Sei sulla pagina 1di 92

Medium-voltage switchgear

No. AGS 531 446-01


Edition 12/2011
www.schneider-electric.com
GHA
Gas-insulated switchgear 40.5 kV ( 40 kA)
for single and double busbar panels
Assembly Instructions
Manufacturer:
Schneider Electric Sachsenwerk GmbH
Rathenaustrasse 2
D-93055 Regensburg
Germany
( +49 (0) 9 41 46 20-0
7 +49 (0) 9 41 46 20-418
Service:
Schneider Electric Sachsenwerk GmbH
Rathenaustrasse 2
D-93055 Regensburg
Germany
( +49 (0) 9 41 46 20-777
7 +49 (0) 9 41 46 20-418
GHA
3 AGS 531 446-01 | Edition 12/2011
Contents
Remarks on this manual ............................................................................. 5
Purpose and target group ........................................................................................... 5
Reference documents ................................................................................................ 5
Terms and symbols used ............................................................................................ 6
Abbreviations used ..................................................................................................... 6
Any questions or suggestions?................................................................................... 6
1 Safety provisions .............................................................................. 7
2 Design, description, variants ........................................................... 8
2.1 Switchgear panels with single busbar ............................................................. 8
2.2 Panels with double busbar .............................................................................11
2.3 Dimensions and weights ............................................................................... 13
2.4 Applicable standards ..................................................................................... 17
2.5 Environmental and operating conditions ....................................................... 17
2.6 Intended use ................................................................................................. 18
2.7 Disposal after the end of service life ............................................................. 18
3 Packaging, transport, storage........................................................ 19
3.1 Shipping units ................................................................................................ 19
3.2 Transport ....................................................................................................... 19
3.3 Storage .......................................................................................................... 20
4 Assembly ......................................................................................... 21
4.1 Safety provisions ........................................................................................... 21
4.2 Important instructions for assembly .............................................................. 21
4.3 Requirements regarding the switchgear room .............................................. 22
4.4 Transporting the panels on the construction site........................................... 25
4.4.1 Transport of panel by means of a crane ................................................... 25
4.4.2 Transport using the transport frame ......................................................... 26
4.4.3 Transporting the panels onto the base frame ........................................... 27
4.5 Attachment of pressure relief duct ................................................................ 28
4.6 Remove cable compartment cover and shutters ........................................... 29
4.6.1 Cable compartment interlock (optional) .................................................... 29
4.6.2 Remove cable compartment cover and shutters ...................................... 30
4.7 Installation of panels ..................................................................................... 32
4.7.1 Installation of the frst switchgear panel .................................................... 32
4.7.2 Removal of transport securing device ...................................................... 32
4.7.3 Pre-coat the high-quality electrical joints of the busbar link ...................... 33
4.7.4 Preassembling the clamping contacts ...................................................... 34
4.7.5 Screw-fastening the panels to one another .............................................. 35
4.8 Compensating shutters for the panel front .................................................... 36
4.9 Busbar link: B link .......................................................................................... 38
4.9.1 Connecting the busbar (fasten preassembled clamping contacts) ........... 40
4.9.2 Contact resistance measurement of busbar screw fastening ................... 41
4.9.3 Fasten silicone sleeve to adjacent panel .................................................. 42
4.9.4 Cover of busbar link in case of panels without pressure relief duct .......... 43
4.10 Reinforcement ............................................................................................... 46
4.11 Screw-fastening the panel to the base frame ................................................ 47
4.12 Mounting the earth bus ................................................................................. 48
5 Busbar attachments ........................................................................ 49
5.1 Safety provisions ........................................................................................... 49
5.2 Assembly of surge arresters ......................................................................... 49
5.3 Assembly of voltage transformers ................................................................. 50
6 Low-voltage cabinet ........................................................................ 52
6.1 Assembly ....................................................................................................... 52
6.2 Connecting the control lines .......................................................................... 53
GHA
4 AGS 531 446-01 | Edition 12/2011 4
Contents
7 Switchgear termination................................................................... 55
7.1 Attachment of the protective tank to the left-hand / right-hand end
of the busbar ................................................................................................. 55
7.2 Switchgear without pressure relief duct ........................................................ 56
7.2.1 Overview ................................................................................................... 56
7.2.2 Attachment of the right-hand or left-hand side wall .................................. 56
7.2.3 Extension of side wall in double busbar switchgear ................................. 58
7.2.4 Gap covers ............................................................................................... 59
7.3 Attachment of fan .......................................................................................... 61
8 Switchgear with pressure relief device ......................................... 63
8.1 Overview ....................................................................................................... 63
8.2 Cover plate ................................................................................................... 65
8.3 Attachment of pressure relief duct ................................................................ 66
8.4 Attachment of side walls for pressure relief from the switchgear room ......... 67
8.5 Attachment of side walls for pressure relief into the switchgear room .......... 68
9 High-voltage connection ................................................................ 69
9.1 Cable compartment with base plates (optional) ............................................ 69
9.2 Outer cone-type bushing ............................................................................... 70
9.3 Inner cone-type socket .................................................................................. 73
10 Replacement of transformer .......................................................... 76
10.1 Current transformer for outer cone-type connection ..................................... 76
10.2 Voltage transformer ....................................................................................... 77
11 Commissioning ............................................................................... 78
11.1 Final steps ..................................................................................................... 78
11.1.1 Attachment of the tool board .................................................................... 78
11.1.2 Cleaning and checking assembly ............................................................. 78
11.1.3 Remount covers ....................................................................................... 79
11.1.4 Damaged paint ......................................................................................... 79
11.1.5 Inspection ................................................................................................. 79
11.2 Commissioning .............................................................................................. 79
12 Optional high-voltage test on commissioning ............................. 80
12.1 Power frequency withstand test of the busbar .............................................. 80
12.2 Cable testing ................................................................................................. 82
12.3 Cable jacket test ............................................................................................ 85
13 Annex ............................................................................................... 86
13.1 Auxiliary products .......................................................................................... 86
13.2 Required tools (not included in the scope of supplies) .................................. 86
13.3 Coating the contact surfaces ......................................................................... 88
13.4 Screw locking compound .............................................................................. 88
13.5 Specifcations for screw connections ............................................................ 89
GHA
5 AGS 531 446-01 | Edition 12/2011
For information which is not included in this manual and the assembly drawings sup-
plied with the equipment, please contact the manufacturer.
As our products are subject to continuous further development, we reserve the right
to make changes regarding the standards, illustrations and technical data.
All dimensions specifed in this manual are in millimeters.
Purpose and target group
This Technical Manual describes assembly and commissioning of gas-insulated
medium-voltage switchgear units of the GHA series.
It is an integral part of the product and must be stored so that it is readily accessible
at all times for and can be used by persons who are to work on the switchgear. If the
switchgear is sold to new owners, they must receive this document along with the
switchgear.
This Technical Manual is exclusively intended for specialist electricians who
have been certifed for the GHA series (training certifcate).
This Technical Manual cannot describe every imaginable individual case or every
customer-specifc version of the product. Thus, only the basic assembly procedure is
described. The detailed assembly work for the switchgear model in question is illus-
trated for each operation required in the assembly drawings provided to this effect.
Reference documents

Purchase agreement with the stipulations regarding the switchgear-specifc
equipment and the legal details

The appropriate switchgear-specifc circuit diagrams / documentation

GHA Operating Manual

The Operating Manuals of the devices installed in the switchgear:
Voltage detection systems, e. g. IVIS (no. AGS 531751-01)
Insulating gas monitoring system IDIS (no. AGS 531691-01)
System for the detection of internal arcs ILIS (optional)
(no. AGS 531761-01)
Devices in the low-voltage cabinet.

The Assembly Instructions of the manufacturer
of the cable connection systems to be connected to the switchgear
of the voltage transformers.

The assembly drawings supplied with the equipment
The following additional
documents must be complied
with:
Remarks on this manual
GHA
6 AGS 531 446-01 | Edition 12/2011 6
Remarks on this manual
Terms and symbols used
This Technical Manual uses certain terms and symbols. They warn about dangers or
provide important information which must be complied with in order to avoid danger
to persons and damage to equipment:
"Danger!"
This danger symbol warns about dangerous electrical voltage.
Contact with voltage may result in fatal injury!
"Warning!"
This danger symbol warns about the risk of injury. Please comply
with all the provisions identifed by this symbol in order to avoid
death or serious injury.
"Warning!"
This danger symbol warns about the risk of falling.
"Important:"
This instruction symbol is used for information which is important to
avoid material damage.
Abbreviations used
For reasons of simplifcation, the following abbreviations are used in this manual:
ESS = Single busbar
DSS = Double busbar
SS1 = Busbar 1
SS2 = Busbar 2
SS-StW = Busbar current transformer
TrSS = Disconnector in the busbar run
U
r
= Rated voltage
I
r
= Rated normal current (feeder panel)
Any questions or suggestions?
Do you have any questions or suggestions regarding this manual, or do you require
further information?
We always strive to provide you with the best-possible information for optimum, safe
use of our products. Thus, do not hesitate to contact us if you have any recommen-
dations, amendments or proposals for improvement.
GHA
7 AGS 531 446-01 | Edition 12/2011
1 Safety provisions
The work described in this manual may only be performed by specialist electricians
with proven experience in conjunction with the GHA series and the applicable safety
provisions.
Please read the whole manual carefully before working on the switchgear.

Metal-enclosed AC switchgear for rated voltages > 1 kV up to including 52 kV:
IEC 62271-200

Use and handling of sulphur hexafuoride (SF
6
) in high-voltage switchgear: IEC
62271-303

The locally applicable accident prevention, operating and work instructions
must be complied with.

Installation: IEC 61936-1/EN 61936-1
1

Operation of electrical equipment: EN 50110-1
1
1
The national standards applicable in the country where the equipment is to be
installed must be complied with.
Before performing work on the panels, it is essential that you comply with the follow-
ing instructions:
Danger!
Risk of fatalities due to high voltage. Isolation from high voltage
and earthing must always be ensured before performing assembly
or maintenance work.
Danger!
Risk of fatalities due to supply voltage. Isolation from supply
voltage must always be ensured before performing assembly or
maintenance work.
Warning!
Risk of injury due to movable parts in mechanical drives. For
maintenance work,
isolate the system from the supply voltage
release the circuit-breakers energy storing device by OFF-
ON-OFF operation and make-proof earthing switches by the
appropriate ON-operation.
Warning!
After removing covers from a switchgear unit, operator safety
may be reduced regarding internal arcs unless the switchgear is
isolated from the power supply. Optimum operator safety is only
ensured if the switchgear is completely disconnected from the
power supply and grounded during assembly.
For the case of an internal fault, the GHA switchgear features pressure relief ports
which prevent the panels and the switchgear from bursting.
This Technical Manual does not include information regarding the safety of buildings
in case of internal faults (pressure load of the switchgear room and necessary pres-
sure relief ports). Pressure calculations for switchgear rooms incl. recommendations
regarding pressure relief ports can be provided on request against a fee. For further
details, please contact the manufacturer.
In case of fre or of internal faults, toxic and caustic decomposition products may be
produced. Comply with the locally applicable accident and safety provisions.
In case of personal injury, take frst-aid measures or cause them to be taken.
Applicable standards
and regulations:
Behaviour in case of incidents or
accidents
GHA
8 AGS 531 446-01 | Edition 12/2011
2 Design, description, variants
2.1 Switchgear panels with single busbar
1
2
3
4
5
6a
7
8
9
10
12
13
14
15
16
17

1 Busbar tank with three-position
switch
2 Jack rings
3 Busbar link
4 Circuit-breaker tank with vacuum
interrupter chambers
5 Toroidal-core current transformer
6a Outer cone-type bushing
6b Inner cone-type socket
7 Voltage transformer (optional)
8 Cable support
9 Cable compartment cover
10 Disconnecting device for voltage
transformer (optional)
11 Test sockets for cable test
12 Capacitive voltage testing system
13 IDIS indicator for insulating gas
monitoring
14 Hinged front frame
15 Manual operator interface
16 Low-voltage cabinet
17 IDIS gas density switch
Fig. 1
Circuit-breaker panel with outer cone-type bushing
1
2
3
4
5
7
11
16
17
18
10
6b
8
9
11
6b
8
7
5
10
Fig. 2
Circuit-breaker panel with inner cone-type socket
GHA
9 AGS 531 446-01 | Edition 12/2011 9
2 Design, description, variants
1 2 3
4
5
6
9
12
10
11
8
7
13
14

1 Right-hand busbar tank with three-
position switch
2 Left-hand busbar tank with three-
position switch
3 Jack rings
4 Busbar link
5 Circuit-breaker tank with vacuum
interrupter chambers
6 Toroidal-core current transformer
(optional)
7 Voltage transformer (optional)
8 Cable compartment cover
9 Test sockets (optional)
10 IDIS indicator for insulating gas
monitoring
11 Hinged front frame
12 Manual operator interface
13 Low-voltage cabinet
14 IDIS gas density switch
Fig. 3
Bus section coupler, shown for rated current I
r
2000 A
6
8
Fig. 4
Bus section coupler, shown for rated current I
r
2500 A
L R
L R
GHA
10 AGS 531 446-01 | Edition 12/2011 10
2 Design, description, variants
Busbar attachments
Fig. 5
Busbar voltage transformers (2 variants available)
Fig. 6
Busbar surge arresters (2 variants available)
Fig. 7
Busbar earthing switch
GHA
11 AGS 531 446-01 | Edition 12/2011 11
2 Design, description, variants
2.2 Panels with double busbar
1
2
7
3
4a
5
6
17 18 19 16
8
9
10
12
13
14
15
11

1 Gas density switch of the IDIS sys-
tem for busbar 1 (rear busbar)
2 Busbar link SS1
3 Circuit-breaker tank with vacuum
interrupter chambers
4a Outer cone-type bushing
4b Inner cone-type socket
5 Toroidal-core current transformer
6 Voltage transformer (optional)
7 Cable support
8 Cable compartment cover
9 Disconnecting device for voltage
transformer (optional)
10 Capacitive voltage testing system
11 IDIS indicator for insulating gas
monitoring
12 Hinged front frame
13 Manual operator interface
14 Low-voltage cabinet
15 Gas density switch of the IDIS sys-
tem for busbar 2 (upper busbar)
16 Busbar link SS2
17 Tank, busbar 2 (upper busbar) with
three-position switch
18 Jack rings
19 Tank, busbar 1 (rear busbar) with
disconnector
20 Test sockets for cable test
Fig. 8
Circuit-breaker panel with outer cone-type bushing
1
2
3
4
5
7
20
16
17
18
10
6b
8 9
5
11
10
7
8
6b
Fig. 9
Circuit-breaker panel with inner cone-type socket
1
2
1
2
GHA
12 AGS 531 446-01 | Edition 12/2011 12
2 Design, description, variants
Fig. 10
Bus section coupler, busbar 2 (busbar 1 analogous)

