MWhonRS485Output dependingasper the
requirement .Sameapplicablefor all typesof energy.
CTSecondaryvalueconfirmation
Thisscreenwill onlyappearsfollowinganedit of CT
secondaryvalue.
If secondaryvalueshownisnot correct, pressingthe
Downkeywill returntoCTsecondaryedit stageby
blankingthebottomlineof thedisplay.
Pressing Up keysetsthedisplayedvalueand
will advancetoEnergyDisplayonModbusmenu.
(Seesection3.2.5)
Password Incorrect.
The unit has not accepted the
Password entered.
Pressing the " Down" key will return to
the Enter Password stage.
Pressing the Upkey exits the
Password menu and returns operation
to the measurement reading mode.
New/ChangePassword
(*Decimal point indicatesthat thiswill beflashing).
Pressingthe Down keywill scroll thevalueof the
first digit from0throughto9, thevaluewill wrapfrom9
roundto0.
Pressingthe Up keytoadvancetheoperationto
thenext digit andsetsthefirst digit, inthiscaseto2
New/ ChangePassword, first digit entered, promptingfor
seconddigit. (*Decimal point indicatesthat thiswill be
flashing).
Pressingthe Down keywill scroll thevalueof the
seconddigit from0throughto9, thevaluewill wrapfrom
9roundto0.
Pressingthe Up keytoadvancetheoperationtothe
next digit andsetstheseconddigit, inthiscaseto1
New/ ChangePassword, thirddigit entered, prompting
for fourthdigit. (* denotesthat decimal point will be
flashing).
Pressingthe Down keywill scroll thevalueof the
fourthdigit from0throughto9, thevaluewill wrapfrom
9roundto0.
Pressingthe Up keytoadvancetheoperationto
theNewPasswordConfirmed andsetsthefourthdigit,
inthiscaseto3.
NewPasswordconfirmed.
Pressingthe Down keywill returntothe
New/ChangePassword.
Pressingthe Up keywill advancestotheSet up
screen.(seesection3.2).
New/ ChangePassword, seconddigit entered,
promptingfor thirddigit. (*decimal point indicatesthat
thiswill beflashing).
Pressingthe Down keywill scroll thevalueof the
thirddigit from0throughto9, thevaluewill wrapfrom9
roundto0.
Pressingthe Up keytoadvancetheoperationto
thenext digit andsetsthethirddigit, inthiscaseto5
3.2.1. System Type
3.2 Set Up Screens
Thisscreenisusedtoset thesystemtype.
Systemtype3 for 3phase3wire&4 for 3phase
4wiresystem.
Pressingthe Up keyacceptsthepresent valueand advances
tothePotential transformer primaryvalueEdit menu(seesection3.2.2)
Pressingthe Down keywill enter thesystemtypeedit mode
andscroll thevaluesthroughvaluesavailable.
Pressingthe Up keyadvancestothesystemtypeconfirmationmenu.
Thisscreenwill onlyappear followingtheedit of
systemtype. If systemtypeistobeDownedagain,
pressingthe Down keywill returntothesystemtype
edit stagebyblankingthebottomlineof thedisplay
pressingthe Up keysetsthedisplayedvalueand
will advancetoPotential Transformer PrimaryValue
Edit menu. (Seesection3.2.2)
System Type Confirmation
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Potential Transformer Digit Edit
Pressingthe Down keywill scroll thevalueof
themost significant digit from0throughto9unless
thepresentlydisplayedPotential Transformer Primary
Valuetogether withtheCurrent Transformer Primary
Value, previouslyset, wouldresult inamaximumpower
of greater than1000MVAper phase inthat case
thedigit rangewill berestricted.
Pressingthe Up keyacceptsthepresent value
at thecursor positionandadvancesthecursor tothe
next lesssignificant digit.
3.2.2. Potential Transformer Primary Value
Thenominal full scalevoltagewhichwill bedisplayedastheL1-N, L2-NandL3-Nfor afour wire(Ln)
systemor asL1-2, L2-3andL3-1inathreewire(LL) system. Thisscreenenablestheuser todisplay
thelinetoneutral andlinetolinevoltagesinclusiveof anytransformer ratios, thevaluesdisplayed
represent thevoltageinkilovolts(notethex1000enunciator).
Pressingthe Up keyacceptsthepresent value
and advancestotheCurrent Transformer Primary
Valueedit menu. (SeeSection3.2.3)
Pressingthe Down keywill enter thePotential
Transformer PrimaryValueEdit mode.
