Isolation Amplifier

Isolation Amplifier W ith N ominal V alu e S elec tor


AD-TV 32 GL
Description
Th e V ARIO-isolation amplifier AD-TV 32 GL serves th e galvanic
separation, c onversion and amplific ation of DC c u rrent and voltage
signals (0/4-20 mA and 0/2-10 V DC). Th e signal dimensions are
adju stable at th e front. Th e starting and end valu es c an h ere be adju sted
independent of eac h oth er. Inpu t, ou tpu t and th e su pply voltage are
separate from eac h oth er with h igh insu lation. An integral elec tronic wide
range power pac k with a h igh degree of effec tiveness allows operation in
a su pply range of 20...253 V DC or 50...253 V AC. Additionally, a
nominal valu e c an be spec ified via switc h at th e front at th e ou tpu t. Th e
inpu t measu ring signal is dec ou pled and with ou t influ enc e du ring th is.
Th e nominal valu e at th e ou tpu t, wh ic h c an be ac tivated and adju sted via
a potentiometer at th e front.
Application
Conversion, bu rden amplific ation and galvanic dec ou pling of ac tive DC-
c u rrent and voltage signals with additional manu al / au tomatic operation
via a nominal valu e spec ific ation, wh ic h c an be ac tivated.
Specific characteristics
Front panel switc h for switc h ing between manu al and au tomatic
operation
V alu e setting for manu al operation by front-fac e potentiometer
Business data
Catalog nu mber AD-TV 32 GL
Technical specifications
Input current
Measu ring range 0/4 ... 20 mA
Inpu t resistanc e 85 Oh m
Input voltage
Measu ring range 0/2 ... 10 V
Inpu t resistanc e > 100 kOh m
Output current
Ou tpu t range 0/4 ... 20 mA
Max. bu rden 500 Oh m
Residu al ripple 50 Ass
Output voltage
Ou tpu t range 0/2 ... 10 V
Min. bu rden > 10 kOh m
Residu al ripple 50 mV ss
Setpoint setting
Front mou nted potentiometer 0 ... 100 %
Supply
V oltage range AC 50 ... 253 V AC, 50/60 Hz
N ominal voltage AC 230 V AC
V oltage range DC 20 ... 253 V DC
N ominal voltage DC 24 V DC
Power c onsu mption AC / DC 2,3 V A / 1W
Transmission behaviour
Basic ac c u rac y < 0,2 %
Temperatu re influ enc e 100 ppm/K
Response time ~ 20 ms
Housing
Dimensions (W xHxD) 18x78x103 mm
Type of protec tion IP 20
Connec tion meth od sc rew c lamp
Terminals, wire c ross sec tion 2,5 mm flex wire / 4 mm one wire
Bolting torqu e terminals 0,5 N m
W eigh t ~ 100 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperatu re 0 ... 50 C
S torage and transport -10 ... 70 C (no th awing)
EMC
Produ c t family standard EN 61326
1)
Emitted interferenc e EN 55011, CIS PR11 Cl. B
Electrical safety requirements
Produ c t family standard EN 61010-1
Overvoltage c ategory II
Pollu tion degree 2
Galvanic isolation, test voltages
Inpu t / ou tpu t 3,75 kV , 50 Hz (1 min.)
S ignal / su pply u nit 4 kV , 50 Hz (1 min.)
Protection circuits
Inpu t elec tric al su rge protec tion
Ou tpu t elec tric al su rge protec tion
Power su pply elec tric al su rge and reverse c u rrent
protec tion
Page 1/2 Printed 25.03.2014 We reserve the right for technical changes.
Isolation Amplifier
Isolation Amplifier W ith N ominal V alu e S elec tor
AD-TV 32 GL
1)
Du ring c h ec king, sligh t signal deviations are possible.
Block and wiring diagram
1
2
8
7
5 +
6
+
Inpu t
Power S u pply
Ou tp.
+
V oltage Cu rrent
3
4
Ju mper
for voltage
ou tpu t
I / U
Dimensions
Powered by TCPDF (www.tc pdf.org)
www.adamczewski.com Page 2/2 Printed 25.03.2014 We reserve the right for technical changes.