Sei sulla pagina 1di 8

DATOS

COMEDOR 29.88 m2
COCINA 8.54 m2
SS-HH 39.94 m2
CORREDOR 26.1225 m2
1.0. AREA TOTAL = 78.37 m2
AREA NO TECHADA = 26.1225 m2
2.0. CALCULO DE LA CARGA INSTALADA (C.I.)
Area
C.I.1 = 78.37 x 50 watts/m2
C.I.1 = 3918.41 Watts
Area CORREDORES
C.I.2 = 26.12 x 10 watts/reflector
C.I.2 = 261.23 watts
POTENCIA INSTALADA TOTAL :
CIT = 4179.64 watts
3.0. CALCULO DE LA MAXIMA DEMANDA (M.D.)
Area de Aulas, direccin, secretaria, sala de profesores, y SS.HH.
M.D.1 = 3918.41 x 0.75 = 2938.8 watts
M.D.1 = 2938.81 Watts
Area de Escalera y Corredor
M.D.2 = 261.23 x 0.75 = 195.92 watts
M.D.2 = 195.92 Watts
MAXIMA DEMANDA TOTAL :
MDT = 3134.73 watts
4.0. CALCULO DE INTENSIDAD DE CORRIENTE
I = MDtotal (watts)
K x V x cos
MD total = 3,134.73 watts
K = 3
V = 220 voltios
Cos = 0.90
I = 9.14 Amp.
CALCULO DE MAXIMA DEMANDA Y POTENCIA INSTALADA
"CONSTRUCCION REEMPLAZO Y EQUIPAMIENTO DE INSTITUCION EDUCATIVA N
32377 DEL CASERIO DE PUEBLO LIBRE DE LAGOPAMPA-DISTRITO DE JIVIA-
LAURICOCHA-HUANUCO"
TABLERO GENERAL AL STD -1.2
Sobre este valor de corriente nominal el C.E.P recomienda aadir un 25% como reserva futura
I diseo = 11.00 Amp.
5.0. CALCULO DE LA SECCION NOMINAL DEL CONDUCTOR :
Seccin Nominal : 6 mm2
6.0. CAIDA DE TENSION :
Mxima Caida de Tensin Permisible (2.5% de 220 Voltios)
MCT = 5.5 Voltios
V = KxIxdxL
S
K = 3
I = 11.00 Amp.
d = 0.0175 Ohm-mm2/m
S = 6.00 mm2
L = 55.00 m.
V = 3.06
3.06 < 5.5 Voltios
Por lo tanto usaremos :
Usando la Tabla 4-VIII, teniendo 4 cables :
Usaremos tubera PVC 3/4 Pulgadas
Con la intesidad de corriente, recurrimos a las tablas del fabricante y de acuerdo a este tenemos que el
conductor a escoger es el cable de 6 mm2 con alma de cobre, con aislamiento y cubierta termoplstica NYY
cuya intensidad de corriente admisible es hasta 72 amperios
DATOS
DIRECCION 22.13 m2
AULAS 50.70 m2
CORREDOR 50.53 m2
1.0. AREA TOTAL AULAS = 72.82 m2
AREA NO TECHADA = 0 m2
2.0. CALCULO DE LA CARGA INSTALADA (C.I.)
Area de Aulas
C.I.1 = 72.82 x 50 watts/m2
C.I.1 = 3641.10 Watts
Area CORREDORES
C.I.2 = 50.53 x 10 watts/reflector
C.I.2 = 505.25 watts
POTENCIA INSTALADA TOTAL :
CIT = 4146.35 watts
3.0. CALCULO DE LA MAXIMA DEMANDA (M.D.)
Area de Aulas, direccin, secretaria, sala de profesores, y SS.HH.
M.D.1 = 3641.10 x 0.75 = 2730.8 watts
M.D.1 = 2730.83 Watts
Area de Escalera y Corredor
M.D.2 = 505.25 x 0.75 = 378.94 watts
M.D.2 = 378.94 Watts
MAXIMA DEMANDA TOTAL :
MDT = 3109.76 watts
4.0. CALCULO DE INTENSIDAD DE CORRIENTE
I = MDtotal (watts)
K x V x cos
MD total = 3,109.76 watts
K = 3
V = 220 voltios
Cos = 0.90
I = 9.07 Amp.
CALCULO DE MAXIMA DEMANDA Y POTENCIA INSTALADA
"CONSTRUCCION REEMPLAZO Y EQUIPAMIENTO DE INSTITUCION EDUCATIVA N
32377 DEL CASERIO DE PUEBLO LIBRE DE LAGOPAMPA-DISTRITO DE JIVIA-
LAURICOCHA-HUANUCO"
TABLERO GENERAL AL STD -1.1
Sobre este valor de corriente nominal el C.E.P recomienda aadir un 25% como reserva futura
I diseo = 11.00 Amp.
