Product Specifications
DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6 25 TONS
BUILT TO LAST, EASY TO INSTALL AND SERVICE
Multiposition design for horizontal or vertical installation without modification.
Two sloped condensate pans on each unit for horizontal or vertical applications.
Cleanable insulation treated with Environmental Protection Agency (EPA) registered
antimicrobial agent improves indoor air quality.
2 inch filters.
High-static design meets a wide range of applications.
Powerfull beltdriven forward curved fans.
Single refrigerant circuit on 072 and 091 sizes. Dual refrigerant circuit on 120300 sizes.
Dual circuit can be field modified for use on single circuit condensers.
Single blower on 6 to 10 ton units; dual blower on 12.5 to 25 ton units.
Cooling coils with mechanically bonded fins provide peak heat transfer.
FAS072120
FAS150300
Nominal
Tons
6
7 1 /2
10
121/2
15
20
25
Number
of
Circuits
1
1
2
2
2
2
2
Unit Dimensions
H x W x L [mm]
561/16 x 49 x 283/16 [1424 x 1244 x 714]
561/16 x 49 x 283/16 [1424 x 1244 x 714]
561/16 x 49 x 283/16 [1424 x 1244 x 714]
561/16 x 89 x 283/16 [1424 x 2261 x 714]
561/16 x 89 x 283/16 [1424 x 2261 x 714]
561/16 x 89 x 283/16 [1424 x 2261 x 714]
659/16 x 1001/2 x 325/8 [1665 x 2553 x 829]
Unit
Weight
lb. [kg]
399 [181]
404 [183]
425 [193]
695 [315]
713 [323]
730 [331]
1050 [477]
508 41 1602 01
05/25/11
TABLE OF CONTENTS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PAGE
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . 3
OPTIONS AND ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . 4
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
PERFORMANCE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
TYPICAL PIPING AND WIRING . . . . . . . . . . . . . . . . . . . . . . . . . 41
TYPICAL CONTROL WIRING SCHEMATIC . . . . . . . . . . . . . . 44
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
508 41 1602 01
MODEL NOMENCLATURE
MODEL SERIES
Position Number
F = R410A Fan Coil Unit
A = Air Conditioning (Cooling Only)
S = Standard Efficiency
10
11
12
13
14
Type
Efficiency
Nominal Tonnage
K = 208/230160
H = 208/230360
M = 460/208/230360
L = 460360
S = 575360
Voltage
Refrigerant System
0 = No options
Future Use
Future Use
A = Original Design
Sales Digit
*Single phase FAS072091 units designate standard motor and high static drive.
All FAS072150 with a M voltage designation are triple voltage; i.e., 208/230/460360.
Size FAS180 is also triple voltage unless high static options is used, See chart below.
MODEL NUMBERS*
Standard Static
High Static
FAS072KAAA0A0A
FAS072KBAA0A0A
FAS072MAAA0A0A
FAS072MBAA0A0A
FAS072SAAA0A0A
FAS072SBAA0A0A
FAS091KAAA0A0A
FAS091KBAA0A0A
FAS091MAAA0A0A
FAS091MBAA0A0A
FAS091SAAA0A0A
FAS091SBAA0A0A
FAS120MAAA0A0A
FAS120MBAA0A0A
FAS120SAAA0A0A
FAS120SBAA0A0A
FAS150MAAA0A0A
FAS150MBAA0A0A
FAS150SAAA0A0A
FAS150SEAA0A0A
FAS180MAAA0A0A
FAS180HEAA0A0A
FAS180SAAA0A0A
FAS180LEAA0A0A
FAS180SEAA0A0A
FAS240HDAA0A0A
FAS240HEAA0A0A
FAS240LDAA0A0A
FAS240LEAA0A0A
FAS240SDAA0A0A
FAS240SEAA0A0A
FAS300HDAA0A0A
FAS300HEAA0A0A
FAS300LDAA0A0A
FAS300LEAA0A0A
FAS300SDAA0A0A
FAS300SEAA0A0A
508 41 1602 01
Fieldinstalled accessories
Tworow hot water coils have copper tubes
mechanically bonded to aluminum plate fins and
nonferrous headers.
Onerow steam coil has copper tubes and aluminum
fins. The Inner Distributing Tube (IDT) design provides
uniform temperatures across the coil face. The steam coil
has a broad operating pressure range; up to 20 psi (138
kPag) at 260_F (126_C). The IDT steam coils are
especially suited to applications where subfreezing air
enters the unit.
Electric resistance heat coils have an openwire design
and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard. Terminal block for
singlepoint power connection is included.
Economizer (enthalpy controlled) provides ventilation
air and free cooling if outside ambient temperature and
humidity are suitable. It can also be used with CO2
sensors to help meet indoor air quality requirements.
Discharge plenum directs the air discharge directly into
the occupied space; integral horizontal and vertical
louvers enable redirection of airflow. Accessory is
available unpainted or painted. Field assembly is required
(only applicable for vertical application and cannot be
used with electric heat).
Returnair grille provides a protective barrier over the
returnair opening and gives a finished appearance to
OPTION*
ACCESSORY{
X
X
X
X
X
X
X
X
X
X
X
X
* Factory-installed option.
{ Field-installed accessory
ACCESSORIES
Model Number
AGRC01AA
AGRPC01AA
AGRC02BA
AGRPC02BA
ASPC01AA
ASPC02BA
ASBC01A
ASBPC01A
ASBC01A
ACSC01A
APDC01AA
APDPC01AA
APDC02BA
APDPC02BA
DNCBDIOX005A00
AEMC01AA
AEMC02BA
AHWC01AA
AHWC02BA
4
Description
Return Air Grille
Return Air Grille, Painted
Return Air Grille
Return Air Grille, Painted
Steam Coil (1 Row)
Steam Coil (1 Row)
Floor Mount Base (Subbase)
Floor Mount Base (Subbase), Painted
Overhead Suspension Brackets
Condensate Overflow Switch
Discharge Plenum
Discharge Plenum, Painted
Discharge Plenum
Discharge Plenum, Painted
CO2 Senser for Economizer
Economizer
Economizer
Hot Water Coil (2 Row)
Hot Water Coil (2 Row)
Specifications subject to change without notice.
Used on
Unit Size (Tons)
6 to 10
6 to 10
121/2 to 20
121/2 to 20
6 to 10 Ton
121/2 to 20
6 to 20
6 to 20
6 to 25
6 to 25
6 to 10
6 to 10
121/2 to 20
121/2 to 20
6 to 20
6 to 10
121/2 to 20
6 to 10
121/2 to 20
508 41 1602 01
ACCESSORIES (CONT.)
Model Number
CARAGRIL003A00
CARAGRIL006A00
CASTCOIL003A00
CASUBASE002A00
CASUBASE004A00
CAPLENUM003A00
CAPLENUM006A00
CAECOMZR003A00
CAHWCOIL003A00
CATRANRY001A00
Description
Return Air Grille
Return Air Grille, Painted
Steam Coil (1 Row)
Floor Mount Base (Subbase)
Floor Mount Base (Subbase), Painted
Discharge Plenum
Discharge Plenum, Painted
Economizer
Hot Water Coil (2 Row)
Transformer Relay Package - Contains 200/230/460 to 24-volt
transformer, indoor fan and solenoid valve relays with wiring
and quick connect terminals. Recommended for 24-volt
thermostat applications when additional VA is required.
Used on
Unit Size (Tons)
25
25
25
25
25
25
25
25
25
6 to 25
ACCESSORY HEATERS
HEATER PART NO.
AAHC05AHA
AAHC10AHA
AAHC15AHA
AAHC25AHA
AAHC35CHA
AAHC10BHA
AAHC20BHA
AAHC30BHA
AAHC50DHA
AAHC20EHA
AAHC40EHA
AAHC50EHA
AAHC70EHA
AAHC05ALA
AAHC10ALA
AAHC15ALA
AAHC25ALA
AAHC35CLA
AAHC10BLA
AAHC20BLA
AAHC30BLA
AAHC50DLA
AAHC20ELA
AAHC40ELA
AAHC50ELA
AAHC70ELA
AAHC05ASA
AAHC10ASA
AAHC15ASA
AAHC25ASA
AAHC35CSA
AAHC10BSA
AAHC20BSA
AAHC30BSA
AAHC50DSA
AAHC20ESA
AAHC40ESA
AAHC50ESA
AAHC70ESA
508 41 1602 01
DESCRIPTION
5.0 kW, 240360
10.0 kW, 240360
15.0 kW, 240360
25.0 kW, 240360
35.0 kW, 240360
10.0 kW, 240360
20.0 kW, 240360
30.0 kW, 240360
50.0 kW, 240360
20.0 kW, 240360
40.0 kW, 240360
50.0 kW, 240360
70.0 kW, 240360
5.0 kW, 480360
10.0 kW, 480360
15.0 kW, 480360
25.0 kW, 480360
35.0 kW, 480360
10.0 kW, 480360
20.0 kW, 480360
30.0 kW, 480360
50.0 kW, 480360
20.0 kW, 480360
40.0 kW, 480360
50.0 kW, 480360
70.0 kW, 480360
5.0 kW, 575360
10.0 kW, 575360
15.0 kW, 575360
25.0 kW, 575360
35.0 kW, 575360
10.0 kW, 575360
20.0 kW, 575360
30.0 kW, 575360
50.0 kW, 575360
20.0 kW, 575360
40.0 kW, 575360
50.0 kW, 575360
70.0 kW, 480360
Nominal
Capacity
5
10
15
25
35
10
20
30
50
20
40
50
70
5
10
15
25
35
10
20
30
50
20
40
50
70
5
10
15
25
35
10
20
30
50
20
40
50
70
Used With
072, 091, 120
072, 091, 120
072, 091, 120
072, 091, 120
091, 120
150, 180, 240
150, 180, 240
150, 180, 240
180, 240
300
300
300
300
072, 091, 120
072, 091, 120
072, 091, 120
072, 091, 120
091, 120
150, 180, 240
150, 180, 240
150, 180, 240
180, 240
300
300
300
300
072, 091, 120
072, 091, 120
072, 091, 120
072, 091, 120
091, 120
150, 180, 240
150, 180, 240
150, 180, 240
180, 240
300
300
300
300
DISCHARGE
PLENUM
RETURNAIR
GRILLE
SUBBASE
FAN
COIL
UNIT
FAN COIL
UNIT
ECONOMIZER
508 41 1602 01
Face...50/50
No. of Circuits per Split
12
15
9
12
16
18
20
Fins/in.