Initiallythemultiplier must beselected, pressingthe
Down keywill movethedecimal point positiontothe
right until it reaches###.#after whichit will returnto
#. ###.
Pressingthe Up keyacceptsthepresent
multiplier (decimal point position) andadvancestothe
Potential Transformer Digit Edit mode.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
restricted, thevaluewill wrap. Example: If primaryvalue
of PTisset as400kV(maxvalue) thenprimaryvalueof
Current isrestrictedto1736A.
Pressingthe Up keywill advancetothenext less
significant digit. (* Denotesthat decimal point will be
flashing).
Note: theflashingdecimal pointindicatesthecursorposition, asteadydecimal pointwill bepresent
toidentifythescalingofthenumberuntil thecursorpositioncoincideswiththesteadydecimal point
position.Atthisstagethedecimal pointwill flash.
Whentheleast significant digit hasbeenset pressingthe Up keywill advancetothe
Potential Transformer PrimaryValueConfirmation stage.
Screenshowingdisplayof 0.120kVi.e. 120Voltsindicatingsteadydecimal point andcursor
flashingat thehundredsof volts position.
3.2.3. Current TransformerPrimary Value
Thenominal Full ScaleCurrent that will bedisplayedastheLinecurrents. Thisscreenenablesthe
user todisplaytheLinecurrentsinclusiveof anytransformer ratios, thevaluesdisplayedrepresent
theCurrent inAmps.
Pressingthe Up keyacceptsthepresent valueandadvancestotheCurrent Transformer
SecondaryValue (Seesection3.2.4)
Pressingthe Down keywill enter theCurrent
Transformer PrimaryValueEdit mode. Thiswill scroll the
valueof themost significant digit from0throughto9,
unlessthepresentlydisplayedCurrent Transformer
PrimaryValuetogether withthePotential Transformer
PrimaryValueresultsinamaximumpower of greater
than1000MVAinwhichcasethedigit rangewill be
Potential Transformer PrimaryValueConfirmation
Thisscreenwill onlyappear followinganedit of the
Potential Transformer PrimaryValue.
If thescalingisnot correct, pressingthe Down
keywill returntothePotential Transformer Primary
ValueEdit stagewiththedigitsflashingindicating
that themultiplier (decimal point position) shouldbe
selected.
Pressingthe Up keysetsthedisplayedvalue
andwill advancetotheCurrent Transformer Primary
Value(Seesection3.2.3.)
Note: 0.120kVi.e. 120V for 4W L-N
120V fpr 3W L-L
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
TheMaximumPower restrictionof 1000MVArefersto120%of nominal current and120%of
nominal voltage, i.e, 694.4MVAnominal power per phase.
Whentheleast significant digit hadbeenset, pressingthe Up keywill advancetothe
Current Transformer PrimaryValueConfirmation stage.
Theminimumvalueallowedis1, thevaluewill beforcedto1if thedisplaycontainszerowhenthe
Up keyispressed.
CurrentTransformerPrimaryValueConfirmation.
Thisscreenwill onlyappear followinganedit of the
.
If thescalingisnot correct, Pressingthe Down key
will returntothe Edit
stagewiththemost significant digit highlighted(associated
decimal point flashing) andthebottomlineof thedisplay
will beblanked.
Pressingthe Up keysetsthedisplayedvalueand
will advancetotheCurrent Transformer SecondaryValue
Edit menu. (Seesection3.2.4).
Current
Transformer PrimaryValue
Current Transformer PrimaryValue
3.2.4. Current Transformer Secondary Value
Thisscreenisusedtoset thesecondaryvaluefor
Current Transformer. Secondaryvalue5 for 5Aor
1 for 1Acanbeselected. Pressing Up key
acceptsthepresent valueandadvancestothe
EnergyDisplayonModbusMenu(Seesection3.2.5).
Pressingthe Down keywill enter theCT
Secondaryvalueedit modeandscroll thevalue
throughthevaluesavailable.
Pressingthe Up keywill advancetotheCT
Secondaryvalueconfirmation.
3.2.6. Reset
Thefollowingscreensallowtheuserstoreset theall Energy, Lo(Min), hi(Max) .
