PURPOSE
2.00
3.00
3.01
3.02
3.03
3.04
3.05
3.06
3.07
3.08
PROJECT DATA
Scope of the Project
Network Data
Maximum Short-circuit currents
Minimum Short-circuit currents
Source Impedance
Fault Resistance
Instrument Transformers
Telecommunication Equipment
4.00
4.01
4.02
4.03
4.04
PROTECTION SYSTEM
Primary Protection
Secondary Protection
Backup Protection
Auto-reclosing
5.00
5.01
5.02
BREAKER PROTECTION
Devices in the Circuit Breaker
Breaker Protection Relays
ANNEX 1
ANNEX 2
R-X DIAGRAMS
ANNEX 3
225917300.doc
1.00
PURPOSE
The purpose of this document is to provide the criteria for relay settings. On this
basis the calculations are performed to provide each setting.
2.00
ANSI/IEEE C37-93
IEC 255
Numerical Line Protection Type REL 316*4. Operating Instructions.
ABB Power Automation
Line Distance Protection Terminal REL 521*2.0. Technical Reference Manual.
ABB Network Partner
Breaker Protection Terminal REL 521*2.0. Users Manual.
ABB Network Partner
225917300.doc
225917300.doc
3.00
PROJECT DATA
3.01
3.02
Network Data
The data of the Transmission Line is the following
LINE
Paramonga
Vizcarra
L-253
Tingo Mara
Vizcarra
L-252
Vizcarra
Antamina
L-255
Aguayta
Tingo Mara
Paramonga
Chimbote
L-215
Paramonga
Zapallal
L-213
225917300.doc
DISTANCE
[km]
Impedance
Positive Sequence
[Ohm/phase]
Impedance
Zero Sequence
[Ohm]
Ro
Xo
144.211
8.298
72.833
39.736
212.284
173.7
9.995
87.727
47.862
255.695
52.08
3.001
26.568
20.745
88.429
73.29
4.217
37.015
20.194
107.890
221.2
19.466
110.6
54.681
365.422
157.5
14.175
124.11
38.903
256.73
3.03
SOURCE
Three-phase fault
[kA]
Line to ground
fault
[kA]
Tingo Mara
Aguayta
SICN
Vizcarra
TOTAL
X/R
1.32
0.27
0.58
2.17
10.1
0.94
0.20
0.39
1.54
8.1
Vizcarra
TingoMara
Paramonga Nueva
Antamina
TOTAL
X/R
0.75
0.97
0.50
0.66
1.72
8.0
1.15
6.8
Antamina
Vizcarra
X/R
1.23
8.2
0.78
6.2
Paramonga Nueva
Vizcarra
Zapallal
Chimbote
Paramonga
TOTAL
X/R
0.52
1.25
0.68
0.27
2.71
6.6
0.36
0.86
0.49
0.38
2.09
7.4
3.04
SOURCE
Tingo Mara
Aguayta
SICN
Vizcarra
TOTAL
X/R
225917300.doc
Three-phase fault
[kA]
1.32
0.27
Line to ground
fault
[kA]
0.95
0.21
1.58
11.5
1.16
8.9
Vizcarra
TingoMara
Paramonga Nueva
Antamina
TOTAL
X/R
0.00
0.61
0.00
0.48
0.61
6.9
0.48
7.0
Antamina
Vizcarra
X/R
0.53
7.0
0.40
6.6
Paramonga Nueva
Vizcarra
Zapallal
Chimbote
Paramonga
TOTAL
X/R
0.66
0.27
0.93
6.5
0.52
0.36
0.88
7.9
3.05
Source Impedance
On the basis of the maximum short circuit current the source impedance at each bus
will be as follows
3.06
BUS
X/R
R
[Ohm]
X
[Ohm]
Tingo Mara
10.1
5.774
58.61
Vizcarra
8.0
9.15
73.34
Antamina
8.2
12.49
102.4
Paramonga Nueva
6.6
7.04
46.29
Fault Resistance
The fault resistance will be the arc resistance plus the tower resistance. The first
value will calculated according to the formula
Rarc = 28707 L / I1.4
Where L is the length of the arc which is typically three times the conductor to
tower spacing and I is the minimum shortcircuit current (average value of both
ends). On this basis the fault resistance will be as follows
225917300.doc
LINE
Vizcarra
Paramonga
L-253
Vizcarra
Tingo Mara
L-252
Vizcarra
Antamina
L-255
3.07
Resistance Arc
[Ohm]
Resistance Tower
[Ohm]
Fault Resistance
[Ohm]
24
25
49
39
25
64
60
25
85
Instrument Transformers
The technical characteristics of Voltage and Current Transformers are the following
Instrument Transformer
Voltage Transformers
Primary
[V]
Secondary
Paramonga
STATION
Vizcarra
Tingo Mara
220000 / 3
138000
220000 / 3
110 / 3
69
100 / 3
500
600
500
[V]
Current Transformers
Primary
[A]
Secondary
3.08
[A]
Telecommunication Equipment
Power Line Carrier will provide support for the Protection System. There will be
three telecommunication links: Vizcarra Paramonga, Vizcarra Tingo Mara and
Vizcarra Antamina. One channel will be installed on each link and there will be
one Teleprotection Signal Equipment over each channel. This equipment will
provide four signals named A, B C and D.
