Single-phase or three-phase transformers which have protection elements against overloads, external short circuits in the low voltage network and surges. Available for single-phase applications in capacities ranging from 5 KVA through 167,5 KVA.
Single-phase or three-phase transformers which have protection elements against overloads, external short circuits in the low voltage network and surges. Available for single-phase applications in capacities ranging from 5 KVA through 167,5 KVA.
Single-phase or three-phase transformers which have protection elements against overloads, external short circuits in the low voltage network and surges. Available for single-phase applications in capacities ranging from 5 KVA through 167,5 KVA.
Aut. Norte, paraje el Noral. Copacabana-Antioquia, Colombia.
(574) 444 04 30 - (574) 274 14 14
www.rymel.com.co
2 Corporative Portfolio
Single-phase or three-phase transformers which have protection elements against overloads, external short circuits in the low voltage network and surges. They also have oil immersed fuses in the high voltage side to insulate them from the electrical network in case of internal faults. Available for single-phase applications in capacities ranging from 5 KVA through 167,5 KVA and for three-phase applications in capacities ranging from 15 KVA through 500 KVA with secondary voltage of 220 V and capacities of up to 1000 KVA with secondary voltage of 440 V. Manufactured meeting: ANSI-57.12.00, IEC-76 and NTC standars.
SELF-PROTECTED TRANSFORMERS
3 Corporative Portfolio
Conventional and submersible junction enclosures manufactured in accordance to ANSI C-57.12.25, ANSI C-57.12.26, ANSI C- 57.12.28, ANSI C-57.12.29, NTC 5110 and RETIE standards. It can be used for single-phase or three-phase applications, with 2, 3, 4, 5 or 6 junction points. Current capacity of 200 and/or 600 A, voltage ratings of up to 34,5 GrdY/19,92 KV and 150 KV BIL.
JUNCTION ENCLOSURES
4 Corporative Portfolio
Manufactured in accordance to: ANSI-C57.12.00, IEC-76, NTC and RETIE standards. Capacities ranging from 3 KVA through 500 KVA, high voltage ratings through 34,5 KV and 200 KV BIL.
Note: These dimensions are approximate. When buying a transformer, please ask for the real dimensions, as they may vary. CONVENTIONAL SINGLE PHASE TRANSFOMERS
5 Corporative Portfolio
Manufactured in accordance to: ANSI C-57.12.00, IEC-76, NTC and RETIE standards. KVA ratings from 15 KVA through 5000 KVA and high voltage ratings through 46 KV and 250 KV BIL.
NA: (Not Applicable). These transformers do not have wheels, but they have pole mounting device. Note: These dimensions are approximate. When buying a transformer, please ask for the real dimensions, as they may vary. CONVENTIONAL THREE PHASE TRANSFOMERS
6 Corporative Portfolio
Specifications single phase pad mounted transformers (Radial Feed and Loop Feed) DIMENSIONS (mm) KVA WEIGHT (KG) OIL VOLUME (L) A B C 25 458 260 940 1230 1000 37,5 480 250 940 1230 1000 50 510 235 940 1230 1000 75 625 250 1150 1230 1100 100 700 255 1150 1230 1100 167 870 260 1300 1300 1360
Note: These dimensions are approximate. When buying a transformer, please ask for the real dimensions, as they may vary.
SINGLE-PHASE PAD MOUNTED TRANSFORMER
7 Corporative Portfolio
Manufactured in accordance to: ANSI C-57.12.25, ANSI C-57.12.26, ANSI C- 57.12.28, ANSI C-57.12.29, NTC 5074 and RETIE standards. Available in capacities through 3000 KVA (Three phase transformers) and through 500 KVA (Single phase transformers). High voltage ratings through 34,5 GrdY/19.92 KV and 150 KV BIL.
CONFIGURATION:
THREE PHASE PAD MOUNTED TRANSFORMER
8 Corporative Portfolio
Note: These dimensions are approximate. When buying a transformer, please ask for the real dimensions, as they may vary.