15
15
17
15
15
17
15
STEAM COIL
20
Max Working Press. (psig at 260_F)
Total Face Area (sq ft)
6.67
6.67
6.67
13.33
13.33
13.33
15.0
Rows...Fins/in.
1...9
1...9
1...9
1...10
1...10
1...10
1...10
HOT WATER COIL
Max Working Pressure (psig)
150
Total Face Area (sq ft)
6.67
6.67
6.67
13.33
13.33
13.33
15.0
Rows...Fins/in.
2...8.5
2...8.5
2...8.5
2...8.5
2...8.5
2...8.5
2...12.5
Water Volume
(gal)
8.3
13.9
14.3
(ft3)
1.1
1.85
1.90
PIPING CONNECTIONS**
Quantity...Size (in.)
DX Coil Suction (ODF)
1...11/8
2...11/8
2...13/8
5
5
DX Coil Liquid Refrig, (ODF)
1... /8
2... /8
Steam Coil, In (MPT)
1...21/2
Steam Coil, Out (MPT)
1...11/2
Hot Water Coil, In (MPT)
1...11/2
1...2
Hot Water Coil, Out (MPT)
1...11/2
1...2
Condensate (PVC)
1...5/8 ODM/1 IDF
FILTERS
Throwaway Factory-Supplied
4...16 x 20 x 2
4...20 x 24 x 2
Quantity...Size (in.)
4...16 x 24 x 2
4...16 x 24 x 2
4...20 x 25 x 2
Access Location
Right or Left Side
* Refer to Alternate Fan Motor Data table, page 36, for alternate motor data.
{ Units are shipped without refrigerant charge.
** All piping sizes are OD inches; equivalent sizes in millimeters follow:
508 41 1602 01
Face...50/50
Fins/m
591
591
670
591
591
670
591
STEAM COIL
138
Max Working Pressure (kPag at 126_C)
Total Face Area (sq m)
0.62
0.62
0.62
1.24
1.24
1.24
1.39
Rows...Fins/m
1...355
1...355
1...355
1...394
1...394
1...394
1...394
HOT WATER COIL
Max Working Pressure (kPag)
1034
Total Face Area (sq m)
0.62
0.62
0.62
1.24
1.24
1.24
1.39
Rows...Fins/m
2...335
2...335
2...335
2...335
2...335
2...335
2...493
Water Volume
(L)
31.4
52.6
54.1
(m3)
0.031
0.052
0.054
PIPING CONNECTIONS**
Quantity...Size (in.)
DX Coil Suction (ODF)
1...11/8
1...11/8
2...11/8
2...11/8
2...11/8
2...11/8
2...13/8
DX Coil Liquid Refrigerant (ODF)
1...5/8
2...5/8
Steam Coil, In (MPT)
1...21/2
1...21/2
1
Steam Coil, Out (MPT)
1...1 /2
1...11/2
1
1
Hot Water Coil, In (MPT)
1...1 /2
1...1 /2
1...2
Hot Water Coil, Out (MPT)
1...11/2
1...11/2
1...2
Condensate (PVC)
1...5/8 ODM/1 IDF
FILTERS
Throwaway Factory-Supplied
4...406 x 508 x 51
4...508x610x51
Quantity...Size
4...406 x 610 x 51
4...406 x 610 x 51
4...508x635x51
Access Location
Right or Left Side
* Refer to Alternate Fan Motor Data table, page 36, for alternate motor data.
{ Units are shipped without refrigerant charge.
** All piping sizes are OD inches; equivalent sizes in millimeters follow:
508 41 1602 01
C09060
UNIT
FAS072
399 (181)
FAS091
404 (183)
FAS120
425 (193)
508 41 1602 01
C101283
UNIT
FAS150
FAS180
FAS240
10
508 41 1602 01
C09484
UNIT
FAS300
508 41 1602 01
11
Dimensions (cont.)
CORNER WEIGHTS
HORIZONTAL POSITION
6
Coil
Fan
Fan
Steam Coil or
Hot Water Coil
Economizer
FAS - U.S.
FAS
UNIT SIZE
FAS072
FAS091
FAS120
FAS
072, 091, 120
FAS150
FAS180
FAS240
FAS
150, 180, 240
FAS300
FAS300
12
UNIT OR
ACCESSORY
WEIGHT
(lb)
399
404
425
215
195
185
400
380
695
713
730
340
285
340
680
625
1050
405
345
450
855
795
2
106.1
107.5
113.0
0.0
0.0
36.8
38.6
35.8
177.7
182.3
186.4
0.0
0.0
66.9
63.7
57.6
268.5
0.0
0.0
88.5
80.1
73.7
3
90.6
91.7
96.5
0.0
0.0
35.7
37.4
34.6
129.8
133.2
136.5
0.0
0.0
62.0
59.0
53.4
196.1
0.0
0.0
82.0
74.1
68.2
4
93.4
94.5
99.4
40.6
36.7
0.0
39.2
37.7
163.7
167.9
171.5
62.0
51.3
0.0
65.0
59.5
247.2
73.8
62.1
0.0
81.6
75.7
66.5
60.4
0.0
64.2
62.1
107.8
91.5
0.0
113.0
106.2
128.4
110.7
0.0
142.0
135.0
67.5
62.0
0.0
65.2
63.8
108.8
90.6
0.0
114.1
105.1
129.6
109.6
0.0
143.4
133.6
0.0
0.0
56.8
59.5
55.1
0.0
0.0
109.8
104.5
94.6
0.0
0.0
145.3
131.3
120.3
0.0
0.0
55.1
57.7
53.4
0.0
0.0
102.0
97.1
87.8
0.0
0.0
134.2
122
111.7
508 41 1602 01
Dimensions (cont.)
FAS - SI
FAS
UNIT SIZE
FAS072
FAS091
FAS120
FAS
072, 091, 120
FAS150
FAS180
FAS300
FAS300
UNIT OR
ACCESSORY
WEIGHT
(kg)
181
183
193
98
89
84
182
173
315
323
155
130
155
310
285
477
184
156
204
387
360
2
48.1
48.6
51.3
0.0
0.0
16.7
17.5
16.3
83.7
85.9
0.0
0.0
30.2
29.0
26.4
126.7
0.0
0.0
39.8
36.4
33.5
3
41.1
41.5
43.8
0.0
0.0
16.2
17.0
15.8
71.5
73.3
0.0
0.0
28.3
26.9
24.4
108.2
0.0
0.0
37.2
33.5
30.8
4
42.3
42.8
45.2
18.4
16.7
0.0
17.8
17.2
73.7
75.6
28.3
23.4
0.0
29.6
27.1
111.6
33.6
28.0
0.0
36.9
34.2
30.2
27.5
0.0
29.1
28.3
49.3
41.8
0.0
51.5
48.5
58.5
50.3
0.0
64.4
61.2
30.6
28.2
0.0
29.6
29.0
49.3
41.2
0.0
51.9
47.9
58.5
49.4
0.0
64.8
60.5
0.0
0.0
25.8
27.0
25.1
0.0
0.0
50.3
47.6
43.1
0.0
0.0
66.2
59.4
54.5
0.0
0.0
25
26.2
24.3
0.0
0.0
46.2
44.2
40.1
0.0
0.0
60.8
55.1
50.6
LEGEND:
ECO - Economizer
HW - Hot Water
508 41 1602 01
13
Dimensions (cont.)
CORNER WEIGHTS
VERTICAL POSITION
5
Economizer
1
4
Mtr
Base Unit
3
2
NOTE: Steam, Hot Water & Plenum
on top of positions 1,2,3,4
FAS - U.S.
FAS
UNIT SIZE
FAS072
FAS091
FAS120
FAS
072, 091, 120
FAS150
FAS180
FAS150, 180
UNIT OR ACCESSORY
NAME
FAN COIL BASE UNIT
FAN COIL BASE UNIT
FAN COIL BASE UNIT
STEAM COIL
HOT WATER COIL
PLENUM
ECONOMIZER
ECO + STEAM COIL
ECO + HW COIL
FAN COIL BASE UNIT
FAN COIL BASE UNIT
STEAM COIL
HOT WATER COIL
PLENUM
ECONOMIZER
ECO + STEAM COIL
ECO + HW COIL
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
UNIT OR
ACCESSORY
WEIGHT
(lb)
399
404
425
215
195
175
195
410
390
695
713
340
285
225
340
680
625
2
114.9
116.3
122.3
54.1
49.4
36.7
0.0
53.4
52.3
210.5
216.0
85.4
70.9
40.0
0.0
89.1
82.5
3
98.0
99.1
108.0
53.4
48.1
36.7
0.0
52.6
50.9
153.8
157.8
84.6
71.6
40.0
0.0
88.7
83.3
4
85.8
86.9
87.1
53.4
48.1
50.8
37.1
91.1
86.5
139.5
143.1
84.6
71.6
72.5
62.0
147.7
136.7
0.0
0.0
0.0
59.9
61.0
56.7
0.0
0.0
0.0
109.5
104.5
94.7
0.0
0.0
0.0
58.3
59.1
54.9
0.0
0.0
0.0
102.0
97.0
87.9
FAS - SI
FAS
UNIT SIZE
FAS072
FAS091
FAS120
FAS
072, 091, 120
FAS150
FAS180
FAS150, 180
UNIT OR ACCESSORY
NAME
FAN COIL BASE UNIT
FAN COIL BASE UNIT
FAN COIL BASE UNIT
STEAM COIL
HOT WATER COIL
PLENUM
ECONOMIZER
ECO + STEAM COIL
ECO + HW COIL
FAN COIL BASE UNIT
FAN COIL BASE UNIT
STEAM COIL
HOT WATER COIL
PLENUM
ECONOMIZER
ECO + STEAM COIL
ECO + HW COIL
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
UNIT OR
ACCESSORY
WEIGHT
(kg)
181
183
193
98
89
80
84
182
173
315
323
155
130
102
155
310
285
2
52.3
52.7
55.6
24.6
22.4
16.8
0.0
23.6
23.1
95.5
97.9
39.0
32.4
18.1
0.0
40.7
37.6
3
44.4
44.9
47.4
24.4
22.1
16.8
0.0
23.3
22.5
69.8
71.6
38.5
32.6
18.1
0.0
40.4
37.8
4
38.8
39.4
41.5
24.4
22.1
23.3
16.2
40.3
38.2
63.3
64.9
38.5
32.6
32.9
28.5
67.3
62.2
0.0
0.0
0.0
25.8
27.0
25.0
0.0
0.0
0.0
49.7
47.6
43.1
0.0
0.0
0.0
25.2
26.5
24.9
0.0
0.0
0.0
45.7
44.2
40.5
LEGEND:
ECO - Economizer
HW - Hot Water
14
508 41 1602 01
Dimensions (cont.)