225917300.doc
4.00
PROTECTION SYSTEM
Protection will be carried by Multifunction Relays. Each protection zone will
include one Transmission Line (or the SVC) and one part of the 220 kV Ring Bus.
There will be two relays per protection zone; one is named Primary Protection and
the other is named Secondary Protection. Additionally, there will be one Breaker
Protection Relay. In the first stage when SVC is not in service, this relay will
provide overcurrent protection on the corresponding part of the Ring Bus.
SVC will not be in service at the first stage, therefore provisional connections must
be done in order to get the proper overlapping protection zones on the 220 kV Ring
Bus. For this reason, one interconnection between current transformer boxes will be
necessary to extent the Antamina Line zone; in the same way, Antamina line
protection will trip the corresponding circuit breaker also. Both provisional
interconnection cables will be installed at the switchyard.
Relay ABB - REL 521 will be used for Primary Protection and Relay ABB - REL
316 will be used for Secondary Protection. Relay ABB - REB 551 will be used for
Breaker Protection.
In Vizcarra Substation, Primary Protection Relays will work with Trip 1 in the
Circuit Breakers and Secondary Protection Relays will work with Trip 2. Each
Breaker Protection will operate with one Lockout Relay to trip and block the
corresponding breakers. These relays will work with Trip 1 and Trip 2.
4.01
Primary Protection
4.01.1 Vizcarra - Paramonga Nueva (L-253)
(L-252) Lines
and
Stepped impedance (21 & 21N) function in the Primary Protection Relays at both
ends of the line will be used to achieve fast fault clearance on all the transmission
line.
The communication scheme will be through the Teleprotection Equipment using
signal A. The logic will be Permissive Underreach Transfer Trip (PUTT) with the
following settings
First Zone
Second Zone :
Directional Earth Fault function (67N) in the Primary Protection Relays will be
used also. It will work with the Teleprotection Equipment using signal C.
Permissive overreach logic will be used to assure that the fault is in the protected
line. The settings will be 15% in the residual current.
225917300.doc
10
Secondary Protection
4.02.1 Paramonga Nueva Vizcarra (L-253)
(L-252) Lines
Stepped impedance (21 & 21N) function in the Primary Protection Relays at both
ends of the line will be used to achieve fast fault clearance on all the transmission
line.
The first zone will operate to give direct trip the local breaker at each substation;
but one communication scheme will be used with the second zone. This scheme
will be trough the Teleprotection Equipment using signal B. The logic will be
Permissive Overreach Transfer Trip (POTT) to assure the fault is in the protected
line. The settings will be as follows
First Zone
:
Second Zone :
Directional Earth Fault function (67N) in the Secondary Protection Relays will be
used also. It will work with the Teleprotection Equipment using signal C.
Permissive overreach logic will be used to assure that the fault is in the protected
line. The settings will be 15% in the residual current.
Secondary Protection will be carried out by Second Zone Impedance function (21
& 21N), which will operate with Permissive Overreach Transfer Trip (POTT)
scheme. The impedance setting will be 120% of the line in order to get the reach for
the full line.
4.02.2 Vizcarra Anatamina Line (L-255)
225917300.doc
11
Stepped impedance (21 & 21N) function in the Primary Protection Relay will be
used to achieve fast fault clearance on all the transmission line. The setting will be
120% of the line in order to cover the full length.
Directional Earth Fault functions (67N) in the Primary Protection Relays will be
used also. The settings will be 15% in the residual current.
Primary Protection Relay will operate one Direct Transfer Trip trough the power
line carrier to trip both ends of the line. It will work with the Teleprotection
Equipment using signal B.
