Class B A AA
Pt100 0.3+0.005|t| 0.15+0.002|t| 0.1+0.00167|t|
Maximum deviations of Pt100 sensors defined in standard
IEC 60751
Seminar HCMC University of Technology
Slide 22 Do Trong Nguyen
05/17/2014
TC Thermocouple - Basic physics
SEEBECK EFFECT
If the conductors' metal is not the same and if the two junctions are at different
temperatures, between them a voltage is generated, and hence an electric current
flows in the circuit.
100C 0C
T
jct.
T
ref.
a
b
Ni
NiCr
A Thermocouple is a temperature sensor, that generates a voltage depending on the
temperature.
This voltage only indicates the temperature difference between the cold junction Tjct
and the reference point Tref . This means that the temperature of Tref must be
known.
Seminar HCMC University of Technology
Slide 23 Do Trong Nguyen
05/17/2014
Noble metals for the highest temperature range
Seminar HCMC University of Technology
Slide 24 Do Trong Nguyen
05/17/2014
TC - Accuracy
Tolerance classes according to IEC 584
Class 1 Special
Class 2 Standard
-9C
-6C
-4C
-2C
C
2C
4C
6C
9C
-40C 375C 1000C
Class 1
Temperature (C)
T
o
l
e
r
a
n
c
e
(
C
)
0
1200C 333C
Seminar HCMC University of Technology
Slide 25 Do Trong Nguyen
05/17/2014
Strengths on both sides: RTD vs. TC
Measuring range
Response time
Repeatability
Vibration
resistance
Linearity
Long-term
stability
Accuracy
-200 to +600C
Fast
Very good
Good/ very good with
new E+H inserts
Good
Very good
High
-250 to +2200C
Very fast
Fair
Very good
Fair
Fair
Medium
RTD TC
Seminar HCMC University of Technology
Slide 26 Do Trong Nguyen
05/17/2014
Product Basket Oil & Gas
Insert types
Fit for purpose
Best sellers
Hygienic line
Heavy duty
High temperature
Selection and
configuration
Seminar HCMC University of Technology
Slide 27 Do Trong Nguyen
05/17/2014
Application
Seminar HCMC University of Technology
iTemp in mixer Level
Flow
Analysis
Pressure
Temperature
Data Monitoring
Solutions
Slide 28 Do Trong Nguyen
05/17/2014
Seminar HCMC University of Technology
Live demonstration with Temperature sensor
Do Trong Nguyen Slide 29
HART connection
05/17/2014
Analytical measurement
Analysis
Emily Serrano Slide 30
320000
electrodes/yr
31000
sensors/yr
150000
pcb/yr
50000
transmitters/yr
14500
assemblies/yr
15000
WWTP
3000
DW
plants
500
Pharma.
plants
200
P&P
plants
2000
breweries/
dairies
400
power
plants
800
chemical
plants
650
analyzers/yr
Analyzers
Chlorine
Conductivity
Oxygen
pH
Sampler
Turbidity
05/17/2014
pH scale
Analysis - pH
Principle
Products
Maintenance
Diagnostics
Installation
Applications
Slide 31 Emily Serrano
05/17/2014
Measuring principle glass electrode
Analysis - pH
pH is a potentiometric measurement method.
The measuring effect is based on a pH sensitive glass membrane
whose surface reacts to the acid content with a specific voltage.
This voltage is then measured relative to a reference element.
pH is calculated according the Nernst law equation.
Slide 32 Emily Serrano
Principle
Products
Maintenance
Diagnostics
Installation
Applications
05/17/2014
Measuring principle ISFET-sensor
Analysis - pH
Contrary to the glass electrode no charges are transported
through the insulator, the effect is purely electrostatic.
No ageing effect on IsFET chip => Longer lifetime
Slide 33 Emily Serrano
Principle
Products
Maintenance
Diagnostics
Installation
Applications
05/17/2014
Seminar HCMC University of Technology
Analysis pH measurement demonstration
Do Trong Nguyen Slide 34
Transmitter
05/17/2014
Seminar HCMC University of Technology
Training room in Bach Khoa University
Do Trong Nguyen Slide 35
05/17/2014
Products Solutions Services
Thank you very much for your attention
Do you have any questions?
Slide 36 Do Trong Nguyen