Fig. 11
Bus coupler
Fig. 12
Metering panel with busbar voltage transformer or with bus-
bar surge arrester (not shown)

Fig. 13
Bus section coupler, busbar 2 (busbar 1 analogous)
1
2
1
2
1
2 1
2
GHA
13 AGS 531 446-01 | Edition 12/2011 13
2 Design, description, variants
2.3 Dimensions and weights
Switchgear panels with single busbar (see Fig. 14, page 15)
Panel type
Rated current I
r
1
[A]
Panel width A
[mm]
Depth
2
[mm]
Depth
3
[mm]
Approx.
weight
[kg]
4
Feeder panel
1250 600
1330
2400/2780
(Height of low-voltage
cabinet:
800/1200)
700
1600
600/800
5
800
2000 1380/1330
5
900
2500 900 1330 1100
L R
Bus section
coupler
1250
800
1330 900
1600/2000 1380 1100
2500 1000 1330 1300
Bus sectionalizer
with disconnector
2500 600 1330 300
Busbar measure-
ment with current
transformer
2500 600 1330
2600/2780
(Height of low-voltage
cabinet:
800/1200)
300
Attached busbar earthing switch +70
Disconnecting device attached to the busbar (for voltage transformer or
surge arrester) (panel height depending on the attachment design, see
Chapter 2.1, page 10)
2400
6
/2500
7
+70
Voltage transformer for outgoing feeder cable / busbar
+120
(3 x 40)
1
In the case of feeder panels, the rated current I
r
refers to the feeder (max. busbar nominal current: 2500 A)
2
The values listed in the Tables are referred to a panel depth without pressure relief duct on the rear.
Depth of panels with rear pressure relief duct: 1595 mm
3
Damping resistor (for optional voltage transformer) on the low-voltage cabinet: specifed height +150
Height of pressure relief duct: 2400
Height of pressure relief duct with fan: 2600
4
including the low-voltage cabinet, without voltage transformer and for feeder panels with outer cone-type bushing
feeder panels with inner cone-type socket: max. + 200 kg
Panels with rear pressure relief duct: max. + 100 kg
5
The dimensions depend on the cable connection system; inner cone-type socket / outer cone-type bushing system
6
Voltage transformer on the busbar can be removed by pulling it laterally (see Fig. 5, page 10)
7
Voltage transformer on the busbar can be removed by pulling it upwards (see Fig. 5, page 10
GHA
14 AGS 531 446-01 | Edition 12/2011 14
2 Design, description, variants
Switchgear panels with double busbar (see Fig. 15, page 16)
Panel type
Rated current I
r
1
[A]
Panel width
A
[mm]
Depth
2
[mm]
Depth
3
[mm]
Approx.
weight
[kg]
4
1
2
Feeder panel
1250 600
1700
2400/2780
(Height of low-voltage
cabinet:
800/1200)
900
1600
600/800
5
900
2000
1860
1200
2500 900 1400
1
2
Bus section coupler
1250/1600
800
1700 1100
2000 1980 1400
2500 1000 2030 1300
1
2
Bus section coupler
1250/1600
800 1700
1100
2000 1400
2500 1000 1850 1300
1
2
Bus coupler
1250/1600
600
1700 900
2000
1860
1100
2500 900 1600
1
2
Bus sectionalizer with
disconnector
1600
2500
600
600
1700
1970
400
450
1
2 Busbar measurement
with current trans-
former
2500 600 1700 2600/2780 600
1
In the case of feeder panels, the rated current I
r
refers to the feeder (max. busbar nominal current: 2500 A).
2
The values listed in the Tables are referred to a panel depth without pressure relief duct on the rear.
Technical details and the design for the rear pressure relief duct must be clarifed with the manufacturer as required.
3
Damping resistor (for optional voltage transformer) on the low-voltage cabinet: specifed height +150
Height of pressure relief duct: 2400
Height of pressure relief duct with fan: 2600
4
The specifed weights apply including the low-voltage cabinet and without the voltage transformer; they refer to feeder panels
with outer cone-type bushing.
- Feeder panels with inner cone-type socket: max. + 200 kg
Panels with rear pressure relief duct: max. + 150 kg
5
The dimensions depend on the cable connection system; inner cone-type socket / outer cone-type bushing
GHA
15 AGS 531 446-01 | Edition 12/2011 15
2 Design, description, variants
Panel type
Rated current I
r
1
[A]
Panel width
A
[mm]
Depth
2
[mm]
Depth
3
[mm]
Approx.
weight
[kg]
4
1
2
Metering panel for volt-
age transformer
2500 600 1700 2400
6
/2500
7
400
1
2
attached busbar earth-
ing switch
2500 600 1700 2400/2780 400
attached voltage transformer for outgoing feeder cable / busbar
+ 120
(3 x 40)
1
In the case of feeder panels, the rated current I
r
refers to the feeder (max. busbar nominal current: 2500 A).
2
The values listed in the Tables are referred to a panel depth without pressure relief duct on the rear.
Technical details and the design for the rear pressure relief duct must be clarifed with the manufacturer as required.
3
Damping resistor (for optional voltage transformer) on the low-voltage cabinet: specifed height +150
Height of pressure relief duct: 2400
Height of pressure relief duct with fan: 2600
4
The specifed weights apply including the low-voltage cabinet and without the voltage transformer; they refer to feeder pan-
els with outer cone-type bushing.
- Feeder panels with inner cone-type socket: max. + 200 kg
Panels with rear pressure relief duct: max. + 150 kg
5
The dimensions depend on the cable connection system; inner cone-type socket / outer cone-type bushing
6
Voltage transformer can be removed by pulling it laterally (see Fig. 12, page 12)
7
Voltage transformer can be removed by pulling it upwards
1340/1380
3
1595
4
2
3
8
0
/
2
7
8
0
1
2
4
0
0
A
2
1
0
0

-

2
3
0
0
+150 +200
5 6

1 with low-voltage cabinet 800/1200
mm
2 Height depends on the busbar
cooler attachments
3 Panel depth depending on rated
current I
r
of the panel (without/with
cooler, see Table)
4 Depth of panel with pressure relief
duct
5 Damping resistor
6 Fan attachment
Fig. 14
Dimensions of a series GHA single busbar panel
GHA
16 AGS 531 446-01 | Edition 12/2011 16
2 Design, description, variants
2
1
0
0

-

2
3
0
0
2
3
8
0
/
2
7
8
0
1
1700/1960
1990
6
/2210
7
A
2
4
0
0
+150 +200
5 4

1 with low-voltage cabinet 800/1200
mm
2 Height depends on the busbar
cooler attachments
3 Panel depth depending on rated
current Ir of the panel (see Table)
4 Damping resistor
5 Fan attachment
6 Depth of panel with pressure relief
duct
7 Depth of panel with pressure relief
duct and bus section coupler of
the rear busbars
(I
r
= 2500 A)
Fig. 15
Dimensions of a series GHA double busbar panel
GHA
17 AGS 531 446-01 | Edition 12/2011 17
2 Design, description, variants
2.4 Applicable standards

metal-enclosed

SF
6
-insulated

type-tested and prefabricated

tested for internal faults (qualifcation IAC)

dimensioned for indoor installation
Designation IEC standard EN standard
Switchgear
IEC 62271-1
IEC 62271-200
EN 62271-200
Circuit-breaker IEC 62271-100 EN 62271-100
Earthing switch IEC 62271-102 EN 62271-102
Disconnector IEC 62271-102 EN 62271-102
Current transformer IEC 60044-1 EN 60044-1
Voltage transformer IEC 60044-2 EN 60044-2
Voltage detection systems IEC 61243-5 EN 61243-5
Protection against accidental con-
tact, foreign bodies and water
IEC 60529 EN 60529
Installation IEC 61936-1 EN 61936-1
1
Operation of electrical equipment EN 50110-1
1
Insulating gas sulphur hexafuoride
SF
6
IEC 60376 EN 60376
Use and handling of sulphur hexa-
fuoride (SF
6
)
IEC 62271-303
1
The national standards applicable in the country where the equipment is to be
installed must be complied with.
Degrees of protection against accidental contact and foreign objects accord-
ing to IEC 60529
Main electric circuits IP65
Drive mechanisms IP2X
1
Low-voltage cabinet IP3X
1
Cable compartment IP3X
1
1
optional IP5X
2.5 Environmental and operating conditions
GHA is an indoor switchgear and may only be operated under normal conditions
in acc. with IEC 62271-1. Operation under conditions deviating from these is only
admissible subject to consultation with and written approval from the manufacturer.
Ambient conditions (in accordance with IEC 62271-1)
Temperature class "Minus 5 indoors
Min./max. ambient temperature C 5
1
/+40
1
Average value over 24 hours C 35
1
mean rel. air humidity: 24 hour/1 month % 95/ 90
Installation altitude above sea-level m 1000
1
1
other values available on request
Type GHA switchgear units are:
GHA switchgear units meet
the following standards and
regulations:
Degree of protection against
accidental contact and foreign
objects:
GHA
18 AGS 531 446-01 | Edition 12/2011 18
2 Design, description, variants
2.6 Intended use
Gas-insulated GHA medium-voltage switchgear units are exclusively intended for
switching and distributing electrical energies. They may only be used in the scope of
the specifed standards and the switchgear-specifc technical data. Any other utiliza-
tion constitutes improper use and may result in dangers and damage.
The manufacturer shall not be held responsible for damage which occurs if

instructions in this Technical Manual are not complied with;

the switchgear is not operated according to its intended use (see above);

the switchgear is assembled, connected or operated improperly;

accessories or spare parts are used which have not been approved by the
manufacturer;

the switchgear is converted without the manufacturers approval, or if inadmis-
sible parts are added.
No liability is accepted for parts provided by customers, e.g. current transformers.
2.7 Disposal after the end of service life
The operating equipment contains the fuorinated greenhouse gas SF
6
covered by
the Kyoto Protocol with a global warming potential (GWP) of 22 200.
SF
6
must be recovered and must not be released into the atmosphere. When trans-
porting and handling SF
6
, the specifcations in IEC 62271 High-Voltage Switchgear
and Controlgear Part 303 Use and Handling of Sulphur Hexafuoride (SF
6
), must
be complied with.
A material and recycling data sheet can be provided on request for the disposal of
series GHA switchgear units at the end of their service life.
Disposal is performed as a service by the manufacturers Service Center and is
subject to a fee.
Liability Disclaimers
GHA
19 AGS 531 446-01 | Edition 12/2011
3 Packaging, transport, storage
3.1 Shipping units
Delivery is effected in terms of prefabricated single switchgear panels. One transport
unit consists of max. 2 individual switchgear panels which are fastened to the pallet.
The busbar compartment with three-position switch, the circuit-breaker compart-
ment, the drive mechanisms and the supporting structures are mounted ready for
connection and routine-tested. The individual busbar links are mounted on site.
The low-voltage cabinets are assembled in the factory or supplied as accessories,
depending on the customers wishes.

If packed exclusively for truck transport, the panels are delivered on a pallet
with PE protective flm.

For sea transport, the units are packed in sealed aluminium foil with desiccant
and in a closed wooden case with tightly closed wooden base (also for con-
tainer transport).

In case of air transport, the panels are packaged in wooden crates with a
protective PE flm hood (dust protection) or in wooden crates, also with closed
wooden bases, however without protective hoods (dust protection).
Important:
The weight of the entire transport unit is indicated on the packaging.
3.2 Transport
Warning!
Danger due to tipping
load.
Transport units must be
protected suffciently
against slipping and tip-
ping during transport.
Warning!
Suffcient stability and evenness of the supporting area (foor)
must be ensured.

Handle shipping units carefully when unloading and unpacking them

Shipping units must be checked upon receipt. Any damage which may have
occurred in transit must be recorded and reported to the manufacturer immedi-
ately.

The consignment must be checked for completeness based on the shipping
documents.

The supplier must be notifed in writing without delay about any possible devia-
tions.
Packaging
Abb. 16
Do not tip the transport units
Transport using a forklift truck
GHA
20 AGS 531 446-01 | Edition 12/2011 20
3 Packaging, transport, storage
The panel may only be transported on a pallet. The entire length of the forks must be
placed under the transport unit (Fig. 17).
Fig. 17
Transport with forklift truck
3.3 Storage
Warning!
Suffcient stability and evenness of the supporting area (foor)
must be ensured.
If the panels are not installed immediately after delivery, they can be stored under
the following conditions:

Panels must be stored in vertical position, and must not be stacked.

Storage only admissible indoors

Panels and accessories must be packed in a wooden crate with a dessicant
and sealed in aluminium foil (storage period max. 2 years after date of packag-
ing).
5 C
+ 40 C
Fig. 18
Diagram showing the storage conditions
Transport using a forklift truck
GHA
21 AGS 531 446-01 | Edition 12/2011
4 Assembly
4.1 Safety provisions
The switchgear panels may only be installed and assembled by the manufacturers
staff or by persons who have been certifed for this work.
The GHA series switchgear panels are delivered with the circuit-breaker set to
OFF, the energy storing device released and the disconnector and earthing switch
set to OFF.
Warning!
Risk of injury due to movable parts in the mechanical drive. The
energy storing device of the circuit-breakers and the earthing
switches must not be charged during assembly.
Warning!
Risk of accidents! Watch out for foor openings in the switchgear
room.
Danger!
Danger due to insuffcient dielectric strength of high-voltage con-
nections in case of assembly under aggravated ambient condi-
tions. During assembly of the busbar link and the high-voltage
connections, it is essential to avoid condensation, dirt and dust
deposits. At the time of installation, the ambient temperature must
amount to 10 C.
Warning!
The top sides of the panels are not meant to be walked on. Per-
sons may fall through them, get injured or may damage the panel.
When work has to be performed on the panel top - e.g. assembly
of defectors, fans or pressure relief ducts - temporarily position a
solid mounting rack to step on.
Warning!
Risk of injury due to non-respect of the safety provisions in Chap-
ter 1, on page 7.
4.2 Important instructions for assembly
Important:

Switchgear with pressure relief duct (see Chapter 8, as of page
63): The pressure relief duct must be mounted before the panel is
positioned on the base frame.