5.0. CALCULO DE LA SECCION NOMINAL DEL CONDUCTOR :
Seccin Nominal : 6 mm2
6.0. CAIDA DE TENSION :
Mxima Caida de Tensin Permisible (2.5% de 220 Voltios)
MCT = 5.5 Voltios
V = KxIxdxL
S
K = 3
I = 11.00 Amp.
d = 0.0175 Ohm-mm2/m
S = 6.00 mm2
L = 45.00 m.
V = 2.50
2.50 < 5.5 Voltios
Por lo tanto usaremos :
Usando la Tabla 4-VIII, teniendo 4 cables :
Usaremos tubera PVC 3/4 Pulgadas
Con la intesidad de corriente, recurrimos a las tablas del fabricante y de acuerdo a este tenemos que el
conductor a escoger es el cable de 6 mm2 con alma de cobre, con aislamiento y cubierta termoplstica NYY
cuya intensidad de corriente admisible es hasta 72 amperios
DATOS
AREA DE AULAS 72.82
AREA DE SERVISIOS 78.37
AREA DE CORREDORES 39.60
AREA DE exterior 648
1.0. AREA TOTAL AULAS = 72.82 m2
AREA DE SERVISIOS 78.37 M2
AREA DE TERRENO = 1716 m2 AREA ILUMINADA EXT
2.0. CALCULO DE LA CARGA INSTALADA (C.I.)
Area de Aulas
C.I.1 = 151.19 x 50 watts/m2
C.I.1 = 7559.51 Watts
Area CORREDORES
C.I.2 = 39.60 x 10 watts/reflector
C.I.2 = 396.00 watts
Area restante
C.I.2 = 648.00 x 5 watts/reflector
C.I.2 = 3240.00 watts
POTENCIA INSTALADA TOTAL :
CIT = 11195.51 watts
3.0. CALCULO DE LA MAXIMA DEMANDA (M.D.)
Calculo de la Carga por metro cuadrado nominal
Cn/m2= 6.524189977
1ros 900m2
M.D.1 = 5871.770979 x 0.75 = 4403.8 watts
M.D.1 = 4403.83 Watts
CALCULO DE MAXIMA DEMANDA Y POTENCIA INSTALADA
"CONSTRUCCION REEMPLAZO Y EQUIPAMIENTO DE INSTITUCION EDUCATIVA N
32377 DEL CASERIO DE PUEBLO LIBRE DE LAGOPAMPA-DISTRITO DE JIVIA-
LAURICOCHA-HUANUCO"
TABLERO GENERAL
Rto
M.D.2 = 5323.74 x 0.5
M.D.2 = 2661.87 Watts
MAXIMA DEMANDA TOTAL :
MDT = 7065.70 watts
4.0. CALCULO DE INTENSIDAD DE CORRIENTE
I = MDtotal (watts)
K x V x cos
MD total = 7,065.70 watts
K = 3
V = 220 voltios
Cos = 0.90
I = 20.60 Amp.
Sobre este valor de corriente nominal el C.E.P recomienda aadir un 25% como reserva futura
I diseo = 26.00 Amp.
5.0. CALCULO DE LA SECCION NOMINAL DEL CONDUCTOR :
Seccin Nominal : 10 mm2
6.0. CAIDA DE TENSION :
Mxima Caida de Tensin Permisible (2.5% de 220 Voltios)
MCT = 5.5 Voltios
V = KxIxdxL
S
K = 3
I = 26.00 Amp.
d = 0.0175 Ohm-mm2/m
S = 10.00 mm2
L = 15.00 m.
V = 1.18
1.18 < 5.5 Voltios
Por lo tanto usaremos :
Usando la Tabla 4-VIII, teniendo 4 cables :
Usaremos tubera PVC 1 Pulgadas
Con la intesidad de corriente, recurrimos a las tablas del fabricante y de acuerdo a este tenemos que el
conductor a escoger es el cable de 25 mm2 con alma de cobre, con aislamiento y cubierta termoplstica NYY
cuya intensidad de corriente admisible es hasta 87 amperios
CABLE DE ENERGIA NYY TRIPOLAR 1X23X10 MM2, 1 HILOS, TEMP. D/OPERACION 80 C, TENSION DE
SERVICIO 1KV, CAPACIDAD D/CORRIENTE ENTERRADO 105 A, AIRE 80 A, DUCTO 85 A, AISLAMIENTO DE
PVC Y CUBIERTA EXTERIOR DE PVC. APLICACION GENERAL COMO CABLE DE ENERGIA.
