Manual
Revision History
Contact Address
1066540000/01/12.11 3
Contents
Contents
Contents .............................................................................................................................4
1. Approvals...............................................................................................................7
1.1 CE........................................................................................................................................................7
1.2 EMC.....................................................................................................................................................7
1.3 ATEX...................................................................................................................................................7
1.4 IECEx ..................................................................................................................................................7
1.5 cFMus .................................................................................................................................................7
1.6 UL........................................................................................................................................................7
1.7 GOST ..................................................................................................................................................7
1.8 DNV.....................................................................................................................................................7
3. Safety Instructions................................................................................................9
3.1 Approved Use ....................................................................................................................................9
3.2 Qualified Personnel...........................................................................................................................9
3.3 Accuracy of the Technical Documentation ....................................................................................9
3.4 Liability...............................................................................................................................................9
3.5 Definitions..........................................................................................................................................9
3.6 Symbol Identification ......................................................................................................................10
3.7 Electrical Precautions.....................................................................................................................10
3.8 General Instructions .......................................................................................................................10
4. Introduction .........................................................................................................11
4.1 Product Description ........................................................................................................................11
4.1.1 Family ACT20X .......................................................................................................................11
4.1.2 General Description ................................................................................................................13
4.1.3 The Six Basic Module Types in Detail ....................................................................................14
5. Installation ...........................................................................................................15
5.1 General .............................................................................................................................................15
5.1.1 Environment ............................................................................................................................15
4 1066540000/01/12.11
Contents
6. Operation .............................................................................................................20
6.1 Normal Operation ............................................................................................................................20
6.2 Warm-Up ..........................................................................................................................................20
6.3 Cleaning ...........................................................................................................................................20
1066540000/01/12.11 5
Contents
6 1066540000/01/12.11
Approvals
1. Approvals
1.6 UL
In accordance with:
In accordance with:
- IEC 60079-0
- IEC 60079-11
- IEC 60079-15
- IEC 60079-26 1.7 GOST
- IEC 61241-0 GOST approval is pending.
- IEC 61241-11
1.8 DNV
IECEx marking: Marine approval is pending.
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
1066540000/01/12.11 7
Warranty Statement
2. Warranty Statement
8 1066540000/01/12.11
Safety Instructions
3. Safety Instructions
1066540000/01/12.11 9
Safety Instructions
10 1066540000/01/12.11
Introduction
4. Introduction
1066540000/01/12.11 11
Introduction
12 1066540000/01/12.11
Introduction
4.1.2 General Description simple, coded mating. The integrated release lever
ensures the connection can be disconnected without
Weidmüller’s ACT20X – new signal converters for
damage when servicing is required. Devices from
hazardous areas: Universal family of products
the ACT20X family have been designed to operate
covers the entire field of hazardous area
in an ambient temperature range of -20 °C to +60 °C
applications with six different basic functions.
– in other words in practically all fields of industry.
The hinged and transparent front plate can easily be
With the introduction of its ACT20X modules opened upwards. It has been designed for simple
Weidmüller is offering a completely new family of accommodation of device markers.
signal converters for hazardous area applications.
With just 11 mm per channel these compactly
Products from the ACT20X assortment are designed
designed modules require very little space in the
to be installed in Zone 2 / Division 2 or in non-
electrical cabinet. All ACT20X converters can be
hazardous areas; international approvals such as
configured via a PC utilizing the software "WI-
ATEX, IECEx and FM (Class I, Division 1 and 2)
Manager". This software is based on vendor-neutral
allow processing of signals from Zone 0 / Division 1.
FDT/DTM technology. The innovative modules are
Put succinctly, the modules are suitable for use in
designed to be installed in safe or hazardous areas
applications across the globe.
of Zone 2. The ACT20X family includes digital and
analogue intrinsically safe converters that both
isolate and convert signals from as well as into
hazardous areas. The innovative signal converters
process 2-wire HART, NAMUR, RTD, thermocouple
or DC signals as well as digital signals with electrical
connection to hazardous area Zone 0. All modules
have 3-way separation and are optionally available
with dual channel functionality. With high levels of
insulation resistance, accuracy and thermal stability
ACT20X modules provide a pure, disturbance free
signal at all times. A relay-based error monitoring
facility simplifies servicing. ACT20X modules can be
utilized in temperatures from -20 °C to +60 °C
without restrictions. They have all relevant
international approvals such as ATEX, IECEx, FM –
in other words, the modules are predestined for use
in applications all over the world.
1066540000/01/12.11 13
Introduction
Temperature/mA Converter
The ACT20X-HTI-SAO temperature signal
isolator/converter facilitates utilization of Pt100
sensors. The input circuit is designed for intrinsically
safe signals from within Zone 0. Analogue signals
are made available on the output side for safe area
devices. A dual-channel version is optionally
available.
Universal Converter
The universal isolator/converter ACT20X-HUI-SAO
is a user configurable temperature and signal
converter for Pt100, thermal and current (mA) inputs
from within Ex Zone 0 as well as an output for non-
hazardous area devices.
14 1066540000/01/12.11
Installation
5. Installation
5.1.1 Environment
This product is designed for use either indoors
(IP20) in a control panel, or in a weather-proof field
enclosure.
Avoid direct sunlight, dust, high temperatures,
mechanical vibrations and shock as well as rain
and heavy moisture.
If necessary, heating in excess of the stated limits
for ambient temperatures should be avoided by
ventilation.
Product must be installed in pollution degree 2,
overvoltage category II as defined in EN 60664-1.
Product is designed to be safe at least under an
altitude of up to 2000 m.
1066540000/01/12.11 15
Installation
16 1066540000/01/12.11
Installation
Do not install input, output and power supply 5.7 Release Lever
cables close to sources of electrical interference! The terminals are released with a release lever.
1066540000/01/12.11 17
Installation
5.8 Encoding
2 Plug encoded connector onto pin header.
NOTICE Encoding element is transferred from connector
to pin header.
Leaving the product connectors uncoded results
Encoding element remains in the pin header
in lack of interchanging protection. All connectors
housing.
will be identically encoded.
Create connector coding plan prior to first
mating and encode connectors accordingly.
Perform encoding procedure for each new
module.
3 1
18 1066540000/01/12.11
Installation
5.9 Configuration
2 Connect the CBX200 USB jack, as shown in the
DANGER illustration:
Configuration must be performed in a 1 2 3
safe area!