Condensation, dirt and dust should be avoided during assembly
on all accounts, in order to prevent damage to the panels.

For assembly, observe the assembly drawings supplied with the
equipment. Read them before you commence assembly work.
The drawing numbers are specifed in this manual under the de-
scription of the assembly work in question.

For all screw connections, refer to the tightening torques specifed
in the Annex.

The transport securing device on the busbars must not be re-
moved before assembly of the busbar link acc. to Chapter 4.7 on
page 32.
GHA
22 AGS 531 446-01 | Edition 12/2011 22
4 Assembly
4.3 Requirements regarding the switchgear room
Important:
Before installing the switchgear panels, make sure that the switchgear
room is checked according to the customer-specifc switchgear docu-
mentation.

Observe the minimum distance between the switchgear and the wall of the
building.

The load-bearing capacity of the fastening areas must correspond to the weight
of the switchgear (perform a stress analysis of the building).

Check base frame for dimensions and tolerances in position.

Check position of foor openings for high-voltage and low-voltage cables.
Before the switchgear is positioned at its site of installation, check that the base
frame dimensions are precisely correct.
Flatness: 1 mm/meter
Straightness: 1 mm/meter
Parallelism: 1 mm/meter
Height difference over the entire length of the switchgear: 2 mm
Design data of GHA switchgear: Examples for various switchgear panel variants

5
0
0
1
1
9
4
4
1
180 600/800 600/800
5
0
5
0
7
2
50
6
8
1
4
2 3
50
900
800
900
800
100
460/660 660
1
7
5
35
5
Fig. 19
Location of base frame and ceiling ducts (example: double busbar switchgear)
1 Rear gap cover
2 Steel base frame
3 Ceiling duct for high-voltage connections
4 Wall of building
5 Possible cross-bracings
6 Cooler attachments
7 Side wall
8 Side wall extension for double busbar switchgear
GHA
23 AGS 531 446-01 | Edition 12/2011 23
4 Assembly
100
1700
1
0
0
0
1340
2
4
0
0
/
2
7
8
0
Fig. 20
Example of panels with single busbar in the switchgear room
500 2100
1
0
0
0
2
3
8
0
/
2
7
8
0
1700
Fig. 21
Example of panels with double busbar in the switchgear room
GHA
24 AGS 531 446-01 | Edition 12/2011 24
4 Assembly
500
1
1700 1595
1
0
0
0
2
4
0
0
Fig. 22
Example of panels with single busbar and pressure relief duct in the switchgear room
1
Switchgear accessible from the rear: 800
500
1
2100 1990
1
0
0
0
2
4
0
0
Fig. 23
Example of panels with double busbar and pressure relief duct in the switchgear room
1
Switchgear accessible from the rear: 800
GHA
25 AGS 531 446-01 | Edition 12/2011 25
4 Assembly
4.4 Transporting the panels on the construction site
Warning!
Make sure the rope or chain is strong enough to bear the weight
of the panel and the trucks. Comply with the relevant provisions
for hoisting equipment.
Warning!
On lowering the panels, make sure that the supporting platform is
suffciently stable and even.
Warning!
Risk of tipping over. During transport, pay attention to the weight
distribution. The center of gravity is at gas tank level in the upper
part of the switchgear panel. Never move panels without using
transport aids.
Warning!
Risk of accidents. Pay attention to foor openings!
4.4.1 Transport of panel by means of a crane
1. Remove transport packaging (protective flms).
2. Attach rope/chains to the jack rings located on the busbar tank (Fig. 24).
Important:
The ropes must have the following minimum lengths: L 900 mm
3. Release transport fastening device of the panel from the transport pallet (Fig.
24, item 1).
4. Lift the panel carefully with the crane.
5. If necessary, mount transport rollers (Fig. 26). Description of assembly, see
following page.
6. Lower the panel slowly to the foor at its place of destination.
1
L


9
0
0

Fig. 24
When lifting, make sure that at least the
minimum rope length L is used.
1 Transport fastening

1
Fig. 25
Panels with cooler and busbar attach-
ments
1 Use an additional frame for crane
transport.

Fig. 26
Mounting the transport rollers (see
Chap. 4.4.2, page 26)
GHA
26 AGS 531 446-01 | Edition 12/2011 26
4 Assembly
4.4.2 Transport using the transport frame
For transport on the foor, a frame must be mounted to the left and right of the
switchgear panel (not included in scope of supplies).
1. Insert locating pins of transport frame into the lateral bore-holes in the support-
ing structure of the switchgear panel, and secure them by means of the two
knurled screws (Fig. 27, item 2).
2. Actuate front toggle lever (3) to its stop in the direction of the arrow. Press the
button on the rear lifting device (4) and actuate lever to its stop in the direction
of the arrow till it reaches its stop.
3. The panel is lifted.
1 2
3 4
5
Fig. 27
Mounting the transport rollers
1 Transport frame
2 Knurled screws
3 Front toggle lever
4 Rear lifting device with push-button
5 Switchgear panel
These panels are delivered from the factory with additional supporting profles
mounted. The supporting profles must not be removed during assembly.
For transport on the foor, the transport rollers must be secured to the supporting
profles to the left and right of the supports provided to this effect (Fig. 28).
Remove a supporting profle before screw-fastening the panel to an adjacent panel.
A supporting profle - left-hand or right-hand - must always be left mounted to the
panel as long as the panel is not screw-fastened to the adjacent panel. Remove sup-
porting profle after having screw-fastened the panels.
Fig. 28
Panel with pre-assembled supporting profles and attached transport rollers
Assembly
Panels with center of gravity
located in the rear part (e. g.
single busbar panel with bus
section coupler on the rear
busbar)
GHA
27 AGS 531 446-01 | Edition 12/2011 27
4 Assembly
4.4.3 Transporting the panels onto the base frame
1. Place two U profles (not included in scope of supplies) on the base frame as
traversing aid and block them by (lower) stops against slipping in the base
frame (Fig. 29, item 1).
2. Adjust the distance between the two U profles in accordance with the panel
width. When positioning the panels, make sure that the transport rollers are
located in the U profles.
3. Move panel onto the base frame, align front edge (see space assignment plan)
and lower the panel.
4. Remove transport rollers and U profles.
1
2 3
Fig. 29
Moving the panel on the base frame
1 U profles with stop edges as traversing aid
2 Transport frame
3 Switchgear panel
GHA
28 AGS 531 446-01 | Edition 12/2011 28
4 Assembly
4.5 Attachment of pressure relief duct
Switchgear units are provided with pressure relief duct, if the following is required:

Accessibility in acc. with IEC 62271-200: Qualifcation IAC AFLR (accessibility
from all sides) and/or

Qualifcation IAC AFL(R) internal arc 40 kA/1 s
Important:
The pre-assembled pressure relief duct supplied with the equipment
must be mounted before the panel is positioned on the base frame.
After installation of the panels, mounting may no longer be possible in
part.
L 2 L 3
Fig. 30
Switchgear panel with single busbar
and pressure relief duct
Fig. 31
Switchgear panel with double busbar
and pressure relief duct
The attachment of the pressure relief duct is described in the assembly drawing in
question:
Panel width
[mm]
Busbar
system
Pressure
relief from the
switchgear
room with
customized
duct
Pressure relief
into the switchgear room
for fan attach-
ment
TrSS
SS-
Stw
600 800 900 1000
Sin-
gle
bus-
bar
Dou-
ble
bus-
bar
Internal arc
qualifcation
IAC AFLR,
25 kA/1 s
Internal arc
qualifcation
IAC AFLR,
40 kA/1 s
AGS002105-02 AGS003379-01
2
AGS002105-04 AGS002105-04
AGS002105-06 AGS002105-06 AGS002105-15
1
AGS002105-07 AGS002105-07 AGS002105-16
1
AGS003216-01 AGS003216-01
AGS002105-08 AGS003379-08
AGS002105-10 AGS002105-10
AGS002105-12 AGS002105-12
AGS002105-14 AGS002105-14
AGS003216-02 AGS003216-02
AGS002105-08 AGS002105-08 AGS002105-18
3
1
Optional fan attachment
2
only to be used for panels without busbar top structure, in this case AGS002105-02
3
only in case of I
r
= 2500 A
GHA
29 AGS 531 446-01 | Edition 12/2011 29
4 Assembly
4.6 Remove cable compartment cover and shutters
4.6.1 Cable compartment interlock (optional)
An additional interlock prevents the cable compartment cover from being removed if
the earthing switch is not switched ON.
1. Charge spring mechanism of the circuit-breaker (Fig. 32, item 3). Earth the
outgoing feeder cable (see Operating Manual).
2. Push interlocking slide of cable compartment cover (2) upwards.
At the same time, the cable compartment cover is unlocked and actuation of the
earthing switch (1) interrupted mechanically and electrically.
Important:
After removing the cable compartment cover, it is impossible to push
the slide (Fig. 32, item 2) down. The earthing switch remains locked.
1
2
3
00346
Fig. 32
Unlock/lock cable compartment cover
1 Insertion opening for manual actuation of the earthing switch
2 Slide for locking/unlocking the cable compartment cover
3 Charge the spring mechanism of the circuit-breaker drive manually (as long no
supply voltage is applied).
Interlocking matrix Earthing switch
Cable compartment
cover
Cable compart-
ment cover
screw-fastened unlocked
removed locked
Earthing switch
ON unlocked
OFF locked
After assembly of the cable compartment cover, press interlocking slide (Fig. 32,
item 2) down.
The earthing switch (1) can be switched off mechanically and electrically.
Unlocking the cable
compartment cover
Locking the cable compartment
cover
GHA
30 AGS 531 446-01 | Edition 12/2011 30
4 Assembly
4.6.2 Remove cable compartment cover and shutters
Important:
Store screws, bolts and shutters carefully for subsequent reuse.
1. Open front frame:
Operating shutter without inspection glass:
Release the two securing bolts (Fig. 33, item 1).
Operating shutter with inspection glass:
Open interlocking mechanism using the double-bit key (Fig. 34, item 2).
Then, open the front frame by swinging it to the left.
2. Unscrew the two securing bolts from the cable compartment cover (3).
3. First pull the cable compartment cover up, then forwards to remove it.
1
1
3
4
Fig. 33
Operating shutter without inspection
glass
1 Securing bolts of the front panel
3 Securing bolts of cable compart-
ment cover
4 Hinged front frame

3
4
2
Fig. 34
Operating shutter with inspection glass
2 Lock and double-bit key
3 Securing bolts of cable compart-
ment cover
4 Hinged front frame
Removing cable compartment
cover
GHA
31 AGS 531 446-01 | Edition 12/2011 31
4 Assembly
Important:
Identify panel in accordance with the nameplate on the operating shut-
ter to avoid confusion.
1. Release screw connection of the operating shutter (Fig. 35, item 5) from the
4 fastening points and remove shutter
2. Release the fastening of the two lateral covers (4) of the right-hand cable tray
and remove covers.
1
2
3
4
5
Fig. 35
Removal of shutters
1 Hinged front frame
2 Operating shutter
3 Cable compartment cover
4 Cable tray cover
5 Screw connection of operating shutter (4 x)
Unscrewing the shutters
GHA
32 AGS 531 446-01 | Edition 12/2011 32
4 Assembly
4.7 Installation of panels
4.7.1 Installation of the frst switchgear panel
Important:
The position of the frst panel is decisive for placement of the subse-
quent panels, thus it is essential that measuring is effected with the
utmost precision!
1. Place the panel on the base frame according to the switchgear-specifc space
assignment plan (see Chapter 4.4.3, page 27).
2. Align panel. Check the panel front for correct horizontal and vertical position. If
applicable, lift the panel and place shims in the direct vicinity of the fastening
areas, until the horizontal position has been reached.
3. Position the following panel on the base frame next to the frst panel according
to the switchgear-specifc space assignment plan.
4. Remove shutters from the panels as described in Chapter 4.6 as of page 29.
4.7.2 Removal of transport securing device
Remove transport securing device above the high-quality electrical joints of the
busbar link.
Remove plastic cover from the busbar bushing (Fig. 36).
The plastic hood above the silicone sleeve is attached laterally and on top of
the retaining clip (Fig. 37). Remove plastic hood carefully applying little force
only.
Fig. 36
Plastic cover on the busbar bushing

Fig. 37
Plastic hood above the silicone sleeve
GHA
33 AGS 531 446-01 | Edition 12/2011 33
4 Assembly
4.7.3 Pre-coat the high-quality electrical joints of the busbar link
Important:

Make sure the high-quality electrical joints are absolutely clean.

Special grease (art. no. AGS 003371-01) and the sponge element
(art. no. S 065969) are either included in the scope of supplies
or must be purchased separately, depending on the agreement
concluded.
In case of doubt, please contact the manufacturer as required.

1. Clean the high-quality electrical joints of the busbar link (Fig. 40) using white
spirit (art. no. S 009 002) and a lint-free cloth (also micro-fbre cloths).
2. For each side of a high-quality electrical joint, press a length of approx. 10 mm
substance out of the tube and apply it using the sponge element (Fig. 40). In
the beginning, apply slightly more (approx. 15 mm), as the sponge also absorbs
grease.
One tube (90 g) is suffcient for approx. 36 complete high-quality electrical joints
(72 high-quality joint surfaces).
Abb. 38
Special grease (art. no. AGS 003371-
01)

Abb. 39
Sponge element (art. no. S 065969)
10-15
1
Fig. 40
High-quality electrical joint at the bus-
bar bushing
1 Make sure that the inner diameter
is greased thoroughly!

10-15
1
Fig. 41
High-quality electrical joint on the sili-
cone sleeve
1 Make sure the electrode ring is
clean!
3. Use the sponge element to spread a uniform thin flm of the the special grease
over the entire surface. Blank spots not covered by grease should be avoided
on all accounts. Once treated, do not touch the surfaces of the high-quality
electrical joints any longer.
Apply special grease and spread
it uniformly by means of the
sponge element.
GHA
34 AGS 531 446-01 | Edition 12/2011 34
4 Assembly
Important:

Busbar bushing (Fig. 40): Check especially the inner diameter
of the high-quality electrical joint for non-greased areas and, if
necessary, re-coat.