Preferred Suspension Technique Overhead Suspension Accessory
UNIT SIZES FAS072120
(FRONT)
508 41 1602 01
15
Dimensions (cont.)
16
508 41 1602 01
Dimensions (cont.)
508 41 1602 01
17
Dimensions (cont.)
Dimension
A
B
C
D
E
F
G
Steam Coil
11/2 MPT [38.1]
21/2 MPT [63.5]
31/8 [79.4]
31/8 [79.4]
49/16 [115.8]
1 9 [584.2]
3 4 [1016.0]
18
Dimension
A
B
C
D
E
F
G
Steam Coil
11/2 MPT [38.1]
21/2 MPT [63.5]
31/8 [79.4]
31/8 [79.4]
49/16 [115.8]
1 9
[584.2]
6 8
[2032.0]
508 41 1602 01
Dimensions (cont.)
508 41 1602 01
Dimension
A
B
C
D
E
F
G
Steam Coil
11/2 MPT [38.1]
21/2 MPT [63.5]
31/8 [79.4]
31/8 [79.4]
49/16 [115.8]
1 9
[584.2]
7 6 [2286.0]
19
Dimensions (cont.)
ECONOMIZER ACCESSORY
UNIT SIZES 072 120
NOTE:
1. For horizontal unit applications, economizer can be attached to end of unit opposite duct connections.
2. Dimensions in [ ] are millimeters.
20
508 41 1602 01
Dimensions (cont.)
1 NOM DIA.
7/8 DIA
117/8
1 0
163/4
(301.6)
(304.8)
HEATER ELEMENTS
(REF ONLY)
1 4
(406.4)
211/4
105/8
CONTROL BOX
(269.9)
811/16
(220.7)
25/16
218/16
(58.7)
(636.5)
1 NOM DIA.
7/8 DIA
1 0
F
D
E
C
A
Unit Size
150-240
300
A
1'31/4
[387.4]
1'33/8
[390.5]
508 41 1602 01
B
4'63/8
[1381.1]
5'47/8
[1636.8]
C
25/16
[58.7]
21/16
[26.9]
D
2'11/4
[641.4]
2'63/16
[766.8]
E
105/8
[269.9]
1'1/4
[311.2]
F
1'4
[406.4]
1'7
[482.6]
G
1'45/16
[414.3]
1'45/16
[414.3]
H
1'63/4
[476.3]
1'10
[558.8]
J
17/8
[327.0]
147/16
[417.1]
21
Fan
I.
I.
= 0.80 + 0.23
= 1.03 in. wg
II.
Next, find the type of drive that satisfies the 864 rpm requirement in the Drive Data tables. For a FAS180 unit,
the Medium-Static Drive table shows an rpm range of
742 to 943. Since the rpm required is 864, the medium-static drive satisfies the requirement and should be
used. Select the standard motor and medium-static drive
combination (option code A Standard or B High Static).
To select an outdoor unit for this FAS180 indoor section,
refer to the Combination Rating sheets for CAS condensing units in the condensing unit Specification
22
508 41 1602 01
PERFORMANCE DATA
FAS COOLING CAPACITIES - ENGLISH
UNIT
FAS
072
091
120
150
180
EVAPORATOR
AIR
Airflow
Ewb
(Cfm)
(_F)
BF
72
1,800
67
.06
62
72
2,400
67
.10
62
72
3,000
67
.12
62
72
2,250
67
.06
62
72
3,000
67
.10
62
72
3,750
67
.12
62
72
3,000
67
.05
62
72
4,000
67
.07
62
72
5,000
67
.12
62
72
3,750
67
.06
62
72
5,000
67
.08
62
72
6,250
67
.10
62
72
4,500
67
.03
62
72
6,000
67
.05
62
72
7,500
67
.08
62
35
45
50
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
124
104
86
143
121
101
158
134
113
155
130
108
179
151
126
197
168
141
200
168
140
228
194
162
250
214
179
251
210
174
289
244
203
319
271
226
310
260
215
361
304
254
401
340
285
60
64
68
69
76
83
77
86
95
75
80
85
86
95
103
96
108
119
96
104
112
111
124
135
123
140
155
121
129
138
139
154
167
155
174
192
150
160
169
175
191
206
196
218
239
113
93
75
131
108
88
144
121
98
141
116
94
164
136
110
180
151
122
182
150
121
208
174
141
228
192
156
228
187
150
263
218
176
290
242
196
281
231
186
329
271
220
366
304
247
55
59
62
64
70
76
71
80
88
68
73
78
80
88
95
89
100
110
88
96
102
102
114
124
114
130
143
110
118
126
128
141
153
143
161
177
136
145
154
161
175
189
181
201
220
101
81
63
117
94
73
129
105
82
126
101
78
146
118
92
161
131
103
161
130
101
185
150
119
204
166
133
202
161
125
233
188
146
258
209
164
249
199
154
292
235
183
325
263
206
49
53
56
58
64
69
65
73
80
61
66
70
72
80
86
82
92
100
79
86
92
93
104
113
105
119
130
99
106
113
116
128
138
131
147
160
122
131
138
145
159
170
164
183
197
87
67
49
101
78
60
111
87
70
108
83
62
126
98
76
139
109
87
138
107
82
159
124
99
175
138
113
173
133
100
200
155
121
221
172
139
214
165
121
250
194
149
280
218
172
43
47
49
52
57
60
58
66
70
54
59
62
64
71
76
73
82
87
70
76
82
83
93
99
94
107
113
87
94
100
103
114
121
116
132
139
108
116
121
128
141
149
146
164
172
71
52
42
83
60
51
92
67
59
89
64
52
103
75
64
115
84
74
113
83
69
130
96
84
143
106
96
140
102
84
162
119
102
180
133
118
174
127
102
205
149
125
229
167
145
37
40
42
44
50
51
51
58
59
46
51
52
56
62
64
63
72
74
60
66
69
71
81
84
81
94
96
74
81
84
88
99
102
101
115
118
92
100
102
110
122
125
127
143
145
LEGEND
BF
Bypass Factor
db
Dry-Bulb Temp (_F)
Ewb
Entering Wet-Bulb Temp (_F)
lwb
Leaving Wet-Bulb Temp (_F)
SHC
Sensible Heat Capacity (1000 Btuh)
TC
Total Capacity (1000 Btuh)
NOTES:
1. Ratings based on approximately 15_F superheat leaving coil.
2. Direct interpolation is permissible. Do not extrapolate.
3. Dashes indicate coil loading limits are exceeded.
4. Evaporator fan heat not deducted from ratings.
508 41 1602 01
40
5. Formulas:
sensible heat capacity (Btuh)
1.1 x cfm
wet-bulb temperature corresponding to enthalpy
Leaving db =
of air leaving coil (hlwb)
total capacity (Btuh)
hlwb = hewb
4.5 x cfm
where hlwb = enthalpy of air entering coil
Leaving db =
entering db
23
UNIT
FAS
240
300
EVAPORATOR
AIR
Airflow
Ewb
(Cfm)
(_F)
BF
72
6,000
67
.03
62
72
8,000
67
.06
62
72
10,000
67
.07
62
72
7,500
67
.04
62
72
10,000
67
.06
62
72
12,500
67
.08
62
35
45
50
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
408
344
286
470
399
333
516
440
369
470
395
329
535
454
380
583
499
420
197
213
227
228
253
275
253
287
317
226
246
265
260
291
320
287
329
367
372
307
248
429
357
290
471
395
322
428
354
287
487
407
332
531
448
367
180
195
208
210
233
254
235
266
294
208
227
244
240
269
296
267
306
341
331
266
207
382
309
242
421
343
271
379
307
240
434
354
279
475
390
310
162
176
188
191
212
230
215
244
266
187
205
221
219
246
268
245
282
310
272
220
164
329
256
202
363
284
232
328
255
193
376
295
235
412
325
269
141
156
164
170
189
202
192
219
232
167
183
193
196
221
235
221
255
269
232
169
139
269
197
170
297
220
196
270
197
163
310
228
199
341
252
228
123
135
139
147
166
170
168
193
196
144
159
163
171
194
199
194
225
228
LEGEND
BF
Bypass Factor
db
Dry-Bulb Temp (_F)
Ewb
Entering Wet-Bulb Temp (_F)
lwb
Leaving Wet-Bulb Temp (_F)
SHC
Sensible Heat Capacity (1000 Btuh)
TC
Total Capacity (1000 Btuh)
NOTES:
1. Ratings based on approximately 15_F superheat leaving coil.
2. Direct interpolation is permissible. Do not extrapolate.
3. Dashes indicate coil loading limits are exceeded.
4. Evaporator fan heat not deducted from ratings.
24
40
5. Formulas:
sensible heat capacity (Btuh)
1.1 x cfm
wet-bulb temperature corresponding to enthalpy
Leaving db =
of air leaving coil (hlwb)
total capacity (Btuh)
hlwb = hewb
4.5 x cfm
where hlwb = enthalpy of air entering coil
Leaving db =
entering db
508 41 1602 01
UNIT
FAS
072
091
120
150
180
EVAPORATOR
AIR
Airflow
Ewb
(L/s)
(_C)
BF
22
850
19
.06
17
22
1130
19
.10
17
22
1420
19
.12
17
22
1060
19
.06
17
22
1420
19
.10
17
22
1770
19
.12
17
22
1420
19
.05
17
22
1890
19
.07
17
22
2360
19
.12
17
22
1770
19
.06
17
22
2360
19
.08
17
22
2980
19
.10
17
22
2120
19
.03
17
22
2830
19
.05
17
22
3540
19
.08
17
2
SHC
17
19
20
20
22
24
23
25
28
22
23
25
25
28
30
28
32
35
28
31
33
33
36
40
36
41
45
35
38
40
41
45
49
45
51
56
44
47
50
51
56
60
57
64
70
LEGEND
BF
Bypass Factor
db
Dry-Bulb Temp (_F)
Ewb
Entering Wet-Bulb Temp (_F)
lwb
Leaving Wet-Bulb Temp (_F)
SHC
Sensible Heat Capacity (1000 Btuh)
TC
Total Capacity (1000 Btuh)
NOTES:
