3 - Main feature and characteristics
- Voltage regulation : 0.5 %.
- U/F function.
- LAM function.
- Quick response : 500 ms.
- Nominal excitation current : 5A.
- Maximum excitation current : 7A during 10 s.
- Supply range / voltage detection :
85 to 139 V (50/60Hz).
- Protection : fuse 8A.
LAM Function
R 250 A.V.R.
Ref : 4548en-2014.02/c Page 1
R 250 is an analog A.V.R. with power controled by
transistors.
It is designed for small alternators with a
SHUNT excitation.
R 250 controls the excitation current in order
to maintain the output voltage of the
alternator.
R 250 is performant in terms of voltage regulation,
simple to set , to use and is reliable.
It is in compliance with I.E.C. 60034-1 standard
and U.L. 508 / C.S.A. approved.
0 1 s 2 s 3 s
LAM
0,9
0,8
fN
0 1 s 2 s 3 s
UN
0
0,9
0,8
(U/f)
1 s 2 s 3 s
100 %
50 Hz 60 Hz Hz
50 Hz
48 Hz
57 Hz
60 Hz
Voltage
Knee
Knee
U/UN
Frequency
U/F function
Variation in the load

L
o
a
d

o
n

t
h
e

s
h
a
f
t

(
k
W
)
Load shedding due to LAM
Max. speed drop with
LAM
without
LAM with LAM
Time Time Time
without LAM
Transient voltage drop
Shunt
AREP
PMG
LSA 40 42.3 44.3 46.2 47.2 49.1 50.2 51.2 53.1 54
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Ref : 4548en-2014.02/c Page 2
5 - Connexion and setting
Settings are done through the A.V.R.
- Potentiometer P1 : voltage setting.
- Potentiometer P2 : stability setting.
- Strap ST3 : frequency selection.
- Jumper : frequency, U/F function, LAM function
- Potentiometer ST4 : remote voltage setting.
R 250 A.V.R.
4 - Operation conditions
- Operating temperature range : - 40 C + 65 C.
- Storage temperature range : - 55 C + 85 C.
- Hygrometry : 98%.
- Maximum choc : 9 g on 3 axis.
- Vibrations : less than 10 Hz , 2 mm peak magnitude.
From 10 Hz to 100 Hz : 100 mm/s, below 100 Hz : 8g.
4 x holes 5.8 x
50 x 115 mm
1
4
0

m
m

75 mm
R 250


V
O
L
T

F
R
E
Q
.

&

L
.
A
.
M
.

C
O
N
F
I
G
.




S
T
A
B

F1
Slow fuse
250V 8 A
P1
Voltage
P2
110 E+ E- 0V
0
9
8
7
65
4
3
2
1
o
1
2
3
5
6
7
9
8
4
60Hz
65Hz
57Hz
47.5Hz
50Hz
KNEE
SPECIAL
LAM
OFF
OFF
13%
13%
25%
25%
LAM
KNEE
KNEE
LAM OFF
LAM OFF
LAM OFF
External potentiometer
for voltage adjusting