Reset (None)
Pressing Up keywill not reset andwill advance
toModbusaddressset menu.(Seesec.3.2.7)
Pressingthe Down keywill enter theReset
option modeandscroll thevalue
throughtheoptionandwrappingbacktoNone.
Pressing Up keyadvancestoModbusaddressset menu.
(seesection3.2.7).
Reset optionselect, (Reset Energy)
Theuser hasscrolledthroughtotheE Energy
value.
Pressing Up keywill select thevalueand
advancetotheReset EnergyConfirmation Mode.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reset EnergyConfirmation.
Pressing Up keyresetstheall Energyparameters
andadvancestotheModbusaddressset
(seesection3.2.7.)
Pressingthe Down keywill re-enter theReset
option mode.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reset optionselect, (Reset Lo)
Theuser hasscrolledthroughtotheLo (Min)
Pressing Up keywill select thevalueand
advancetotheReset LoConfirmation Mode.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reset LoConfirmation
Pressingthe Down keywill re-enter the
Reset optionSelect mode.
Pressing Up keyresetstheLo(Min)
readingsandadvancestoModbusAddressset menu
(seesection3.2.7).
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reset optionselect, (Reset Hi)
Theuser hasscrolledthroughtotheHi (Max)
Pressing Up keywill select thevalueand
advancetotheReset Hi Confirmation Mode.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reset hI (Max) Confirmation.
Pressingthe Down keywill re-enter the
Reset optionSelect mode.
Pressing Up keyresetsthehI (Max)
readingsandadvancestoModbusaddressset menu
(seesection3.2.7).
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reset optionselect, (Reset ALL)
Theuser hasscrolledthroughtotheALL .
Pressing Up keywill select thevalueand
advancetotheReset ALLConfirmation Mode.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Reset ALLConfirmation.
Pressingthe Down keywill re-enter the
Reset optionSelect mode.
Pressing Up keyresetsALLthereadings
andadvancestotheModbusaddressset menu
(seesection3.2.7).
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
3.2.7 Address Setting :
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
This screen applies to the RS 485 output only.
This screen allows the user to set RS485 address for instruments
Enter Address, prompt for first digit.
(* Denotesthat decimal point will beflashing).
Pressthe Down keytoscroll thevalueof thefirst digit
Pressthe Up keytoadvancetonext digit.
The range of allowable address is 1 to 247 .
Enter Address, first digit entered, prompt for seconddigit
(* Denotesthat decimal point will beflashing).
Usethe Down keytoscroll thevalueof theseconddigit
Pressthe Up keytoadvancetonext digit.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Enter Address, seconddigit entered, prompt for thirddigit
(* Denotesthat decimal point will beflashing).
Usethe Down keytoscroll thevalueof thethirddigit
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Enter Address for thirddigit .
Pressthe Up keytoadvancetoAddressconfirmationScreen.
3.2.8 Auto Scrolling :
Thisscreenallowsuser toenablescreenscrolling.
Pressing Up keyacceptsthepresent statusand
advancetotheLowCurrent noisecutoff (seesection3.2.9).
AutoscrollingEdit.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Pressingthe Up keywill select thestatusdisplayedand
advancetotheLowCurrent noisecutoff (seesection3.2.9).
Pressingthe Down keywill enter theAutoScreen
ScrollingEdit andtogglethestatusYes andNo.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
3.2.10 RS 485 Baud Rate :
Thisscreenallowstheuser toset BaudRateof RS485port.
Thevaluesdisplayed onscreenareinkbaud..
Pressing Up keyacceptsthepresent valueand
advancetotheParity Selection(seesection3.2.11).
Pressingthe Down keywill enter theBaudRate
Edit modeandscroll thevaluethrough2.4, 4.8, 9.6, 19.2and
backto2.4
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
AddressconfirmationScreen.
ThisScreenconfirmsthe Address set byuser .
Pressthe Up keytoadvancetonext Screen
AutoScrolling ( 3.2.8)
3.2.9. Low Current noise cutoff.
Thisscreenallowstheuser toset Lownoisecurrent cutoff inmA.
Pressing Up keyacceptsthepresent valueand
advancetoModbusbaudratesetting
Pressingthe Down keywill enter theLowcurrent
noisecutoff Edit modeandscroll theValue through0&30
andwrappingbackto0. Setting30will displaymeasured
currentsas 0below30mA.
