How To Make 4-20 mA Current Loop

Measurements
It seems that at least one 4-20 mA (milliamp) measurement is required by our typical customer, and
the way to do it is a constant source of confusion for many. So I thought Id zero in on the various 4-
20 mA current loop configurations and elaborate on the specifics that you need to know to make a
successful measurement. The following discussion is ordered from the most to least common
configuration, and I hope to cover all those that I have encountered in customer applications. If
yours isnt included, please use the comments section to fill me in.
4-20 mA Current Loop Basics
Sensors or other devices with a 4-20 mA current loop output are extremely common in industrial
measurement and control applications. They are easy to deploy, have wide power supply
requirements, generate a low noise output, and can be transmitted without loss over great distances.
We encounter them all the time in both process control and basic measurement data logger and data
acquisition applications.
The idea behind 4-20 mA current loop operation is that the sensor draws current from its power
source in direct proportion to the mechanical property it measures. Take the example of a 100 psi
sensor with a current loop output. With 0 psi applied, the sensor draws 4 mA from its power source.
With 100 psi applied the sensor draws 20 mA. At 50 psi the sensor draws 12 mA and so on. The
relationship of mechanical property measurement to current output is almost always linear, allowing
the resulting current loop data to be scaled with a simple mx+b formula to reveal more useful
measurements scaled into engineering units.
How you actually measure the 4-20 mA current loop signal is a function of the sensors architecture
and the capabilities of the instrument youll use for the measurement.
Terminology
So that my discussion translates well across the various kinds of 4-20 mA current loop
configurations, Ive opted to standardize the terminology I use to describe each. Heres an overview:
E (dc excitation)
Most configurations that follow will show a DC voltage excitation source that I denote as E. Many
who use current loop sensors for the first time are surprised to learn that they need to supply this
excitation source. Nonetheless, unless the sensor is self-powered (i.e. AC line powered) an external
dc source is required. The good news is that this can sometimes be supplied by the instrument, and
the range of acceptable values is usually very wide, typically 10-24 V dc.
R (shunt resistor)
Heres a bit of trivia for you: No instruments measure current directly. They all do it indirectly by
measuring the voltage dropped across a resistor of known value, and then they use Ohms Law to
calculate actual current. The resistor is referred to as a shunt, is absolutely required to make a
current measurement, and is either supplied externally to, or built into the measuring instrument.
For clarity, I assume that its supplied externally.
i (current loop value ranging from 4-20 mA)
This is the 4-20 mA current signal generated by the sensor. Note that some sensors may draw 0-20
mA and even other values, but the vast majority of them use the 4-20 mA convention.
v (shunt voltage thats proportional to current)
This is the voltage actually measured by the instrument. Since our industry has standardized on a
shunt value of 250 Ohms, v will range between 1 and 5 volts for a 4-20 mA current loop signal (v=i
* resistance). Note that shunt resistor value is arbitrary as long as its known. You also need to
ensure that it doesnt burden the loop, so lower values are better than higher. Yes, I mean lower.
Remember that were working with current, not voltage, so the rules are inverted. Just as infinitely-
high resistor loads work well for a voltage source, you can take the load all the way to zero Ohms for
a current source without consequence.
Self-powered Sensors
I promised to order these configurations from most
to least common, and the self-powered sensor just
noses out the first runner up. Self-powered sensors
are those that, well, power themselves. The sensor
may have an integral ac power supply, thereby
negating the need for an external DC power source.
Or it may not be a sensor at all. It could be an output
from a PLC or other source that is internally
powered.

2-wire Sensors (Low-side Shunt)
Okay, this can get confusing for first-time 4-20 mA
current loop users. Yes, it is possible to both power
the sensor and measure the current it draws over the
same two wires. In the 2-wire examples shown here,
only two wires connect the sensor to its power
supply, and the sensor draws current from it in
direct proportion to the mechanical property that it
measures. As current changes, the voltage developed
across resistor R will change, thus providing a signal
thats suitable to connect to a measuring instrument like a data logger or data acquisition system.
In most situations, care should be taken to place the resistor in the low-side of the loop as shown
here, as opposed to the high-side. Doing so will allow non-isolated instruments to make the
measurement. In the next section, Ill deal with a high-side shunt placement and discuss these
cautions in more detail.