1. Ratings based on approximately 15_F superheat leaving coil.
2. Direct interpolation is permissible. Do not extrapolate.
3. Dashes indicate coil loading limits are exceeded.
4. Evaporator fan heat not deducted from ratings.
508 41 1602 01
TC
33
27
22
38
32
26
42
35
29
41
34
27
48
40
32
53
44
36
53
44
35
61
51
41
67
56
46
67
55
44
77
64
52
85
71
57
82
68
55
96
79
65
107
89
72
4
SHC
16
17
18
19
21
22
21
24
26
20
21
23
23
26
28
26
29
32
26
28
30
30
33
36
33
38
42
32
35
37
38
41
45
42
47
52
40
43
45
47
51
55
53
59
65
TC
29
24
18
34
28
22
38
31
24
37
30
23
43
35
27
47
38
30
47
38
30
54
44
35
60
49
39
59
47
37
68
55
43
76
61
48
73
58
45
86
69
54
95
77
60
7
SHC
14
16
16
17
19
20
19
21
23
18
19
21
21
23
25
24
27
29
23
25
27
27
30
33
31
35
38
29
31
33
34
38
40
38
43
47
36
38
41
43
46
50
48
54
58
TC
25
20
14
30
23
18
33
25
20
32
24
18
37
29
22
41
32
26
41
31
24
47
36
29
51
40
33
51
39
29
59
45
35
65
50
41
63
48
36
73
57
44
82
64
50
10
SHC
13
14
14
15
17
18
17
19
20
16
17
18
19
21
22
21
24
26
21
22
24
24
27
29
27
31
33
26
28
29
30
33
35
34
39
41
32
34
36
37
41
44
43
48
50
TC
21
15
12
24
18
15
27
20
17
26
19
15
30
22
19
34
25
22
33
24
20
38
28
25
42
31
28
41
30
25
47
35
30
53
39
34
51
37
30
60
44
37
67
49
42
SHC
11
12
12
13
15
15
15
17
17
14
15
15
16
18
19
19
21
22
18
19
20
21
24
25
24
28
28
22
24
25
26
29
30
29
34
34
27
29
30
32
36
37
37
42
42
5. Formulas:
sensible heat capacity (Btuh)
1.1 x cfm
wet-bulb temperature corresponding to enthalpy
Leaving db =
of air leaving coil (hlwb)
total capacity (Btuh)
hlwb = hewb
4.5 x cfm
where hlwb = enthalpy of air entering coil
Leaving db =
entering db
25
UNIT
FAS
240
300
EVAPORATOR
AIR
Airflow
Ewb
(L/s)
(_C)
BF
22
2830
19
.03
17
22
3780
19
.06
17
22
4720
19
.07
17
22
3540
19
.04
17
22
4720
19
.06
17
22
5900
19
.08
17
2
SHC
58
62
67
67
74
81
74
84
93
66
72
78
76
85
94
84
96
107
LEGEND
BF
Bypass Factor
db
Dry-Bulb Temp (_F)
Ewb
Entering Wet-Bulb Temp (_F)
lwb
Leaving Wet-Bulb Temp (_F)
SHC
Sensible Heat Capacity (1000 Btuh)
TC
Total Capacity (1000 Btuh)
NOTES:
1. Ratings based on approximately 15_F superheat leaving coil.
2. Direct interpolation is permissible. Do not extrapolate.
3. Dashes indicate coil loading limits are exceeded.
4. Evaporator fan heat not deducted from ratings.
26
TC
109
90
73
126
105
85
138
116
94
125
104
84
143
119
97
156
131
107
4
SHC
53
57
61
62
68
74
69
78
86
61
66
72
70
79
87
78
90
100
TC
97
78
61
112
91
71
123
100
79
111
90
70
127
104
82
139
114
91
7
SHC
48
52
55
56
62
67
63
71
78
55
60
65
64
72
79
72
83
91
TC
80
64
48
96
75
59
106
83
68
96
75
57
110
86
69
121
95
79
10
SHC
41
46
48
50
56
59
56
64
68
49
54
57
57
65
69
65
75
79
TC
68
50
41
79
58
50
87
64
58
79
58
48
91
67
58
100
74
67
SHC
36
40
41
43
49
50
49
57
58
42
47
48
50
57
58
57
66
67
5. Formulas:
sensible heat capacity (Btuh)
1.1 x cfm
wet-bulb temperature corresponding to enthalpy
Leaving db =
of air leaving coil (hlwb)
total capacity (Btuh)
hlwb = hewb
4.5 x cfm
where hlwb = enthalpy of air entering coil
Leaving db =
entering db
508 41 1602 01
UNIT
FAS
072
FAS
091
FAS
120
FAS
150
FAS
180
FAS
240
FAS
300
Cap.
146
173
209
168
209
240
209
243
279
370
425
465
402
458
479
458
487
499
511
575
626
Ldb
134
126
123
129
123
117
123
115
111
150
137
128
141
129
118
129
115
105
122
112
106
2ROW
HOT WATER COIL
Water
Flow
Cap. Ldb (Gpm)
156.0 140
15.6
183.0 131
18.3
206.0 124
20.6
174.0 133
17.4
206.0 124
20.6
238.0 118
23.8
299.0 152
29.9
275.0 124
27.5
316.0 119
31.6
362.0 149
36.2
409.0 136
40.9
456.0 128
45.6
412.0 145
41.2
471.0 133
47.1
529.0 125
52.9
506.0 138
50.6
584.0 128
58.4
652.0 120
65.2
649.0 140
64.9
752.0 130
75.2
842.0 122
84.2
PD
3.4
4.3
5.2
4.0
5.2
6.5
5.0
6.6
8.2
4.2
5.1
6.0
4.5
5.5
6.6
5.1
6.3
7.5
5.7
7.1
8.5
LEGEND:
Cap. - Capacity (Btuh in thousands)
Ldb - Leaving Air Dry Bulb Temp (_F)
PD . - Pressure Drop (ft water)
* Based on 5 psig steam, 60F enteringair temperature. All steam coils
are nonfreeze type.
Based on 200F entering water, 20F water temperature drop, 60F en
teringair temperature.
AIRFLOW
(L/s)
850
1150
1450
1000
1400
1800
1450
1900
2350
1750
2350
2950
2100
2800
3500
2900
3800
4700
3500
4700
5900
UNIT
FAS
072
FAS
091
FAS
120
FAS
150
FAS
180
FAS
240
FAS
300
Cap.
43
53
62
48
59
71
62
72
82
108
122
136
117
129
140
135
140
146
149
166
183
Ldb
57
53
51
55
50
47
50
46
44
66
58
53
61
53
48
53
46
41
50
44
41
2ROW
HOT WATER COIL
Water
Flow
Cap. Ldb
PD
(L/s)
46
59
1.0
10.2
53
53
1.2
12.8
61
50
1.3
16.0
50
56
1.1
11.5
60
50
1.3
15.3
70
47
1.5
19.5
88
65
1.9
15.0
90
54
2.0
24.7
93
48
2.0
24.5
106
65
2.3
12.4
120
57
2.6
15.2
134
52
2.9
17.9
120
62
2.6
13.3
137
55
3.0
16.2
154
51
3.3
19.5
150
58
3.3
15.6
170
52
3.7
18.6
191
49
4.1
22.3
189
60
4.1
16.9
218
53
4.7
20.8
247
50
5.4
25.4
NOTES:
LEGEND:
Cap. - Capacity (Btuh in thousands)
Ldb - Leaving Air Dry Bulb Temp (_C)
PD . - Pressure Drop (ft water)
* Based on 34.5 kPag steam, 15.6C enteringair temperature. All steam
coils are nonfreeze type.
Based on 93.3C entering water temperature, 11.1C water temperature
drop, 15.6C enteringair temperature.
NOTES:
1.
1.
2.
3.
2.
3.
10
20
30
Steam Pressure
(psig)
0
2
5
STEAM COIL
EnteringAir Temp (_F)
40
50
60
70
1.06
0.98
0.91
0.85
1.09
1.02
0.95
0.89
1.13
1.06
1.00
0.93
80
0.41
0.58
0.75
0.92
1.09
0.33
0.51
0.68
0.85
1.02
0.24
0.43
0.60
0.78
0.95
80
0.78
0.82
0.87
508 41 1602 01
Water Temp
Drop (_C)
11
16
Steam Pressure
(kPag)
0
14
35
STEAM COIL
EnteringAir Temp (_C)
4
10
16
20
1.07
0.99
0.91
0.86
1.10
1.02
0.95
0.90
1.14
1.07
0.99
0.95
25
0.43
0.58
0.73
0.89
1.04
0.35
0.51
0.66
0.82
0.97
0.26
0.42
0.58
0.74
0.90
25
0.80
0.84
0.89
27
UNIT
FAS
072
091
120
150
180
240
300
AIRFLOW
(Cfm)
1,800
2,100
2,400
2,700
3,000
2,250
2,600
3,000
3,400
3,750
3,000
3,500
4,000
4,500
5,000
3,750
4,300
5,000
5,700
6,250
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
0.0
Rpm Bhp
419 0.21
471 0.31
524 0.44
578 0.61
633 0.81
290 0.10
349 0.19
579 0.70
646 0.99
705 1.31
421 0.35
626 0.98
706 1.42
786 1.99
867 2.70
410 0.43
455 0.62
514 0.92
575 1.32
624 1.71
437 0.61
499 0.95
555 1.34
620 1.91
677 2.52
542 1.29
620 1.99
700 2.92
781 4.10
862 5.56
476 1.39
545 2.14
615 3.12
685 4.37
756 5.92
0.2
Rpm Bhp
471 0.26
519 0.37
568 0.51
619 0.69
671 0.90
510 0.39
561 0.55
621 0.79
683 1.09
739 1.42
592 0.73
664 1.08
738 1.54
815 2.12
893 2.84
467 0.55
504 0.74
556 1.06
612 1.47
657 1.87
483 0.72
538 1.07
590 1.48
651 2.06
706 2.69
577 1.42
652 2.15
728 3.10
806 4.30
885 5.79
510 1.58
574 2.35
641 3.36
709 4.64
778 6.22
Rpm
797
819
844
875
910
806
834
874
920
964
854
908
967
1028
1092
788
811
847
884
915
797
830
860
896
929
849
890
938
993
1054
752
797
843
891
942
1.0
Bhp
0.77
0.92
1.11
1.33
1.60
0.95
1.16
1.47
1.86
2.26
1.41
1.87
2.45
3.16
4.00
1.72
2.04
2.52
3.09
3.59
2.03
2.53
3.04
3.71
4.39
2.95
3.76
4.78
6.08
7.69
3.29
4.25
5.51
7.02
8.83
Rpm
862
882
905
932
963
870
893
928
970
1011
908
958
1014
1073
1135
851
871
903
939
969
856
888
918
952
984
907
947
990
1039
1096
804
842
888
935
983
1.2
Bhp
0.92
1.09
1.28
1.51
1.79
1.12
1.34
1.66
2.06
2.48
1.59
2.07
2.67
3.41
4.28
2.05
2.39
2.91
3.52
4.06
2.38
2.94
3.49
4.21
4.93
3.40
4.27
5.32
6.62
8.24
3.96
4.76
6.05
7.64
9.52
LEGEND
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure
Bold indicates field-supplied drive or motor is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than the standard motor and standard drive combination is required. Refer to fan
motor and drive tables to complete selection.
