Tape Method for

Insulating Bus-Bar Connections


535kV to Meet ANSI C37.20 Requirements
General Motors

,, ,,,,
,, ,,,,
,
,, ,,
,

Instructions

Cable to Bus-Bar

Bus-Bar to Bus-Bar

A. Prepare Cable
1. Train Cable into position and cut to proper length.
2. Prepare cable and install terminal lug (and
termination if applicable) per manufacturers
direction.
3. Bolt lug to Bus-Bar.
B. Insulate Connection
1. Apply 1 half-lapped layer of Scotch Super 33+
Tape over lug and bolted connection.
NOTE: This layer is applied so connection can
be easily re-entered.
2. Fill in around bolts and sharp areas with
Scotchfil Electrical Putty to smooth
connection.
NOTE: Do not substitute any materials for Scotchfil
Electrical Putty.
3. Insulate connection with half-lapped layers
Scotch 2228 Rubber Mastic Tape. Apply tape
over entire connection area according to tape
chart (reverse). Stretch tape approximately 20%.
4. Apply 2 half-lapped layers of Super 33+ Tape
over insulating tape, extending 1 (25mm) onto
cable insulation or jacket, or existing bus
insulation. (See main illustration.)

A. Bolt Bus-Bars Together


B. Insulate Connection
1. Apply 1 half-lapped layer of Scotch Super 33+
Tape over bolted connection.
NOTE: This layer is applied so connection can be
easily re-entered.
2. Fill in around bolts and sharp areas with
Scotchfil Electrical Putty to smooth
connection.
NOTE: Do not substitute any materials for Scotchfil
Electrical Putty.
3. Insulate connection with half-lapped layers
Scotch 2228 Rubber Mastic Tape. Apply tape
over entire connection area according to tape
chart (reverse). Stretch tape approximately 20%.
4. Apply 2 half-lapped layers of Super 33+ Tape
over insulating tape, extending 1 (25mm) onto
existing bus insulation. (See main illustration.)

78-8124-4142-2A

2228 Tape Chart


(X)
Dimension
In./(mm)

Straight Bar
No. of
Half-Lapped
Layers

Bolted
Connections
No. of
Half-Lapped Layers

600 Volts

0.5/(13)

5-8kV

1.0/(25)

15kV

2.0/(51)

25kV

2.0/(51)

35kV

2.5/(64)

Voltage

Typical Clearances for Rectangular Bus-Bar


Tape Insulated
(Indoor Clearance)
Voltage
Rating
(kV)

BIL
(kV)

Minimum Minimum
Dimension Dimension
b
c

15 & Below

110

2.2 in.
(56mm)

2.5 in.
(64mm)

25

125

2.5 in.
(64mm)

3.5 in.
(89mm)

35

150

4.5 in.
(114mm)

5.5 in.
(140mm)

Important Notice
All statements, technical information and recommendations related to the Sellers products are based on information believed to be reliable, but the
accuracy or completeness thereof is not guaranteed. Before utilizing the product, the user should determine the suitability of the product for its
intended use. The user assumes all risks and liability whatsoever in connection with such use.
Any statements or recommendations of the Seller which are not contained in the Sellers current publications shall have no force or effect unless
contained in an agreement signed by an authorized office of the Seller. The statements contained herein are made in lieu of all warranties,
expressed or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose which warranties are
hereby expressly disclaimed.
SELLER SHALL NOT BE LIABLE TO THE USER OR ANY OTHER PERSON UNDER ANY LEGAL THEORY, INCLUDING BUT NOT LIMITED TO
NEGLIGENCE OR STRICT LIABILITY, FOR ANY INJURY OR FOR ANY DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES
SUSTAINED OR INCURRED BY REASON OF THE USE OF ANY OF THE SELLERS PRODUCTS.

Electrical Products Division


6801 River Place Blvd.
Austin, TX 78726-9000

Printed on 50% recycled paper


with 10% post-consumer

Litho in USA
3M 1998 78-8124-4142-2A

Potrebbero piacerti anche