1066540000/01/12.11 19
Operation
6. Operation
6.2 Warm-Up
The product is designed to start-up as soon as
power is supplied. However a warm-up period of 15
minutes is required before it performs to the
specifications above.
When auxiliary power is switched on, for the first
200 ms the product will consume up to 200 mA.
20 1066540000/01/12.11
Product Installation / Operation
1066540000/01/12.11 21
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
51 54
41 44
PWR
LED 1
CH1
LED 2
CH2
LED 3
ACT20X
11 12 13 14
21 22 23 24
Device OK
activated yellow ON energized
Channel 1
22 1066540000/01/12.11
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
21 SW Sense 51 GND
power supply
22 NAMUR Ex input 52 +24 V DC
23 SW Supply channel 2 53 NC
status relay
24 NAMUR + 54 COM
7.1.5 Specifications
Features
Configuration and monitoring via FDT/DTM-Software "WI-Manager".
Selection of direct or inverted function for each channel.
The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,
2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.
Extended self diagnostic: Monitoring of error events and cable breakage via the individual status relay.
LED indication for operation status and malfunction.
3-way galvanic isolation between input, output and supply.
1066540000/01/12.11 23
24
CPU
Device status, Green 51 Gnd. -
Ch. 1 status, Yellow/Red
52 Supply +24 VDC
Ch. 2 status, Yellow/Red
FLASH
53
Status relay N.C.
Rp
12
41 Opto - or relay N.O.
(3) (4) (2) (1) or relay N.C.
11
Channel 2 Channel 2
Switch, NAMUR
Rp = 15 kΩ
cable error sensor 44 Opto + or relay N.O.
24 VNAMUR or relay N.C.
Rs = 750 Ω
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Rp
23 43 Opto - or relay N.O.
or relay N.C.
Rp Rs
22
1066540000/01/12.11
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Channel 2:
+ N.O. or Ch. 2:
Rs N.C.
13 43 Relay Opto -
- Rp
Rp
Relay Opto +
12 42 Channel 1:
N.O. or Ch. 1:
N.C.
11 41 Relay Opto -
Rs
Supply +19.2...31.2 VDC
Rp
23 52
- Rp
Module status
22 53
N.C.
21 54
Module status
1066540000/01/12.11 25
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Power Supply
Supply voltage 19.2…31.2 V DC
NAMUR supply 8 V DC / 8 mA
Max. consumption (2-channels) ≤3W
Fuse 400 mA / 250 V AC
Environmental Specifications
Specifications range -20…+60 °C
Storage temperature -20…+85 °C
Relative humidity (non-condensation) < 95 %
Calibration temperature +20…28 °C
26 1066540000/01/12.11
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
General Specifications
Communications interface, CBX200 USB / "WI-Manager" / ACT20X DTM
adapter / configuration software / FDT-DTM
device driver
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP20
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire AWG 26…14 / 0.13…2.08 mm²
Response time for cable fault < 200 ms
Default Settings
Channel 1 function direct
Channel 2 function direct
Short circuit indication yes
Breakage indication yes
1066540000/01/12.11 27
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
28 1066540000/01/12.11
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
51 54
41 44
PWR
LED 1
CH1
LED 2
CH2
LED 3
ACT20X
11 12 13 14
21 22 23 24
Device
OK OFF ON energized
Channel 1
1066540000/01/12.11 29
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
7.2.4 Specifications
Features
Configuration and monitoring are performed via FDT/DTM Software "WI-Manager".
The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,
2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.
The passive signal inputs for RTD, TC and mA are made for one or two channels and completely
electrically isolated.
The two-channel version is suitable to use as a signal splitter.
3-way galvanic isolation between input, output and supply.
Front LEDs indicate operation status and malfunction.
The cold junction compensation for TC-signal inputs is either the internal cold junction compensation, or for
higher accuracy is an external cold junction compensation terminal available –- 1 channel 1160640000
ACT20X-CJC-HTI-S PRT 11 or 2 channel 1160650000 ACT20X-CJC-HTI-S PRT 21.
Extended self diagnostic: Monitoring of error events and cable breakage via the individual status relay.
30 1066540000/01/12.11
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
Gnd.
Gnd.
TC
TC
+
+
-
-
RTD, connec-
RTD, connec-
2
2
tion, wries
tion, wires
3
3
4
4
+
+
-
Current Current
1066540000/01/12.11 31
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
42
12 2-wire supply -
44
+
mA mA
4...20 mA Channel 2
41
11 - -
43
2-wire supply +
54 Module status
21
RTD Input
Pt100, according to -200…+850 °C, IEC 60751
Ni100, according to -60…+250 °C, DIN 43760
Sensor types Pt10*, Pt20*, Pt50*, Pt100, Pt250, Pt300, Pt400,
(* = without short circuit detection) Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.) 50 Ω
Sensor current nom. 0.2 mA
Effect of sensor cable resistance (3/4-wire) < 0.002 Ω
Sensor error detection (programmable) ON/OFF
32 1066540000/01/12.11
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
1066540000/01/12.11 33
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
Current Input
Measurement range 0…20 mA
Programmable measurement ranges 0…20 / 4…20 mA
Input resistance nom. 20 Ω + PTC 50 Ω
Sensor error detection (programmable) ON/OFF
Current Output
Programmable signal ranges 0…20 mA / 4…20 mA / 20…0 mA / 20…4 mA
Load max. 4 mA / 600 Ω / 12 V DC
Load stability ≤ 0.01 % of span / 100 Ω
Sensor error detection 0 / 3.5 mA / 23 mA / none
Output limitation:
on 4…20 and 20…4 mA signals 3.8…20.5 mA
on 0…20 and 20…0 mA signals 0…20.5 mA
Current limit ≤ 28 mA
34 1066540000/01/12.11
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
Power Supply
Supply voltage 19.2…31.2 V DC
Max. consumption (2-channels) ≤ 3.5 W
Fuse 1.25 A / 250 V AC
Environmental Specifications
Ambient temperature -20…+60 °C
Storage temperature -20…+85 °C
Relative humidity (non-condensation) < 95 %
Calibration temperature +20…28 °C
General Specifications
Communications interface, CBX200 USB / "WI-Manager" / ACT20X DTM
adapter / configuration software / FDT-DTM
device driver
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP20
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire AWG 26…14 / 0.13…2.08 mm²
EMC immunity influence ≤ 0.5 % of span
Extended EMC immunity: ≤ 1 % of span
NAMUR NE 21, A criterion, burst
Signal/Noise ratio min. 60 dB (0…100 kHz)
1066540000/01/12.11 35
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
Default Settings
Input type Temperature
Connection type 3-wire
Temperature unit °C
Temperature sensor type Pt100
Temperature range 0…150°C
Output current range 0…20 mA
Output current on error 0…23 mA
Analog output response time (1/10 s) 1s
36 1066540000/01/12.11
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
1066540000/01/12.11 37
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
51 54
41 44
PWR
LED 1
CH1
LED 2
CH2
LED 3
ACT20X
11 12 13 14
21 22 23 24
Device OK
Channel 1
38 1066540000/01/12.11
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
21 GND 51 GND
power supply
22 Ex 1 Ex output 52 +24 V DC
23 Ex 2 channel 2 53 COM
status relay
24 Ex 3 54 NC
7.3.4 Specifications
Features
Solenoid/alarm driver for the control of solenoids, acoustic alarms and LEDs installed in the hazardous
area.
