TEST REPORT Format No: EP07A01 (A Govt of India Enterprise) 400/220 KV Bhiwadi SS, Alwar-Bhiwadi Road, PO Khijuriwas, Bhiwadi (Raj.) 301019, Ph: +91-1493-511096,513344 Email: rtlstl.bhiwadi@gmail.com
SampleNumber: 201405258 Report Number: STL/3447/201405258/2014 Report Date: 28-May-14 Sampling Date: 21.05.14 Receipt Date: 26.05.14 Testing Date: 28.05.14 Next Due Date: 21.08.14 Oil Temp. C 68 Wdg Temp. C 77 Load 80 voltage, in kV 406 Sample Description: Inuslating Oil Sample in Syringe and Bottle Total Acidity NT BreakDownVoltage 58.9 Flash Point NT InterFacialTension@27C NT Resistivity @ 90C NT Total particle count NT Tan Delta @ 90C NT Water Content 21 Total Gas Content 6.85 Nitrogen (N2) 4.94 Oxygen (O2) 0.71 Hydrogen (H2) 16 Methane (CH4) 63 Ethylene (C2H4) 3 Ethane (C2H6) 3 Acetylene (C2H2) 0.0 Carbon Monoxide (CO) 393 Carbon Dioxide (CO2) 11531 Appearance Yellow Station: BALLIA Equipment: BUS REACTOR Make CGL Serial No: T9198/1 Capacity 80 MVAR Volt.Class 420 kV Oil Type PARAFINIC Breather AIR CELL Cooling: ONAN Inst.Date: 01.03.07 Last Filt. Date: 20.03.08 Requisition Ref: NR-1/BALLIA/O&M/ Requisition Date: 21.05.14 Name & Designation: DGM BALLIA Organisation POWERGRID BALLIA Address 400 KV / 500 KV HVDC S/S VPO - IBRAHIM PATTI BALLIA UP SAMPLE SENT BY SAMPLE DETAILS EQUIPMENT DETAILS TEST RESULTS IEEE-C57.104-1991 (Rogers Ratio): IEC-60599-1999 ANALYSIS: STL REMARKS: REPORTED BY: ISSUED BY: ppm kV E12 ohm-cm -- mN/m mgKOH/g C % % % ppm ppm ppm ppm ppm ppm ppm --- --- --- DGA results do not show increasing trend in fault gases levels wrt last sample. Water content results are violating limits. Please send Furan oil sample 3 monthly basis. Kindly follow-up with RHQ/LKO O&M for fruther instructions. Normal DGA Healthy Equipment Thermal Fault of 300-700 degC (T2). Ratio of carbon oxides do not indicate cellulose deterioration. 50 Min. 20 0.1 0.2 Max. Min. Max. Min. Max. Min. 15 0.3 125 Oil Parameters Dissolved Gas Analysis Sample Remarks: Condition on Receipt: OK IS-6792 IS-13567 IS-6262 IS-6104 IEC-62021 ASTM D-6450 100 120 50 65 1 350 2500 IEEE-C57.104 Reference Standard: IS-1866-2000 Reference Standard: Test Method: IEC 60567 Furan Analysis (Test Method: IEC-61198: 1993) 2-Furfural 0.267 ppm --- ppm --- 2-Furfuryl Achohol 0.000 ppm --- 5-Methyl 2-Furfural 0.064 ppm --- 2-Acetyl-Furfural 0.008 ppm --- Inhibitor Content Determination (Test Method:ASTM D-2668) Total Furan Content 0.341 ppm --- PARAMETER Measured Value Violation Limit Measured Value Test Method Violation Limits, max UoM PARAMETER Unit Of Measurement Resistivity @ 27C NT E12 ohm-cm IS-6103 IS-6103 --- ASTM-6786 Test Conditions for Resistivity and Tan Delta Tests: (a) Type of cell used: NT (b) Average Voltage gradient in the sample: NT (c) Test Frequency for Tan-delta test: NT (d) Room Temp(degC): NT (e) RH (%): NT DBPC NT % --- DBP NT % --- Phone/ Fax: 05491-251409 email: BDV in KV : 61.1 , 52.1 , 39.9 , 73 , 65.8 , 61.3 , Test frequency:61.8Hz , Electrode type:Brass Hemispherical , Oil Temp:27 DegC Amit Sharma, Narendra Kumar, Jr. Engineer Engineer 5-Hyd Methyl 2-Fur 0.002 OIL PARAMETERS : DGA : Water, CO,CO2, VIOLATIONS: Count/cc GENERAL REMARKS: 1. The results pertain only to the sample deposited at STL and STL does not guarantee the performance of oil or euipment from which the sample is said to be drawn. 2. The above test report shall not be reproduced, except in full, without written approval of STL. 3. NT = Not Tested Page 1 of 1