Check the electrode ring in the silicone sleeve (Fig. 41, item 1) for
cleanness and the absence of grease and, if necessary, clean.
4.7.4 Preassembling the clamping contacts
4. The following factory setting of the clamping contacts (Fig. 42) must be checked
prior to assembly:
Turn the two screws until the two clamping contacts are in loose contact, then
turn the screws back by a half turn of the thread.
5. Clean and grease busbar contact surfaces and contact points on the clamping
contact (see Chapter 13.3, page 88).
6. Carefully slip the clamping contacts into the busbar tubes of the left-hand panel.
3 2
1
Fig. 42
1 Check the clamping contact screws.
2 Clean and grease the contact surfaces
3 Insert the contact tips
GHA
35 AGS 531 446-01 | Edition 12/2011 35
4 Assembly
4.7.5 Screw-fastening the panels to one another
1. Push panels carefully together. Clearance between busbar tanks: 153 2 mm
(Fig. 43, item 1).
2. Connect panels to one another
(assembly drawing AGS 000913-01):
front panel screw connection:
9 x self-locking screw M8 to its stop (Fig. 43, item 3).
Panels with a width of 900 or 1000 mm are screw-fastened using compen-
sating shutters (see Chapter 4.8, page 36).
rear panel screw connection:
Screw-fasten connecting link to the jack ring plate
2 x self-locking screw connection M8 (Fig. 43, item 2).
Panel types Pressure relief duct Mat. no.
without with
All panel variants, except busbar
current transformers
AGS000913-03
AGS000913-01
Busbar current transformer
AGS000913-02
AGS000913-05
3
2
1
9x
1532
2
Fig. 43
Screw-fastening the panels to one another
1 Check setting 153 2; measuring location: Edge shown on the busbar tank
2 Rear panel screw connection: fasten connecting link
3 Screw-fasten panels on the front.
GHA
36 AGS 531 446-01 | Edition 12/2011 36
4 Assembly
4.8 Compensating shutters for the panel front
Compensating shutters are only required for panels with a width of 900/1000 mm
(see also switchgear-specifc documentation), panels with a width of 600/800 mm do
not require compensating shutters in-between each other. The shutters are always
supplied in preassembled condition as accessories. The compensating shutter vari-
ants are subdivided in accordance with the following dependencies:
Height of low-voltage cabinet 800 mm or 1200 mm
Nominal width of compensating shutter 50 mm or 100 mm, depending on panel
arrangement (see Table)
Panel with
panel width [mm]
Panel width, adjacent panel
(left-hand or right-hand)
[mm]
Rated width, compensating
shutter (left-hand or right-
hand)
[mm]
900/1000
600/800 50
900/1000 100
A
1
2
3
4
5
50 100
4 4 1/2 3/5
900/1000
A
Fig. 44
Compensating shutters in the panel front
1 Upper compensating shutter, width
100 mm
2 Lower compensating shutter, width
100 mm
3 Lower compensating shutter, width
50 mm
4 Screw connection M8 (12 x per
shutter)
5 Upper compensating shutter, width
50 mm
Required nominal width of the
compensating shutter depending
on the panel arrangement:
GHA
37 AGS 531 446-01 | Edition 12/2011 37
4 Assembly
In-line panel, left-
hand
Panel width
LV cabinet height End panel, left-
hand
600/800 mm
In-line panel,
right-hand
Panel width
800 1200
not required 600/800
AGS003372-01
900/1000
AGS003372-02
In-line panel, left-
hand
Panel width
LV cabinet height End panel, left-
hand
900/1000 mm
In-line panel,
right-hand
Panel width
800 1200
AGS003372-01
600/800/900/1000
AGS003372-02
In-line panel, left-
hand
Panel width
LV cabinet height Center panel
600/800 mm
In-line panel,
right-hand
Panel width
800 1200
600/800
not required 600/800
AGS003372-01
900/1000
AGS003372-02
900/1000
AGS003374-01
600/800
AGS003374-02

AGS003372-01
+AGS003374-01
900/1000

AGS003372-02
+AGS003374-02
In-line panel, left-
hand
Panel width
LV cabinet height Center panel
900/1000 mm
In-line panel,
right-hand
Panel width
800 1200
600/800/900/1000

AGS003372-01
+AGS003374-01
600/800/900/1000

AGS003372-02
+AGS003374-02
In-line panel, left-
hand
Panel width
LV cabinet height End panel, right-
hand
600/800 mm
In-line panel,
right-hand
Panel width
800 1200
600/800 not required
900/1000
AGS003374-01
AGS003374-02
In-line panel, left-
hand
Panel width
LV cabinet height End panel, right-
hand 900/1000
mm
In-line panel,
right-hand
Panel width
800 1200
600/800/900/1000
AGS003374-01
AGS003374-02
In-line panel, left-
hand
Panel width
LV cabinet height End panel, left-
hand
900 mm
In-line panel,
right-hand
Panel width
800 1200
AGS002596-01
600/800
AGS002596-02
AGS002597-01
900/1000
AGS002597-02
Front compensating shutter,
attachment to panel
GHA
38 AGS 531 446-01 | Edition 12/2011 38
4 Assembly
In-line panel, left-
hand
Panel width
LV cabinet height Center panel
900/1000 mm
In-line panel,
right-hand
Panel width
800 1200
600/800
AGS002598-01
600/800
AGS002598-02
AGS002599-01
900/1000
AGS002599-02
900/1000
AGS002596-01
600/800
AGS002596-02
AGS002597-01
900/1000
AGS002597-02
In-line panel, left-
hand
Panel width
LV cabinet height End panel, right-
hand 900 mm
In-line panel,
right-hand
Panel width
800 1200
600/800
AGS002600-01
AGS002600-02
900/1000 not required
4.9 Busbar link: B link
L1
L2
L3
L1
L2
L3
SS1
SS2
Fig. 45
Overview of designations for busbars and phase angle
Upper busbar = SS2 Rear busbar = SS1
Front compensating shutter,
attachment to panel
GHA
39 AGS 531 446-01 | Edition 12/2011 39
4 Assembly
1 2 3 4 5 6
7
Fig. 46
Overview of busbar link
1 Busbar support with high-quality
electrical joint
2 Busbar
3 Spacer pin
4 Retaining clip
5 Busbar clamping contacts
6 Silicone sleeve with securing
half-shells
Fig. 47
Tool for compressing
the silicone sleeve - fork

Fig. 48
Tool for compressing the silicone
sleeve (alternative) - claw fastener
To get access to the pre-assembled clamping contacts and to complete the busbar
link, it is necessary to press the silicone sleeve back.
To this effect, only the auxiliary equipment approved by the manufacturer may be
used, e.g. the fork Fig. 47 and the claw fastener Fig. 48.
Position the tool according to the illustration and press the silicone sleeve back.
Relieve the silicone sleeve. To do so, slowly release the silicone sleeve using the
tool being used, and remove the tool.
Detail drawing of a
B-link
Tool for pressing the silicone
sleeve back (see also Annex,
Chapter 13.2, page 85)
GHA
40 AGS 531 446-01 | Edition 12/2011 40
4 Assembly
4.9.1 Connecting the busbar (fasten preassembled clamping
contacts)
Important:
The two lugs of the upper clamping contact must be located between
the busbar tubes.
Assembly drawing for single and double busbar: AGS 002 268-01
1. Position the preassembled clamping contacts (see Chapter 4.7.4, page 34) acc.
to Fig. 49, item 2. The two lugs of the upper clamping contact must be located
between the busbar tubes (see Fig. 49, item 4).
2. Tighten the clamped connection with a torque of 8 1 Nm.
3. After tightening the clamped connection applying the specifed torque, remove
the red flm from the sandwich label (5). A green stripe appears which indicates
that the busbar link has been established correctly.
1
8 1 Nm
0-3 mm
2
3
4
5
4
Fig. 49
Busbar link
1 Tool
2 Clamping contacts
3 Busbar
4 Locating lugs
5 Sandwich label
GHA
41 AGS 531 446-01 | Edition 12/2011 41
4 Assembly
4.9.2 Contact resistance measurement of busbar screw fastening
Important:
Comply with the manufacturers specifcations regarding the contact
resistance measuring unit.
1. Set the feeder panel for resistance measurement in testing position (A)
(Fig. 50): Switch disconnector and circuit-breaker ON, refer also to operating
manual.
2. Connect the clip-on ammeter probes of the contact resistance measuring unit to
the high-voltage cable connection in the right-hand panel (B).
Illustrated: Outer cone-type bushing. Use suitable current probes for the inner
cone-type bushing.
3. On the lined-up panel, connect clip-on ammeter probes of the contact resis-
tance measuring unit to the busbar tube by means of inner cone-type current
probes (C).
4. Apply test current 100 A DC (D).
5. Measure contact resistance R between the busbar tube and the lug of the
clamping contact (E). Set value R: 5 .
If the measured value exceeds the specifed value:
Undo busbar screw fastening.
Clean contact surfaces carefully and repeat the mounting and measuring
procedure.
In this way, check the contact resistance of all phases between all panels.
100 A DC
00243
C
D
E
A
B
R 5
Fig. 50
Contact resistance measurement
GHA
42 AGS 531 446-01 | Edition 12/2011 42
4 Assembly
4.9.3 Fasten silicone sleeve to adjacent panel
Important:
Check pre-coated high-quality electrical joints again for absolute clean-
ness.
The surfaces of the high-quality electrical joint must be coated com-
pletely and uniformly with a thin layer of special grease.
Check high-quality electrical joints for non-greased areas and, if neces-
sary, coat again, see Chapter 4.7.3, page 33.
6. Relieve the silicone sleeve. To do so, slowly release the silicone sleeve using
the tool being used, and remove the tool.
7. Clean spacer pins (accessories, Fig. 46, item 3) and welding studs and coat
them with a screw locking compound (see Chapter 13.3, page 87). Screw-
fasten spacer pin onto the welding studs.
8. Slip retaining clip onto the two pins. The sides of the retaining clip must butt
against the retaining lugs of the securing half-shells.
Subsequently, position the cage with the cup springs and fasten retaining clip
by means of a M8 self-locking nut. The surfaces of the high-quality electrical
joint must be compressed by the retaining clip.
1
(121,5 Nm)
2
3
4
(121,5 Nm)
Fig. 51
Fastening the silicone sleeve to the adjacent panel
1 Spacer pin
2 Retaining clip
3 Cup spring package
4 Nut
Checking high-quality electrical
joints
Mounting the retaining clips
GHA
43 AGS 531 446-01 | Edition 12/2011 43
4 Assembly
4.9.4 Cover of busbar link in case of panels without pressure relief
duct
Panel width, adja-
cent panel, left-hand
[mm]
Panel width
[mm]
Assembly drawing
Single busbar Double busbar
600/800 600 AGS003202-01 AGS003202-02
600/800 800 AGS003202-01 AGS003203-02
900/1000 600/800 AGS003204-01 AGS003204-02
600/800 900 AGS003205-01 AGS003205-02
900/1000 900 AGS003206-01 AGS003206-02
600/800 1000 AGS002609-02 AGS003205-02
900/1000 1000 AGS002610-02 AGS003206-02
SS-StW 600/800 AGS003215-03 AGS003215-07
SS-StW 900 AGS003215-04 AGS003215-08
600/800 SS-StW AGS003215-01 AGS003215-05
900 SS-StW AGS003215-02 AGS003215-06
1
2
Fig. 52
Cover of busbar link
1 Cover of upper busbar link
2 Cover of rear busbar link
GHA
44 AGS 531 446-01 | Edition 12/2011 44
4 Assembly
Cover of busbar link in case of panels with pressure relief duct
Fig. 53
Cover of busbar link in case of panels with pressure relief duct
Panel width
[mm]
adjacent panel, right-hand
Panel width
[mm]
Busbar sys-
tem
Mat. no.
SS-Stw 600 800 900 1000 SS-Stw 600 800 900 1000
Single
bus-
bar
Dou-
ble
bus-
bar
AGS002115-05
AGS002115-03
AGS003217-01
AGS002115-04
AGS002115-06
AGS003217-02
AGS002115-06
AGS002115-02
AGS002115-07
AGS003217-05
AGS002115-08
AGS002115-09
AGS003217-06
AGS003217-03
AGS003217-04
AGS003217-07
AGS003217-08
AGS003217-09
AGS003217-10
AGS002115-10
AGS002115-11
H O AGS002115-14
O = Bus section coupler with upper busbar separation (SS2)
H = Bus section coupler with rear busbar separation (SS1)
GHA
45 AGS 531 446-01 | Edition 12/2011 45
4 Assembly
Panel width
[mm]
adjacent panel, right-
hand
Panel width
[mm]
Busbar
system
LV
cabinet
Height
[mm]
Cover
Pressure
relief device
Cover SS (to
the right-hand
adjacent
panel)
Cover
LV cabinet
S
S
-
S
t
w
6
0
0
8
0
0
9
0
0
1
0
0
0
S
S
-
S
t
w
6
0
0
8
0
0
9
0
0
1
0
0
0
S
i
n
g
l
e

b
u
s
b
a
r
D
o
u
b
l
e

b
u
s
b
a
r
8
0
0
1
2
0
0
AGS002113-01 AGS003386-03 -
AGS002113-03 AGS003386-01 AGS003416-02
AGS002113-03 AGS003386-01 AGS003416-04
- - -
AGS002113-03 AGS003386-02 AGS003416-02
AGS002113-03 AGS003386-02 AGS003416-04
AGS002113-04 AGS003386-05 AGS003416-03
AGS002113-04 AGS003386-05 AGS003416-05
- - AGS003416-02
- - AGS003416-04
AGS002113-04 AGS003386-05 AGS003416-03
AGS002113-04 AGS003386-05 AGS003416-05
AGS002113-02 AGS003386-03 -
AGS002113-05 AGS003386-01 AGS003416-02
AGS002113-05 AGS003386-01 AGS003416-04
AGS002113-05 AGS003386-02 AGS003416-02
AGS002113-05 AGS003386-02 AGS003416-04
AGS002113-06 AGS003386-05 AGS003416-03
AGS002113-06 AGS003386-05 AGS003416-05


- - -
- - AGS003416-02
- - AGS003416-04
- - AGS003416-02
- - AGS003416-04
- - AGS003416-02
- - AGS003416-04
- - AGS003416-03
- - AGS003416-05
GHA
46 AGS 531 446-01 | Edition 12/2011 46
4 Assembly
4.10 Reinforcement
Required in case of

internal arc strength acc. to IEC 62271-200, qualifcation IAC AFL(R), internal
arc 40 kA/1 s

Seismic design / vibration-resistance
Fan
attachment
Panel width
adjacent panel,
left-hand
Panel
width
Assembly drawing
with-
out
with Single busbar Double busbar
600/800 600 AGS003389-01 AGS003389-02
600/800 800 AGS003389-01 AGS003389-02
900/1000 600/800 AGS003389-03 AGS003389-04
600/800 900/1000 AGS003389-05 AGS003389-06
900 900 AGS003389-07 AGS003389-08
900 1000 AGS003389-09 AGS003389-10
1000 900 AGS003389-09 AGS003389-10
SS-StW 600/800 AGS003389-11 AGS003389-12
SS-StW 900 AGS003389-13 AGS003389-14
600/800 SS-StW AGS003389-15 AGS003389-16
900 SS-StW AGS003389-17 AGS003389-18
Fig. 54
Reinforcements
GHA
47 AGS 531 446-01 | Edition 12/2011 47
4 Assembly
4.11 Screw-fastening the panel to the base frame
Important:
The switchgear panels may not be screw-fastened to the base frame
before they have all been installed and adjusted.
Cut thread M8 in the base frame at the securing points provided to this effect
(Fig. 55). To this effect, drill initial holes of 6.8. Screw-fasten the panels 2 x each
on the front and rear.
1
1
4
2 3
Fig. 55
Fastening points in the base frame
If the rear fastening points are not
accessible, e. g. due to voltage trans-
formers, fastening links (Fig. 56) can be
mounted.
Screw-fasten both fastening links to the
panel's supporting structure.
Cut a thread M8 in the base frame on
the specifed fastening points. To this
effect, drill initial holes of 6.8.


