Earthing is topic generally known to everybody and I hope importance of
earthing in our electrical system is also known. Still I have chosen to discuss this topic, as I will like you to introspect: a) Do we really know new concepts, which are being introduced in earthing practices world wide b) Do we really abide by the earthing re!uirements c) Do we really understand comple"ity of earthing # give due importance to it $y e"perience shows that due importance is not given to earthing practice and many a times it is done to complete a formality for getting electrical inspectors approval. %ence a discussion on general earthing practices is essential. I. WHY EARTHING IS REQUIRED? &.& Everybody knows earthing is re!uired to be done for safety, to avoid shocks and to protect life. 'his becomes possible due to the solidly earthed neutral system adopted by us for distribution. 'his also provides reference (ero potential for the system # make preserves the safety and security of the system by ensuring that potential of conductor is restricted to a rated value consistent with level of inculation. In addition to prohibiting shocks dose earthing have any other function in the electrical system )es, it provides convenience of effective way of tripping circuits using relays under fault conditions this protecting precious e!uipment in the system and earthing fi"es the system neutral voltage. Earthing also provides effective way of dissipating lightening energy without damage to buildings * structures. 'hus earthing improves service continuity, avoids damage to e!uipment # danger to human life. +f course, even proper and effective earthing may not provide protection against faults other than earth faults and tripping in such cases is dependant on over current trips. 1.2 Comparison of Eart!" # Un!art!" S$st!m ,nearthed systems are utili(ed in some areas based on thought of gaining additional service continuity as earthed systems are designed to remove faulty circuits from system. %owever it is a common e"perience world over that better service continuity is possible with earthed system. -onsider following points. &...& $ultiple /round 0aults: 1hile service continuity is ensured in unearthed system in one ground fault condition in case of occurrence of another ground fault before removal of first fault results in outage and possible damage to the e!uipment. $any times such single ground faults are not located unless a comprehensive # organi(ed maintenance program is in place. &.... 2rcing 0aults : 0ault currents caused due to arcing faults in phases or phase and ground can be low and may not the sufficient to trip over current devices in unearthed system. 3ut detecting leakage currents # tripping due to even low leakage currents is possible in earthed system* &...4 /round 0ault identification and locating fault is easy in earthed system. &...5 In both cases earthing of e!uipment and structures is essential for protection of life and property. %igh fault currents in earthed system can cause %a(ard to workers due to heat generated. &...6 Earthed system essentially tries to keep voltages of phases to the desired levels, which are not possible in case of unearthed system and fre!uent over voltages, and imbalance can cause fre!uent failure of e!uipment # insulation in unearthed system. II. EARTHING C%ASSI&ICATIONS : Earthing schemes are classified in per IE- 758 and IS 4954 based on various methods adopted as: &) '' System .) ': System 4) I' System ;et us now look in to details of connections used for each system. 1' TT S$st!m +ne point at the supply source generally the star point is connected directly to earth and all e"posed conductive metal parts <:on live = body) are connected to separate earth electrode near the installation. 'his electrode may or may not be electrically independent of the source star point earthing. 2' TN S$st!m In this case also one or more points of sources generally star point is connected directly to earth and e"posed parts <body) are connected to source earth by means of protective earth conductor. 'here are various versions of this system. ..& ': = - Scheme: :eutral conductor is also used as protective conductor and used as earth. 'his is identified as >E: conductor. 'his scheme re!uires efficient e!uipotantial conductor using dispersed earth electrodes. 'his scheme is not suitable for portable e!uipment and conductors less than &9 s!.mm. ... ': = S Scheme In this scheme protective conductor and neutral conductors are separate <6 conductors) 'his can be used in case of mobile e!uipment also. ..4 ': = - = S -ombination of ': = - # ': = S schemes is used at some places. 'hough no separate >E conductor originates from source earth it is separated at start of installation. (' IT S)!m! 'here is no connection between earth and source neutral. E"posed parts are connected to direct earth. :eutral can be taken if re!uired. 'hese are generally 4 phase 4 wire system. 1e generally use some %ybrid scheme for earthing in ':. I' Scheme is generally not used in our distribution scheme. II. TY*ES O& EARTH E%ECTRODES : i. *ip! + Ro" Eartin,- $etallic pipe * rod of appropriate diameter are used as earth electrodes in this scheme. /enerally rods are directly driven in ground up to a depth of minimum ..9 mtrs. rods can be &4 or &7 mm dia. steel cored copper pipes are minimum ..6 mtr. length either /I &99 mm dia or 59 mm /I. ;onger length pipes are used as earth electrode by boring in hard strata where soil resistance is high to reach low soil resistance earth. 'he diameter of pipe dose not make ma?or difference in earth resistance, as can be seen from attached graph. ii. *.at! E.!)tro"!- >late electrodes of -I, -,, or /I are used for plate earthing. 'he recommended si(es are at least @99 " @99 mm and thickness of &. mm in case of -I, @ mm incase of /I and 4.&6 mm in case of copper. 