How do you run diagnostics on a WinCC Operator Station for all the S7-400 CPUs connected?
Instructions
There are two possible diagnostics methods:
Via the add-on "System diagnostics - S7-400 CPU diagnostics"
Via the Online View of the SIMATIC Manager
The advantage of the "System diagnostics - S7-400 CPU diagnostics" method is that you can see the
diagnostics imbedded in WinCC on any OS. This means that the operating system layer of the OS still
cannot be reached by the operator and a STEP 7 / PCS 7 ES does not have to be installed on the
OS.
Description of "System diagnostics - S7-400 CPU diagnostics"
"System diagnostics - S7-400 CPU diagnostics" includes visualization and detailed diagnostics of S7-
400 / S7-400H CPUs on an OS. The diagnostics concept can be implemented on an operator station
(OS) - without access to STEP 7 - to display online the current operating status of the CPUs/H-CPUs
connected. CPU diagnostics is fully configured in just three easy steps on the Engineering Station
(ES) and Operator Station (OS).


Once the connection has been set up successfully the current operating mode of the CPU/H-CPU
configured is shown in the Overview. A detailed display of the current operating mode is given via the
six tabs of the OCX. Any error statuses that occur are diagnosed.

No. Procedure on the ES
1 Call diagnostics blocks in the S7 program (e.g. OB 35).
2 Export the Hardware Configuration (.cfg file).
3 Compile the OS
No. Procedure on the OS
1 Insert the diagnostics OCX in the WinCC picture.
2 Connect the structure variable to the diagnostics control.
3 Specify the storage path of the exported HW Config file (.cfg file).
"General I" tab 1. Order number (MLFB), firmware and release of the H-
CPU available ONLINE.
2. MPI address, subrack and slot.
3. Setting of the key switch (up to CPU firmware version
V3, otherwise always RUN-P).
Page 1 of 6 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Ser...
5/3/2014 https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objid=9985721&nodeid0=...

Fig. 1

4. Status of the LEDs "INTF", "EXT", "RUN", "STOP",
"REDF", "MSTR", "RACKx", "IFMxF" and "BUSxF".
"Diagnostics Buffer" tab

Fig. 2

This tab displays the last 20 entries (maximum) of the
diagnostics buffer of the CPU/H-CPU. The detailed data of the
diagnostics message is displayed in field under the entry
selected.
Furthermore, you can save the displayed diagnostics buffer
entries in a text file.
"Scan Cycle Time" tab

Fig. 3

Display of the current and maximum cycle times.
"Memory" tab

Fig. 4

Display of the assigned and free work memory data.
"H-State" tab Display of the H-CPU state.
Page 2 of 6 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Ser...
5/3/2014 https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objid=9985721&nodeid0=...
"System diagnostics - S7-400 CPU Diagnostics" offers the following advantages:
1. No need for Engineering Software on the OS (STEP 7 / PCS 7 ES).
2. Few, simple configuration steps.
3. Simple transfer of changes in the Hardware Configuration - at any time and online in WinCC
simple via a picture change.
4. Direct recognition of the CPU status in the OS.
5. Central acquisition of diagnostics data in the diagnostics buffer.
6. WinCC-compatible display of data.
More information is available under the following link:
http://www.siemens.com/systemdiagnostics
Fig. 1

Fig. 5

"General II" tab

Fig. 6

Display of the plant designation, comments, firmware version
and order number (MLFB).
Page 3 of 6 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Ser...
5/3/2014 https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objid=9985721&nodeid0=...

Fig. 2

Fig. 3
Page 4 of 6 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Ser...
5/3/2014 https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objid=9985721&nodeid0=...

Fig. 4

Fig. 5
Page 5 of 6 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Ser...
5/3/2014 https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objid=9985721&nodeid0=...

Fig. 6

Entry ID:9985721Date:2011-09-13
My tags : Create new bookmark/tag
Siemens AG 2014 - Corporate Information - Privacy Policy - Terms of Use
Page 6 of 6 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Ser...
5/3/2014 https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objid=9985721&nodeid0=...

Potrebbero piacerti anche