POWER GRID CORPORATION OF INDIA LTD.

SPECIALIZED TESTING LABORATORY


TEST REPORT
Format No: EP07A01
(A Govt of India Enterprise)
400/220 KV Bhiwadi SS, Alwar-Bhiwadi Road, PO Khijuriwas, Bhiwadi (Raj.) 301019, Ph: +91-1493-511096,513344 Email: rtlstl.bhiwadi@gmail.com

SampleNumber: 201405258 Report Number: STL/3447/201405258/2014 Report Date: 28-May-14
Sampling Date: 21.05.14
Receipt Date: 26.05.14
Testing Date: 28.05.14
Next Due Date: 21.08.14
Oil Temp. C 68
Wdg Temp. C 77
Load 80
voltage, in kV 406
Sample Description: Inuslating Oil Sample in Syringe and Bottle
Total Acidity NT
BreakDownVoltage 58.9
Flash Point NT
InterFacialTension@27C NT
Resistivity @ 90C NT
Total particle count NT
Tan Delta @ 90C NT
Water Content 21
Total Gas Content 6.85
Nitrogen (N2) 4.94
Oxygen (O2) 0.71
Hydrogen (H2) 16
Methane (CH4) 63
Ethylene (C2H4) 3
Ethane (C2H6) 3
Acetylene (C2H2) 0.0
Carbon Monoxide (CO) 393
Carbon Dioxide (CO2) 11531 Appearance Yellow
Station: BALLIA
Equipment: BUS REACTOR
Make CGL
Serial No: T9198/1
Capacity 80 MVAR
Volt.Class 420 kV
Oil Type PARAFINIC
Breather AIR CELL
Cooling: ONAN
Inst.Date: 01.03.07
Last Filt. Date: 20.03.08
Requisition Ref: NR-1/BALLIA/O&M/
Requisition Date: 21.05.14
Name & Designation: DGM BALLIA
Organisation POWERGRID BALLIA
Address 400 KV / 500 KV HVDC S/S
VPO - IBRAHIM PATTI
BALLIA UP
SAMPLE SENT BY
SAMPLE DETAILS EQUIPMENT DETAILS
TEST RESULTS
IEEE-C57.104-1991 (Rogers Ratio):
IEC-60599-1999 ANALYSIS:
STL REMARKS:
REPORTED BY: ISSUED BY:
ppm
kV
E12 ohm-cm
--
mN/m
mgKOH/g
C
%
%
%
ppm
ppm
ppm
ppm
ppm
ppm
ppm
---
---
---
DGA results do not show increasing trend in fault gases levels wrt last sample. Water content results are violating limits.
Please send Furan oil sample 3 monthly basis. Kindly follow-up with RHQ/LKO O&M for fruther instructions.
Normal DGA Healthy Equipment
Thermal Fault of 300-700 degC (T2). Ratio of carbon oxides do not indicate cellulose deterioration.
50 Min.
20
0.1
0.2
Max.
Min.
Max.
Min.
Max.
Min.
15
0.3
125
Oil Parameters
Dissolved Gas Analysis
Sample Remarks:
Condition on Receipt: OK
IS-6792
IS-13567
IS-6262
IS-6104
IEC-62021
ASTM D-6450
100
120
50
65
1
350
2500
IEEE-C57.104
Reference Standard: IS-1866-2000
Reference Standard:
Test Method: IEC 60567
Furan Analysis (Test Method: IEC-61198: 1993)
2-Furfural 0.267 ppm
---
ppm
--- 2-Furfuryl Achohol 0.000
ppm
---
5-Methyl 2-Furfural 0.064
ppm
---
2-Acetyl-Furfural 0.008
ppm
---
Inhibitor Content Determination (Test Method:ASTM D-2668)
Total Furan Content 0.341 ppm
---
PARAMETER Measured
Value
Violation Limit Measured
Value
Test Method Violation
Limits, max
UoM PARAMETER Unit Of
Measurement
Resistivity @ 27C NT E12 ohm-cm IS-6103
IS-6103
--- ASTM-6786
Test Conditions for Resistivity and Tan Delta Tests: (a) Type of cell used: NT (b) Average
Voltage gradient in the sample: NT (c) Test Frequency for Tan-delta test: NT (d) Room
Temp(degC): NT (e) RH (%): NT
DBPC NT %
---
DBP NT %
---
Phone/ Fax: 05491-251409
email:
BDV in KV : 61.1 , 52.1 , 39.9 , 73 , 65.8 , 61.3 , Test frequency:61.8Hz , Electrode
type:Brass Hemispherical , Oil Temp:27 DegC
Amit Sharma, Narendra Kumar, Jr. Engineer Engineer
5-Hyd Methyl 2-Fur 0.002
OIL PARAMETERS : DGA : Water, CO,CO2, VIOLATIONS:
Count/cc
GENERAL
REMARKS:
1. The results pertain only to the sample deposited at STL and STL does not guarantee the performance of oil or euipment from which the sample is
said to be drawn. 2. The above test report shall not be reproduced, except in full, without written approval of STL. 3. NT = Not Tested
Page 1 of 1