Two hardware versions make it possible to choose either low (35 mA) or high (60 mA) current output with
1-channel or 2-channel versions.
Configuration and monitoring via FDT/DTM-Software "WI-Manager".
Selection of direct or inverted function for each channel and the possibility of reducing the output current to
the hazardous area to suit the application.
The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,
2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.
Extended self diagnostic: Monitoring of error events via the individual status relay.
LED indication: green and 2 yellow/red front LEDs to indicate operation status and malfunction.
3-way galvanic isolation between input, output and supply, 2.6 kV AC.
1066540000/01/12.11 39
40
Device status, G
reen 51 Gnd. -
CPU
Ch. 1 status,
Yellow/Red
52 Supply +24 VDC
Ch. 2 status,
Yellow/Red
53 Statusrelay N.C.
FLASH
54 Statusrelay N.C.
Output + R Ex3 Driver
14
R Ex2
13
Input +
CPU
Switch
PNP
V+
41
11 Input Gnd.
Output, Gnd.
EEPROM
Channel 1
Input + R Ex3
24
44 Input +
V+
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
R Ex2
23
NPN
Switch
PNP
22 R Ex1
V+
43
Input Gnd.
21
Output, Gnd.
Channel 2
1066540000/01/12.11
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
13 43
+V +V
12 42
11 41
Power Supply
Alarm Solenoid GND -
24 51
Channel 2:
+19.2...31.2 V DC
23 52
Module status
22 53
N.C .
21 54
Module status
PNP Input
Trigger level (low) ≤ 8 V DC
Trigger level (high) ≥ 10 V DC
1066540000/01/12.11 41
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Output
Output ripple < 40 mV RMS
ACT20X-SDI-HDO-L-S, ACT20X-2SDI-HDO-S,
low current (< 35 mA), Vout no load Vout with load Iout max.
Ex barrier data channel 1
11–12 min. 24 V min. 12.5 V 35 mA
11–13 min. 24 V min. 13.5 V 35 mA
11–14 min. 24 V min. 14.5 V 35 mA
ACT20X-2SDI-HDO-S,
low current (< 35 mA), Vout no load Vout with load Iout max.
Ex barrier data channel 2
21–22 min. 24 V min. 12.5 V 35 mA
21–23 min. 24 V min. 13.5 V 35 mA
21–24 min. 24 V min. 14.5 V 35 mA
ACT20X-SDI-HDO-H-S,
high current (< 60 mA), Vout no load Vout with load Iout max.
Ex barrier data channel 1
min. 9 V 60 mA
11–12 min. 24 V
min. 11.5 V 50 mA
min. 10 V 60 mA
11–13 min. 24 V
min. 12.5 V 50 mA
min. 11 V 60 mA
11–14 min. 24 V
min. 13.5 V 50 mA
42 1066540000/01/12.11
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Power Supply
Supply voltage 19.2…31.2 V DC
Max. consumption (2-channels) ≤ 3.5 W
Fuse 1.25 A / 250 V AC
EMC immunity influence < ±0.5 % of span
Extended EMC immunity: < ±1 % of span
NAMUR NE 21, A criterion, burst
Environmental Specifications
Ambient temperature -20…+60 °C
Storage temperature -20…+85 °C
Relative humidity (non-condensation) < 95 %
Calibration temperature +20…28 °C
General Specifications
Communications interface, CBX200 USB / "WI-Manager" / ACT20X DTM
adapter / configuration software / FDT-DTM
device driver
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP20
Screw terminal torque 0.5 Nm
Wire size, stranded wire AWG 26…14 / 0.13…2.08 mm²
Default Settings
Channel 1 function Direct
Channel 2 function Direct
1066540000/01/12.11 43
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
44 1066540000/01/12.11
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
51 54
41 44
PWR
LED 1
CH1
LED 2
CH2
LED 3
ACT20X
11 12 13 14
21 22 23 24
1066540000/01/12.11 45
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
11 + 3W / 4W 41 Out
output
12 – / CJC 2W / 3W / 4W M3 42 Out +
21 – – 51 +24 V DC power
22 + – 52 GND supply
23 + 53 NC status
24 + 54 COM relay
7.4.4 Specifications
Features
Configuration and monitoring via FDT/DTM-Software "WI-Manager".
The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,
2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.
The active or passive signal inputs for RTD, TC, potentiometer, V and mA are completely electrically
isolated.
The device detects automatically whether an active or passive current signal is connected.
The cold junction compensation for TC-signal inputs is either the internal cold junction compensation, or for
higher accuracy is an external cold junction compensation terminal available –- 1 channel 1160640000
ACT20X-CJC-HTI-S PRT 11.
Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
Front LEDs indicates operation status and malfunction.
3-way galvanic isolation between input, output and power supply.
46 1066540000/01/12.11
Illustration 7-11:
1066540000/01/12.11
Device status, Red/Green
Gnd. 51 Supply -
CPU
Channel 1 status, Red
52 Supply +24 VDC
Channel 2 status, Red
FLASH
53
Status relay N.C.
RTD and lin. R,
connection,
54 Status relay N.C.
Potentiometer
wires TC 0.2 mA
4 3 2 14
Supply
42 I+ 2-wire supply -
MUX
PTC
12
- 41 2-wire supply +
CPU
CJC on PCB Gnd.