Lowcurrent cutoff Edit.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Lowcurrent noisecutoff Confirmation.
pressingthe Down keywill re-enter theLowcurrent
Noisecutoff Edit mode.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Pressing Up keyset displayedvalueand
will advancetoModbusbaudratesetting.
(Seesection3.2.10)
Pressing Up keyset displayedselectedParity and
will advancetoEnergyDigit Rollover (reset) count settingscreen
(Seesection3.2.12)
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
3.2.11 RS 485 Parity Selection :
Thisscreenallowstheuser toset Parity&number of stopbitsof RS485port.
Pressing Up keyacceptsthepresent valueand will advance
toEnergyDigit Rollover (reset) count settingscreen(Seesection3.2.12).
Pressingthe Down keywill enter theParity&stopbit
Edit modeandscroll thevaluethrough
odd: oddparitywithonestopbit
no1 : noparitywithonestopbit
no2 : noparitywithtwostopbit
E: evenparitywithonestopbit
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
RS485Parityconfirmation:
Pressing Down keywill bere-enter intoParityEdit mode.
4. RS 485 ( ModBus ) Output :
Theinstrument supportsMODBUS(RS485) RTUprotocol( 2-wire) .
Connectionshouldbemadeusingtwistedpair shieldedcable. All "A" and"B" connectionsaredaisychained
together. ThescreensshouldalsobeconnectedtotheGnd terminal. Toavoidthepossibilityof loopcurrents,
anEarthconnectionshouldbemadeat onepoint onthenetwork.Loop(ring) topologydoesnot requireany
terminationload. Linetopologymayor maynot requireterminatingloadsdependingonthetypeandlength
of cableused. Theimpedanceof theterminationloadshouldmatchtheimpedanceof thecableandbeat both
endsof theline. Thecableshouldbeterminatedat eachendwitha120ohm(1/4Watt min.) resistor.
RS485network supports maximumlengthof 1.2km. IncludingtheMaster, amaximumof 32instruments
canbeconnectedinRS485network.Thepermissibleaddressrangefor Instrument isbetween
1and247 for 32instruments. Broadcast Mode (address0) isnot allowed.
Themaximumlatencytimeof an is200msapprox. i.e. thisistheamount of timethat
canpassbeforethefirst responsecharacter isoutput.
Instrument
After sendinganyquerythroughsoftware( of theMaster) , it must allow 200ms of timetoelapsebefore
assumingthat theInstrument isnot goingtorespond. If slavedoesnot respondwithin200ms,
Master canignorethepreviousquery and canissuefreshquerytotheslave.
TheeachbyteinRTUmode has followingformat:
8-bit binary, hexadecimal 0-9, A-F
2hexadecimal characterscontainedineach8-bit fieldof
themessage
4bytes(32bits) per parameter.
Floatingpoint format ( toIEEE754)
Most significant bytefirst (Alternative least significant bytefirst)
FormatofDataBytes
2byteCyclical RedundancyCheck(CRC) ErrorCheckingBytes
1start bit,
8databits, least significant bit sent first
1bit for even/oddparity
1stopbit if parityisused; 1or 2bitsif noparity
Byteformat
CommunicationBaudRateisuser selectablefromthe front panel between 2400, 4800, 9600, 19200bps.
Twoconsecutive16bit registers represent oneparameter. Refer tablebelowfor theaddresses of
3Xregisters andaddresses for theparametersmeasuredbytheinstruments.
RegisterAddresses:
Accessing3Xregisterforreadingmeasuredvalues:
Eachparameter isheldinthe3Xregisters. ModbusCode04 isusedtoaccessall parameters.
1Word=16bit register
Toread parameter
1) Volts3: Start address=04(Hex) Noof words=02
2) Current 3: Start address=0A(Hex) Noof words=02
EachQuery for reading thedatamust berestrictedto40parametersor less. Exceedingthe40parameter
limit will causeaModBusexceptioncodetobereturned.
Address
(Register)
Parameter
No.