'he plates are generally not larger than &.. " &.. mtr. as re!uired earth reasistance can be obtained by using multiple small electrode plates than by using larger plates. 'he plates are generally buried at atAleast &.6 mtr. below normal /; with watering pipe. 'o get best results a separation of &9 mtrs. is re!uired but for @99 " @99 mm plate si(e a clearance of ..9 mtrs. between two electrodes is also sufficient. iii. /att or Strip E.!)tro"!- In areas where very shallow low resistance soil is available an earth mat using strips of appropriate si(e can be done to get re!uired earth resistance value. III. SOI% TREAT/ENT 'he soil resistance play ma?or role in the earthing system. In certain strata even multiple earth electrodes do not provide ade!uately low earth resistance. In such cases to reduce the soil resistively highly conductive waterAsoluble materials like salt are used for artificial treatment of soil. ;ot of water is also used so that such waterAsoluble material also spreads in surrounding soil to provide permanent conditions of lower soil resistance. In very hard strata slurry of bentonite is also recommended to provide proper earth contact and conducive surrounding. 'he effectiveness of artificial soil treatment remains for longer duration in close te"ture soils but can reduce in loose soils and water logged areas. %ence it is advisable to check earthing resistance of such earthing stations regularly. In case of artificial treatment as salts are used it propagates corrosion of earth electrodes. 'his has to be considered while selection of electrodes. I0. /ATERIA% &OR EARTH E%ECTRODE $ain criteria for selection of material for earth electrode will be soil resistance and chemical composition, which can create corrosion. 'hough material dose not affect initial earth resistance it can give varied results in longer runs. /enerally copper earth tinned or not provides most satisfactory results where average weight * volume loss is not more than 9..B per year. 'his is followed by galvani(ed iron where loss is about 9.6B a year. ;oss in other forms of Iron like cast iron or mild steel is more than ...B a year. 0. EARTHING CONDUCTOR- @.& Selection and connection of earthing conductors is also very important in view of providing minimum resistance in path between earth electrode and the load. 'he cross section of earth conductor should be suitable for carrying the fault currents of the system without getting heated or creating sparks that can lead to fire. 'he conductor crossA section is generally determined by following formula I C D & S E t I C 0ault current in amps S C -ross section in mm . t C 'ime re!uired for operation of tripping * disconnection device. D C 0actor dependent on material of protection conduit. It is also important that all the earth conductors are properly connected to electrode and to each other and ?oints coated by bituminous paint or grease. 2 typical recommended connecting method is given below which also satisfies the re!uirement of test link for testing earthing electrode. @.& Do we form a grid of all earth station If we follow recommendation of ->FI earthing committee, answer is )es. 'hese committee has recommended to grid of all earthing stations including ;2 and electronic earths through separate connecting conductor.<e!uipotantial -onductor) 2lternator * /enerator neutral earthing generally do not form part of grid due to operating re!uirements. 0I. CHOSING SITE &OR EARTHING- ;ow earth resistance depends mainly on the soil resistance at the station hence choosing proper site for earthing site. Soil resistance depends on chemical composition and concentration of dissolved salts and moisture content in soil. %ence sites as far as possible chosen in i) 1et marshy /rounds. ii) 3lack cotton soil area. iii) -lay and loam mi"ed soil with some sand gravel. iv) Damp and wet sand peat. Sites should not be as far as possible chosen in i) Dry sand and gravel ii) ;ime stone area. iii) :atural rocky area. iv) 1ell drained site or area where water flow is there. v) :ewly filled area. In case there is no alternative but to make earthing in rocky area it is advisable to determine the soil resistance by taking test bores at multiple places. 3ase on the soil resistance depth and no of earthing can be decided to get desired results. 0II. STATUTORY REQUIRE/ENTS O& EARTHING - .) Earthing shall generally be carried out in accordance with re!uirements of Indian Electricity Fules &76@ with up to date amendments, ISS and Felevant regulations of Electricity Supply 2uthority. 4) 2ll medium voltage e!uipment shall be earthed with two distinct # separate earth connections. 5) In %igh and E"tra %igh voltages neutrals shall be earthed by not less than two separate and distinct connections each having separate earth electrode in generating station or substations and at any other earth point provided it dose not cause interference. 6) In cases where direct earthing is harmful like high fre!uency or cordless induction furnaces rela"ation may be obtained from competent authority. @) Earth electrodes shall be provided in accordance with IS 4954. 8) 2ll earthing connection shall be as far as possible visible for inspection. G) 'he provisions shall be made in earthing systems such that testing of each earth electrode is possible 7) Earth resistance shall be such as to confirm with degree of shock protection desired. &9) Each earth station shall in any case be tested for earth resistance on a dry day at least once in two years and record of such tests shall be kept. &&) It is recommended that drawing showing main earth connection # electrodes shall be prepared for each installation. &.) :o cutout, switch or link other than linked switch arrangement to operate on earthed neutral and phase <live) conductors shall be inserted on earthing conductor in a supply system. 'his however dose not include generators and transformers where operation re!uires earth isolation facility.