NOTES:
Maximum allowable fan speed is 1100 rpm for unit sizes 028 and 030; 1200 rpm for all other sizes. Fan performance is based on deductions for wet
coil, clean 2-in. filters, and unit casing. See table below for factory-supplied filter pressure drop. For 60 Hz units, the medium-static drive and
standard motor combination is not available for 028 size.
28
508 41 1602 01
UNIT
FAS
072
091
120
150
180
240
300
AIRFLOW
(Cfm)
1,800
2,100
2,400
2,700
3,000
2,250
2,600
3,000
3,400
3,750
3,000
3,500
4,000
4,500
5,000
3,750
4,300
5,000
5,700
6,250
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
1.4
Rpm
921
942
963
987
1015
930
950
980
1018
1057
961
1005
1058
1116
1176
912
928
956
990
1019
912
942
971
1005
1036
961
1000
1041
1086
1138
874
886
930
976
1023
Bhp
1.07
1.26
1.47
1.71
1.99
1.29
1.53
1.86
2.26
2.69
1.78
2.27
2.90
3.66
4.56
2.39
2.75
3.30
3.96
4.54
2.75
3.34
3.95
4.72
5.48
3.86
4.79
5.88
7.21
8.83
5.33
5.36
6.60
8.25
10.20
2.76
1028
3.14
1083
3.54
3.13
1036
3.53
1087
3.94
3.71
1056
4.13
1104
4.56
4.40
1086
4.85
1130
5.31
5.02
1112
5.50
1156
5.99
3.12
1019
3.52
1070
3.92
3.76
1041
4.18
1088
4.61
4.40
1067
4.86
1112
5.33
5.23
1101
5.75
1145
6.27
6.04
1131
6.61
1174
7.17
4.31
1058
4.77
1104
5.24
5.32
1097
5.85
1142
6.38
6.47
1137
7.07
1181
7.67
7.82
1178
8.47
9.46
5.91
940
6.80
990
7.50
6.13
982
7.32
1020
8.10
7.20
1007
7.89
1045
8.71
8.86
1051
9.49
1086
10.17
10.88
1097
11.56
1.6
Rpm
975
997
1017
1039
1065
986
1005
1031
1065
1101
1012
1052
1101
1157
971
982
1007
1039
1067
967
992
1020
1054
1084
1011
1050
1090
1133
1180
897
930
969
1014
1061
2.2
Rpm
Bhp
1120 1.72
1143 1.97
1164 2.25
1185 2.55
1136
2.03
1154
2.33
1175
2.72
1158
2.64
1186
3.18
1135 3.95
1138 4.37
1151 5.00
1174 5.78
1198 6.49
1120
4.35
1134
5.06
1156
5.81
1187 6.79
1147
5.71
1184
6.91
2.4
Rpm
Bhp
1164 1.90
1186 2.16
1181
2.22
1185 4.36
1187 4.81
1196 5.46
1168
4.79
1179 5.52
1198 6.29
LEGEND
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure
Bold indicates field-supplied drive or motor is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than the standard motor and standard drive combination is required. Refer to fan
motor and drive tables to complete selection.
NOTES:
Maximum allowable fan speed is 1100 rpm for unit sizes 028 and 030; 1200 rpm for all other sizes. Fan performance is based on deductions for wet
coil, clean 2-in. filters, and unit casing. See table below for factory-supplied filter pressure drop. For 60 Hz units, the medium-static drive and
standard motor combination is not available for 028 size.
508 41 1602 01
29
UNIT
FAS)
072
091
120
150
180
240
300
AIRFLOW
(L/s)
850
990
1130
1270
1420
1060
1230
1420
1600
1770
1420
1650
1890
2120
2360
1770
2030
2360
2690
2950
2120
2500
2830
3210
3540
2830
3300
3780
4250
4720
3540
4130
4720
5310
5900
0
r/s
6.98
7.84
8.73
9.63
10.55
4.83
5.81
9.65
10.76
11.74
7.02
10.44
11.76
13.10
14.45
6.84
7.58
8.57
9.59
10.40
7.28
8.32
9.25
10.33
11.29
9.03
10.34
11.67
13.01
14.36
7.94
9.08
10.24
11.42
12.60
50
kW
0.16
0.23
0.33
0.45
0.61
0.07
0.14
0.52
0.74
0.97
0.26
0.73
1.06
1.48
2.01
0.32
0.46
0.69
0.99
1.28
0.45
0.71
1.00
1.42
1.88
0.96
1.48
2.17
3.05
4.15
1.04
1.59
2.33
3.26
4.42
r/s
7.86
8.64
9.46
10.31
11.18
8.50
9.35
10.35
11.39
12.32
9.86
11.06
12.31
13.59
14.89
7.78
8.40
9.27
10.20
10.96
8.05
8.97
9.83
10.85
11.77
9.62
10.86
12.14
13.44
14.75
8.51
9.57
10.68
11.81
12.96
kW
0.19
0.27
0.38
0.51
0.67
0.29
0.41
0.59
0.81
1.06
0.54
0.80
1.15
1.58
2.12
0.41
0.55
0.79
1.10
1.39
0.54
0.80
1.10
1.54
2.01
1.06
1.60
2.31
3.21
4.32
1.18
1.75
2.51
3.46
4.64
250
r/s
kW
13.29 0.57
13.65 0.69
14.07 0.83
14.58 0.99
15.17 1.19
13.44 0.71
13.90 0.87
14.57 1.10
15.34 1.39
16.07 1.69
14.23 1.05
15.13 1.39
16.11 1.83
17.14 2.35
18.20 2.98
13.13 1.28
13.52 1.52
14.11 1.88
14.74 2.30
15.25 2.68
13.28 1.51
13.84 1.89
14.34 2.27
14.93 2.76
15.49 3.27
14.15 2.20
14.84 2.80
15.63 3.56
16.54 4.53
17.56 5.73
12.53 2.46
13.28 3.17
14.05 4.11
14.85 5.24
15.70 6.58
300
r/s
kW
14.36 0.69
14.71 0.81
15.08 0.96
15.53 1.13
16.05 1.33
14.50 0.83
14.89 1.00
15.47 1.24
16.17 1.53
16.86 1.85
15.14 1.19
15.96 1.54
16.89 1.99
17.89 2.54
18.92 3.19
14.19 1.53
14.51 1.78
15.05 2.17
15.65 2.63
16.15 3.03
14.27 1.78
14.80 2.19
15.30 2.60
15.87 3.14
16.40 3.67
15.12 2.54
15.78 3.18
16.50 3.96
17.32 4.94
18.26 6.14
13.40 2.95
14.04 3.55
14.80 4.51
15.58 5.70
16.38 7.10
LEGEND
ESP External Static Pressure
Bold indicates field-supplied drive or motor is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than the standard motor and standard drive combination is required. Refer to fan
motor and drive tables to complete selection.
NOTES:
Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and 030; 20 r/s for all other sizes. Fan performance is based on deductions for wet coil,
clean 51-mm filters, and unit casing. See table below for factory-supplied filter pressure drop. For 60 Hz units, the medium-static drive and
standard motor combination is not available for 028 size.
30
508 41 1602 01
UNIT
FAS
072
091
120
150
180
240
300
AIRFLOW
(L/s)
850
990
1130
1270
1420
1060
1230
1420
1600
1770
1420
1650
1890
2120
2360
1770
2030
2360
2690
2950
2120
2500
2830
3210
3540
2830
3300
3780
4250
4720
3540
4130
4720
5310
5900
350
r/s
15.34
15.69
16.04
16.44
16.91
15.50
15.84
16.34
16.97
17.61
16.02
16.76
17.64
18.60
19.61
15.21
15.46
15.94
16.51
16.99
15.21
15.69
16.18
16.75
17.26
16.01
16.67
17.35
18.11
18.96
14.57
14.76
15.49
16.26
17.04
kW
0.80
0.94
1.09
1.27
1.49
0.96
1.14
1.38
1.69
2.01
1.33
1.70
2.16
2.73
3.40
1.78
2.05
2.46
2.95
3.39
2.05
2.49
2.94
3.52
4.09
2.88
3.57
4.39
5.37
6.58
3.97
3.99
4.92
6.15
7.61
400
r/s
16.25
16.61
16.95
17.32
17.75
16.43
16.75
17.19
17.76
18.35
16.87
17.53
18.35
19.28
16.19
16.37
16.78
17.32
17.78
16.11
16.54
17.01
17.57
18.07
16.85
17.50
18.17
18.88
19.67
14.95
15.51
16.15
16.91
17.68
2.06
17.13
2.34
18.04
2.64
2.33
17.26
2.63
18.12
2.94
2.77
17.60
3.08
18.40 3.40
3.28
18.09
3.62
18.84 3.96
3.74
18.54 4.10 19.26 4.47
2.33
16.98
2.62
17.83
2.93
2.80
17.35
3.12
18.14
3.44
3.28
17.79
3.63
18.54
3.97
3.90
18.34
4.29
19.08
4.67
4.50
18.84
4.93
19.57 5.35
3.22
17.64
3.56
18.39
3.91
3.96
18.28
4.36
19.03
4.75
4.82
18.95
5.27
19.68
5.72
5.83
19.63
6.31
7.05
4.41
15.67
5.07
16.50
5.59
4.57
16.36
5.46
17.00
6.04
5.37
16.78
5.88
17.42
6.50
6.61
17.51
7.08
18.10 7.58
8.11
18.28 8.62
550
r/s
kW
18.66 1.28
19.04 1.47
19.40 1.67
19.75 1.90
18.93
1.51
19.24
1.74
19.59
2.03
19.30
1.97
19.77
2.37
18.91 2.94
18.96 3.26
19.18 3.73
19.57 4.31
19.96 4.84
18.66
3.24
18.90
3.77
19.27
4.33
19.78 5.06
19.12
4.26
19.73
5.15
600
r/s
kW
19.39 1.41
19.77 1.61
19.68
1.66
19.75 3.25
19.78 3.59
19.94 4.07
19.47
3.57
19.64 4.11
19.97 4.69
LEGEND
ESP External Static Pressure
Bold indicates field-supplied drive or motor is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than the standard motor and standard drive combination is required. Refer to fan
motor and drive tables to complete selection.