2-wire Sensors (High-side Shunt)
This configuration is almost exactly like the low-side,
2-wire approach, but it places the shunt resistor in
the high-side of the loop. Note that while the voltage
across the resistor is proportional to the current
drawn by the sensor (j ust l i ke the l ow-si de
approach), there is also a common mode voltage
(CMV) present on either side to ground. On one side
to ground the CMV is equal to the supply voltage. On
the other side to ground its equal to the supply voltage, less the voltage dropped by the resistor (v).
The presence of the CMVs places conditions on the instrument that you use to measure v. Specially,
the instrument needs to have an isolated front end so it can float to the level of the CMV and still
successfully make the measurement. Try this with a non-isolated, single-ended instrument and you
will short-circuit the sensor to ground. A non-isolated differential instrument will either saturate or
provide erroneous results.
3-wire Sensors
Three-wire sensors with a process current output
have a separate wire for ground, signal (4-20 mA),
and the power supply. This configuration is the
easiest for current loop beginners to grasp, one input
for power and a second for the current loop with a
common ground. The primary advantage of a 3-wire
sensor over its 2-wire counterpart is its ability to
drive higher resistive loads. Resistors drop voltage
for any given current in direct proportion to their
resistance value. Holding current constant, higher resistances drop more voltage. Turning back to
the 2-wire sensor and holding current constant, as the shunt resistance increases the voltage drop
across the sensor also increases. You might reach a point where the voltage dropped by the shunt
lowers the voltage drop across the sensor below the minimum required for it to operate properly.
We had a customer whose 2-wire current loop measurements functioned beautifully until loop
current reached about 18 mA, at which point everything went haywire. Upon close examination, we
determined that the supply voltage she used was too low by at least 0.56-V. She needed 2 mA more
measurement to reach full scale, which translates to 0.56 V with her 250-Ohm resistor. The solution
was to use a higher voltage power supply to ensure that the voltage drop across the sensor stayed
above the minimum level. She could have also used a 3-wire sensor, which ensures that the voltage
applied to the sensor is independent of shunt resistor voltage drop.
Watch Your Grounds (or use an isolated
instrument)
Contrary to what many believe (and have been erroneously taught in school), grounds are almost
never the same in industrial settings, exactly where most 4-20 mA current loop sensors are used.
Two or more grounds that are the same means that they are at the same potential. If so, a
measurement between the grounds of the various field sensors and the instrument using a digital
volt meter (DVM) on both its DC and AC settings will show zero volts, or very close to it. In reality,
youll measure at least several volts, and Ive seen as much as 75 Volts. When grounds that are not
at the same potential are tied together (which you need to do to make the measurement), current
flows through them, creating several possible measurement outcomes for non-isolated instruments:
The measurement is noisy. 1.
The measurement is inaccurate. 2.
You irreparably damage the instrument. 3.
You saturate the instrument (its not damaged, but you cant make a successful measurement, 4.
either.)
To remedy these problems requires the following:
Use an isolated instrument for your 4-20 mA current loop measurements. This single decision 1.
allows you to ignore all other grounding issues in exchange for successful measurements in any
situation. If you dont have an isolated instrument, read on
Ensure that the loop power source is isolated. This means that its output ground (the one 2.
connected to the sensor) is not tied to its input ground (the one that connects to AC line power.)
An isolated power source means that the output ground can be tied to another ground (like a non-
isolated instrument) without consequence.
In self-powered applications, ensure that the low-side of the loop is isolated from its power 3.
source.
If you lack control over the power sources and determine that they are not isolated, then your 4.
only option is to power ALL devices (power supplies, self-powered sensors, the instrument, and its
connected PC) from exactly the same power outlet. Dont make the mistake of using outlets that
are close to each other. If you run out of receptacles on a single outlet, then use a power strip.
Again, its worth repeating that all of the cautions associated with proper grounding disappear if an
isolated instrument is used to make the measurement.
Sensors with 4-20 mA outputs are encountered in all disciplines and in many configurations. Contact
us with any questions that arise in your unique situation.