Globul Project TP and External Alarm
connection and test guide

Page 2 HUAWEI TECHNOLOGIES CO., LTD.
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 3 HUAWEI TECHNOLOGIES CO., LTD.
TP indoor with generator
TP indoor without generator
Reuse of existing indoor PSS
TP outdoor
TP outdoor installed in shelter without generator
TP outdoor installed in shelter with generator
TP and external alarm solution & cable
connection typical scenarios
Page 4 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 1 TP Indoor site with Generator
BTS BBU
Existing DDF Box
Door Temperature
&humidity
Smoke Air-condition
Low fuel
DG.
Running
TP SMU
R-Phase down
S-Phase down
T-Phase down / AC Main failure
(R+S+T phase down)
Rectifier failure
TP48200B
Page 5 HUAWEI TECHNOLOGIES CO., LTD.
ALM No. Globul ALM Requirement Existing DDF to BBU New TP SMU to BBU
ALM1 High/Low Temperature High/Low Temperature
ALM2 Fire/Smoke Fire/Smoke
ALM3 Door open / Tamper/Intrude Door open / Tamper/Intrude
ALM4 Air conditioner failure Air conditioner failure
ALM5 R-phase down / Low fuel level Low fuel level R-phase down
ALM6 S-phase down / Backup generator running Backup generator running S-phase down
ALM7 T-phase down / AC Main failure (R+S+T phase down) Spare T-phase down / AC Main failure (R+S+T phase down)
ALM8 Rectifier failure Spare Rectifier failure
Scenario 1 TP Indoor site with Generator
Page 6 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 2 TP Indoor site without Generator
BTS BBU
Krone DDF Box
Door Temperature
&humidity
Smoke Air-condition
TP SMU
R-Phase down
S-Phase down
T-Phase down / AC Main failure
(R+S+T phase down)
Rectifier failure
TP48200B
Page 7 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 2 TP Indoor site without Generator
ALM No. Globul ALM Requirement Existing DDF to BBU New TP SMU to BBU
ALM1 High/Low Temperature High/Low Temperature
ALM2 Fire/Smoke Fire/Smoke
ALM3 Door open / Tamper/Intrude Door open / Tamper/Intrude
ALM4 Air conditioner failure Air conditioner failure
ALM5 R-phase down / Low fuel level R-phase down
ALM6 S-phase down / Backup generator running S-phase down
ALM7 T-phase down / AC Main failure (R+S+T phase down) T-phase down / AC Main failure (R+S+T phase down)
ALM8 Rectifier failure Rectifier failure
Page 8 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 3 Reuse existing power system Indoor
BTS BBU
Krone DDF Box
Door Temperature
&humidity
Smoke Air-condition
R-Phase down
/Low fuel
DG.Runnig
/ S-Phase down
T-Phase down/
AC Main failure
Rectifier failure
Page 9 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 3 Reuse existing power system Indoor
ALM No. Globul ALM Requirement Existing Krone DDF to BBU
ALM1 High/Low Temperature High/Low Temperature
ALM2 Fire/Smoke Fire/Smoke
ALM3 Door open / Tamper/Intruder Door open / Tamper/Intruder
ALM4 Air conditioner failure Air conditioner failure
ALM5 R-phase down / Low fuel level R-phase down / Low fuel level
ALM6 S-phase down / Backup generator running S-phase down / Backup generator running
ALM7 T-phase down / AC Main failure (R+S+T phase down) T-phase down / AC Main failure (R+S+T phase down)
ALM8 Rectifier failure Rectifier failure
Page 10 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 4 TP Outdoor Site
BTS BBU
Door Temperature
&humidity
Smoke
TP SMU
R-Phase down
S-Phase down
T-Phase down / AC Main failure
(R+S+T phase down)
Rectifier failure
TP48200A
Page 11 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 4 TP Outdoor Site
ALM No. Globul ALM Requirement New TP SMU to BBU
ALM1 High/Low Temperature High/Low Temperature
ALM2 Fire/Smoke Fire/Smoke
ALM3 Door open / Tamper Door open / Tamper
ALM4 Air conditioner failure Spare (No Air conditioner)
ALM5 R-phase down / Low fuel level R-phase down (No generator)
ALM6 S-phase down / Backup generator running S-phase down (No generator)
ALM7 T-phase down / AC Main failure (R+S+T phase down) T-phase down / AC Main failure (R+S+T phase down)
ALM8 Rectifier failure Rectifier failure
Page 12 HUAWEI TECHNOLOGIES CO., LTD.
Appendix 1 Communication cable for BBU side
Page 13 HUAWEI TECHNOLOGIES CO., LTD.
Appendix 2
Communication cable for TP SMU and existing DDF side
8-Pin Cable 1 8-Pin Cable 2
ALM1+ ALM1- ALM2+ ALM2- ALM3+ ALM3- ALM4+ ALM4- ALM5+ ALM5- ALM6+ ALM6- ALM7+ ALM7- ALM8+ ALM8-
Orange&
White
Orange
Green
&White
Green
Blue&
White
Blue
Brown&
White
Brown
Orange
& White
Orange
Green
&White
Green
Blue&
White
Blue
Brown&
White
Brown
TP UIM
Page 14 HUAWEI TECHNOLOGIES CO., LTD.
Appendix 3 Globul project alarm setting guide attached
Page 15 HUAWEI TECHNOLOGIES CO., LTD.
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 16 HUAWEI TECHNOLOGIES CO., LTD.
Ethernet Cable from SMU02B to BBU for all sites
TP48200A/200B
SMU02B
Ethernet cable
UPEU
Step detail:
Connect IOOI on SMU02B and MON0 on BBU UPEU card
with provided Ethernet cable. (If MON0 has been used, you can
use MON1 instead.
Page 17 HUAWEI TECHNOLOGIES CO., LTD.
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 18 HUAWEI TECHNOLOGIES CO., LTD.
Outdoor TP Smoke sensor installation