NOTES:
Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and 030; 20 r/s for all other sizes. Fan performance is based on deductions for wet coil,
clean 51-mm filters, and unit casing. See table below for factory-supplied filter pressure drop. For 60 Hz units, the medium-static drive and
standard motor combination is not available for 028 size.
508 41 1602 01
31
SIZE
072
091
120
150
180
FAS
CFM
2,400
3,000
4,000
5,000
6,000
dB(A)
86.3
88.3
91.6
91.1
92.7
63
93.2
95.3
98.6
97.3
98.9
LEGEND:
ASHRAE - American Society of Heating, Refrigerating and Air
Conditioning, Inc.
HVAC
- Heating, Ventilation and Air Conditioning
125
89.2
91.3
94.6
93.3
94.9
UNIT
072
FAS
091
FAS
120
FAS
150
FAS
180
FAS
240
FAS
300
FAS
32
AIRFLOW
(Cfm)
1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
PRESSURE DROP
(in. wg)
0.05
0.08
0.11
0.07
0.11
0.15
0.11
0.17
0.23
0.06
0.10
0.13
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
4000
74.2
76.3
79.6
78.3
79.9
NOTES:
1. The above estimated sound power levels are based upon the
ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be
different than the actual sound power levels.
3. The acoustic center of the unit is located at the geometric center of
the unit.
2000
78.2
80.3
83.6
82.3
83.9
UNIT
072
FAS
091
FAS
120
FAS
150
FAS
180
FAS
240
FAS
300
FAS
AIRFLOW
(L/s)
850
1150
1450
1000
1400
1800
1450
1900
2350
1750
2350
2950
2100
2800
3500
2900
3800
4700
3500
4700
5900
PRESSURE DROP
(Pa)
13
20
28
17
27
38
28
42
56
15
24
33
20
30
42
32
47
64
36
55
76
508 41 1602 01
AIRFLOW
(Cfm)
2,400
3,000
4,000
5,000
6,000
8,000
10,000
VANE DEFLECTION
Straight
21:5
455
39
33
24
45
38
28
55
46
33
45
38
28
50
43
31
60
51
37
76
65
47
NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the
following multipliers to determine throw values for other terminal velo
cities.
TERMINAL VELOCITY
(Fpm)
50
100
150
508 41 1602 01
THROW FACTOR
X 1.50
X 0.75
X 0.50
AIRFLOW
(L/s)
1150
1400
1900
2350
2800
3800
4700
VANE DEFLECTION
Straight
21:5
455
11.71
9.91
7.20
13.87
11.71
8.63
16.65
13.93
9.99
13.77
11.63
8.57
15.41
13.25
9.55
18.17
15.44
11.20
23.26
19.89
14.38
NOTE: Throw distances shown are for 0.381 m/sec terminal velocity.
Use the following multipliers to determine throw values for other termin
al velocities.
TERMINAL VELOCITY
(m/sec)
0.254
0.508
0.762
THROW FACTOR
X 1.50
X 0.75
X 0.50
33
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
AIRFLOW
(Cfm)
1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
DISCHARGE
PLENUM
0.06
0.10
0.14
0.09
0.14
0.21
0.14
0.22
0.32
0.07
0.12
0.17
0.10
0.16
0.23
0.16
0.26
0.37
0.15
0.24
0.34
AIRFLOW
(L/s)
850
1150
1450
1000
1400
1800
1450
1900
2350
1750
2350
2950
2100
2800
3500
2900
3800
4700
3500
4700
5900
DISCHARGE
PLENUM
15
25
36
20
34
51
36
56
79
18
29
43
24
39
56
41
64
91
37
59
86
RETURN AIR
GRILLE
0.01
0.01
0.02
0.01
0.02
0.03
0.02
0.04
0.06
0.01
0.02
0.02
0.01
0.02
0.03
0.02
0.04
0.06
0.02
0.03
0.05
Hot Water
0.10
0.16
0.23
0.15
0.23
0.35
0.23
0.37
0.53
0.11
0.17
0.25
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
Steam
0.10
0.16
0.23
0.15
0.23
0.35
0.23
0.37
0.53
0.11
0.17
0.25
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
Electric
0.04
0.06
0.10
0.06
0.10
0.15
0.10
0.17
0.26
0.04
0.07
0.11
0.06
0.10
0.15
0.10
0.17
0.26
0.09
0.16
0.24
ECONOMIZER
0.05
0.07
0.09
0.06
0.09
0.15
0.09
0.17
0.28
0.05
0.07
0.11
0.06
0.09
0.15
0.09
0.17
0.28
0.06
0.09
0.14
Electric
9
16
26
12
24
39
26
43
65
10
17
26
14
24
37
26
43
65
22
39
60
ECONOMIZER
12
18
23
13
22
39
23
43
69
12
17
27
15
22
37
23
43
69
15
22
35
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
34
RETURN AIR
GRILLE
2
3
5
2
5
8
5
10
15
2
5
5
2
5
7
5
10
15
5
7
12
Hot Water
25
41
60
33
57
85
60
93
132
26
43
62
36
57
82
60
93
132
67
109
157
HEATING COILS
Steam
25
41
60
33
57
85
60
93
132
26
43
62
36
57
82
60
93
132
67
109
157
508 41 1602 01
ELECTRICAL DATA
STANDARD MOTORS
FAN MOTOR
UNIT
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
V*PHHz
208/230160
208/230360
460360
575360
208/230160
208/230360
460360
575360
208/230360
460360
575360
208/230360
460360
575360
208/230360
460360
575360
208/230360
460360
575360
208/230360
460360
575360
VOLTAGE
LIMITS
187253
187253
414506
518632
187253
187253
414506
518632
187253
414506
518632
187253
414506
518632
187253
414506
518632
187253
414506
518632
187253
414506
518632
Hp (kW)
1.3 (0.97)
2.4 (1.79)
2.4 (1.79)
1.0 (0.75)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.4 (1.79)
2.4 (1.79)
3.0 (2.24)
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
LEGEND
FLA
Full Load Amps
MOCP Maximum Overcurrent Protection
* Motors are designed for satisfactory operation within 10% of nomin
al voltages shown. Voltages should not exceed the limits shown in
the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in
accordance with NEC (National Electrical Code) (U.S.A. standard),
Article 440.
2. Motor FLA values are established in accordance with UL
(Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. Indoor fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
4. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the
percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
508 41 1602 01
POWER SUPPLY
Minimum Circuit
Amps
MOCP
9.5
15
7.5
15
3.3
15
1.7
15
13.8
20
6.5
15
3.3
15
3.0
15
7.3
15
3.3
15
3.0
15
7.5
15
3.3
15
4.8
15
13.3
20
6.0
15
4.8
15
18.4/17.0
30/25
8.5
15
6.4
15
26.9/24.3
45/40
12.1
20
9.8
15
FLA
7.6
5.8
2.6
1.4
11.0
5.8
2.6
2.4
5.8
2.6
2.4
5.8
2.6
3.8
10.6
4.8
3.8
14.7/13.6
6.8
5.1
21.5/19.4
9.7
7.8
681
=
227
= 100 x
227
= 1.76%
35
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
V*PHHz
208/230160
208/230360
460360
575360
208/230160
208/230360
460360
575360
208/230360
460360
575360
208/230360
460360
575360
208/230360
460360
575360
208/230360
460360
575360
208/230360
460360
575360
VOLTAGE
LIMITS
187253
187253
414506
518632
187253
187253
414506
518632
187253
414506
518632
187253
414506
518632
187253
414506
518632
187253
414506
518632
187253
414506
518632
Hp (kW)
2.4 (1.79)
2.9 (2.16)
2.9 (2.16)
2.0 (1.49)
2.4 (1.79)
2.9 (2.16)
2.9 (2.16)
3.0 (2.24)
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
3.7 (2.76)
3.7 (2.76)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
LEGEND
FLA
Full Load Amps
MOCP Maximum Overcurrent Protection
* Motors are designed for satisfactory operation within 10% of nomin
al voltages shown. Voltages should not exceed the limits shown in
the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in
accordance with NEC (National Electrical Code) (U.S.A. standard),
Article 440.
2. Motor FLA values are established in accordance with UL
(Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. Indoor fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
4. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the
percentage of voltage imbalance.