SPECIFICATIONS Voltage range up to 25 KV/ 1,2 KV D/y Connection and 15KV/1,2 KV D/y Connection Three phase pad mounted transformers (Radial Feed Type) 15 KV DIMENSIONS (mm) KVA WEIGHT (KG) OIL VOLUME (L) A B C M N D 45 647 280 108 132 104 36 18 47 75 768 311 112 132 106 38 18 47 112,5 875 361 114 132 122 43 18 47 150 1000 393 114 132 122 47 18 47 225 1275 517 121 138 135 53 18 47 300 1433 569 125 138 139 56 18 47 400 1718 618 129 140 147 57 18 47 500 2965 753 131 152 148 62 18 47 630 2240 775 140 162 158 64 18 47 800 2720 905 165 166 158 63 18 47 SPECIFICATIONS Voltage range up to 35 KV/1,2 KV Y/y Connection Three phase pad mounted transformers (Radial Feed Type) DIMENSIONS (mm) KVA WEIGHT (KG) OIL VOLUME (L) A B C M N D 75 680 380 121 149 124 56 18 53 112,5 880 390 121 149 124 56 18 53 150 990 400 121 149 140 56 18 53 225 1200 450 127 164 146 56 18 53 300 1360 490 127 164 146 56 18 53 400 1730 565 143 174 161 62 18 53 500 2100 600 143 174 161 62 18 53 630 2615 990 145 160 175 75 18 53 800 3080 1065 156 174 168 68 18 53
9 Corporative Portfolio
SPECIFICATIONS Voltage range up to 15 KV / 1,2 KV D/y Connection Three phase pad mounted transformers (Loop Feed Type) DIMENSIONS (mm) KVA WEIGHT (KG) OIL VOLUME (L) A B C M N D 45 784 385 125 144 104 36 18 47 75 909 423 129 144 106 38 18 47 112,5 1027 489 131 144 115 43 18 47 150 1164 532 130 144 119 47 18 47 225 1462 682 136 152 132 53 18 47 300 1632 746 140 152 135 56 18 47 400 1925 790 144 152 143 57 18 47 500 2199 872 146 152 148 62 18 47 630 2420 930 155 166 159 64 18 47 800 3030 1140 166 168 148 64 18 47 SPECIFICATIONS Voltage range up to 25 KV / 1,2 KV D/y Connection Three phase pad mounted transformers (Loop Feed Type) DIMENSIONS (mm) KVA WEIGHT (KG) OIL VOLUME (L) A B C M N D 45 540 335 141 144 106 48 18 47 75 680 380 141 144 106 48 18 47 112,5 880 390 141 144 106 48 18 47 150 990 400 141 144 124 48 18 47 225 1200 458 151 159 130 56 18 47 300 1360 490 151 159 130 56 18 47 400 1730 565 151 169 147 60 18 47 500 2100 600 151 176 153 60 18 47 630 2500 970 160 168 163 68 18 47 800 3050 1170 166 170 160 69 18 47 SPECIFICATIONS Voltage range up to 35 KV / 1,2 KV Y/y Connection Three phase pad mounted transformers (Loop Feed Type) DIMENSIONS (mm) KVA WEIGHT (KG) OIL VOLUME (L) A B C M N D 75 680 380 141 159 124 56 18 53 112,5 880 390 141 159 124 56 18 53 150 990 400 141 159 140 56 18 53 225 1200 458 151 174 146 56 18 53 300 1360 490 151 174 146 62 18 53 400 1730 565 151 184 161 62 18 53 500 2300 1010 152 176 158 67 18 53 630 3200 1350 170 184 165 74 18 53 800 3500 1410 170 184 177 74 18 53 Note: These dimensions are approximate. When buying a transformer, please ask for the real dimensions, as they may vary.
10 Corporative Portfolio
Single-phase or three-phase open winding dry type transformers with self-extinguishing H-class insulation suited for high temperatures, and high voltage ratings through 15 KV. For voltage ratings through 1,2 KV transformers they come with an IP20 protection enclosure included. For voltage ratings through 15 KV no enclosure is provided and can be manufactured with or without electrical shielding. These transformers are useful for raising or lowering voltage levels, in residential, commercial or industrial applications. Low voltage transformers, are available in KVA ratings ranging from 1 KVA through 500 KVA. For three-phase transformers with high voltage ratings up to 15 KV are available in capacities ranging from 75 KVA through 630 KVA. Rymel dry transformers offer optimum efficiency, low losses level, and minimum noise levels.
DRY TYPE TRANSFORMERS
11 Corporative Portfolio
These transformers are manufactured in accordance to: ANSI C-57.12.23, ANSI C-57.12.24, NTC 4406 and RETIE standards. These transformers are available in capacities of up to 3000 KVA for three-phase transformers and up to 500 KVA for single-phase transformers. High voltage rating through 34,5 GrdY/19.92 KV and 150 KV BIL. If the customer requires it, the tank can be made of stainless steel.
CONFIGURATION: Radial Feed type for the end of medium voltage circuit and Loop Feed type to continue the medium voltage circuit. Load switch (ON-OFF) for radial feed type transformer and 4-position switch for loop feed type transformer.
SUBMERSIBLE TRANSFORMERS
12 Corporative Portfolio
Window and bar type CTs for indoor and outdoor use, with capacities ranging from 2.5VA through 15VA; precision classes ranging from 0.2 s through 1.0 and current ratings ranging from 50/5 through 4000/5. Meet the IEC 60/85, IEC 60044-1 and NTC 2205 Standards.