Install the smoke sensor on the top of the cabinet
Page 19 HUAWEI TECHNOLOGIES CO., LTD.
Outdoor TP temperature and humidity sensor installation

Install the temperature sensor on the left rack in the cabinet
Page 20 HUAWEI TECHNOLOGIES CO., LTD.
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF Sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 21 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 1 Ericsson BTS with SMT EAS


Ext ALM
CODE
TEXT STRING
New ALM
Need
Sensor side connection change for
New TP
Sensor side connection change for
Reusing Existing Power
ALM1 HIGH TEMPERATURE ALM1 Series Connect to ALM1 Port Series Connect to ALM1 Port
ALM2 FLOOD None Remove ALM cable Remove ALM cable
ALM3
EXTERNAL ALARM SYSTEM LOW
BATTERY None Remove ALM cable Remove ALM cable
ALM4
EXTERNAL ALARM SYSTEM 220V AC
MAIN BREAKDOWN / low battery alternator None Remove ALM cable Remove ALM cable
ALM5 TAMPER ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM6 FIRE / SMOKE ALM2 Connect to Ext ALM2 Port Connect to Ext ALM2 Port
ALM7 INTRUDER ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM8 R PHASE BREAKDOWN / R or S or T ALM5 No need Connect to Ext ALM5 Port
ALM9
S PHASE BREAKDOWN / high engine
temperature / gen running ALM6 No need Connect to Ext ALM6 Port
ALM10 T PHASE BREAKDOWN /low fuel level ALM7 No need Series Connect to Ext ALM7 Port
ALM11 AIR CONDITIONING ALM4 Connect to Ext ALM4 Port Connect to Ext ALM4 Port
ALM12 ALARM SYSTEM OFF None No need No need
ALM13 LOW TEMPERATURE ALM1 Series Connect to Ext ALM1 Port Series Connect to Ext ALM1 Port
ALM14
AVIATION LIGHT / intruder in generator
section None No need No need
ALM15 LOW BATTERY BTS None No need No need
ALM16 MAINS 220V AC BREAKDOWN ALM7 No need Series Connect to Ext ALM7 Port
Page 22 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 2 Motorola BTS with SMT EAS