% Voltage Imbalance
36
= 100 x
POWER SUPPLY
Minimum Circuit
Amps
MOCP
13.8
20
9.4
15
4.3
15
2.9
15
13.8
15
9.4
15
4.3
15
4.8
15
12.8
20
6.0
15
4.8
15
12.7
20
6.0
15
6.4
15
18.4/17.0
30/25
6.0
15
6.4
15
26.9/24.3
45/40
12.1
20
9.8
15
35.0/31.5
60/60
15.8
30
12.9
20
FLA
11.0
7.5
3.4
2.3
11.0
7.5
3.4
3.8
10.2
4.8
3.8
10.2
4.8
5.1
14.6/13.6
6.8
5.1
21.5/19.4
9.7
7.8
28.2/25.2
12.6
10.3
681
=
227
= 100 x
227
= 1.76%
508 41 1602 01
Unit
FAS
VPHHz
Hp
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
208360
AAHC05AHA
240360
AAHC05ALA
480360
AAHC05ASA
575360
208360
072-120
AAHC10AHA
240360
AAHC10ALA
480360
AAHC10ASA
575360
208360
AAHC15AHA
240360
kW
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
FLA
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
LEGEND
FLA
Hp
MCA
MOCP
Nominal
Capacity
(kW)
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15
ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage
Stage
1
2
Total
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
FLA
10.4
10.4
10.4
10.4
10.4
12.0
12.0
12.0
12.0
12.0
6.00
6.00
6.00
5.00
5.00
5.00
20.8
20.8
20.8
20.8
20.8
24.1
24.1
24.1
24.1
24.1
12.0
12.0
12.0
10.0
10.0
10.0
31.3
31.3
31.3
31.3
31.3
36.1
36.1
36.1
36.1
36.1
MCA*
22.5
26.8
19.5
22.4
25.8
24.5
28.8
21.5
24.4
27.8
10.8
11.8
13.5
8.0
9.2
11.0
35.6
39.8
32.6
35.4
38.8
39.6
43.8
36.6
39.4
42.8
18.3
19.3
21.0
14.3
15.4
17.3
48.6
52.9
45.6
48.5
51.9
54.6
58.9
51.6
54.5
57.9
MOCP*
25
35
20
25
30
25
35
25
25
30
15
15
15
15
15
15
40
40
35
40
40
40
50
40
40
50
20
20
25
15
20
20
50
60
50
50
60
60
60
60
60
60
208
230
240
400
440
460
480
550
575
600
0.915
1.089
480
575
508 41 1602 01
37
Unit
FAS
VPHHz
AAHC15ALA
480360
AAHC15ASA
575360
Hp
2.4
2.9
3.7
1.0
2.0
3.0
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0
2.4
2.4
2.9
3.7
2.4
2.4
2.9
3.7
2.4
2.9
3.7
2.0
3.0
208360
072-120
AAHC25AHA
240360
AAHC25ALA
480360
AAHC25ASA
575360
208360
AAHC35CHA
091, 120
240360
AAHC35CLA
480360
AAHC35CSA
575360
kW
1.79
2.16
2.76
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24
1.79
1.79
2.16
2.76
1.79
1.79
2.16
2.76
1.79
2.16
2.76
1.49
2.24
FLA
2.6
3.4
4.8
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8
11.0
5.2
7.5
10.2
11.0
5.2
7.5
10.2
2.6
3.4
4.8
2.3
3.8
LEGEND
FLA
Hp
MCA
MOCP
FLA
18.0
18.0
18.0
15.1
15.1
15.1
52.1
52.1
52.1
52.1
52.1
60.1
60.1
60.1
60.1
60.1
30.1
30.1
30.1
25.1
25.1
25.1
73.0
73.0
73.0
73.0
84.2
84.2
84.2
84.2
42.1
42.1
42.1
35.1
35.1
MCA*
25.8
26.8
28.6
20.6
21.7
23.6
74.7
78.9
71.7
74.5
77.9
84.7
88.9
81.7
84.6
87.9
40.8
41.8
43.6
33.1
34.3
36.1
105.0
97.7
100.6
104.0
119.0
111.7
114.6
118.0
55.9
56.9
58.6
46.8
48.7
MOCP*
30
30
30
25
25
25
80
80
80
80
80
90
90
90
90
90
50
50
50
35
35
40
110
100
110
110
125
125
125
125
60
60
60
50
50
208
230
240
400
440
460
480
550
575
600
0.915
1.089
480
575
38
Nominal
Capacity
(kW)
15
15
15
15
15
15
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
35
35
35
35
35
35
35
35
35
35
35
35
35
ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage
Stage
1
2
Total
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
11.3
26.3
15.0
11.3
26.3
15.0
11.3
26.3
15.0
11.3
26.3
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
508 41 1602 01
Unit
FAS
VPHHz
Hp
2.9
3.7
5.0
2.9
3.7
5.0
2.9
3.7
5.0
3.0
5.0
2.9
3.7
5.0
2.9
3.7
5.0
2.9
3.7
5.0
3.0
5.0
2.9
3.7
5.0
2.9
3.7
5.0
2.9
3.7
5.0
3.0
5.0
208360
AAHC10BHA
240360
AAHC10BLA
480360
AAHC10BSA
575360
208360
AAHC20BHA
240360
150, 180,
240
AAHC20BLA
480360
AAHC20BSA
575360
208360
AAHC30BHA
240360
AAHC30BLA
480360
AAHC30BSA
575360
kW
2.16
2.76
3.73
2.16
2.76
3.73
2.16
2.76
3.73
2.24
3.73
2.16
2.76
3.73
2.16
2.76
3.73
2.16
2.76
3.73
2.24
3.73
2.16
2.76
3.73
2.16
2.76
3.73
2.16
2.76
3.73
2.24
3.73
FLA
7.5
10.2
14.7
7.5
10.2
13.6
3.4
4.8
6.8
3.8
5.1
7.5
10.2
14.7
7.5
10.2
13.6
3.4
4.8
6.8
3.8
5.1
7.5
10.2
14.7
7.5
10.2
13.6
3.4
4.8
6.8
3.8
5.1
LEGEND
FLA
Hp
MCA
MOCP
Nominal
Capacity
(kW)
10
10
10
10
10
10
10
10
10
10
10
20
20
20
20
20
20
20
20
20
20
20
30
30
30
30
30
30
30
30
30
30
30
ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage
Stage
1
2
Total
7.5
7.5
7.5
7.5
7.5
7.5
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
14.9
14.9
14.9
14.9
14.9
14.9
19.9
19.9
19.9
19.9
19.9
19.9
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
15.0
7.5
22.5
15.0
7.5
22.5
15.0
7.5
22.5
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
FLA
20.8
20.8
20.8
24.1
24.1
24.1
12.0
12.0
12.0
10.0
10.0
41.5
41.5
41.5
47.9
47.9
47.9
24.1
24.1
24.1
20.1
20.1
62.5
62.5
62.5
72.2
72.2
72.2
36.1
36.1
36.1
30.1
30.1
MCA*
35.4
38.8
44.4
39.4
42.8
47.1
19.3
21.0
23.5
17.3
19.6
51.2
64.6
70.2
69.2
72.6
76.8
34.3
36.1
38.6
29.9
31.5
87.5
90.9
96.5
99.6
103.0
107.2
49.4
51.1
53.6
42.4
44.0
MOCP*
40
40
50
40
50
50
20
25
25
20
20
70
70
80
70
80
80
35
40
40
30
35
90
100
100
100
110
110
50
60
60
50
50
208
230
240
400
440
460
480
550
575
600
0.915
1.089
480
575
508 41 1602 01
39
FAN MOTOR
HEATER PART NO.
SIZE
Hp
VPHHz
3.7
5.0
208360
7.5
AAHC50DHA
3.7
5.0
240360
7.5
FAS180-240
AAHC50DLA
3.7
5.0
480360
7.5
3.0
AAHC50DSA
5.0
575360
7.5
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
208360
AAHC20EHA
240360
AAHC20ELA
480360
AAHC20ESA
575360
FAS300
208360
AAHC40EHA
240360
AAHC40ELA
480360
AAHC40ESA
575360
kW
2.76
3.73
5.59
2.76
3.73
5.59
2.76
3.73
5.59
2.24
3.73
5.59
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
FLA
10.2
14.7
21.5
10.2
13.6
19.4
4.8
6.8
9.7
3.8
5.1
7.8
21.5
28.0
19.4
25.2
9.7
12.6
7.8
10.3
21.5
28.0
19.4
25.2
9.7
12.6
7.8
10.3
LEGEND
FLA
Hp
MCA
MOCP
FLA
104.3
104.3
104.3
120.3
120.3
120.3
60.1
60.1
60.1
50.2
50.2
50.2
41.5
41.5
47.9
47.9
24.1
24.1
20.1
20.1
83.4
83.4
96.2
96.2
47.9
47.9
40.2
40.2
MCA* MOCP*
143.1
150
148.7
150
157.2
175
163.1
175
167.4
175
174.6
175
81.2
90
83.7
90
87.3
90
67.5
70
69.1
70
72.5
80
78.7
80
86.9
100
84.1
90
91.3
100
42.2
50
45.8
50
34.9
35
38.0
40
131.1
150
139.2
150
144.5
150
151.8
175
71.9
80
75.6
80
60.0
60
63.1
70
208
230
240
400
440
460
480
550
575
600
0.915
1.089
480
575
40
ELECTRIC HEATER(S)
Actual Capacity (kW)
Nominal
Stage
Stage
Capacity
1
2
Total
(kW)
50
22.6
15.0
37.6
50
22.6
15.0
37.6
50
22.6
15.0
37.6
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
20
14.9
14.9
20
14.9
14.9
20
19.9
19.9
20
19.9
19.9
20
20.0
20.0
20
20.0
20.0
20
20.0
20.0
20
20.0
20.0
40
15.0
15.0
30.0
40
15.0
15.0
30.0
40
20.0
20.0
40.0
40
20.0
20.0
40.0
40
20.0
20.0
40.0
40
20.0
20.0
40.0
40
20.0
20.0
40.0
40
20.0
20.0
40.0
508 41 1602 01
MOISTURE
INDICATOR
SIGHT GLASS*
FIELD
SUPPLIED
POWER
ELECTRIC
HEATER
ACCESSORY
POWER WIRES
LLSV*
FILTER LIQUID
DRIER* LINE
INSULATED
VAPOR
LINE
CONTROL
WIRES
INDOOR
UNIT
CONDENSATE DRAIN
POWER WIRES
INDOOR
THERMOSTAT
FUSED DISCONNECT
PER NEC
TO OPEN SIGHT
DRAIN
C09054
LEGEND:
NEC - National Electrical Code
TXV - Thermostatic Expansion Valve
* Field-supplied
{ Double riser may be required. Consult condensing unit product data catalog for details.
NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general pointsofconnection guides
only and are not intended for, or to include all details for, a specific
installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.
5. Internal factorysupplied TXVs not shown.
508 41 1602 01
41
FAS
C09055
LEGEND:
LLSV - Liquid Line Solenoid Valve
NEC - National Electrical Code
TXV - Thermostatic Expansion Valve
* Field-supplied
{ Double riser may be required Consult condensing unit product data catalog ro details.
NOTES:
42
508 41 1602 01
508 41 1602 01
43
DISCONNECT
HC1
L1
L2
HTR1
HC1
SUPPLY
L3
3Ph ONLY
EQUIP GND
CIRCUIT
BREAKER
(5 HP AND
LARGER)
FAS
CONTROL BOX
TERMINAL BLOCK
TB1
BLK
12
22
BLK
13
23
BLK
IFM
UNIT WIRING
Y1
Y2
W1
W1
W2
W2
21
IFC
11
WHT
IFC
C
WHT
R
Y1
Y2
W1
W2
CONNECT TO
24 VAC AT
CONDENSING
UNIT
G
C
X
THERMOSTAT
C09050
44
508 41 1602 01
APPLICATION DATA
Operating limits
General
IMPORTANT: Do not bury refrigerant piping underground.