Parameter ModbusStartAddressHex
HighByte LowByte HighByte HighByte
3P4W 3P3W
30001 1 Volts1 00 0
30003 2 Volts2 00 2
30005 3 Volts3 00 4
30007 4 Current 1 00 6
30009 5 Current 2 00 8
30011 6 Current 3 00 A
30013 7 W1 00 C X
30015 8 W2 00 E X
30017 9 W3 00 10 X
30019 10 VA1 00 12 X
30021 11 VA2 00 14 X
30023 12 VA3 00 16 X
30025 13 VAR1 00 18 X
30027 14 VAR2 00 1A X
30029 15 VAR3 00 1C X
30031 16 PF1 00 1E X
30033 17 PF2 00 20 X
30035 18 PF3 00 22 X
30037 19 --------- 00 24
30039 20 00 26
30041 21 00 28
30043 22 VoltsAve 00 2A
30045 23 VoltsSum 00 2C
30047 24 Current Ave 00 2E
30049 25 Current Sum 00 30
30051 26 WattsAve 00 32
30053 27 WattsSum 00 34
30055 28 VAAve 00 36
30057 29 VASum 00 38
30059 30 VAr Ave 00 3A
30061 31 VAr Sum 00 3C
30063 32 PFAve 00 3E
30065 33 PFSum 00 40
30067 34 00 42
30069 35 00 44
30071 36 Freq 00 46
X
30071 36 Freq 00 46
30073 00 48 37 Watt Hour 00
30075 00 4A 38 00
30077 39 VARHour 00 4C
30079 40 00 4E
30081 41 VAh 00 50
30133 67 VoltsAveMax 00 84
30135 68 VoltsAveMin 00 86
30141 71 Current AveMax 00 8C
30143 72 Current AveMin 00 8E
30201 101 VL1- 2( Calculated) 00 C8 X
30203 102 VL2- 3( Calculated) 00 CA X
30205 103 VL3- 1( Calculated) 00 CC X
30225 113 I neutral 00 E0 X
Table:forReadingtheMeasuredParametersfromInstrument
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
---------
---------
----
----
----
---- ----
----
----
----
----
----
---------
---------
---------
--------- -----
-----
-----
-----
VRY
KVAr
Sys
V
KW
VBR
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
VRY
KVAr
Sys
V
KW
VBR
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
PhY
x1000
Hz
KVAh
PhY
3.2.12 Energy Digit Rollover (reset) count :
Thisscreen
whichenergywill rollbacktozerodependsuponsettingof Wh,KWh,
&MWh.
enablesuser for settingmaximumenergycount after
Pressingthe Down keywill enter the
count edit mode. Thiswill scroll thevalueof reset count from
7to14forWh,from7to12forKWh&from7to9forMWh.
Energydigit reset
Pressingthe Up keysetsthedisplayedvalueand

will exit from
set up.
Pressing Upkey will advancetoEnergydigit reset count confirmationscreen.
Pressingthe Down keywill re-enter Energydigit reset count edit mode.
Ex. If energy isset Wh&It will set Energydigit
count to10thenenergywill reset after 9,999,999,999 &thenwill
displayonmodbus
Note:
1)Defaultvalueissetto14i.eifenergycountcrosses14digititwill rollbacktozero.
2)Energydisplaysonmodbusissetto(2)&energydigitresetcount issetto12.Energyscreen
ondisplaywill show-------i.eEnergyoverflow.whenenergycrossesthe11digitcount.
3)Energydisplaysonmodbusissetto(3)&energydigitresetcount issetto9.Energyscreen
ondisplaywill show-------i.eEnergyoverflow.whenenergycrossesthe8digitcount.
rollbacktozero.
Pressingthe Up keywill set thevalueandexit fromset up.
VRY
KVAr
Sys
V
A
VYB
KVA
Min
KW
VBR
Max
x1000
KVArh
x1000
x1000
IN
PhR
Hz
KVAh
PhY
P.F.
KWh
PhB
Pressingthe Up keywill select thevalueandadvances
totheParity Selection(seesection3.2.11).
RS485BaudRateconfirmation:
Pressing Down keywill bere-enter intoBaudRateEdit mode.
Accessing4XregisterforReading&Changingthesettinginsideinstrument:
Eachsettingisheldinthe4Xregisters.ModBuscode03isusedtoreadthecurrent settingandcode16
isusedtowrite/changethesetting.
ExceptionCases:Anexception codewill begeneratedwheninstrment receivesModBusquerywith
validparity&error checkbut whichcontainssomeother error ( e.g. Attempt toset floatingpoint variableto
aninvalidvalue) Theresponsegeneratedwill beFunctioncode ORedwithHEX(80H).