PRIMER NIVEL
NIV. LUMIN TIP. LUMIN REL. LOCAL IND RELAC COEFIC. C.U FAC. MAN N LAMP N LUMIN N LUMINA.
( Lux ) Lamp. 40W R. L. LOCAL UTILIZ. Redond f. m. UNID REDOND CORREGIDO
DIRECCION EXISTENTE 3.54 6.25 3 22.13 300.00 3 1.03 H 0.39 0.39 0.65 7.88 3.00 3
AULA 01 6.55 7.74 3 50.70 300.00 3 1.61 F 0.46 0.46 0.65 15.31 5.00 6
COMEDOR 5.28 5.66 3 29.88 300.00 3 1.24 G 0.43 0.43 1.65 9.65 3.00 7
COCINA 3.05 2.80 3 8.54 300.00 3 0.66 J 0.27 0.27 0.65 4.39 1.00 2
SS.HH. NIOS 3.23 5.29 3 17.09 300.00 3 0.91 H 0.39 0.39 0.65 6.09 2.00 2
SS.HH. NIAS 3.23 5.29 3 17.09 300.00 3 0.91 H 0.39 0.39 0.65 6.09 2.00 2
SS.HH. INVALIDOS 1.80 1.80 3 3.24 300.00 3 0.41 J 0.27 0.27 1.65 1.67 1.00 1
SS. DOCENTES 1.17 1.80 3 2.53 100.00 3 0.39 J 0.27 0.27 0.65 0.43 0.00 1
Sub total 151.19 total 24
INSTITUCION EDUCATIVA N 32377 DEL CASERIO DE PUEBLO LIBRE DE LAGOPAMPA
CALCULO DE I LUMI NACI ON I NTERI OR
EXPEDIENTE TCNICO:
PROYECTO:CONSTRUCCION REEMPLAZO Y EQUIPAMIENTO DE INSTITUCION
EDUCATIVA N 32377 DEL CASERIO DE PUEBLO LIBRE DE LAGOPAMPA-DISTRITO DE
JIVIA-LAURICOCHA-HUANUCO
MEMORI A DE CALCULOS ELECTRI COS
AMBIENTE
ANCHO
m
LARGO
m ALTO m
AREA
m2
De acuerdo al CODIGO NACIONAL DE ELECTRICIDAD - UTILIZACION vigente, promulgada mediante
Resolucin No. 037-2006-MEM/DM, del 17 de Enero del 2006, en la Seccin 050-204 "Cargas de circuitos
y Factores de Demanda para Escuelas", tenemos:
ITEM DESCRIPCION DEL LOCAL MODULOS DESCRIPCION GENERAL
AREA
m2
CARGA
UNITARIA
W/m2
POTENCIA
INSTALADA
(Kw)
FACTOR DE
DEMANDA f.d
MAXIMA
DEMANDA
(Kw)
DIRECCION EXISTENTE 22.13 50 1.11 0.30 0.33
AULA 01 50.70 50 2.53 0.30 0.76
COMEDOR 29.88 50 1.49 0.30 0.45
COCINA 8.54 50 0.43 0.30 0.13
SS.HH. NIOS 17.09 10 0.17 0.30 0.05
SS.HH. NIAS 17.09 10 0.17 0.30 0.05
SS.HH. INVALIDOS 3.24 10 0.03 0.30 0.01
SS. DOCENTES 2.53 10 0.03 0.30 0.01
5.96 1.79
En nuestro caso, se tendr en cuenta una potencia de :
1.79 KW
Por lo tanto se concluye que se debera optar el suministro de Energia Electrica a traves de una SUB ESTACION ya que segun el C.N.E
Si LA MAXIMA DEMANDA < 15KW No se necesita del Empleo de una SUB ESTACION
LA MAXIMA DEMANDA > 15KW Necesita del Empleo de una SUB ESTACION
MAXIMA DEMANDA DEL COMPLEJO EDUCATIVO (Kw)
EXPEDIENTE TCNICO:
PROYECTO:CONSTRUCCION REEMPLAZO Y EQUIPAMIENTO DE INSTITUCION EDUCATIVA N 32377 DEL CASERIO DE PUEBLO LIBRE DE LAGOPAMPA-DISTRITO
DE JIVIA-LAURICOCHA-HUANUCO
MEMORI A DE CALCULOS ELECTRI COS
CALCULO DE LA POTENCI A I NSTALADA Y LA MAXI MA DEMANDA
INSTITUCION EDUCATIVA N 32377 DEL CASERIO DE PUEBLO LIBRE DE LAGOPAMPA
1 AREA PROYECTADA
MODULO 01 AULA ,
MODULO DE SERV.
HIGIENICOS, MOD
COCINA

Potrebbero piacerti anche