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit
cycling, and less part-load operation. Equipment should
be selected to perform at no less than 300 cfm/ton (40 L/s
per kW).
The air handler fan must always be operating when the
condensing unit is operating.
For variable air volume (VAV) systems with supply-toreturn air recycling, use the equipment room as a return
air plenum.
P/N
1178747
1178748
1178747
1178747
1178747
1178747
1178748
FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
NOZZLE
Qty...Part No.
1...TDEBX8
1...1116
12...1/4
1...E5
4 Row
1...TDEBX8
1...1126
15...1/4
1...C6
120
4 Row
2...TDEX6
2...1115
9...1/4
2...E4
150
4 Row
2...TDEBX8
2...1115
12...3/16
2...E5
180
4 Row
2...TDEBX8
2...1126
16...1/4
2...C6
18...3/16
20...3/16
2...C8
UNIT
COIL
TYPE
TXV
Qty...Part No.*
072
4 Row
091
240
4 Row
2...TDEBX11
2...1126
300
4 Row
2...TDEBX11
2...1126
2...C15
LEGEND
TXV - Thermostatic Expansion Valve
* Danfoss part numbers shown.
Sporlan Valve Co. part numbers shown.
NOTE: Hot gas bypass applications require fieldsupplied auxiliary side connector.
508 41 1602 01
45
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
1725
1.3
56Y
1725
2.4
56Y
5/
5/
1745
5.0
S184T
11/8
1745
7.5
S213T
13/8
1745
5.0
184T
11/8
1755
7.5
S213T
13/8
1725
2.4
56Y
1725
2.4
56Y
1725
2.4
56Y
1725
2.9
56Y
1725
3.7
56Y
5/
5/
5/
7/
7/
1725
1.0
56
1725
2.0
56HZ
1725
2.0
56HZ
1725
3.0
56HZ
1725
3.0
56HZ
5/
7/
7/
7/
7/
LEGEND:
NEMA National Electrical Manufacturers Association (U.S.A.)
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
1725
2.4
56Y
1725
2.4
56Y
5/
5/
1725
5.0
S184T
11/8
1745
7.5
S213T
13/8
1745
10.0
S215T
13/8
1745
5.0
184T
11/8
1755
7.5
S213T
13/8
1750
10.0
D215T
13/8
1725
2.9
56Y
1725
2.9
56Y
1725
3.7
Y56Y
1725
3.7
Y56Y
7/
7/
7/
7/
1725
2.0
56HZ
1725
3.0
56HZ
1725
3.0
56HZ
7/
7/
7/
1745
5.0
184T
11/8
LEGEND:
NEMA National Electrical Manufacturers Association (U.S.A.)
MOTOR HP
EPACT MINIMUM
1.3*
2.4
2.9
3.7
5.0
89.5%
7.5
91.7%
10.0
91.7%
LEGEND:
EPACT - Energy Policy and Conservation Act of 1992
* Singlephase only.
46
508 41 1602 01
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
28.75
0.97
56Y
15.9
28.75
1.79
56Y
15.9
28.75
1.79
56Y
15.9
28.75
1.79
56Y
15.9
28.75
1.79
56Y
15.9
28.75
2.16
56Y
22.2
28.75
2.76
56Y
22.2
29.08
3.73
S184T
28.6
29.08
5.60
S213T
34.9
28.75
0.75
56
15.9
28.75
1.49
56HZ
22.2
28.75
1.49
56HZ
22.2
28.75
2.24
56HZ
22.2
28.75
2.24
56HZ
22.2
29.08
3.73
184T
28.6
29.25
5.60
S213T
34.9
LEGEND:
NEMA National Electrical Manufacturers Association (U.S.A.)
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
28.75
1.79
56Y
15.9
28.75
1.79
56Y
15.9
28.75
2.16
56Y
22.2
28.75
2.16
56Y
22.2
28.75
2.76
Y56Y
22.2
28.75
2.76
Y56Y
22.2
29.08
3.73
S184T
28.6
29.08
5.60
S213T
34.9
29.17
7.46
S215T
34.9
28.75
1.50
56HZ
22.2
28.75
2.24
56HZ
22.2
28.75
2.24
56HZ
22.2
29.08
3.73
184T
28.6
29.08
3.73
184T
28.6
29.25
5.60
S213T
34.9
29.17
7.46
D215T
34.9
LEGEND:
NEMA National Electrical Manufacturers Association (U.S.A.)
508 41 1602 01
47
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
2.43.4
2.83.8
3.44.4
2.83.8
2.83.8
3.74.7
4.35.3
2.5
2.5
2.5
2.5
2.5
3.0
3.0
8.8
1
1A
8.8
1
1A
8.8
1
1A
9.0
17/16
1A
9.0
17/16
1A
9.4
17/16
1B
40.3
41.3
42.3
42.3
42.3
41.8
11.0
115/16
2B*
(2) 42.8
(2) 43.8
568
470666
1200
647
549745
1200
764
666863
1200
632
537728
1200
632
537728
1200
771
679863
1200
752
682841
1100
19.6
19.6
19.7
19.1
19.1
15.3
13.1
10.44
12.32
10.44
12.32
10.44
12.32
10.44
12.32
10.44
12.32
9.12
10.99
6.67
9.43
* Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
3.44.4
3.44.4
3.44.4
3.44.4
3.74.7
4.35.3
4.35.3
2.5
2.5
2.5
2.5
3.0
3.0
3.0
8.8
1
1A
8.0
1
1A
8.0
1
1A
8.2
17/16
1A
8.6
17/16
1B
9.4
17/16
1B
42.3
40.3
40.3
41.3
41.8
41.8
9.4
115/16
2B*
(2) 38.8
(2) 39.8
764
666863
1200
841
733949
1200
841
733949
1200
820
715926
1200
842
742943
1200
881
798984
1200
881
798984
1100
19.7
21.6
21.6
21.1
16.7
15.3
15.3
10.44
12.32
10.44
12.32
10.44
12.32
10.44
12.32
10.44
12.32
9.16
10.99
6.67
9.43
* Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
48
508 41 1602 01
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
3.44.4
3.44.4
3.44.4
3.74.7
4.35.3
4.35.3
4.35.3
2.5
2.5
2.5
3.0
3.0
3.0
3.0
7.0
1
1A
41.3
6.0*
1
1A
37.3
6.0
1
1A
37.3
7.4
17/16
1B
39.8
7.9
17/16
1B
39.8
7.4
17/16
2B
36.8
8.6
115/16
2B
37.8
961
838
1084
1200
1121
978
1200*
1200
1121
978
1200
1200
979
873
1096
1200
1060
950
1171
1200
1118
1014
1200
1200
1024
873
1075
1100
24.6
28.7
28.7
19.4
18.4
19.4
16.7
10.44
12.32
10.44
12.32
10.44
12.32
10.44
12.32**
9.16
10.99
8.16
10.02
6.67
9.43
* Values for 3phase motor shown. For singlephase motor, pulley pitch diameter is 7 in. and resulting fan speed is 8371096 rpm.
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.
** 575v unit has a center distance of 9.1610.99.
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
61.0
86.4
71.1
96.5
86.4
111.8
71.1
96.5
71.1
96.5
94.0
119.4
109.2
134.6
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
2.5
2.5
2.5
2.5
2.5
3.0
3.0
224
25.4
1A
224
25.4
1A
224
25.4
1A
229
36.5
1A
229
36.5
1A
239
36.5
1B
1024
1049
1074
1074
1074
1062
279
49.2
2B*
(2) 1087
(2) 1113
9.5
7.811.1
20.0
10.8
9.212.4
20.0
12.7
11.114.4
20.0
10.5
9.012.1
20.0
10.5
9.012.1
20.0
12.9
11.314.4
20.0
12.5
11.414.0
18.3
0.327
0.327
0.328
0.318
0.318
0.255
0.218
265313
265313
265313
265313
265313
232279
169240
* Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
508 41 1602 01
49
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
86.4
111.8
86.4
111.8
86.4
111.8
86.4
111.8
94.0
119.4
109.2
134.6
109.2
134.6
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
2.5
2.5
2.5
2.5
3.0
3.0
3.0
224
25.4
1A
203
25.4
1A
203
25.4
1A
208
36.5
1A
218
36.5
1B
239
36.5
1B
1074
1024
1024
1049
1062
1062
239
49.2
2B*
(2) 986
(2) 1011
12.7
11.1
14.4
20.0
14.0
12.2
15.8
20.0
14.0
12.2
15.8
20.0
13.7
11.9
15.4
20.0
14.0
12.4
15.7
20.0
14.7
13.3
16.4
20.0
14.7
13.3
16.4
18.3
0.328
0.360
0.360
0.352
0.278
0.255
0.255
265313
265313
265313
265313
265313
232279
169240
* Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
FAS072
FAS091
FAS120
FAS150
FAS180
FAS240
FAS300
86.4
111.8
86.4
111.8
86.4
111.8
94.0
119.4
109.2
134.6
109.2
134.6
109.2
134.6
2.5
2.5
2.5
3.0
3.0
3.0
3.0
178
25.4
1A
1049
152*
25.4
1A
947
152
25.4
1A
947
188
36.5
1B
1011
201
36.5
1B
1011
188
36.5
2B
935
203
49.2
2B
935
16.0
14.0
18.1
20.0
18.7
16.3
20.0*
20.0
18.7
16.3
20.0
20.0
16.3
14.4
18.3
20.0
17.7
15.8
19.5
20.0
18.6
16.9
20.0
20.0
17.1
14.6
17.9
18.3
0.410
0.478
0.478
0.323
0.307
0.323
0.278
265313
265313
265313
265313**
232279
207255
169240
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)
* Values for 3phase motor shown. For singlephase motor, pulley pitch diameter is 178 mm and resulting fan speed is 14.018.3 r/s.
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.
** 575v unit has a center distance of 233279.
50
508 41 1602 01
GUIDE SPECIFICATIONS
Commercial Packaged Air-Handling Unit
handled
per
Part 2 PRODUCTS
2.01 EQUIPMENT
cfm (L/s)
in. wg
D. Motor:
A. Base Unit:
51
508 41 1602 01