+ CPU /
11 Safety
V
24
loop
EEPROM 44 Relay N.O.
+
23
Tx
43 Relay N.O.
-
PTC
22
+
10
- 21
Current
Voltage
2-wire transmitter
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
47
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
14 42 +
mA
Channel 1:
mA +
13 41 -
*
Relay
12 44
NO
11 43 Relay
* Order separately:
CJC connector
Power connection
Current Voltage
Gnd.
24 51
Channel 2:
+
Supply +19.2...31.2 VDC
Tx 23 52
-
+
Device status
+ 22 53
NC
21 54 Device status
Supply via
power rail
Zone 0, 1, 2, 20, 21, 22 / Zone 2 / FM Cl. 1,
Cl. I/II/III, div. 1 gr. A-G div. 2, gr. A-D or safe area
Illustration 7-12: Applications
48 1066540000/01/12.11
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
1066540000/01/12.11 49
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
Current Input
Measurement range 0…20 mA
Programmable measurement ranges 0…20 and 4…20 mA
Input resistance nom. 20 Ω + PTC 50 Ω
Sensor error detection:
loop break (only when input is selected as Yes
4…20 mA)
Voltage Input
Measurement range 0…12 V DC
Programmable measurement ranges 0…1 V / 0.2…1 V / 0…5 V / 1…5 V / 0…10 V /
2…10 V
Input resistance nom. > 10 MΩ
Current Output
Signal range (span) 0…23 mA
Programmable signal ranges 0…20 mA / 4…20 mA / 20…0 mA / 20…4 mA
Load max. 4 mA / 600 Ω / 12 V DC
Load stability ≤ 0.01 % of span / 100 Ω
Sensor error detection 0 / 3.5 mA / 23 mA / none
NAMUR NE 43, Upscale / Downscale 23 mA / 3.5 mA
Output limitation:
on 4…20 and 20…4 mA signals 3.8…20.5 mA
on 0…20 and 20…0 mA signals 0…20.5 mA
Current limit ≤ 28 mA
50 1066540000/01/12.11
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
Power Supply
Supply voltage 19.2…31.2 V DC
Max. consumption ≤ 3.5 W
Fuse 1.25 A / 250 V AC
Environmental Specifications
Ambient temperature -20…+60 °C
Storage temperature -20…+85 °C
Relative humidity (non-condensation) < 95 %
1066540000/01/12.11 51
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
General Specifications
Communications interface, CBX200 USB / "WI-Manager" / ACT20X DTM
adapter / configuration software / FDT-DTM
device driver
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP20
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire AWG 26…14 / 0.13…2.08 mm²
EMC immunity influence ≤ 0.5 % of span
Extended EMC immunity: ≤ 1 % of span
NAMUR NE 21, A criterion, burst
Signal/Noise ratio min. 60 dB (0…100 kHz)
Response time (0…90 %, 100…10 %):
Temperature input, programmable 1…60 s
mA / V input, programmable 0.4…60 s
Default Settings
Input type Temperature
Connection type 3-wire
Temperature unit °C
Temperature sensor type Pt100
Temperature range 0…150 °C
Output current range 0…20 mA
Output current on error 23 mA
Analog output response time (1/10 s) 1s
52 1066540000/01/12.11
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
Hysteresis
Setpoint high
Window
Setpoint low
Hysteresis
Time
Closed
Relay On Relay On
Relay contact (N.O.)
Open
Input
signal ON delay
OFF delay
Setpoint
(increasing)
Hysteresis
Time
Closed
Relay On
Relay contact (N.O.)
Open
1066540000/01/12.11 53
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
54 1066540000/01/12.11
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
51 54
41 44
PWR
LED 1
CH1
LED 2
CH2
LED 3
ACT20X
11 12 13 14
21 22 23 24
Device OK
activated OFF active energized
defective red inactive de-energized
Channel 1
1066540000/01/12.11 55
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
21 I Passive 51 GND
power supply
22 I Passive + Ex input 52 +24 V DC
23 I Active Return channel 2 53 NC
status relay
24 I Active Supply 54 COM
7.5.4 Specifications
Features
HART-compatible for 0.5...2.5 kHz
Configuration and monitoring via FDT/DTM-Software "WI-Manager".
The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,
2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.
The active or passive mA current signal inputs are completely electrically isolated.
The device detects automatically whether an active or passive current signal is connected.
The two-channel device can be used as a signal splitter.
Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
Front LEDs indicates operation status and malfunction.
3-way galvanic isolation between input, output and power supply.
56 1066540000/01/12.11
51 Supply -
Supply, Green
Illustration 7-16:
CPU
Ch. 1 status, Red 52 Supply +24 VDC
1066540000/01/12.11
Ch. 2 status, Red 53
FLASH
Status relay N.C.
- 13
+
- 23
+
mA
-
22
+
43
Gnd.
- 21 Channel 2
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
57
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
2-wire supply –
+ 14 42
+
4...20 mA
Tx mA mA
- - -
13 41
Channel 1:
2-wire supply +
2-wire supply –
+ 12 44
+
4...20 mA
Current mA mA
- - -
11 43
2-wire supply +
23 52
Module status
+ 22 53
Current N.C.