Panel width
[mm]
Seismic design /
vibration-resistance
Mat. no.
600 800 900 1000 without with
AGS002206-01
AGS002206-02
AGS002206-03
AGS002206-04
The base frame must be designed in view of the seismic design. The panels are
fastened to the base frame by means of screws M12.
Additional securing points
(optional)
1
2
3
Fig. 56
Rear fastening links
1 Rear base frame
2 Fastening link
3 Screw connection
GHA
48 AGS 531 446-01 | Edition 12/2011 48
4 Assembly
4.12 Mounting the earth bus
Important:
Observe the specifc standards referring to earthing systems which ap-
ply in the country in question.
1. Clean all contact areas of the connecting bar and the appropriate earth bar in
the switchgear panels and coat them with lubricant (KL) (see Chapter 13.3,
page 88).
2. Slip the connecting bar into the adjacent panel's supporting structure through
the cutout in the panel.
3. Screw-fasten the connecting bar with the support brackets on both sides, to the
earth bar in question and screw-fasten the support brackets to the panel.
4. Mount the connecting piece for switchgear earthing (Fig. 57, item 6). Connect
the earth bus to the earthing system of the switchgear building. Connecting
lines and screw accessories are not included in the scope of supplies.
Connecting piece for switchgear earthing: AGS 000294-03
Panels with base plates: Observe Chapter 9.1, page 69.
The earth bus should be connected to the earth conductor of the building's earth
connection at least at the frst and at each tenth panel of the switchgear.
Panel width
[mm]
Panel width
Adjacent panel
[mm]
Assembly drawing
600 (also for end panel right-hand)
600/800
AGS 000294-01
800 (also for end panel right-hand) AGS 000294-02
600 900 AGS 000294-04
900 (also for end panel right-hand) 600/800 AGS 002510-01
900 900 AGS 002510-02
1000
600/800 AGS 002510-03
900 AGS 002510-04
1
2
3
4
5
6 ( 13 mm)
Fig. 57
Mounting the earth bar and connecting bar
1 Earth bar
2 Support brackets
3 Connecting bar
4 Screw-fastening the support brackets to the earth bar and the connecting bar
5 Screw-fastening the support brackets to the panel
6 External point of connection for the earth bus of the panel
The earth bars are screw-
fastened from panel to panel by
means of connecting bars (Fig.
57, item 3).
GHA
49 AGS 531 446-01 | Edition 12/2011
5 Busbar attachments
5.1 Safety provisions
Warning!
When performing assembly work on busbar attachments, the ap-
propriate disconnecting device must be in earthed position (see
Operating Manual).
Warning!
Please comply with the safety provisions in Chapter 1, page 7.
5.2 Assembly of surge arresters
Important:

Remove grease and silicone from the contact surfaces and insu-
lating areas on the inner cone-type sockets in the tank and on the
surge arresters before assembly.

Comply with the assembly instructions of the surge arrester.
1. Clean and grease contact surfaces on the surge arrester and inside the inner
cone-type socket (see Chapter 13.3, page 88).
2. Clean the insulating areas of the surge arrester and in the inner cone-type
socket carefully and apply a uniform flm of special paste (see instructions for
assembly of the surge arrester).
3. Slip surge arrester in correct axial position into the inner cone-type socket and
screw-fasten it.
4. Screw-fasten the earthing cable of the surge arrester on the busbar tank.
Fig. 58
Surge arrester
GHA
50 AGS 531 446-01 | Edition 12/2011 50
5 Busbar attachments
5.3 Assembly of voltage transformers
Rated voltage U
r
[kV] Assembly drawing
24 AGS 001861-02
> 24 AGS 001861-01
Important:

Remove grease and silicone from the contact surfaces and insu-
lating areas on the inner cone-type sockets in the tank and on the
voltage transformers before assembly.

Observe the instructions for assembly of the voltage transformers.

The weight of the transformers must be taken into consideration!
Support the transformer or secure it by attaching a crane hook to
the transformer jack rings.
1. Clean and grease contact surfaces on the transformer connector and inside the
inner cone-type socket (see Chapter 13.3, page 88).
2. Clean the insulating areas of the transformer connector and inside the inner
cone-type socket carefully and apply a uniform flm of special paste (see as-
sembly instructions for voltage transformer).
3. Push voltage transformer into inner cone-type socket in correct axial direction
and screw-fasten it (Fig. 59, item 2); 4 x M8 self-locking nut.
Fasten transformer additionally to angle bracket (4).
2 x M8 self-locking screw
4. Connect the transformer secondary lines (plug-in contacts) (6). Comply with
the marking! Fasten the protective hose (tighten nut by hand and fx cables by
means of cable clamps, 7 and 8).
5. Mount cover plate (5) above the transformer cables.
2 x M5 Torx screw
1 2 4
5
3
3
7
6
8
Fig. 59
Assembly / disassembly of busbar voltage transformer
1 Attachment with disconnecting device on busbar
2 Connecting socket and fange fastening
3 Voltage transformer
4 Angle bracket
5 Cover plate for transformer wiring
6 Terminal connection of transformer cables
7 Fastening by means of cable clamp
8 Fastening the protective hose
GHA
51 AGS 531 446-01 | Edition 12/2011 51
5 Busbar attachments
The voltage transformers are inserted from above into the inner cone-type socket in
the busbar tank (optional, Fig. 60).
Assembly is effected as described above.
Fig. 60
Voltage transformer attachment from above
Rated voltage U
r
[kV] Assembly drawing
24 AGS 002260-02
> 24 AGS 002260-01
GHA
52 AGS 531 446-01 | Edition 12/2011
6 Low-voltage cabinet
6.1 Assembly
The low-voltage cabinets are either supplied as accessories or already mounted to
the panel, depending on the transport requirements.
1. Remove transport protection covers from the interface between drive compart-
ment and low-voltage cabinet. All the wiring with terminals for the low-voltage
cabinet must be located in the drive area below the upper sheet metal edge.
2. Assign the low-voltage cabinet to the appropriate panel. Remove the packag-
ing of the low-voltage cabinet and place the cabinet on the lifting table (Fig. 61).
Raise lifting table until the low-voltage cabinet is above the drive area.
3. Carefully push the low-voltage cabinet onto the panel above the drive area,
align it and screw-fasten it to the panel. To this effect, open the switch cabinet
door using the double bit key.
Lower screw fastening (1): 4x M8 self-locking screw;
rear screw fastening (2): 4x M8 self-locking screw.
4. Screw-fasten the low-voltage cabinets laterally to one another (3).
Screw-fasten by means of a M8 self-locking screw connection, depending on
the height of the low-voltage cabinet 800/1200: 2x/3x.
Assembly drawing: AGS 003252-02
1
33
2
4
5
1
2
2x/3x
6
Top view
3
4x
4x
Fig. 61
Mounting the low-voltage cabinet
1 Lower screw fastening (4x)
2 Rear screw fastening (4x)
3 Lateral screw fastening (2x/3x)
4 Lifting table
5 Low-voltage cabinet
6 Spacer
GHA
53 AGS 531 446-01 | Edition 12/2011 53
6 Low-voltage cabinet
6.2 Connecting the control lines
1. Slip the terminals of the drive box wiring onto the terminal strips in the low-volt-
age cabinet according to the marking on the connector (Fig. 62).
2. Close opening in the base of the low-voltage cabinet to the drive area by means
of a cover plate (2).
5 x M6 self-locking screw connection.
1
2
3
Fig. 62
1 Drive wiring to terminal strip in low-voltage cabinet
2 Cover plate
3 Fastening the cover plate
1. Route the secondary lines for the intra-panel wiring through the lateral rubber
sleeves of the low-voltage cabinet (Fig. 63).
2. The ring circuits are designed with connectors and are connected to the ap-
propriate terminal strips in the low-voltage cabinet according to the connector
designations (or the circuit diagram) (2).
1
2
Fig. 63
Ring circuits between panels
1 Bushing in the wall of the low-voltage cabinet
2 Connection of the ring circuits to terminal strips
Connecting internal control lines
of panel:
Connecting the ring circuits:
GHA
54 AGS 531 446-01 | Edition 12/2011 54
6 Low-voltage cabinet
Customized low-voltage lines for control and measuring purposes can be routed on
the right-hand inside of each panel (Fig. 64).
3. Route external cables from the cable basement into the cable compartment of
the panel (1) and place them in the right-hand cable tray of the panel to the low-
voltage cabinet (3).
Fasten cables to the panel by means of cable clamps (2).
4. Connect external cables to the terminal strip in the low-voltage cabinet ac-
cording to the circuit diagram. Additionally, ground shielded lines on the cable
supports.
5. Re-fasten metallic cable tray covers in the supporting structure (4).
4 x M8 self-locking screw
1
1
2
3
4
Fig. 64
Placing external control cables
1 External control lines
2 Cable clamp
3 Low-voltage cabinet
4 Metallic cable tray covers
Placing external control lines in
the switchgear panel:
GHA
55 AGS 531 446-01 | Edition 12/2011
7 Switchgear termination
7.1 Attachment of the protective tank to the left-hand /
right-hand end of the busbar
On the busbar end, a protective tank
must be mounted on the left and right
sides of the voltage-proof busbar caps.
Panel width [mm] End
panel
Single busbar Double busbar
600/800
left-hand
side
1 x AGS001760-01
AGS001760-05
+AGS001760-03
right-
hand
side
1 x AGS001760-02
AGS001760-02
+AGS001760-04
900/1000
left-hand
side
AGS002570-05
AGS002570-01
+AGS002570-03
right-
hand
side
AGS002570-02
AGS002570-02
+AGS002570-04
Panel width [mm] End
panel
Single busbar Double busbar
600/800
left-hand
side
AGS001760-30
AGS001760-35
+ AGS001760-20
right-
hand
side
AGS001760-31
AGS001760-31
+ AGS001760-21
900/1000
left-hand
side
AGS001760-32
AGS001760-32
+ AGS001760-22
right-
hand
side
AGS001760-33
AGS001760-33
+ AGS001760-23
1
2
Fig. 65
Protective tanks at the busbar end
(example) for
1 upper busbar
2 rear busbar (in case of
double busbar switchgear)
Models without pressure relief
duct
Models with pressure relief duct
GHA
56 AGS 531 446-01 | Edition 12/2011 56
7 Switchgear termination
7.2 Switchgear without pressure relief duct
(Accessibility in acc. with IEC 62271-200: IAC AFL)
7.2.1 Overview
Shown (Fig. 66): The switchgear is accessible from the front and on the right-hand
side (the switchgear is located in the left-hand corner of the room).
Additional variants (not shown):
The switchgear is accessible from the front and from the left-hand side (the
switchgear is located in the right-hand corner of the room).
The switchgear is accessible from the front and from both sides (the switchgear
is located against the wall of the building, but not in a corner of the room).
Important:
Comply with the appropriate documentation for the switchgear. It de-
fnes the applicable variant in accordance with the customer's require-
ments.
All individual parts are included in the accessories. Design is identical for the right-
hand and left-hand sides.
1
2
3
4
5
100
180
1
7
0
0
5
0
0
6
Fig. 66
Design example: Switchgear located in the left-hand corner of the room
1 Switchgear
2 Lateral gap cover (see Chapter 7.2.4, page 59)
3 Side wall (see Chapter 7.2.2, page 56)
4 Side wall extension for double busbar switchgear units (see Chapter 7.2.3,
page 58)
5 Rear gap cover (see Chapter 7.2.4, page 59)
6 Wall of building
7.2.2 Attachment of the right-hand or left-hand side wall
Height of low-voltage
cabinet [mm]
Assembly drawing of side wall
left-hand side right-hand side
800 AGS 000630-01 AGS 000630-03
1200 AGS 000630-02 AGS 000630-04
GHA
57 AGS 531 446-01 | Edition 12/2011 57
7 Switchgear termination
If applicable, remove the covers of the lateral cable ducts in the cable compartment
(Fig. 67, item 3).
1. Screw-fasten fre-protection board (2) and base plate (1) to one another (11);
2 x M8 self-locking screws.
2. Screw-fasten (10) base plate (1) to the last panel (8);
2 x M8 self-locking screws.
3. Fasten base plate to the spacer bar (9). 2 x M8 self-locking screws. Cut thread
M8 in the base frame.
4. Screw-fasten top and bottom side wall sections (4) to one another (6);
6 x M8 self-locking screw connections.
5. Mount complete side wall. To this effect, screw-fasten:
side wall to base plate (1); 5 x M8 self-locking screw.
side wall to panel (8); 9 x M8 self-locking screws.
side wall to low-voltage cabinet (7) (see also Chapter 6.1); 3 x M8 self-
locking screws.
rear side wall fastening (5) with the retaining plate on the panel;
3 x M8 screw fastening (only required for ESS, not for DSS).
9
2
5
6
8
7
3
5
4
2
11
1
11
1
10
6
Fig. 67
Attaching the right-hand side wall
1 Base plates
2 Fire-protection plates
3 Cable tray cover
4 Top and bottom side wall sections
5 Rear screw fastening of the side wall to the panel
6 Screw fastening of the two side wall sections
7 Screw fastening the side wall to the low-voltage cabinet
8 Screw fastening the side wall to the panel supporting
structure
9 Screw fastening the base plate to the base frame
10 Screw fastening the base plate to the panel
11 Screw fastening the fre-protection board to the base plate
GHA
58 AGS 531 446-01 | Edition 12/2011 58
7 Switchgear termination
7.2.3 Extension of side wall in double busbar switchgear
Height of low-voltage
cabinet [mm]
Assembly drawing of side wall
left-hand side right-hand side
800 AGS 000633-01 AGS 000633-03
1200 AGS 000633-02 AGS 000633-04
In double busbar switchgear, the side wall (Chapter 7.2.2, page 56) is extended to
the rear (Fig. 68).
1. Mount side wall acc. to Chapter 7.2.2, page 56.
2. Screw-fasten upper and lower cover bracket (Fig. 68, item 5) and upper and
lower termination plates (1 and 2) to the side wall (4).
3. Mount the rear fastening link (3).
1
2
3
5
4
Fig. 68
Side wall extension for double busbar switchgear
1 Upper termination plate
2 Lower termination plate
3 Fastening link with screw fastening
4 Screw-fasten the termination plates and cover bracket to the side wall
5 Upper and lower cover bracket
GHA
59 AGS 531 446-01 | Edition 12/2011 59
7 Switchgear termination
7.2.4 Gap covers
Height of low-
voltage cabinet
[mm]
Wall clear-
ance [mm]
Assembly drawing for gap cover
left-hand side right-hand side
800
100
+30
/130
+30
AGS 002341-01 AGS 002341-02
1200 AGS 002341-03 AGS 002341-04
The lateral gap cover is installed
between the end panel and the side wall
of the building (Fig. 69).
The nominal width of the gap cover
is always 100 mm.
1. Insert base plate (6) and screw-
fasten it to panel.
1 x M8 self-locking screw
2. Fasten base plate to the front and
rear parts of the base frame (8).
2 x M8 self-locking screws;
drill thread M8 into the base frame.
3. Screw-fasten upper and lower gap
covers (1) to the panel.
11 x M8 hex. bolt
4. Apply gap cover (2) on wall side
as shown in the drawing and mark
securing bore-holes on the wall of
the building and on the mounted
gap cover.
5. Remove gap cover on wall side.
Provide securing bore-holes for the
mounted gap cover ( 4.5) and for
the building wall ( 10).
Subsequently, insert dowel pins
into the building wall.
6. Screw-fasten gap cover on building
wall.
11 x M8 hex. bolt
7. Screw-fasten both gap covers to
one another.
11 x M5 hex. bolt.
Variants with wall clearance 130
+30
are
possible depending on the swtchgear
confguration (see switchgear documen-
tation).
In this case, the securing bore-holes
between the two gap covers must be
marked and drilled anew.
Front lateral gap cover
8
1
2
4
1
2
3
5
8
7
6
1
0
0
Fig. 69
Lateral gap cover (shown on the left-
hand switchgear termination)
1 Gap cover on panel side
2 Gap cover on the wall side
3 Screw fastening of gap covers: M5
hex. bolt
4 Screw fastening to the panel: M8
hex. bolt
5 Wall fastening: dowel pin and M8
hex. bolt
6 Base plate
7 Screw fastening to the panel
8 Screw fastening to the base frame
GHA
60 AGS 531 446-01 | Edition 12/2011 60
7 Switchgear termination
Rear gap cover
Wall
clear-
ance
[mm]
Height of
LV cabinet
[mm]
Busbar system Mat. no. in case of side wall
side
800 1200 ESS
Attachment on the front to
end wall or at the ear to end
wall
DSS
Attachment only at the rear
to end wall
left-hand side right-hand side
100 AGS001967-01 AGS001967-02
100 AGS001967-03 AGS001967-04
300 AGS001967-05 AGS001967-06
500 AGS001967-07 AGS001967-08
100 AGS001963-01 AGS001963-02
100 AGS001963-03 AGS001963-04
300 AGS001963-05 AGS001963-06
500 AGS001963-07 AGS001963-08
The rear gap cover is installed between the mounted side wall and the rear wall of
the building (Fig. 70).
The nominal width of the gap cover is 100 mm for single busbar and 500 ( 300) mm
for double busbar. Assembly is performed identically.
1. Screw-fasten upper and lower gap covers (1) to the side wall.
11 x M8 hex. bolt
2. Apply gap cover (2) on wall side as shown in the drawing and mark securing
bore-holes on the wall of the building and on the mounted gap cover.
3. Remove gap cover on wall side. Provide securing bore-holes for the mounted
gap cover ( 4.5) and for the building wall ( 10). Subsequently, ft dowel pins
in the wall of the building.
4. Screw-fasten gap cover on building wall.
9 x M8 hex. bolt
5. Screw-fasten both gap covers to one another.
9 x M5 hex. bolt.
Fig. 70
Rear gap cover (shown for left-hand switchgear end, 100 mm wall clearance)
1 Front gap cover
2 Gap cover on the wall side
3 M5 hex. bolt
4 M8 hex. bolt
5 Fastening to building wall: Dowel and M8 hex. bolt
3
5
2
1
4
100
+30
50
1
0
5
1
2
3
4
5
A
GHA
61 AGS 531 446-01 | Edition 12/2011 61
7 Switchgear termination
7.3 Attachment of fan
1
2
3
4
Fig. 71
Fan attachment
1 Cover plate
2 Fan
3 Angular bracket on the low-voltage
cabinet
4 Low-voltage cabinet
Panel width [mm] Height, low-voltage cabinet
[ mm ]
Mat. no.
800/900 1000 800 1200
AGS003149-02
AGS003154-02
AGS003149-03
AGS003154-03
Height, low-voltage cabinet [ mm ] Mat. no.
800 1200
AGS003181-01
AGS003181-02
Panel width [mm] Panel width, adjacent panel,
right-hand [mm]
Mat. no.
900 1000
600 / 800 / 900 / 1000 AGS003183-13
600 / 800 / 900 / 1000 AGS003183-12
Angular bracket (Fig. 71, item 3)
Attachment of angular bracket
on the low-voltage cabinet
(Fig. 71, item 3)
Cover plate (Fig. 71, item 1)
GHA
62 AGS 531 446-01 | Edition 12/2011 62
7 Switchgear termination
Panel variant 50 Hz 60Hz Busbar
system
Mat. no.
Sin-
gle
bus-
bar
Dou-
ble
bus-
bar
Bus section coupler 2500A AGS002723-04
Feeder panel 2500A AGS002723-03
Bus section coupler 2500A AGS002723-02
Feeder panel 2500A AGS002723-05
Current transformer in the
busbar run 2500A
AGS003216-04
Disconnector in the busbar
run 2500A
AGS003515-01
Disconnector in the busbar
run 2500 A