Theexceptioncodesarelistedbelow
01 Illegal function Thefunctioncodeisnot supportedbyinstrument.
02 Illegal Data
Address
Attempt toaccessaninvalidaddressor anattempt toread
or writepart of afloatingpoint value
03 Illegal Data
Value
Attempt toset afloatingpoint variabletoaninvalidvalue
Functioncode:
03 ReadHoldingRegisters Readcontent of read/writelocation( 4X)
04 Readinput Registers Readcontent of readonlylocation( 3X)
16 PresetsMultipleRegisters Set thecontent of read/ writelocations( 4X)
Address
(Register)
Parameter
No.
Parameter ModbusStartAddressHex
HighByte LowByte HighByte HighByte
40007 4 SysVoltage 00 06
Read/Write
Readonly
40009 5 SysCurrent 00 08 Readonly 40009 5 SysCurrent 00 08 Readonly
5 SysType 00 0A 40011 6 00 Read/ Write
40013 7
00 0E 40015 8 EnergyReset 00 Writeonly
00 14 40021 11 ModAddr. 00 Readonly
40023 12
00 18 40025 13 MinReset 00 Writeonly
00 1A 40027 14 MaxReset 00 Writeonly
40029 15
40031 16
00 24 40037 19 SysPower 00 ReadOnly
00 26 40039 20 00 Read/ Write
---- ---- ---- ----
---- ---- ---- ----
---- ---- ---- ----
---- ---- ---- ----
Address Parameter Description
40007 System
Voltage
ThisaddressisreadonlyanddisplaysSystemVoltage
40009 System
Current
ThisaddressisreadonlyanddisplaysSystemCurrent
Thisaddressisusedtoset theSystemtype.
Writeoneof thefollowingvaluetothisaddress.
2=3Phase3Wire
3=3Phase4Wire.
Writinganyother valuewill returnerror .
40011 System
Type
40013
40015 Reset Energy
Counter
Thisaddressisusedtoreset theEnergyCounter.
Writezerovalue tothisregister toreset theenergycounter.
Writinganyother valuewill returnanerror.
40021 Instrument
Address
Thisaddressisreadonly&displayinstrument address
between1to247.
40023
40025 Min- Reset Thisaddressisusedtoreset theMinparametersvalue.
WriteZerovaluetothisregister toreset theMinparameters.
Writinganyother valuewill returnanerror.
40027 Max- Reset Thisaddressisusedtoreset theMaxparametersvalue.
WriteZerovaluetothisregister toreset theMaxparameters.
Writinganyother valuewill returnanerror.
40029
40031
Explanationfor4Xregister:
40037 SysPower System Power isthemaximumsystempower basedonthe
valuesof systemtype, systemvoltsandsystemcurrent.
40041 WordOrder WordOrder controlstheorder inwhichinstrument
receivesor sends floating- point numbers:- normal or reversed
register order . Innormal mode, thetworegistersthat makeup
afloatingpoint numbersaresent most significant bytesfirst.
Inreversedregister mode, thetworegistersthat makeup
afloatingpoint numbersaresent least significant bytesfirst.
Toset themode, writethevalue2141.0 intothisregister-
theinstrument will detect theorder usedtosendthisvalueand
set that order for all ModBustransactioninvolvingfloatingpoint
numbers.
---- ----
---- ----
----
----
----
----
6. Installation
Mounting is by four side clamps, slide the side clamps through side slot till side clamp
gets firmly locked in a groove (Refer fig.) Consideration should be given to the space
required behind the instrument to allow for bends in the connection cables.
SLIDEINTHISDIRECTIONANDLOCK
PANEL
Instrument
Frontside
Refer the diagramfor explanation 5. Phaser Diagram :
Inductive
Capacitive
Capacitive Inductive
Connections Quadrant
Power ( P )
Sign of
Active
Power ( Q )
Sign of
Reactive
Factor ( PF )
Sign of
Power
Inductive /
Capacitive
Import 1 + P + Q + L
Import 4 + P - Q + C
Export 2 - P + Q - C
Export 3 - P - Q - L
Inductive means Current lags Voltage
Capacitive means Current leads Voltage
The instrument displays Active power ( P )with +( positive sign ) ,
the connection is Import .
When instrument displays Active power ( P )with - ( negative sign ) ,
the connection is Export .
6.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives
when installed to a good code of practice for EMC in industrial environments,
e.g.
1. Screened output and lowsignal input leads or have provision for fitting
RF suppression components, such as ferrite absorbers, line filters etc., in
the event that RF fields cause problems.