- 21 54
Module status
Current Input
Measurement range 3.5…23 mA
Alarm setpoint, low/high limit (programmable) 0…28 mA
Sensor error detection < 1 mA
Current Output
Signal range (programmable) 3.5…23 mA
Load max. 20 mA / 600 Ω / 12 V DC
Load stability ≤ 0.01 % of span /100 Ω
Sensor error detection (programmable) 3.5 mA / 23 mA / none
58 1066540000/01/12.11
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
Current limit ≤ 28 mA
Effect of supply voltage change < 10 μA
Power Supply
Supply voltage 19.2…31.2 V DC
Max. consumption (2-channels) ≤3W
Fuse 1.25 A / 250 V AC
Environmental Specifications
Specifications range -20…+60 °C
Storage temperature -20…+85 °C
Relative humidity (non-condensation) < 95 %
Calibration temperature +20…28 °C
1066540000/01/12.11 59
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
General Specifications
Communications interface, CBX200 USB / "WI-Manager" / ACT20X DTM
adapter / configuration software / FDT-DTM
device driver
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP20
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire AWG 26…14 / 0.13…2.08 mm²
EMC immunity influence ≤ 0.5 % of span
Extended EMC immunity: ≤ 1 % of span
NAMUR NE 21, A criterion, burst
Response time for cable fault < 200 ms
HART Communication
Frequency range 0.5…2.5 kHz
Signal / noise ratio min. 60 dB (0.5…10 kHz)
Response time (0…90 %, 100…10 %) < 5 ms
Default Settings
Low/high limit 3.8 mA / 20.5 mA
60 1066540000/01/12.11
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
1066540000/01/12.11 61
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
51 54
41 44
PWR
LED 1
CH1
LED 2
CH2
LED 3
ACT20X
11 12 13 14
21 22 23 24
Device
OK OFF ON energized
defective red fault state de-energized
Channel 1
62 1066540000/01/12.11
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
21 Out 51 GND
power supply
22 Out + Ex output 52 +24 V DC
23 channel 2 53 NC
status relay
24 54 COM
7.6.4 Specifications
Features
HART-compatible for 0.5...2.5 kHz
Configuration and monitoring via FDT/DTM-Software "WI-Manager".
The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,
2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.
The mA current signal inputs are completely electrically isolated.
The device detects automatically whether an active or passive current signal is connected.
Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
Front LEDs indicates operation status and malfunction.
3-way galvanic isolation between input, output and power supply.
1066540000/01/12.11 63
64
CPU
Device status, Green 51 Gnd.
Ch. 1 status, Red
Illustration 7-19:
52 Supply +24 V DC
Ch. 2 status, Red
13 V+
I+
41
Input Gnd.
Channel 1
24
I+
44
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
23
Channel 2 is identical to channel 1
Current, 4...20 mA 22
+
250 Ω
mA 43
- Input Gnd.
21
Output, Gnd. Channel 2
* NC = No connection
1066540000/01/12.11
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
Channel 1:
14 42
Channel 1:
13 41
Channel 2:
12 44
Load
4...20 mA
11 43
Supply +19.2...31.2 V DC
23 52
Module status
22 53
Load
N.C.
4...20 mA
21 54
Module status
Current Input
Measurement range 3.5…23 mA
Input resistance nom. 20 Ω + PTC 50 Ω
Alarm setpoint, low/high limit (programmable) 0…28 mA
Sensor error detection < 1 mA
Current Output
Signal range (programmable) 3.5…23 mA
Load max. 20 mA / 725 Ω / 14.5 V DC
Load stability ≤ 0.01 % of span / 100 Ω
1066540000/01/12.11 65
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
Power Supply
Supply voltage 19.2…31.2 V DC
Max. consumption (2-channels) ≤ 3.5 W
Fuse 1.25 A / 250 V AC
Environmental Specifications
Ambient temperature -20…+60 °C
Storage temperature -20…+85 °C
Relative humidity (non-condensation) < 95 %
Calibration temperature +20…28 °C
General Specifications
Communications interface, CBX200 USB / "WI-Manager" / ACT20X DTM
adapter / configuration software / FDT-DTM
device driver
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP20
Screw terminal torque 0.5 Nm
66 1066540000/01/12.11
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
HART Communication
Frequency range 0.5…2.5 kHz
Signal / noise ratio min. 60 dB (0.5…10 kHz)
Response time (0…90 %, 100…10 %) < 5 ms
Default Settings
Low/high limit 3.8 mA / 20.5 mA
1066540000/01/12.11 67
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
68 1066540000/01/12.11
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
DANGER
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
If the sensor circuits have been installed in a type of protection other than “intrinsic safety”, the module must
not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 69
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
70 1066540000/01/12.11
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
in hazardous area
Configuration in
safe area only!
Zone 0, 1, 2, 20, 21, 22 or Zone 2
Not connected
Configuration
CBX200 for
NAMUR Sensor
Contact Sensor
Switch w Shunt
-20 = Ta = 60 °C
Switch
+ CH1 14 44
13 43
- 12 42
11 41
+ CH2 24 54
23 53
- 22 52
21 51
ACT20X
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo 10.6 V DC
Io 12 mA DC
Po 32 mW
Lo/Ro 1150 H/
Group Co Lo
IIC 2 F 260 mH
IIB 6 F 780 mH
IIA 18 F 1000 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 71
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
72 1066540000/01/12.11
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
DANGER
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
If the sensor circuits have been installed in a type of protection other than “intrinsic safety”, the module must
not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 73
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
74 1066540000/01/12.11
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
in hazardous area
Configuration in
safe area only!
Zone 0, 1, 2, 20, 21, 22 or Zone 2
Not connected
Configuration
CBX200 for
NAMUR Sensor
Contact Sensor
Switch w Shunt
-20 = Ta = 60 °C
Switch
+ CH1 14 44
13 43
- 12 42
11 41
+ CH2 24 54
23 53
- 22 52
21 51
ACT20X
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo 10.6 V DC
Io 12 mA DC
Po 32 mW
Lo/Ro 1150 H/
Group Co Lo
IIC 2 F 260 mH
IIB 6 F 780 mH
IIA 18 F 1000 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 75
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
76 1066540000/01/12.11
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
FM Installation Drawing
DANGER
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring must be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The module must be installed in an enclosure suitable for the environment where it is used.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure according
to the regulations in the CEC for Canada or NEC for USA.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 77
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
78 1066540000/01/12.11
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
in hazardous area!
Do not connected
Configuration in
safe area only!