SPECIFICATIONS Service Voltage (V): 120/208; 480/277 Voltage ratings (V): 600 Class (%): 0,5 s; 0,5; 1 Installation: Indoor or outdoor Number of cores: 1 Load (VA): 2,5; 5; 10 Primary Current (Window type) (A) 100, 150, 200, 300, 400, 500, 600, 700, 800, 900, 1000, 1200, 1500, 2000, 2500, 3000, 4000. Primary Current (Bar type) (A) 100, 150, 200, 300, 400, 500, 600, 700, 800. Secondary Current (A): 5 Thermal Current (Ith) (A): 80 In Dynamic Current (Id) (A): 200 In Security Factor: <= 5 Voltage at 60 Hz 1 minute: 3 KV Insulation: Thermal class type 65 Type-Model (Window Type) TCIV (Indoor use); TCEV (Outdoor use) Type- Model (Bar-Type) TCIB (Indoor use); TCEB (Outdoor use)
CURRENT TRANSFORMERS
13 Corporative Portfolio
REPAIR SERVICE FOR: Oil immersed transformers Dry transformers
MAINTENANCE OF TRANSFORMERS ON SITE AND/OR IN OUR FACILITIES: Washing and drying of the active part. Dielectric oil change. Rubber gasket change. Tank cleaning and painting. Electrical testing protocol. Revision of the instrumentation. In order to define if the maintenance is going to be made on site or in our facilities depends on the result of a set of tests that must be periodically performed, and the correct interpretation of such tests. ELECTRICAL TESTS: Megger insulation resistance. Dielectric absorption ratio DAR. Polarization index. Step Voltage Testing. Winding resistance. Turns Ratio Test (TTR)
REPAIR SERVICE (SERVY RYMEL)
14 Corporative Portfolio
The visual inspection is not enough to know what is the general condition of the transformer, for this reason the electrical tests are required as a complement to know the condition of the solid insulation of the transformers, as they inevitably will deteriorate over time and its condition will show how much remaining lifetime has the equipment. PHYSICAL-CHEMICAL ANALYSIS:
Dielectric Breakdown Voltage. (ASTM D877) Number of neutralization. (ASTM D974) Interfacial Tension (ASTM D2285) Color (ASTM D1500) Relative Density (ASTM D1298) Quality index Quantitative analysis if PCB (Dexil) (USEPA Method 9079) THERMOGRAPHIC INSPECTION: This technique allows contactless measurement of temperature, and also the observation of images formed by the infrared radiation source. This technique is applicable for high and low voltage lines, control and power enclosures, electrical joints, hot spots, distribution and power transformers, electric motors, among other applications.
15 Corporative Portfolio
We have venture in the development of special developments or custom made products such as: Current Limiting Bobbins: Used to limit the fault currents to 3 KA, during 2 seconds in medium voltage (rating through 15 KV) lines, BIL 95 KV and current ratings of 50, 100, 150 and 400 A.
Anti-theft covers (MAGLOCK): High technology and high reliability covers with a specially designed stainless steel lock which provides total adjustment between the cover and the manhole, and avoids movement. To remove the lock is necessary a special tool, with a unique code assigned to each utility company. MAGLOCK helps to protect the infrastructure of the utility companies against theft, vandalism and accidents; Round Type MAGLOCK: Covers available in polypropylene, metal and polyconcrete. Rectangular Type MAGLOCK R-1: Covers available in polypropylene.
SPECIAL DEVELOPMENTS:
16 Corporative Portfolio
Advantages: Dust and moisture resistant. Do not require electricity. Do not require civil works or locksmithing for its installation. Avoid vibrations between the cover and the ground (Less noise pollution, higher lifetime of the cover because the material supports less fatigue stresses).
Oil immersed combined measurement transformers: Manufactured with high class accuracy for measurement (0,2% or 0,5%) and Voltage rating through 15 KV. It has a front enclosure to install the energy meter, the terminal board and the wireless modem (If a remote measurement system is required). Useful as measurement equipment for medium voltage in single or three- phase applications, by means of three or two elements method (As required by the client) using current transformers (CT) and potential transformers (PT). Current transformer (CT) specifications: Capacities ranging from 2.5VA through 15VA and current ratings ranging from 50/5 A through 4000/5 A. Potential transformer (PT) specifications: Specially designed to obtain low losses in both copper and iron. Capacities from 10 VA, Input voltage ratings of 13.200 V or 7.620 V and Input Voltage ratings of 120 V.
17 Corporative Portfolio
Complete measurement system transformers: This is a completely self-protected transformer which has internal fuses, a surge protection device (SPD) in the high voltage and one in the low voltage. It also has a current transformer (CT) per phase in the low voltage connected to an energy meter.
Transmission network failure detector:
Allows the detection of presence or absence of energy in the 13,2 KV transmission lines and transmits the events via GPRS or RADIO to a SCADA platform or a WEB application.
Auto-transformers: Equipment specially designed to raise the voltage in specific situations where, by regulation, the voltage drops are high and do not allow offering the required voltage to the user.