AGS003515-01
+AGS003532-01
Disconnector in the busbar
run 2500A
1

AGS003515-01
+AGS003532-02
Fan (Fig. 71, page 61, item 2)
GHA
63 AGS 531 446-01 | Edition 12/2011
8 Switchgear with pressure relief
device
8.1 Overview
Switchgear units with pressure relief duct are accessible on all sides and can thus
be located centrally in the room.
Important:

The pressure relief duct must be mounted before the panel is
positioned on the base frame (see Chapter 4.5, page 28). After
installation of the panels, mounting is no longer possible.

The customized pressure relief duct and the pressure relief fap
are included in the scope of supplies.
The attachments for the pressure relief duct are included in the accessories.
The pressure relief ducts and the side walls are attached on the construction site.
L 2 L 3
Fig. 72
Switchgear panel with single busbar
and pressure relief duct

Fig. 73
Switchgear panel with double busbar
and pressure relief duct
Available for:

Accessibility in acc. with IEC 62271-200: Qualifcation IAC AFLR (accessibility
from all sides) and/or

Qualifcation IAC AFL(R) internal arc 40 kA/1 s
The connection for a customized pressure relief duct is integrated on the left and/or
right in the side wall (see switchgear-specifc documentation).
Available for:

Switchgear with pressure relief duct and opening into the switchgear room

Internal arc strength acc. to IEC 62271-200, qualifcation IAC AFL(R), internal
arc 25 kA/1 s (40 kA/1 s)
Switchgear with pressure relief
duct: Model with pressure relief
from the switchgear room
Model with pressure relief into
the switchgear room
GHA
64 AGS 531 446-01 | Edition 12/2011 64
8 Switchgear with pressure relief
device
1
2
3
4
2


5
0
0
520
1
5
9
5
180
180
5
6 7
2
0
0
9
520 180
1
180
4
7
2 2
8
6
Fig. 74
Illustrated: Switchgear with single busbar, accessible on all sides
1 Switchgear
2 Side walls (see Chapter 8.4, page 66)
3 Integrated pressure relief duct of the switchgear (see Chapter 4.5, page 28)
4 Connection for switchgear pressure duct with connecting fange
5 Wall of building
6 Customized pressure relief duct
7 Pressure relief fap in the wall of the building
8 Assembly aisle for switchgear not accessible from the rear
switchgear accessible from the rear: 800
GHA
65 AGS 531 446-01 | Edition 12/2011 65
8 Switchgear with pressure relief
device
8.2 Cover plate
Required in case attached pressure relief duct
Panel width [mm] Panel width, adja-
cent panel, right-
hand [mm]
Pressure relief from the
switchgear room 40kA
800/1200 LV cabinet
Pressure relief into the switch-
gear room 40kA 1200 mm LV
cabinet
SS-
StW
600 800 900 1000
600 / 800 AGS002115-16
900 / 1000 AGS002115-15
600 / 800 AGS002115-17
900 / 1000 AGS002115-16
600 / 800 / 900 / 1000 AGS003216-03 AGS003216-03
Fig. 75
Cover plate
GHA
66 AGS 531 446-01 | Edition 12/2011 66
8 Switchgear with pressure relief
device
8.3 Attachment of pressure relief duct
1
2
Fig. 76
1 Reinforcement 2 Pressure relief duct
Panel width [mm] Busbar
system
Assembly drawing
600 800 900 1000 ESS DSS
AGS002110-05
AGS002110-06
AGS002110-05
Single parts for pressure relief duct
Panel width
[mm]
adjacent panel, right-
hand
Panel width [mm]
Busbar
system
Pressure relief Reinforcement Special attach-
ments
600 800 900 1000 600 800 900 1000 ESS DSS
AGS002103-04 AGS002104-01 AGS002103-03
1
AGS002103-04 AGS002104-02 AGS002103-03
1
AGS002103-05 AGS002104-01 -
AGS002103-05 AGS002104-02 -
AGS002103-05 AGS002104-02 AGS002103-12
2
AGS002103-05 AGS002104-03 AGS002103-12
2
AGS002103-06 AGS002104-02 AGS002103-08
3
AGS002103-06 AGS002104-03 AGS002103-08
3
without AGS002103-04 - AGS002103-03
1
without AGS002103-05 - -
without AGS002103-05 - AGS002103-12
2
without AGS002103-06 - AGS002103-08
3
AGS002103-04 AGS002104-02 -
AGS002103-04 AGS003481-02 -
AGS002103-05 AGS002104-02 -
AGS002103-05 AGS003481-02 -
AGS002103-05 AGS002104-03 AGS002103-12
2
AGS002103-05 AGS003481-04 AGS002103-12
2
AGS002103-06 AGS003481-01 AGS002103-08
3
AGS002103-06 AGS003481-03 AGS002103-08
3
AGS002103-06 AGS002104-03 AGS002103-08
3
1
Item number required in case of pressure discharge 40 kA into the room, item number AGS002103-04 deleted
2
Item number required in case of fan attachment 2500 A FB900 and pressure relief duct; item number AGS002103-05 deleted
3
Item number required in case of fan attachment 2500 A FB1000 and pressure relief duct; item number AGS002103-06 deleted
GHA
67 AGS 531 446-01 | Edition 12/2011 67
8 Switchgear with pressure relief
device
8.4 Attachment of side walls for pressure relief from the switchgear room
1
5
2
0
Fig. 77
Side wall with connection fange for customized pressure relief duct (item 1)
Height LV cabinet
[mm]
Busbar system Connection fange for
customized pressure
relief duct*
Mat. no. in case of side wall on the
Panel width (600, 800, 900)
800 1200 ESS DSS
left-hand
side
right-hand
side
left-hand side right-hand side

AGS002130-01
AGS002175-01
AGS002123-01
AGS002124-01

AGS002123-02
AGS002124-02
AGS002130-02
AGS002175-09

AGS002130-05
AGS002175-05
AGS002130-06
AGS002124-05

AGS002130-05
AGS002124-06
AGS002130-06
AGS002175-06

AGS002130-03
AGS002175-01
AGS002123-03
AGS002124-01

AGS002123-04
AGS002124-02
AGS002130-04
AGS002175-09

AGS002130-07
AGS002175-05
AGS002130-08
AGS002124-05

AGS002130-07
AGS002124-06
AGS002130-08
AGS002175-06
* required for routing the pressure relief duct outwards at the side of the end panel to the left or right
GHA
68 AGS 531 446-01 | Edition 12/2011 68
8 Switchgear with pressure relief
device
8.5 Attachment of side walls for pressure relief into the
switchgear room
Fig. 78
Side wall without connection fange and model with pressure relief into the switch-
gear room
Height LV
cabinet
[mm]
Busbar
system
Internal arc strength, qualifcation IAC
AFLR, internal arc (1s)
Mat. no. in case of side wall on
the
Panel width (600, 800, 900)
800 1200 ESS DSS 25 kA 40 kA left-hand side right-hand side