Configuration
CBX200 for
-20 = Ta = 60 °C
NAMUR Sensor
Contact Sensor
Switch w Shunt
Switch
Simple Apparatus or
Intrinsically safe apparatus
with entity parameters:
Vmax (Ui) = Vt (Uo) + CH1 14 44
Imax (Ii) = It (Io) 13 43
Pi = Pt (Po) - 12 42
Ca(Co) = Ccable + Ci
La(Co) = Lcable + Li
11 41
+ CH2 24 54
23 53
- 22 52
21 51
ACT20X
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo, Vt 10.6 V DC
Io, Isc 12 mA DC
Po, Pt 32 mW
Lo/Ro, La/Ra 1150 H/
Group C o, C a Lo, La
IIC or A, B 2 F 260 mH
IIB or C, E, F 6 F 780 mH
IIA or D, G 18 F 1000 mH
1066540000/01/12.11 79
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
80 1066540000/01/12.11
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter)
DANGER
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
If the sensor circuits (Terminals 11…14, 21…24) have been installed in a type of protection other than
“intrinsic safety”, the module must not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 81
ACT20X-(2)HTI-(2)SAO-S
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo 8.7 V
Io 18.4 mA
Po 40 mW
Lo/Ro 892 H/
Ui 10 V
Ii 30 mA
Ci 30 nF
Li 820 nH
Group Co Lo
IIC 5 F 100 mH
IIB 50 F 300 mH
IIA 1000 F 700 mH
82 1066540000/01/12.11
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 83
ACT20X-(2)HTI-(2)SAO-S
Group Co Lo
IIC 0.3 F 80 mH
IIB 1.6 F 250 mH
IIA 8 F 600 mH
84 1066540000/01/12.11
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 85
86 1066540000/01/12.11
IECEx Installation Drawing
DANGER
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
If the sensor circuits (Terminals 11…14, 21…24) have been installed in a type of protection other than
“intrinsic safety”, the module must not be reinstalled in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 87
ACT20X-(2)HTI-(2)SAO-S
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo 8.7 V
Io 18.4 mA
Po 40 mW
Lo/Ro 892 H/
Ui 10 V
Ii 30 mA
Ci 30 nF
Li 820 nH
Group Co Lo
IIC 5 F 100 mH
IIB 50 F 300 mH
IIA 1000 F 700 mH
88 1066540000/01/12.11
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 89
ACT20X-(2)HTI-(2)SAO-S
Group Co Lo
IIC 0.3 F 80 mH
IIB 1.6 F 250 mH
IIA 8 F 600 mH
90 1066540000/01/12.11
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 91
92 1066540000/01/12.11
FM Installation Drawing
DANGER
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring must be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The module must be installed in an enclosure suitable for the environment where it is used.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure according
to the regulations in the CEC for Canada or NEC for USA.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 93
CBX200 – "WI-Manager" Software
For installation in Zone 2 / Division 2 the following must be observed:
- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.
94 1066540000/01/12.11
ACT20X-(2)HTI-(2)SAO-S
Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)
Ex Input
Uo, Vt 8.7 V
Io, It 18.4 mA
Po 40 mW
Lo/Ro 892 H/
Ui 10 V
Ii 30 mA
Ci 30 nF
Li 820 nH
Group C o, C a Lo, La
IIC Group A, B 5 F 100 mH
IIB Group C, E, F 50 F 300 mH
IIA Group D, G 1000 F 700 mH
1066540000/01/12.11 95
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
96 1066540000/01/12.11
ACT-20X-(2)HTI-(2)SAO-S
1066540000/01/12.11 97
Group C o, C a Lo, La
IIC or Group A, B 0.3 F 80 mH
IIB or Group C, E, F 1.6 F 250 mH
IIA or Group D, G 8 F 600 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
98 1066540000/01/12.11
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
DANGER
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
If the sensor circuits have been installed in a type of protection other than “intrinsic safety”, the module must
not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 99
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
100 1066540000/01/12.11
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (11–12)
Ex Output
Group Co Lo Lo/Ro
8965410000 (ACT20X-SDI-HDO-H-S
Uo 28 V IIC 80 nF 2.69 mH 44 µH/Ω
Io 115 mA IIB 640 nF 10.8 mH 176 µH/Ω
Po 0.81 W IIA 2.1 µF 20.8 mH 353 µH/Ω
Terminal (11–13)
Ex Output
Group Co Lo Lo/Ro
8965410000 (ACT20X-SDI-HDO-H-S)
Uo 28 V IIC – – –
Io 125 mA IIB 640 nF 9.1 mH 162 µH/Ω
Po 0.88 W IIA 2.1 µF 17.6 mH 325 µH/Ω
Terminal (11–14)
Ex Output
Group Co Lo Lo/Ro
8965410000 (ACT20X-SDI-HDO-H-S)
Uo 28 V IIC – – –
Io 135 mA IIB 640 nF 7.8 mH 150 µH/Ω
Po 0.95 W IIA 2.1 µF 15.1 mH 301 µH/Ω
1066540000/01/12.11 101
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Input
Um 253 V, max. 400 Hz
102 1066540000/01/12.11
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
DANGER
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
If the sensor circuits have been installed in a type of protection other than “intrinsic safety”, the module must
not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 103
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
104 1066540000/01/12.11
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (11–12)
Ex Output
Group Co Lo Lo/Ro
8965410000 (ACT20X-SDI-HDO-H-S
Terminal (11–13)
Ex Output
Group Co Lo Lo/Ro
8965410000 (ACT20X-SDI-HDO-H-S)
Uo 28 V IIC – – –
Io 125 mA IIB 640 nF 9.1 mH 162 µH/Ω
Po 0.88 W IIA 2.1 µF 17.6 mH 325 µH/Ω
Terminal (11–14)
Ex Output
Group Co Lo Lo/Ro
8965410000 (ACT20X-SDI-HDO-H-S)
Uo 28 V IIC – – –
Io 135 mA IIB 640 nF 7.8 mH 150 µH/Ω
Po 0.95 W IIA 2.1 µF 15.1 mH 301 µH/Ω
1066540000/01/12.11 105
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Input
Um 253 V, max. 400 Hz
106 1066540000/01/12.11
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
FM Installation Drawing
DANGER
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring shall be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The module must be installed in an enclosure suitable for the environment where it is used.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure according
to the regulations in the CEC for Canada or NEC for USA.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 107
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
108 1066540000/01/12.11
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
1066540000/01/12.11 109
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (11–12)
Ex Output
Group Co Lo Lo/Ro
8965410000 (ACT20X-SDI-HDO-H-S
Uo 28 V IIC 80 nF 2.69 mH 44 µH/Ω
Io 115 mA IIB 640 nF 10.8 mH 176 µH/Ω
Po 0.81 W IIA 2.1 µF 20.8 mH 353 µH/Ω
Terminal (11–13)
Ex Output
Group Co Lo Lo/Ro
8965410000 (ACT20X-SDI-HDO-H-S)
Uo 28 V IIC – – –
Io 125 mA IIB 640 nF 9.1 mH 162 µH/Ω
Po 0.88 W IIA 2.1 µF 17.6 mH 325 µH/Ω
Terminal (11–14)
Ex Output
Group Co Lo Lo/Ro
8965410000 (ACT20X-SDI-HDO-H-S)
Uo 28 V IIC – – –
Io 135 mA IIB 640 nF 7.8 mH 150 µH/Ω
Po 0.95 W IIA 2.1 µF 15.1 mH 301 µH/Ω
110 1066540000/01/12.11
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Input
Um 253 V, max. 400 Hz
1066540000/01/12.11 111
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
112 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
DANGER
For safe installation of the Universal Converter ACT20X-HUI-SAO-S the following must be
observed: The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure in type of protection Ex-n or
Ex-e, providing an IP protection of at least IP54. Cable entry devices and blanking elements shall fulfil the
same requirements.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 113
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
114 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21–23)