4.03
Backup Protection
4.03.1 Remote Protection
Backup Protection will be carried out by the second, third, fourth and fifth zones of
Impedance function in both Primary and Secondary Protection Relays.
Second zone will reach part of the next line and will have time delay in the first
time step. Fourth zone will be used to reach the next line and third zone will be
used to reach line back. Third and fourth zones will have time delay in the second
time step. Fifth zone will reach the protected line plus shortest next line. The
settings and timing will be as follows
Zone
Impedance Set
Time Delay
Second
400 ms
Third
700 ms
Fourth
700 ms
Fifth
1500 ms
225917300.doc
12
Auto-reclosing
4.04.1 Paramonga Nueva Vizcarra (L-253)
Automatic single-pole reclosing will be used with line protection. There will not be
three-pole reclosing. This function will be carried out by Breaker Protection Relay.
If there is a fault phase to ground in this line, two breakers must trip: Breaker IN2402 (52-01) and IN-2400 (52-02) and the Auto-reclosing will be as follows:
1) Breaker IN-2402 (52-01) will trip all the poles, but Breaker IN-2400 (52-02)
will trip only the pole corresponding to the faulted phase
2) Time delay for Auto-reclosing will be 500 ms and after this Breaker IN-2400
(52-02) will close.
3) If the fault is cleared the Breaker IN-2400 (52-02) will remain closed. Breaker
52-01 must be closed later by the Breaker Protection Relay.
4) If the fault is not cleared, Breaker IN-2400 (52-02) will trip the three poles
4.04.2 Vizcarra Tingo Mara Lines (L-252)
Automatic single-pole reclosing will be used with line protection. There will not be
three-pole reclosing. This function will be carried out by Breaker Protection Relay.
If there is a fault phase to ground in this line, two breakers must trip: Breaker IN2400 (52-02) and IN-2406 (52-03) and the Auto-reclosing will be as follows:
1) Breaker IN-2406 (52-03) will trip all the poles, but Breaker IN-2400 (52-02)
will trip only the pole corresponding to the faulted phase
2) Time delay for Auto-reclosing will be 500 ms and after this Breaker IN-2400
(52-02) will close.
3) If the fault is cleared the Breaker IN-2400 (52-02) will remain closed. Breaker
IN-2406 (52-03) must be closed later by the Breaker Protection Relay.
4) If the fault is not cleared, Breaker IN-2400 (52-02) will trip the three poles
4.04.3 Vizcarra Antamina Line (L-255)
225917300.doc
13
There will not be auto-reclosing in this line. However, provisions for future
application will be included. Programming on the Relay will be switched OFF and
connection jumpers for the reclosing circuit will be removed.
5.00
BREAKER PROTECTION
Breaker Protection will be done by the devices incorporated in the equipment and
Breaker Protection Relay.
5.01
5.02
225917300.doc
14
2) If 150 ms later (total 300 ms) the fault is not cleared, Breaker Relay will trip
Breaker IN-2402 (52-01) and Breaker IN-2406 (52-03). At the same time, one
direct transfer will be sent to Paramonga and Tingo Mara.
5.02.3 Breaker IN-2406 (52-03)
The Relay will operate in two steps:
1) If the main protection sends the trip signal and 150 ms later the fault is not
cleared, Breaker Relay will repeat the trip signal
2) If 150 ms later (total 300 ms) the fault is not cleared, Breaker Relay will trip
Breaker IN-2404 (52-04) and Breaker IN-2400 (52-02). At the same time, one
direct transfer will be sent to Tingo Mara.
5.02.4 Breaker IN-2404 (52-04)
The Relay will operate in two steps:
1) If the main protection send the trip signal and 150 ms later the fault is not
cleared, Breaker Relay will repeat the trip signal
2) If 150 ms later (total 300 ms) the fault is not cleared, Breaker Relay will trip
Breaker IN-2402 (52-01) and Breaker IN-2406 (52-03).
225917300.doc
15
ANNEX 1
225917300.doc
16
ANNEX 2
R-X DIAGRAMS
Figure 1.0
Figure 2.0
Figure 3.0
Figure 4.0
Figure 5.0
Figure 6.0
Figure 7.0
Figure 8.0
Figure 9.0
Figure 10.0
225917300.doc
17
ANNEX 3
Figure 1
Figure 2
Figure 3
Figure 4
225917300.doc
18