AGS002123-02
AGS002124-02
AGS002123-01
AGS002124-01

AGS002130-05
AGS002124-06
AGS002130-06
AGS002124-05

AGS002123-04
AGS002124-02
AGS002123-03
AGS002124-01

AGS002130-07
AGS002124-06
AGS002130-08
AGS002124-05
GHA
69 AGS 531 446-01 | Edition 12/2011
9 High-voltage connection
Depending on customer requirements, the panels can be equipped at choice with
outer cone-type bushings or inner cone-type sockets.
Optionally, the panels can also be supplied with high-voltage terminals for conductor
bars (see switchgear-specifc documentation).
9.1 Cable compartment with base plates (optional)
The cable compartment of a panel can be designed optionally with mounted base
plates. Thus, the cable compartment and the cable basement are separated from
each other.
1. For assembly of the high-voltage cables, remove the front base plates and the
plastic sleeves (Fig. 79).
2. Cut the plastic sleeves to ft the cable diameter and slip them over the cable
before mounting the cable connectors.
3. After mounting the cables, position plastic sleeves, then reinsert and screw-
fasten the removed base plate.
1
2
3
4
Fig. 79
Panel with base plates
1 Base plate
2 Plastic sleeves
3 High-voltage cable (cable support not shown)
4 Perforated sheet metal cutout for connection of a connecting cable to the
switchgear earth bus (see also Chapter 48, page 4.12). Break sheet-metal
cutouts out as required.
Preassemble base plate in
the panel
GHA
70 AGS 531 446-01 | Edition 12/2011 70
9 High-voltage connection
9.2 Outer cone-type bushing
Standard design of the outer cone-type bushings:

in acc. with EN 50181, terminal type C (screw-type contact with internal thread
M16 and reinforced conductor pin for 1250 A rated current)

for cable Tee screw-type plugs
L1
L2
L3
L1
L2
Fig. 80
1 x outer cone-type bushing per phase with one double cable connection each
L1
L2
L3
L2
L1
L1
L1
L1
Fig. 81
2 x outer cone-type bushing per phase with one triple cable connection each
GHA
71 AGS 531 446-01 | Edition 12/2011 71
9 High-voltage connection
635,5
7
4
6
,
4
600
191 191
96
800
229 229
564
5
9
0
7
4
0
L1 L2 L3
L1 L2 L3
Fig. 82
Dimension drawings for outer cone-type bushing with one terminal per phase (top)
and with two terminals per phase (bottom)
Warning!
The cable support must be adjusted and the cable/cable connec-
tor must be fastened so that no additional forces act on the outer
cone-type bushing! The bushings may be damaged due to inad-
missible stress, so that insulating gas can escape.
Practically all the commercially available cable connection systems (fully insulated,
metal-enclosed or partially insulated) can be mounted to the switchgear.
Tools and accessories (cable clips, screws, spring washers etc.) for the assembly
of the cable connection systems (cable connectors) are not included in the scope of
supplies.
The switchgear is accessible from the front to enable assembly of the cable connec-
tion systems. To this effect, remove front cable compartment covers (see Chapter
4.6.2, page 30).
Dimension drawings
GHA
72 AGS 531 446-01 | Edition 12/2011 72
9 High-voltage connection
Danger!
Close vacant outer cone-type bushings with surge-proof caps (not
included in the scope of supplies).
1. Put the adjustable cable supports (Fig. 83, item 4) in the required position and
fasten them (horizontally and vertically adjustable).
2. Mount cable connectors according to the manufacturer's Assembly Instructions.
3. Remove the protective transport caps from the appliance couplers. Use a
cleaning agent to remove grease and silicone from the appliance couplers (see
Chapter 13.1, page 86).
4. Coat contact areas of Cu insert on the appliance coupler and screw-type con-
tact with a thin grease flm (see Chapter 13.3, page 88).
5. Treat insulating surfaces as specifed by the manufacturer of the cable connec-
tor. Slip cable connector on the appliance coupler.
The cable connection to the outer cone-type bushing (thread M16) must be
tightened with a max. torque of 405 Nm. Observe the manufacturer's specif-
cations.
6. If necessary, re-adjust cable support, align cables and fasten them to the cable
support using cable clips.
7. Connect earthing cables (2) of cable and cable connector to the cable support
(3). Coat contact surfaces (see Chapter 13.3, page 88).
If surge arresters are provided, the switchgear can be equipped additionally with
retaining plates to which the fasteners for surge arresters can be mounted.

The contact areas of the earth connections must be coated as described in the
Annex.

For assembly, refer to the instructions of the manufacturer of the surge arrest-
ers.
1
4
5
2
3
Fig. 83
High-voltage cable connector, outer cone-type, screw-type contact
1 Screw-type contact
2 Cable connector
3 Earth conductors
4 Cable supports, adjustable
5 Cable clip
Cable assembly
GHA
73 AGS 531 446-01 | Edition 12/2011 73
9 High-voltage connection
9.3 Inner cone-type socket
Inner cone-type sockets acc. to EN 50181 can be standard equipment of the panels.
Cable connectors, tools, accessories (cable clips, screws, spring washers etc.) are
not included in the scope of supplies.
Important:

When shrink-ftting cable end boxes, make sure that the cable
connection area of the panel is not heated beyond the admissible
service temperature.
We cannot accept any liability for consequential damage (e.g.
damaged cables of the capacitive indicator) which might result
from shrink-ftting components in the cable compartment using an
open fame.

An accessible cable tray must be provided below the panel for as-
sembly of the cable supports and the high-voltage cables.
L1
L2
L3
L1
4
3
2
2
7
5
Fig. 84
Inner cone-type sockets with cable supports above spacer bar level
2
8
9
2
6
6
1
1
3
Fig. 85
Inner cone-type cable socket with cable supports below spacer bar level (attachment on site)
GHA
74 AGS 531 446-01 | Edition 12/2011 74
9 High-voltage connection
(only required for models acc. to Fig. 87)
Assembly drawing AGS 003010-04
The individual parts are included in the accessories.
1. Screw-fasten sides to the supporting structure of the panel.
2. Mount the cable support.
Fig. 86
Attachment of cable support in case of inner cone-type socket design acc. to Fig. 87
Installation of the base plates (optional and only for versions acc. to Fig. 87).
Assembly drawing AGS 003014-01.
The individual parts are included in the accessories.
1. Cut the plastic sleeves to ft the cable diameter and slip them over the cable
before mounting the cable connectors.
2. After mounting the cables, position plastic sleeves, then insert and screw-fasten
the base plate.
1
2 3 4 (2)
Fig. 87
Installation of the base plates
1 Floor pan
2 Cable support
3 Divided base plates
4 Plastic sleeves
Installation of the cable support
Base plates in the accessories
GHA
75 AGS 531 446-01 | Edition 12/2011 75
9 High-voltage connection
Warning!
The cable support must be adjusted and the cable/cable connec-
tor must be fastened so that no additional forces act on the inner
cone-type socket! The bushings may be damaged due to inadmis-
sible stress, so that insulating gas can escape.
1. Mount cable connector (Fig. 88,
item 2) according to the instruc-
tions of the cable connector
manufacturer.
2. Remove transport protective
caps from the appliance couplers
(socket-contacts). Remove grease
and silicone from appliance cou-
plers using a cleaning agent (see
Chapter 13.1, page Fig. 87).
3. Slightly grease contact surfaces on
the appliance coupler and on the
cable connector (see Chapter 13.3,
page 88).
4. Treat insulating surfaces as speci-
fed by the manufacturer of the
cable connector. Insert cable con-
nector in inner cone-type socket
(press down) and screw-fasten
safely. Tighten screw fastenings M8
with a torque of 15 3 Nm.
5. If necessary, re-adjust cable sup-
port (5), align cables and fasten
them to the cable support using
cable clips (4).
6. Connect earthing cables (3) of
cable and cable connector to the
cable support (5). Coat contact sur-
faces (see Chapter 13.3, page 88).
Danger!
Close unused inner cone-type sockets with surge-proof dummy
plugs
If the metallic connector housing features
a conductive contact surface touching
the metal enclosure of the switchgear
(applies to Pfsterer model, system
CONNEX): Do not connect the cable's
earth conductor to the connector
housing (contact-making). Make sure
that the earth conductor is connected
directly to the cable support.
Cable assembly
1
2
3
4 5
Fig. 88
1 Socket contacts
2 Cable connector
3 Earth conductors
4 Cable clip
5 Cable support
Fig. 89
Connection of cable earth conductor if
cable-type transformers are used
Connector shell with conductive
contact surface with reference to
switchgear's metal enclosure:
GHA
76 AGS 531 446-01 | Edition 12/2011
10 Replacement of transformer
Danger!
Risk of fatalities due to high voltage. The appropriate parts of the
switchgear must be isolated from the power supply and earthed.
Warning!
Refer to the safety provisions in Chapter 1, page 7.
10.1 Current transformer for outer cone-type connection
The current transformers for cable connections equipped with outer cone-type con-
nectors can be replaced easily as required.
1. Isolate the outgoing feeder cable concerned from the power supply and earth it
(see Operating Manual).
2. Remove cable compartment cover (see Chapter 4.6, page 29).
3. Remove cable connections (see Chapter 9, page 69).
4. Release transformer wiring in low-voltage cabinet and pull it back to the trans-
formers (Fig. 90, item 2). Mark connection points in low-voltage cabinet.
5. Remove front transformer retaining plates (4).
6. Pull transformer with retaining plate off the bushing. Cut through cable clamp
fastening (5) of the current transformers. Fasten new transformers to the retain-
ing plate using cable clamps.
7. For fastening and wiring, reverse above sequence of operations.
Observe specifed tightening torques (see Chapter 13.4, page 88).
Subsequently, connect cable connectors again and mount cable compartment cover.
1
2 3 4 5
4
Fig. 90
Replace current transformers in case of outer cone-type connection
1 Bushing with outer cone-type bushing
2 Current transformer
3 Retaining plate
4 Fastening of the transformer retaining plate
5 Cable clamp
GHA
77 AGS 531 446-01 | Edition 12/2011 77
10 Replacement of transformer
10.2 Voltage transformer
Danger!
When performing assembly work on voltage transformers, the ap-
propriate disconnecting device must be in earthed position (see
Operating Manual).
1. Isolate the outgoing feeder cable/busbar concerned from the power supply and
earth it (see Operating Manual).
2. Establish access to the voltage transformer:
Busbar: Access from above
Outgoing feeder cable: Remove cable compartment cover (see Chapter 4.6,
page 4.6).
3. Disconnect transformer cables from low-voltage cabinet and pull them back to
the transformer.
4. Disconnect screw fastening of transformers (4 nuts at each fange coupling and
- partially - 2 screws at the angle bracket).
Important:
The weight of the transformers must be taken into consideration!
Support the transformer or secure it by attaching a crane hook to the
transformer jack rings.
5. Carefully pull the transformer out of the inner cone-type socket in correct axial
direction (without tilting it).
6. Mount new voltage transformers (see Chapter 5.3, page 50) or close high-volt-
age terminal with surge-proof caps.
1 2 4
5
3
3
7
6
8
Fig. 91
Assembly / disassembly of busbar voltage transformer
1 Attachment with disconnecting device on busbar
2 Connecting socket and fange fastening
3 Voltage transformer
4 Angle bracket
5 Cover plate for transformer wiring
6 Terminal connection of transformer cables
7 Fastening by means of cable clamp
8 Fastening the protective hose
GHA
78 AGS 531 446-01 | Edition 12/2011
11 Commissioning
11.1 Final steps
11.1.1 Attachment of the tool board
1. Fasten tool panel at choice to the left or right side of the side wall (depending
on switchgear installtion) (Fig. 92); 2 x M5 Torx screw.
2. Place operating elements and instruction manuals on the tool board acc. to Fig.
92.
1
5
4
3
2
9
8
7
6
Fig. 92
Tool board attachment
1 Tool board
2 Fastening by means of a M5 Torx
screw
3 Double-bit key for low-voltage
cabinet
4 Crank for actuation of earthing
switch / disconnector
5 Handle for transformer disconnect-
ing device (inner cone-type cable
socket)
6 Spring charging crank for energy-
storing device
7 Assembly and Operating Instruc-
tions
8 Handle for transformer disconnect-
ing device (outer cone-type cable
bushing)
9 Service address
11.1.2 Cleaning and checking assembly
Danger!
The high-voltage supply must not be connected. All active parts
must be earthed.

Clean the switchgear, removing contamination resulting from assembly work.

Remove all the attached information tags, cards, brochures and instructions no
longer needed.

Check the tightening torques of all screw fastenings and connections estab-
lished on the site of installation:
Cable fttings on appliance couplers
Surge-proof covers on the appliance couplers
Earth conductor
Panel screw fastenings
Special attachments
Important:
Make sure the fastening of the silicone sleeves and busbar connection
are no longer detached.
GHA
79 AGS 531 446-01 | Edition 12/2011 79
11 Commissioning
11.1.3 Remount covers (see Chapter 4.6, page 29)

Lateral low-voltage cable tray cover

Cable compartment cover

Operating shutter

Close front frame again.
11.1.4 Damaged paint
The components are powder-coated. Minor damage to the paint can be repaired
using commercially available paint (standard colour RAL 7044 or corresponding
colour).
11.1.5 Inspection

Check the switchgear for damage which might be due to transport or assembly
work.

Compare data on nameplate to the required ratings.

Check rated supply voltage of control and operating devices.

Check wiring laid on site.

Check insulation gas monitoring:
IDIS system: see operating manual IDIS (AGS 531 690-01)
11.2 Commissioning
Danger!
The high-voltage supply must not be connected. All active parts
must be earthed.
Important:

Refer to the operating manual of the GHA series.

While the power supply is not available, blocking coils (locking the
interrogation slides and circuit-breaker push-buttons, depending
on design) are in locked position. An undervoltage release (op-
tional) has dropped out. In this case, frst perform items 3 to 5.