Input Group Co Lo Lo/Ro
Uo 28 V IIC 80 nF 1000 mH 4 mH/Ω
Io 1.1 mA IIB 640 nF 1000 mH 17 mH/Ω
Po 8 mW IIA 2.1 µF 1000 mH 35 mH/Ω
Terminal (21–22)
Input Group Co Lo Lo/Ro
Uo 8.3 V IIC 7 µF 1000 mH 100 mH/Ω
Io 0.2 mA IIB 73 µF 1000 mH 400 mH/Ω
Po 0.4 mW IIA 1000 µF 1000 mH 800 mH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 115
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
116 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (24-22)
Input
Ui 30 V
Ii 120 mA
Pi 900 mW
Ci 3 nF
Li 2 µH
1066540000/01/12.11 117
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
118 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21-22)
Input
Ui 30 V
Ii 120 mA
Pi 900 mW
Ci 3 nF
Li 2 µH
1066540000/01/12.11 119
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
120 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
DANGER
For safe installation of the Universal Converter ACT20X-HUI-SAO-S the following must be
observed: The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 121
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
122 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21–23)
Input Group Co Lo Lo/Ro
Uo 28 V IIC 80 nF 1000 mH 4 mH/Ω
Io 1.1 mA IIB 640 nF 1000 mH 17 mH/Ω
Po 8 mW IIA 2.1 µF 1000 mH 35 mH/Ω
Terminal (21–22)
Input Group Co Lo Lo/Ro
Uo 8.3 V IIC 7 µF 1000 mH 100 mH/Ω
Io 0.2 mA IIB 73 µF 1000 mH 400 mH/Ω
Po 0.4 mW IIA 1000 µF 1000 mH 800 mH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 123
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
124 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (24-22)
Input
Ui 30 V
Ii 120 mA
Pi 900 mW
Ci 3 nF
Li 2 µH
1066540000/01/12.11 125
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
126 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21-22)
Input
Ui 30 V
Ii 120 mA
Pi 900 mW
Ci 3 nF
Li 2 µH
1066540000/01/12.11 127
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
128 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
FM Installation Drawing
DANGER
For safe installation of the Universal Converter ACT20X-HUI-SAO-S the following must be
observed: The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring must be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure having an
IP protection of at least IP54.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 129
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
130 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
1066540000/01/12.11 131
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21–23)
Input Group Co Lo Lo/Ro
Uo, VOC 28 V IIC or A, B 80 nF 1000 mH 4 mH/Ω
Io, ISC 1.1 mA IIB or C, E, F 640 nF 1000 mH 17 mH/Ω
Po 8 mW IIA or D, G 2.1 µF 1000 mH 35 mH/Ω
Terminal (21–22)
Input Group Co Lo Lo/Ro
Uo, VOC 8.3 V IIC or A, B 7 µF 1000 mH 100 mH/Ω
Io, ISC 0.2 mA IIB or C, E, F 73 µF 1000 mH 400 mH/Ω
Po 0.4 mW IIA or D, G 1000 µF 1000 mH 800 mH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
132 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
1066540000/01/12.11 133
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
134 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (24-22)
Input
Ui 30 V
Ii 120 mA
Pi 900 mW
Ci 3 nF
Li 2 µH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 135
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
136 1066540000/01/12.11
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21-22)
Input
Ui, Vmax 30 V
Ii, Imax 120 mA
Pi 900 mW
Ci 3 nF
Li 2 µH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 137
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
138 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
DANGER
For safe installation of ACT20X-(2)HAI-(2)SAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure in type of protection Ex-n or
Ex-e, providing an IP protection of at least IP54. Cable entry devices and blanking elements shall fulfil the
same requirements.
In type of protection “intrinsic safety ia IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The Loop Supply and Current Input terminals for the same channel shall not be applied at the same time.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 139
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
T 53
13 CH1
52
12 51
11
24
T 44
23 43
22 CH2 42
41
21
ACT20X-(2)HAI-(2)SAO-S
Group Co Lo
IIC 0.08 F 3 mH
IIB 0.6 F 12 mH
IIA 2.15 F 25 mH
140 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 141
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
13 53
CH1
52
12 51
11
24
44
23 43
22 CH2 42
41
21
ACT20X-(2)HAI-(2)SAO-S
142 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group Co Lo
IIC 0.08 F 3 mH
IIB 0.6 F 12 mH
IIA 2.15 F 25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 143
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
+
13 53
CH1
52
12 51
11
T
24
44
23 43
_ 22 CH2 42
41
21
ACT20X-2HAI-2SAO-S
Group Co Lo
IIC 0.08 F 3 mH
IIB 0.6 F 12 mH
IIA 2.15 F 25 mH
144 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 145
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
13 53
CH1
52
+ 12 51
11
24
44
23 43
22 CH2 42
_ 41
21
ACT20X-2HAI-2SAO-S
146 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group Co Lo
IIC 0.08 F 3 mH
IIB 0.6 F 12 mH
IIA 2.15 F 25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 147
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
148 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
DANGER
For safe installation of ACT20X-(2)HAI-(2)SAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety ia IIIC” the parameters for intrinsic safety for gas group IIB are
applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The Loop Supply and Current Input terminals for the same channel shall not be applied at the same time.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 149
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
T 53
13 CH1
52
12 51
11
24
T 44
23 43
22 CH2 42
41
21
ACT20X-(2)HAI-(2)SAO-S
Group Co Lo
IIC 0.08 F 3 mH
IIB 0.6 F 12 mH
IIA 2.15 F 25 mH
150 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 151
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
13 53
CH1
52
12 51
11
24
44
23 43
22 CH2 42
41
21
ACT20X-(2)HAI-(2)SAO-S
152 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group Co Lo
IIC 0.08 F 3 mH
IIB 0.6 F 12 mH
IIA 2.15 F 25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 153
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
+
13 53
CH1
52
12 51
11
T
24
44
23 43
_ 22 CH2 42
41
21
ACT20X-2HAI-2SAO-S
Group Co Lo
IIC 0.08 F 3 mH
IIB 0.6 F 12 mH
IIA 2.15 F 25 mH
154 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 155
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
13 53
CH1
52
+ 12 51
11
24
44
23 43
22 CH2 42
_ 41
21
ACT20X-2HAI-2SAO-S
156 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group Co Lo
IIC 0.08 F 3 mH
IIB 0.6 F 12 mH
IIA 2.15 F 25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
1066540000/01/12.11 157
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
158 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
FM Installation Drawing
DANGER
For safe installation of ACT20X-(2)HAI-(2)SAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
In Class I, Division 2 installations, the subject equipment shall be mounted within a tool-secured enclosure
which is capable of accepting one or more of the Class I, Division 2 wiring methods specified in the National
Electrical Code (ANSI/NFPA 70) or Canadian Electrical Code (C22.1).