Note: It is good practice to install sensitive electronic instruments that are
performing critical functions, in EMC enclosures that protect against electrical
interference which could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a
source of interference.
3. To protect the product against permanent damage, surge transients must
be limited to 2kV pk. It is good EMC practice to suppress differential
surges to 2kV at the source. The unit has been designed to automatically
recover in the event of a high level of transients. In extreme
circumstances it may be necessary to temporarily disconnect the
auxiliary supply for a period of greater than 5 seconds to restore correct
operation.
4. ESDprecautions must be taken at all times when handling this product.
The Current inputs of these products are designed for connection in to
systems via Current Transformers only, where one side is grounded.
Caution
1. In the interest of safety and functionality this product must be installed by
a qualified engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some of the terminal
connections of this unit. Ensure that all supplies are de-energised before
attempting any connection or disconnection.
3. These products do not have internal fuses therefore external fuses must
be used to ensure safety under fault conditions.
As the front of the enclosure conforms to IP54 it is protected fromwater spray
fromall directions, additional protection to the panel may be obtained by the
use of an optional panel gasket. The terminals at the rear of the product
should be protected fromliquids.
The instrument should be mounted in a reasonably stable ambient
temperature and where the operating temperature is within the range
0
-10 to 55 C . Vibration should be kept to a minimumand the product should
not be mounted where it will be subjected to excessive direct sunlight.
6.2 Case Dimension and Panel Cut Out
3.78
96mm
FRONT DISPLAY
AREA
3.78
96mm
3.15
80mm
3.62
92mm
PANEL CUTOUT
3.62
92mm
MAX PANEL THICKNESS 0.18,5mm
6.4 Auxiliary Supply
The instrument should ideally be powered froma dedicated supply, however
it may be powered fromthe signal source, provided the source remains within
the limits of the chosen auxiliary voltage.
6.5 Fusing
It is recommended that all voltage lines are fitted with 1 amp HRC fuses.
6.6 Earth/Ground Connections
For safety reasons, CT secondary connections should be grounded in
accordance with local regulations.
6.3 Wiring
Input connections are made directly to screw-type terminals with indirect
wire pressure. Numbering is clearly marked in the plastic moulding. Choice of
cable should meet local regulations. Terminal for both Current and Voltage
2
inputs will accept upto 3mm x 2 diameter cables.
Note : It is recommended to use wire with lug for
connection with meter.
7. Connection Diagrams
3-PHASE4-WIREUNBALANCEDLOAD
DIGITALMETERINGSYSTEM
2 5 8 11 1 3 4 6 7 9 13 14
L N
AUX
SUPPLY
P1 S1
S1 P1
P1 S1
L1
L2
L3
N
L
O
A
D
3-PHASE3-WIREUNBALANCEDLOAD
DIGITALMETERINGSYSTEM
P1 S1
P1 S1
L N
AUX
SUPPLY
L1
L2
L3
N
L
O
A
D
2 5 8 3 4 6 7 9
Operating Measuring Ranges
Voltage 5 .. 120 %of Rated Value
Current 5 .. 120 %of Rated Value
Frequency 40 .. 70 Hz
SystemCT primary values Std. Values upto 4kA (1 or 5Amp secondaries)
8. Specification :
System
3 Phase 3 Wire / 4 Wire programmable at site
Inputs
Nominal input voltage
(Three wire and Four wire)
Max continuous input
voltage
Max short duration input
voltage
Nominal input voltage burden
57.7 V to 277V (100V to 480 V ) L-N L-N L-L L-L
120%of Rated Value
2 x Rated Value
(1s application repeated 10 times
at 10s intervals)
0.2VA approx. perphase
Nominal input current 1A / 5A AC rms programmable at site
Max continuous input current 120%of Rated Value
Nominal input current burden 0.6VA approx. per phase
Max short duration current input 20 x (1s application repeated Rated Value
5 times at 5 min. intervals)
Auxiliary
a.c. supply voltage tolerance +20 %/ -15 %of Rated Value
a.c. supply frequency range 45 to 66 Hz
a.c. supply burden 4.5VA
Power Factor 0.8 Lag ... 1 ... 0.8 Lead
d.c. supply burden 3W
Standardnominal Auxillary
supply
110V /50 Hz , 230V /50 Hz ,380V , AC AC AC/50 Hz
100 - 250V AC- DC, 12 - 48V DC voltages &Frequency
00 3 04 40005 EnergydisplayonModbus

Read/ Write
00 28 40041 21 WordOrder 00 WriteOnly
Energydigit Rollover(reset) count
40005
Thisaddressisusedtoset energydisplayonmodbusinWh,
KWh
Energydisplay
onModbus
&MWh.