The energy-storing device of the circuit-breaker drive is charged
autonomously as soon as the supply voltage is applied.
1. Perform manual switching trials on the individual switching devices.
2. Check switch position indicators.
3. Apply supply voltage.
4. Check electrical functions of control and operating devices:
Motor drives for disconnector and earthing switch (optional)
Closing and opening releases for circuit-breaker
5. Check switch position indicators and interlocks.
6. Before connecting, check the connected feeder cables for phase coincidence
(see Operating Manual).
GHA
80 AGS 531 446-01 | Edition 12/2011
12 Optional high-voltage test on
commissioning
12.1 Power frequency withstand test of the busbar
A power frequency test of the busbar can be performed optionally. The test voltage
is supplied via the high-voltage terminal of a panel. To this effect, a test unit and test
cables are required, which are not included in the scope of supplies.
Warning!
Please comply with the safety provisions in Chapter 1, page 7.
Danger!
No high-voltage cables must be connected in the incoming feeder
panel for the voltage test and on the busbar. All high-voltage
terminals must be closed surge-proof during the test phase.
Earth the residual phases using commercially available earthing
devices.
Important:
All the switching operations mentioned in this context must be per-
formed in accordance with the applicable Operating Manual GHA.
1. All panels must be isolated from the power supply, and earthed.
2. Incoming feeder panel for voltage test:
Remove the cable compartment cover.
Test phase: Mount test cable to the high-voltage terminal (see Fig. 93).
Open high-voltage terminals must be closed surge-proof during the test
phase. Earth the residual phases using commercially available earthing
devices.
Earth the voltage transformers and capacitive measuring points. Discon-
nect surge arresters.
4
3
5
6
7
2
1
Fig. 93
1 Outgoing feeder panels
2 Incoming feeder panel for voltage test
3 Voltage transformer
4 Busbar
5 Test unit (e g. high-voltage source, test transformer)
6 Test cable
7 Busbar voltage transformer
General
Preparations
GHA
81 AGS 531 446-01 | Edition 12/2011 81
12 Optional high-voltage test on
commissioning
3. Busbar:
Earth voltage transformer / surge arrester.
Earth capacitive measuring connectors.
Close open high-voltage terminals in a surge-proof fashion.
4. Power frequency withstand test of the busbar:
Connect test unit to the test cable.
Switch earthing switch in the incoming feeder panel OFF.
Switch disconnector and circuit-breaker in the incoming feeder panel ON.
Perform power frequency withtstand tests successively for all phases (L1,
L2, L3) according to the specifcations of the test unit manufacturer.
Important:
Observe admissible test values for the switchgear and the admissible
test values for power-frequency tests after installation of the switchgear
in accordance with IEC 62271-200.
5. Once the power frequency withstand test has been completed, earth all the
tested high voltage lines again.
Comply with the applicable safety provisions!
6. Once the power-frequency test has been completed:
remove the test unit and the test cable,
reconnect earthed or removed voltage transformers, capacitive measuring
connectors or surge arresters.
Mount high-voltage cable or surge-proof covers on the incoming feeder
panel and reinsert cable compartment cover.
Power frequency withstand test:
Once the power-frequency test
has been completed:
GHA
82 AGS 531 446-01 | Edition 12/2011 82
12 Optional high-voltage test on
commissioning
12.2 Cable testing

Cable tests with the cables connected can be performed for outer cone-type as
well as for inner cone-type cable connections for each phase.

The test sockets for inner cones are accessible from the panel front after re-
moval of the cable compartment cover (Fig. 94, page 83).

The busbar can be operated with rated voltage during cable tests in the outgo-
ing feeder (see nameplate).

For cable testing, a test unit and a test adapter are required, which are not
included in the scope of supplies.
Warning!
Please comply with the safety provisions in Chapter 1, page 7..
Important:

All the switching operations mentioned in this context must be per-
formed in accordance with the applicable Operating Manual GHA.

The assembly, operating and testing instructions for cable fttings
and connectors and the test unit must be taken into consideration.

Comply with the admissible limits (see Table). Other limits are
only admissible after having obtained the written approval of the
manufacturer.
Admissible limits for the switchgear panels in case of cable tests
U
r
[kV]
DC test voltage for
initial / repeat test
[kV]
max. 15 min.
0.1 Hz AC test voltage

[kV]
max. 60 min.
12 34 19
24 67 45
36 76 57
40,5 62
1. Isolate outgoing feeder cable of the appropriate switchgear panel from the
power supply.
2. Isolate outgoing feeder cable in remote station.
3. Earth outgoing feeder cable.
4. Remove cable compartment cover (see Chapter 4.6).
5. Earth connected voltage transformers in the outgoing feeder cable.
6. Short-circuit and earth capacitive measuring points in outgoing feeder cable.
7. Remove surge-proof covers from measuring points:
Inner cone:
Remove dummy plug
Outer cone:
Remove terminating elements in Tee plugs as specifed by the manufac-
turer
General
Preparations
GHA
83 AGS 531 446-01 | Edition 12/2011 83
12 Optional high-voltage test on
commissioning
8. Connect test adapter to test connector and test unit (Fig. 94 and Fig. 95). Com-
ply with the manufacturer's specifcations.
Important:

Make sure that the distance between the metallic components of
the test adapter and the earthed subconstruction of the switchgear
is suffciently dimensioned.

Earth the residual phases using commercially available earthing
devices.
1
2
Fig. 94
Test cable for inner cone-type socket (size 2)
1 Test socket
2 Test cable
1
2
Fig. 95
Cable test, outer cone
1 Cover and adapter
2 Test adapter
Performing the cable test
GHA
84 AGS 531 446-01 | Edition 12/2011 84
12 Optional high-voltage test on
commissioning
9. In case of optional interlocking
of the cable compartment cover,
the circuit-breaker cannot be
switched off until after simulation of
a cable compartment cover (Fig.
96).
Warning!
Interrupting the inter-
locking protection:
With the cable compart-
ment cover removed,
the earthing switch
interlock may only be
eliminated during cable
test!
Swing interlock (1) of the
cable compartment cover
downwards and keep it in this
position.
Push interlocking slide (2)
down; the actuating port for
the earthing switch is set free.
10. Set switchgear panel to test position.
If an intertripping circuit is provided,
the circuit-breaker is switched off
by actuation of the earthing switch
towards OFF (Fig. 97).
Free actuating port of the
earthing switch (B) by push-
ing the interrogation slide (A)
upwards, and insert the crank
(C).
Turn crank counterclockwise
by approx. one rotation,
until the circuit-breaker has
switched OFF (D).
The crank cannot be removed.
11. Perform cable test according to the specifcations of the manufacturer of the
cable or the cable connector, taking the admissible limits into consideration
(see Table on page 81).

Perform cable test for all phases.
1
2
Fig. 96
Unlocking the earthing switch
1 Cable compartment cover interlock
2 Interlocking slide
Test position:
Earthing switch ON
Circuit-breaker OFF
00243
A
B
C
D
Fig. 97
Set switchgear panel to test position
GHA
85 AGS 531 446-01 | Edition 12/2011 85
12 Optional high-voltage test on
commissioning
12. Earth outgoing feeder cable again:
Switch earthing switch completely OFF
Charge spring mechanism
Switch earthing switch ON again
13. Remove test set.
Inner cone-type socket:
Close test socket surge-proof using the dummy plug.
Outer cone-type bushing:
Provide cable fttings with terminating element according to the manufac-
turer's instructions.
14. Re-connect voltage transformer.
15. De-earth capacitive measuring points in outgoing feeder cable and reset short-
circuit.
16. Mount cable compartment cover again.
12.3 Cable jacket test
If there are no documents to inform whether a cable jacket test may be performed on
the cable connection system, the manufacturer of the cable connection system must
be consulted before performing such a test.
Warning!
Do not connect the cable's earth conductor to the connector
housing (contact-making). Make sure to check the earthing cable
directly.
1. To perform the cable jacket test, disconnect the earth connections (Cu shield)
from the cable support.
2. To determine any damage on the outer plastic jackets or sheathes between the
cable's Cu shield and the earth, apply test DC voltage in accordance with the
applicable standard or the instructions of the cable manufacturer.
3. Once the test has been completed, re-mount the earth connection (Cu shield)
on the cable support.
Fig. 98
Cable jacket testing principle
for outer cone
After the cable test
GHA
86 AGS 531 446-01 | Edition 12/2011
13 Annex
13.1 Auxiliary products
The auxiliary products are available from the manufacturer. The use of other auxil-
iary products is not admissible.
Warning!
Risk of injury if these products are handled improperly. Observe
the safety data sheets of the manufacturers of the auxiliary prod-
ucts.
Auxiliary products Ref. no.
Cleaning agent S 008 152
Synthetic lubricant (KL), 0.5 kg can ST 312-111-835
Liquid lubricant FL, 0.5 kg can S 008153
Touch-up pen RAL 7044, silk-grey, 50 ml S 009 561
Touch-up pen, special paint (specify colour shade) S 009 562
Screw locking compound Loctite 648

ST318-225-001
Auxiliary products for assembly of the busbar link
(B-Link)
Ref. no.
Cleaning agent Ethanol, type 641 (methylated spirit) S 009 002
Special grease Klberalfa

HBK 83-102 AGS 003371-01


Sponge element S065969
lint-free cloth (also micro-fber cloths)
lint-free rubber gloves
13.2 Required tools (not included in the scope of
supplies)
Cutter

Nail puller
approved torque wrenches with different bits for hexagon
socket screws and socket-head screws and nuts; bits for
screw and nut grades M 5, M 6, M 8, M 10, M 12
Screwdriver and Philips screwdriver
Nipping pliers
4 crane straps / chains each of L 2000 mm, lifting ca-
pacity 1500 kg
lint-free, clean cloths
GHA
87 AGS 531 446-01 | Edition 12/2011 87
13 Annex
Fig. 99
Transport frame
Fig. 100
Fork to compress the silicone sleeve

Fig. 101
Claw fastener
Fig. 102
Lifting table for low-voltage cabinet
Fig. 103
U profles with stop as traversing aid
GHA
88 AGS 531 446-01 | Edition 12/2011 88
13 Annex
13.3 Coating the contact surfaces
Important:
Contact areas, once coated with synthetic lubricant, should not be
touched, if possible.
1. Contact surfaces must be subjected to preliminary treatment before screw-
fastening (see Table below).
2. Immediately after the pre-treatment, coat both contact surfaces sparingly with a
thin and uniform flm of synthetic lubricant so that the space between the con-
tact surfaces is completely flled once the screws have been fastened.
Material of contact surfaces Pre-treatment
Silver-plated Clean
1
Copper or copper alloy Clean
1
, expose metallic surface
2
Aluminium Clean
1
, expose metallic surface
2
Steel Clean
1
, expose metallic surface
2
Galvanized steel Remove passivation, not, however, the zinc
layer
3
Sheet metal, hot dip galvanized Clean
1
; passivation need not be removed
1
Clean by means of a lint-free cloth; use cleaning agent in case of serious con-
tamination
2
Expose metallic surface
- by treating the entire surface with emery cloth or a rotating grinding tool (grain
size 100 or 80) or
- using a wire brush which is clearly marked for use exclusively for aluminium or
exclusively for copper
3
using a brass brush, steel brush
13.4 Screw locking compound
Important:

Observe the specifcations of the manufacturer of the screw lock-
ing compound.

In case the thread reach exceeds 1.2 x the screw diameter and in
case of blind hole threads, only wet the nut's thread.
1. Preparing the thread surfaces: clean and degrease thread surfaces using
cleaning agent and a lint-free cloth.
2. Application of adhesive: Coat the entire circumference of 2 or 3 threads in the
area to be glued with liquid screw locking compound.
Max. time for positioning: 60 sec.
GHA
89 AGS 531 446-01 | Edition 12/2011 89
13 Annex
13.5 Specifcations for screw connections
Important:

The threads of screws and bolts must generally not be pre-treat-
ed!

Max. tolerance for the effective tightening torques: 15%

The nut must correspond in strength to the grade of the screw/bolt
used or be of better quality.
Grade or material
Screw/bolt Plastic 8.8 10.9
Self-locking screw
8.8
Thread Tightening torques [Nm]
M 4 0.25 2.6
M 5 0.5 5.0 7.0
M 6 0.8 8.8 12.3
M 8 1.8 21.0 30.0
M 10 3.5 42.0 59.0
M 12 6.0 70.0 97
M 16 12 170
M 20 330
Screw connection for current
transmission
Screw connection for terminal
strips
Screws and bolts: Grade 8.8
Conductor material: copper
Thread Tightening
torques [Nm]
M 6 6.5
M 8 17
M 10 35
M 12 68
M 16 135

Thread Tightening
torques [Nm]
M 2.5 (M 2.6) 0.5
M 3 0.7
M 3.5 1.0
M 4 1.5
M 5 2.5
General screw connections
Notes:
Schneider Electric
35, rue Joseph Monier
CS 30323
92506 Rueil-Malmaison Cedex, France
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com

AGS 531 446-01 | 12/2011
As our products are subject to continuous development, we reserve the
right to make changes regarding the standards, illustrations and technical
data described in this Technical Manual. For any requests, please contact
the address given below.
Schneider Electric Sachsenwerk GmbH
Rathenaustrasse 2
D-93055 Regensburg, Germany
( +49 (0) 9 41 46 20-0
7 +49 (0) 9 41 46 20-418


S
c
h
n
e
i
d
e
r

E
l
e
c
t
r
i
c

2
0
1
2


A
l
l

r
i
g
h
t
s

r
e
s
e
r
v
e
d

t
o

t
h
i
s

t
e
c
h
n
i
c
a
l

m
a
n
u
a
l
.

R
e
p
r
o
d
u
c
t
i
o
n

a
n
d

m
a
k
i
n
g

a
v
a
i
l
a
b
l
e

o
f

t
h
i
s

t
e
c
h
n
i
c
a
l

m
a
n
u
a
l
,

o
r

e
x
t
r
a
c
t
s
,

t
o

t
h
i
r
d

p
a
r
t
i
e
s

a
r
e

p
r
o
h
i
b
i
t
e
d
.

O
n
l
y

i
n
t
e
g
r
a
l

r
e
p
r
o
d
u
c
t
i
o
n

o
f

t
h
i
s

t
e
c
h
n
i
c
a
l

m
a
n
u
a
l

i
s

p
e
r
m
i
t
t
e
d

w
i
t
h

t
h
e

w
r
i
t
t
e
n

p
e
r
m
i
s
s
i
o
n

f
r
o
m

S
c
h
n
e
i
d
e
r

E
l
e
c
t
r
i
c
.

E
l
e
c
t
r
o
n
i
c

c
o
p
i
e
s

i
n

e
.
g
.

P
D
F
-
f
o
r
m
a
t

o
r

s
c
a
n
n
e
d

v
e
r
s
i
o
n

h
a
v
e

t
h
e

s
t
a
t
u
s

f
o
r

i
n
f
o
r
m
a
t
i
o
n

o
n
l
y


.

T
h
e

o
n
l
y

v
a
l
i
d

v
e
r
s
i
o
n

o
f

t
h
i
s

t
e
c
h
n
i
c
a
l

m
a
n
u
a
l

i
s

a
l
w
a
y
s

e
n
c
l
o
s
e
d

d
i
r
e
c
t
l
y

t
o

t
h
e

p
r
o
d
u
c
t

i
n

q
u
e
s
t
i
o
n

b
y

t
h
e

f
a
c
t
o
r
y
.

Potrebbero piacerti anche