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure having an
IP protection of at least IP54.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
The Loop Supply and Current Input terminals for the same channel shall not be applied at the same time.
The wiring of unused terminals is not allowed.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 159
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
160 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
-20 ≤ Ta ≤ +60ºC
CBX200 for
Simple Apparatus or
Intrinsic safe apparatus
with entity parameters:
24
T 44
23 43
22 CH2 42
41
21
ACT20X-(2)HAI-(2)SAO-S
1066540000/01/12.11 161
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group Co Lo
IIC or A, B 0.08 F 3 mH
IIB or C, E, F 0.6 F 12 mH
IIA or D, G 2.15 F 25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
162 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
-20 ≤ Ta ≤ +60ºC
CBX200 for
Simple Apparatus or
Intrinsic safe apparatus
with entity parameters:
24
44
23 43
22 CH2 42
41
21
ACT20X-(2)HAI-(2)SAO-S
1066540000/01/12.11 163
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group Co Lo
IIC or A, B 0.08 F 3 mH
IIB or C, E, F 0.6 F 12 mH
IIA or D, G 2.15 F 25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
164 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
Intrinsic safe apparatus
with entity parameters:
Group Co Lo
IIC or A, B 0.08 F 3 mH
IIB or C, E, F 0.6 F 12 mH
IIA or D, G 2.15 F 25 mH
1066540000/01/12.11 165
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
166 1066540000/01/12.11
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
in hazardous area
Not connected
Configuration
CBX200 for
Intrinsic safe apparatus
with entity parameters:
24
44
23 43
22 CH2 42
_ 41
21
ACT20X-2HAI-2SAO-S
1066540000/01/12.11 167
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)
Group Co Lo
IIC or A, B 0.08 F 3 mH
IIB or C, E, F 0.6 F 12 mH
IIA or D, G 2.15 F 25 mH
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
Um 253 V, max. 400 Hz
168 1066540000/01/12.11
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
DANGER
For safe installation of ACT20X-(2)SAI-(2)HAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “Ex ia Da” the parameters for intrinsic safety for gas group IIB are applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 169
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
13 53
CH1
52
+ 12 51
mA
- 11
24
44
23 43
22 CH2 42
+
mA 41
- 21
ACT20X-(2)SAI-(2)HAO-S
Group Co Lo
IIC 0.08 F 4 mH
IIB 0.65 F 16 mH
IIA 2.15 F 32 mH
170 1066540000/01/12.11
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Current Input
Um 253 V, max. 400 Hz
1066540000/01/12.11 171
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
172 1066540000/01/12.11
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
DANGER
For safe installation of ACT20X-(2)SAI-(2)HAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “Ex ia Da” the parameters for intrinsic safety for gas group IIB are applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 173
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
in hazardous area
Not connected
Configuration
CBX200 for
14 54
13 53
CH1
52
+ 12 51
mA
- 11
24
44
23 43
22 CH2 42
+
mA 41
- 21
ACT20X-(2)SAI-(2)HAO-S
Group Co Lo
IIC 0.08 F 4 mH
IIB 0.65 F 16 mH
IIA 2.15 F 32 mH
174 1066540000/01/12.11
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Current Input
Um 253 V, max. 400 Hz
1066540000/01/12.11 175
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
176 1066540000/01/12.11
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
FM Installation Drawing
DANGER
For safe installation of ACT20X-(2)SAI-(2)HAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
In Class I, Division 2 or Zone 2 installations, the subject equipment shall be mounted within a tool-secured
enclosure which is capable of accepting one or more of Class I, Division 2 wiring methodes specified in the
National Electrical Code (ANSI/NFPA 70) or the Canadian Electrical code (C22.1).
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure having an
IP protection of at least IP54.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG (26-14).
The year of manufacture can be taken from the first two digits in the serial number.
1066540000/01/12.11 177
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
178 1066540000/01/12.11
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
in hazardous area
Not connected
Configuration
-20 ≤ Ta ≤ +60ºC
CBX200 for
Simple apparatus or
intrinsic safe apparatus
with entity parameters: 14 54
Vmax (Ui) ≥ Vt (Uo) 13 53
CH1
Imax (Ii) ≥ It (Io) 52
+ 12 51
Pi ≥ Pt (Po) mA
Ca ≥ Ccable + Ci - 11
La ≥ Lcable + Li
24
44
23 43
22 CH2 42
+
mA 41
- 21
ACT20X-(2)SAI-(2)HAO-S
Group Co Lo
IIC 0.08 F 4 mH
IIB 0.65 F 16 mH
IIA 2.15 F 32 mH
1066540000/01/12.11 179
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Current Input
Um 253 V, max. 400 Hz
180 1066540000/01/12.11
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
1066540000/01/12.11 181
Weidmüller Interface GmbH & Co. KG
P.O. Box 3030
32720 Detmold
Klingenbergstraße 16
32758 Detmold
Germany
Phone +49 (0) 5231 14-0
Fax +49 (0) 5231 14-2083
E-Mail info@weidmuller.com Order number:
Internet www.weidmueller.com 1066540000/01/12.11