Ext ALM
CODE TEXT STRING
New ALM
Need
Sensor side connection change for
New TP
Sensor side connection change for
Reusing Existing Power
ALM1 HIGH / LOW TEMPERATURE ALM1 No need No need
ALM2 FIRE/SMOKE ALM2 No need No need
ALM3 INTRUDER ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM4 LOW DC VOLTAGE None Remove ALM cable Remove ALM cable
ALM5 R PHASE BREAKDOWN ALM5 No need No need
ALM6 FLOOD None No need Remove ALM cable
ALM7 AC MAINS FAILURE ALM7 No need Series Connect to Ext ALM7 Port
ALM8 AVIATION LIGHT FAILURE None No need Remove ALM cable
ALM9 TAMPER ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM10 AIR CONDITIONER FAILURE ALM4 Connect to Ext ALM4 Port Connect to Ext ALM4 Port
ALM11 S PHASE BREAKDOWN ALM6 No need Connect to Ext ALM6 Port
ALM12 T PHASE BREAKDOWN ALM7 No need Series Connect to Ext ALM7 Port
ALM13 RECTIFIER FAILURE ALM8 No need Connect to Ext ALM8 Port
ALM14 ALARM SYSTEM LOW BATTERY None No need No need
ALM15 ALARM SYSTEM MAINS AC DOWN None No need No need
ALM16
PERSONNEL ON SITE /Alarm system
status/ None No need No need
Page 23 HUAWEI TECHNOLOGIES CO., LTD.
Scenario 3 BTS with A.C.S EAS



Ext ALM
CODE
TEXT STRING
New ALM
Need
Sensor side connection change for
New TP
Sensor side connection change for
Reusing Existing Power
ALM1 HIGH / LOW TEMPERATURE ALM1 No need No need
ALM2 FIRE/SMOKE ALM2 No need No need
ALM3 DOOR OPEN ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Ple
ALM4 LOW DC VOLTAGE (psu1, psu2) None Remove ALM cable Remove ALM cable
ALM5 R or S or T PHASE DOWN ALM5 Series Connect to Ext ALM5 Port Series Connect to Ext ALM5 Port
ALM6 FLOOD None No need Remove ALM cable
ALM7 AC MAINS FAILURE (R and S and T down) ALM7 No need No need
ALM8 AVIATION LIGHT FAILURE None No need Remove ALM cable
ALM9 TAMPER ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM10 AIR CONDITIONER FAILURE ALM4 Connect to Ext ALM4 Port Connect to Ext ALM4 Port
ALM11 BACKUP GENERATOR RUNNING ALM6 No need Connect to Ext ALM6 Port
ALM12 SPARE (FREE COOLING ALARM) None No need No need
ALM13 RECTIFIER FAILURE (PSU1, PSU2,) ALM8 No need Connect to Ext ALM8 Port
ALM14 LOW FUEL LEVEL ALM5 Series Connect to Ext ALM5 Port Series Connect to Ext ALM5 Port
ALM15 FUEL TANK ALARM (where applicable) ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM16 PERSONNEL ON SITE None No need No need
Page 24 HUAWEI TECHNOLOGIES CO., LTD.
Existing DDF/OVP type on sites



New type Ericsson DDF Old type Ericsson DDF
For indoor sites with new TP, make ALM1~ALM4 ports of existing DDF 16 ports to report the 4 existing alarms from DDF
to Huawei BTS, ALM5~ALM8 from new TP to Huawei BTS.
For indoor sites reusing existing power, make ALM1~ALM8 ports of existing DDF 16 ports to report the 8 existing alarms
from DDF to Huawei BTS.