1=
3=EnergyinMWh.
Writeoneof thefollowingvaluetothisaddress.
EnergyinWh. 2=EnergyinKWh.
40039 Energydigit
Reset Count
Thisaddress
If Energy inWhcount will beset
inbetween7to14 r InKWhset inbetween7to12&InMWhset
isusedtosettingmaximumenergycount after
whichenergywill rollbacktozerodependsuponsettingof Wh,
KWh,&MWh. displayonmodbus
o
inbetween7to9.
Reference conditions for Accuracy :
0
23 C +2 C
50 or 60Hz +2%
Sinusoidal (distortion factor 0.005)
Rated Value +1 %
Reference temperature
Input frequency
Input waveform
Auxiliary supply voltage
Auxiliary supply frequency
Nominal range of use of influence quantities for measurands

0
0 to 50 C Temperature
Auxiliary supply voltage
Auxiliary supply frequency
Display
3 line 4 digits . Digit height 11mm
Approx. 1 seconds
LED
Update
Controls
Two push buttons User Interface
Standards
IEC 61326
10V/mmin-Level 3 industrial lowlevel
electromagnetic radiation environment
IEC 61000-4-3.
IEC 61010-1 , Year 2001
EMC Immunity
Safety
Isolation
2.2 kV RMS 50 Hz for 1 minute
between all electrical circuits
Dielectric voltage withstand
test between circuits and
accessible surfaces
Temperature Coefficient
0
0.025%/ C for Voltage (50..120%of Rated Value)

0
(For Rated value range of use
Error change due to variation of an
influence quantity
2 * Error allowed for the reference
condition applied in the test.
Rated Value +1 %
Rated Value +10 %
Rated Value +10 %
0
0.05%/ C for Current ( 10..120%of Rated Value )
0
0... 50 C )
IEC 60529 IP for water &dust
Power Factor cos phi =1 for Active power
Accuracy
Voltage
Current
Active Power
Reactive Power
Apparent Power
Active Energy
Reactive Energy
Apparent Energy
Power Factor
Frequency
Standard (CL 1.0)
Optional (CL 0.5)
on request
Optional (CL 0.2)
on request
0.5 %of Range +
-
0.5 %of Range +
-
0.5 %of Range +
-
0.5 %of Range +
-
0.5 %of Range +
-
1.0 % +
-
1.0 % +
-
1.0 % +
-
1.0 %of Unity +
-
0.15 %of Mid Frequency +
-
0.5 %of Range
0.5 %of Range
0.5 %of Range
0.5 %of Range
0.5 %of Range
0.5 %
0.5 %
0.5 %
1.0 %of Unity +
- 0.5 %of Unity +
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
0.2 %of Range +
-
0.2 %of Range +
-
0.2 %of Range +
-
0.2 %of Range +
-
0.2 %of Range +
-
0.2 % +
-
0.2 % +
-
0.2 % +
-
Measurement error is much less than error specified above.Variation due to influence quantity
Is less than twice the error allowed for reference condition.
sin phi =1 for Reactive power
Voltage 50%.........100%of Rated Value
Current 10%.........100%of Rated Value
Environmental
0
-10 to 55 C
0
-20 to +65 C
0 .. 90 %RH

3 minute (minimum)
15g in 3 planes
10 .. 55 Hz, 0.15mmamplitude
IP 54 as per IEC 60529
Operating temperature
Storage temperature
Relative humidity
Warmup time
Shock
Vibration
Enclosure ( front only )
Enclosure
96mmx 96mmDIN Quadratic
Polycarbonate Housing ,
Screw-type terminals
<80 mm
0.620 kgApprox.
Style
Material
Terminals
Depth
Weight
Self extinguish &non dripping as per UL 94 V-0
ModBus ( RS 485 ) Option :
ModBus ( RS 485 ) Protocol
19200 , 9600 , 4800 or 2400 Baud Rate
( Programmable )
Odd or Even, with 1 stop bit, Parity
Or None with 1 or 2 stop bits
B A Gnd
RS485
9. Connection for Optional RS 485 (modbus):
RS 485 ( Modbus )