Page 25 HUAWEI TECHNOLOGIES CO., LTD.
In case of New type Ericsson DDF on site




Use the provided by Huawei Ethernet cables for making RG45 connection between BBU/Upper UPEU alarm ports and Ericsson
DDF/OVP box without cutting them one cable in case of TP indoor and two cables in case of reusing existing PSS
In this case the sequence of cable connections for external sensors changes as it is shown on the picture pairs ports marked
with yellow labels .

Page 26 HUAWEI TECHNOLOGIES CO., LTD.
Existing DDF type on sites



Existing DDF on 2123 site Existing DDF on 2007 site
For indoor sites with new TP, make ALM1~ALM4 ports of
existing DDF 16 ports to report the 4 existing alarms from DDF to
Huawei BTS, ALM5~ALM8 from new TP to Huawei BTS.
For indoor sites reusing existing power, make ALM1~ALM8 ports of existing DDF 16 ports to report the 8 existing alarms
from DDF to Huawei BTS.

Page 27 HUAWEI TECHNOLOGIES CO., LTD.
Existing DDF connection reusing existing Guardian Power



Existing DDF sensor side cable connection when reusing existing Guardian power
without generator.
Short circuit connection for
Alarm 6 port.

Because Guardian power
dont support S phase or T
phase down alarm.
Page 28 HUAWEI TECHNOLOGIES CO., LTD.
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF Sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 29 HUAWEI TECHNOLOGIES CO., LTD.
AC Mains failure alarm test procedure (Necessary)



1. Power on the system normally with battery back up;

2. Switch off the AC input breaker and wait several minutes, view the active alarm information on the LCD,
and view the alarm information on M2000 to check if the alarm is reported;

3. Switch on the AC input breaker, view the active alarm information on LCD, and view the alarm information
on M2000 to check if the alarm disappeared.

Indoor TP (TP48200B) Outdoor TP (TP48200A)
Page 30 HUAWEI TECHNOLOGIES CO., LTD.
Rectifier failure alarm test procedure (Necessary)



1. Insert a plastic stick to stop the rectifier fan and wait several minutes to check the rectifier fault. View the
active alarm information on the LCD, and view the alarm information on M2000 to check if the alarm is reported.

2. Remove the stick. View the active alarm information on LCD, and view the alarm information on M2000 to
check if the alarm disappeared.

Page 31 HUAWEI TECHNOLOGIES CO., LTD.
Smoke alarm test procedure (Optional)



Below is described the usual way to check this alarm but in this project it will be not checked

1. Spray the smoker sensor to check if the alarm is reported with OMC if they view the alarm information
on M2000.
2. Wait several minutes after the alarm is active and check with OMC if the alarm is disappeared on M2000.
Page 32 HUAWEI TECHNOLOGIES CO., LTD.
Temperature and Door open alarm test procedure



High temperature alarm test (Optional)

1. Carefully heat the temperature sensor with heat-air-gun to reach the threshold value. Keep the airflow away
from plastic details and cabinet insulation. View the active alarm information on the LCD, and view the alarm
information on M2000 to check if the alarm is reported.

2. Cool the temperature sensor or wait the temperature to be normal, view the alarm information on M2000 to
check if the alarm is disappeared.

Door open alarm test (Necessary)

1. Open the door of Cabinet or shelter to check the active alarm information on M2000 with OMC.

2. Close the door of Cabinet or shelter to check if the alarm is disappeared on M2000 with OMC.

Page 33 HUAWEI TECHNOLOGIES CO., LTD.
Air conditioner failure and D.G running alarm test procedure



Air conditioner failure alarm test (Necessary)

1. Shut down the precision air conditioner ( Floor mounted) or heat the temperature sensor of wall mounted air
Conditioner to check if there is a right alarm information on M2000 with OMC.

2. Start the precision air conditioner again and check with OMC if the alarm is disappeared on M2000.

D.G (Generator) running alarm test (Optional)

1. Start the generator to check with OMC if the alarm is reported on M2000.

2. Shut down the generator to check with OMC if the alarm is disappeared on M2000.

Thank you